This document contains a request for information and details regarding a federal contract opportunity for the renovation of Building 119. The project involves renovations to be completed at Building 119 located at 159th Fighter Wing in New Orleans, Louisiana, with an estimated value between $1 million and $5 million. The period of performance is 18 months. The requirement is set aside 100% for small businesses with a size standard of $39.5 million. The NAICS code is 236220 for commercial and institutional building construction. The RFI provides specifications for various light fixtures and electrical components needed for the renovation, including mounting heights, luminaire schedules, and sizing for wire gutters and external power interrupters. It also includes details on the pre-bid site visit scheduled for August 12, 2022 and encourages prospective offerors to attend.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

· Drawing E-101 key note 2 and 3 calls for light fixture type P and PE to be mount at different elevation . Luminaire schedule on drawing E-611 call for the P and PE to me mounted at 13-foot 4-inch AFF. Which is the correct mounting height for the P and PE light fixtures?

Schedule calls “PENDANT, MT 13'-4'' AFF, UIO”. If the room has no keynote the mounting height is what is listed in the schedule. If it has a keynote with a different height, mount to that.

· Drawing E-101 the type V wall mounted light fixture in restroom There no luminaire requirements requirement shown in drawing. Please provide the luminaire for type V light fixture.

Vanity Fixture Basis of Design:

1. HOUSING, FINISH & REFLECTORS - - BRUSHED NICKEL HOUSING WITH SQUARE ACRYLIC DIFFUSER.

2. LAMPS - LED LAMP TO HAVE 3000K KELVIN COLOR TEMPERATURE OF LIGHT WITH A CRI OF 80 OR GREATER AND AN L70 OF 50,000 HOURS OR GREATER PRODUCING 1300 LUMENS.

3. DRIVER - LED DRIVER TO BE 277 VOLT. FIXTURE TO HAVE A DIGITALLY ADDRESSABLE DRIVER AND/OR LOW VOLTAGE DIGITAL ADDRESSABLE CONTROL DEVICE.

4. CERTIFICATION - UL LISTED FOR DAMP LOCATION SPACE.

5. WARRANTY - PROVIDE A MINIMUM 10-YEAR WARRANTY BY MANUFACTURER.

6. FIXTURE TYPE -TYPE ' V ‘- 1300 LUMENS, 2’ VANITY

· Drawing ES 101 detail B4 is showing a wire gutter to be install on top of the MDP for the service entrance conductors. There six additional feeders for panelboard and transform that must enter the top of the MDP. What size wire gutter is required to accommodate the service entrance conductors and feeders?

Service entrance laterals must be in their own raceway.

· Drawing E-402 key note 8 is calling for providing external power interrupter for under-voltage. The no information provided on the drawings or specification provided for external power interrupter for under-voltage. Please all information required to include manufactures, voltage and amperage for the external power interrupter for under-voltage?

Provide an external power interrupter that meets the requirements of equipment.