This document is a detailed heating plant piping diagram for the Selfridge Air National Guard Base in Michigan, specifically for the repair of HVAC systems in Building 105. The diagram provides a comprehensive technical schematic for new heating hot water boilers, including components such as boiler circulation pumps, air/dirt separators, isolation valves, temperature and pressure relief valves, condensate traps, and acidic condensate routing to a neutralization tank. The piping diagram shows the interconnections and layout for high-efficiency condensing boilers with stainless steel heat exchangers, designed to be installed in a lead/lag configuration with associated pumping and control systems. The technical drawing is part of a solicitation (W50S8525BA003) for the Michigan Army National Guard, detailing the precise mechanical engineering specifications for replacing the existing heating boiler systems in the facility.

View the file

Other files

File Type Posted
OF1419 Abstract of Offers W50S8525BA003.pdf PDF
Solicitation Amendment W50S8525BA0030001 SF 30.pdf PDF
Sheet 5 of 8.pdf PDF
Sheet 3 of 8.pdf PDF
RFIs B105 HVAC.pdf PDF
Sheet 8 of 8.pdf PDF
SOW Addendum 01.pdf PDF
Sign In Sheet 7-16-2025.pdf PDF
W50S8525BA001 Pre-Bid Conference_Site Visit Slides 7-16-2025.pptx PPTX presentation

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HWRHWS

HWR

T

HWS HWRHWS

FS

PRESSURE

GAUGE

BLADDER

EXPANSION

TANK

SITE

GLASS

FLOOR MOUNTED BLADDER

EXPANSION TANK WITH

SHOTFEEDER AND AIR/DIRT

SEPARTOR AN MAKEUP

WATER CONNECTION.

FS

H W

R

H W

S

HWR TEMP. SENSOR BY

TEMPERATURE CONTROLS

CONTRACTOR. MOUNT IN

THERMOWELL.

B&G #87 VENT

OR EQUAL

THERMOMETER (TYP)

4" DRAIN COCK W/THREADED HOSE CONN.

AND CAP (TYP.)

STRAINER

PLUG VAVLE

BOILER CIRC. PUMP

NON-SLAM CHECK

VALVE

DIRT LEG (TYP.)

TO FLOOR DRAIN

EX. FLOOR DRAIN

CONDESATE ACID WASTE

NEUTRALIZATION TANK

(BY BOILER

MANUFACTURER)

TAP OFF

SIDE

PRESSURE GAUGE

CHECK

VALVEBOILER FLOW SWITCH.

MOUNT IN PIPE WELL

BUTTERFLY

ISOLATION VALVE

(TYP.)

BP-1

BP-2

HWR TO

SYSTEM

B-2 B-1

BOILER CIRC.

PUMP

EXTEND TO FLOOR

DRAIN

CONDENSATE TRAP

UNION (TYP.)

REDUCER AS

REQUIRED (TYP.)

LOCAL VENT W/

GOOSNECK

3/4" ACIDIC CONDENSATE

ROUTE TO ACID

NEUTRALIZATION TANK

1-1 4"G

CIRCUIT SETTER

BALANCING VAVLE

TEMPERATURE AND PRESSURE RELIEF

VALVE. PIPE FULL SIZE TO FLOOR DRAIN

3" CONCRETE

HOUSEKEEPING PAD

VENT STACK

COMBUSTION AIR INTAKE

BP-3

BP-4

T

HWS TEMP. SENSOR BY

TEMPERATURE CONTROLS

CONTRACTOR. MOUNT IN

THERMOWELL.

TO WH LOOP

PRV

AIR/DIRT SEPERATOR

24JUL2025

VGLZ 242015

1 2 3 4 5

1 2 3 4 5

A

B

C

D

A

B

C

D

SHEET OF

Engineer/Consultants

Sheet Title

REPAIR HVAC

BLDG 105

NEW HEATING

HW BOILERS

PIPING &

CONTROLS

6 8

REVISIONS:

Project Number:

File:

Drawn By:

Designed By:

Checked By:

J. AUSTIN

Mark Date Description

PROJECT

Scale: N.T.S.

Date:

P:\CES_CECE Engineers\AutoCAD Users\CE Shared AutoCAD Settings\Templates\Template Graphics\127 WG.jpg P:\CES_CECD Site Development\ArtWork\127CE\CE Color PATCH small.jpg

T. RESH

T. RESH

RD

HEATING PLANT PIPING DIAGRAM

SCALE: N.T.S.

01 7/23/2025 GENERAL REVISION

AutoCAD SHX Text 127th WING/CIVIL ENGINEER

AutoCAD SHX Text

SELFRIDGE AIR

AutoCAD SHX Text

NATIONAL GUARD

AutoCAD SHX Text

BASE, MICHIGAN

File details come from the government source that posted it. Updated .