Sheet 6 of 8.pdf
PDF 180 KB Posted
- Attached to
- VGLZ 242015 Repair HVAC B105
- Solicitation number
- W50S8525BA003
About this file
This document is a detailed heating plant piping diagram for the Selfridge Air National Guard Base in Michigan, specifically for the repair of HVAC systems in Building 105. The diagram provides a comprehensive technical schematic for new heating hot water boilers, including components such as boiler circulation pumps, air/dirt separators, isolation valves, temperature and pressure relief valves, condensate traps, and acidic condensate routing to a neutralization tank. The piping diagram shows the interconnections and layout for high-efficiency condensing boilers with stainless steel heat exchangers, designed to be installed in a lead/lag configuration with associated pumping and control systems. The technical drawing is part of a solicitation (W50S8525BA003) for the Michigan Army National Guard, detailing the precise mechanical engineering specifications for replacing the existing heating boiler systems in the facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| OF1419 Abstract of Offers W50S8525BA003.pdf | ||
| Solicitation Amendment W50S8525BA0030001 SF 30.pdf | ||
| Sheet 5 of 8.pdf | ||
| Sheet 3 of 8.pdf | ||
| RFIs B105 HVAC.pdf | ||
| Sheet 8 of 8.pdf | ||
| SOW Addendum 01.pdf | ||
| Sign In Sheet 7-16-2025.pdf | ||
| W50S8525BA001 Pre-Bid Conference_Site Visit Slides 7-16-2025.pptx | PPTX presentation |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HWRHWS
HWR
T
HWS HWRHWS
FS
PRESSURE
GAUGE
BLADDER
EXPANSION
TANK
SITE
GLASS
FLOOR MOUNTED BLADDER
EXPANSION TANK WITH
SHOTFEEDER AND AIR/DIRT
SEPARTOR AN MAKEUP
WATER CONNECTION.
FS
H W
R
H W
S
HWR TEMP. SENSOR BY
TEMPERATURE CONTROLS
CONTRACTOR. MOUNT IN
THERMOWELL.
B&G #87 VENT
OR EQUAL
THERMOMETER (TYP)
4" DRAIN COCK W/THREADED HOSE CONN.
AND CAP (TYP.)
STRAINER
PLUG VAVLE
BOILER CIRC. PUMP
NON-SLAM CHECK
VALVE
DIRT LEG (TYP.)
TO FLOOR DRAIN
EX. FLOOR DRAIN
CONDESATE ACID WASTE
NEUTRALIZATION TANK
(BY BOILER
MANUFACTURER)
TAP OFF
SIDE
PRESSURE GAUGE
CHECK
VALVEBOILER FLOW SWITCH.
MOUNT IN PIPE WELL
BUTTERFLY
ISOLATION VALVE
(TYP.)
BP-1
BP-2
HWR TO
SYSTEM
B-2 B-1
BOILER CIRC.
PUMP
EXTEND TO FLOOR
DRAIN
CONDENSATE TRAP
UNION (TYP.)
REDUCER AS
REQUIRED (TYP.)
LOCAL VENT W/
GOOSNECK
3/4" ACIDIC CONDENSATE
ROUTE TO ACID
NEUTRALIZATION TANK
1-1 4"G
CIRCUIT SETTER
BALANCING VAVLE
TEMPERATURE AND PRESSURE RELIEF
VALVE. PIPE FULL SIZE TO FLOOR DRAIN
3" CONCRETE
HOUSEKEEPING PAD
VENT STACK
COMBUSTION AIR INTAKE
BP-3
BP-4
T
HWS TEMP. SENSOR BY
TEMPERATURE CONTROLS
CONTRACTOR. MOUNT IN
THERMOWELL.
TO WH LOOP
PRV
AIR/DIRT SEPERATOR
24JUL2025
VGLZ 242015
1 2 3 4 5
1 2 3 4 5
A
B
C
D
A
B
C
D
SHEET OF
Engineer/Consultants
Sheet Title
REPAIR HVAC
BLDG 105
NEW HEATING
HW BOILERS
PIPING &
CONTROLS
6 8
REVISIONS:
Project Number:
File:
Drawn By:
Designed By:
Checked By:
J. AUSTIN
Mark Date Description
PROJECT
Scale: N.T.S.
Date:
P:\CES_CECE Engineers\AutoCAD Users\CE Shared AutoCAD Settings\Templates\Template Graphics\127 WG.jpg P:\CES_CECD Site Development\ArtWork\127CE\CE Color PATCH small.jpg
T. RESH
T. RESH
RD
HEATING PLANT PIPING DIAGRAM
SCALE: N.T.S.
01 7/23/2025 GENERAL REVISION
AutoCAD SHX Text 127th WING/CIVIL ENGINEER
AutoCAD SHX Text
SELFRIDGE AIR
AutoCAD SHX Text
NATIONAL GUARD
AutoCAD SHX Text
BASE, MICHIGAN