FAKZ189366 DSP Facility Addendum No. 1 SIGNED.pdf
PDF 7 MB Posted
- Attached to
- Deployable Spare Parts Warehouse Vertical Construction Solicitation Federal contract opportunity
- Solicitation number
- W50S6N-25-B-A010
About this file
This is Addendum No. 1 to the F-35 Deployable Parts Storage Facility construction project (FAKZ182366) dated August 4, 2025. The addendum revises multiple construction drawings and specifications for a facility at Dannelly Field, Montgomery, AL being built by Seay Seay & Litchfield, P.C.
The addendum updates 13 drawing sheets with revised dates ranging from July 30 to August 1, 2025, including site layout plans, grading and drainage, architectural plans, structural details, fire sprinkler systems, plumbing, mechanical, and electrical drawings. Additionally, 10 specification sections are being replaced with revised versions dated July 30-31, 2025, covering areas such as project information, regulatory requirements, commissioning, concrete work, doors and frames, fire protection specialties, sprinkler systems, plumbing, HVAC, and fire detection systems. The revised drawings include detailed floor plans, electrical schematics, mechanical layouts, and fire safety plans for the approximately 6,000 square foot storage facility addition. Key features shown include storage areas, electrical systems, HVAC equipment, fire suppression systems, and security provisions for F-35 fighter jet deployable parts storage operations.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| DSP ABSTRACT Final KO Signed.pdf | ||
| DSP Bid Opening Sign In Sheet.pdf | ||
| FAKZ189366DSP Facility RFI 1 Response SIGNED.pdf | ||
| Solicitation Amendment W50S6N25BA0100001 SF 30.pdf | ||
| PreBid DSP Slides.pptx | PPTX presentation | |
| W50S6N25BA010 PreBid Conference Sign-in Roster.pdf | ||
| FAKZ189366 TYPE B-3 SPECS VOL I SIGNED.pdf | ||
| FAKZ189366 TYPE B-3 SPECS VOL II SIGNED UPDATED.pdf | ||
| Dannelly Field Entry Authorization List.pdf | ||
| FAKZ189366 TYPE B-3 DRAWINGS SIGNED.pdf | ||
| Solicitation - W50S6N25BA010 V7.pdf | ||
| FAKZ189366 TYPE B-3 SPECS VOL I SIGNED.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F-35 Deployable Parts Storage Facility FAKZ182366 ADDENDUM NO. 1 Page 1 of 3 Seay Seay & Litchfield, P.C. 4 August 2025
Date: 4 August 2025
To: Major Jeremy Hendrick
Subject: ADDENDUM NO. 1
Project: F-35 DEPLOYABLE PARTS STORAGE FACILITY
Job #: ANG# FAKZ182366
SSL# 19084
From: David Donovan
The Plans and Specifications for the F35 Deployable Parts Storage Facility (FAKZ182356), dated 10 April 2025 are amended as follows. (Where there are conflicts between the plans and specifications and the addendum, this addendum shall govern).
Item No. 1: Refer to Drawings. Delete drawing sheet C2.1 “DSP Site Layout Plan” and replace with included drawing sheet C2.1 with a revised date of 30 July 2025.
Item No. 2: Refer to Drawings. Delete drawing sheet C3.1 “DSP Site Grading and
Drainage Plan” and replace with included drawing sheet C3.1 with a revised date of 30 July 2025.
Item No. 3: Refer to Drawings. Delete drawing sheet C6.1 “DSP Site Details” and replace with included drawing sheet C6.1 with a revised date of 30 July 2025.
Item No. 4: Refer to Drawings. Add included drawing sheet A0.1 “Phasing/ Site
Access” with a revised date of 30 July 2025.
Item No. 5: Refer to Drawings. Delete drawing sheet LS1.0B “Life Safety Plan” and replace with included drawing sheet LS1.0B with a revised date of 30 July
Item No. 6: Refer to Drawings. Delete drawing sheet A2.1B “Plans – DSP Storage” and replace with included drawing sheet A2.1B with a revised date of 30 July 2025.
Item No. 7: Refer to Drawings. Delete drawing sheet A3.0B “DSP Schedules” and replace with included drawing sheet A3.0B with a revised date of 30 July
ADDENDUM NO. 1 Page 2 of 3 Seay Seay & Litchfield, P.C. 4 August 2025
Item No. 8: Refer to Drawings. Delete drawing sheet S0.1B “General Notes –
Schedules – Typical Details – DPS Storage” and replace with included drawing sheet S0.1B with a revised date of 1 August 2025.
Item No. 9: Refer to Drawings. Delete drawing sheet FP1.1B “Fire Sprinkler Floor
Plan” and replace with included drawing sheet FP1.1B with a revised date of 31 July 2025.
Item No. 10: Refer to Drawings. Delete drawing sheet P1 .1B “Plumbing Waste Vent and Gas Piping Floor Plan – DSP Storage” and replace with included drawing sheet P1 .1B with a revised date of 31 July 2025.
Item No. 11 Refer to Drawings. Delete drawing sheet M2.1B “Mechanical Floor Plan
– DSP Storage” and replace with included drawing sheet M2.1B with a revised date of 31 July 2025.
Item No. 12: Refer to Drawings. Delete drawing sheet E0.2B “Electrical Details” and replace with included drawing sheet E0.2B with a revised date of 30 July
Item No. 13: Refer to Drawings. Delete drawing sheet E1.1B “DSP Storage Electrical
Plans” and replace with included drawing sheet E1.1B with a revised date of 30 July 2025.
Item No. 14: Refer to Specifications. Delete specification section 00 0102 – Project
Information and Summary. Delete specification section 00 0102 and replace it with the attached specification section 00 0102 with a revised date of 30 July 2025. Revisions are noted with bold, italicized, and struck through text.
Item No. 15: Refer to Specifications. Delete specification section 01 4100 – Regulatory
Requirements. Delete specification section 01 4100 and replace it with the attached specification section 01 4100 with a revised date of 30 July 2025.
Revisions are noted with bold, italicized, and struck through text.
Item No. 16: Refer to Specifications. Delete specification section 01 9113 – General
Commissioning Requirements. Delete specification section 01 9113 and replace it with the attached specification section 01 9113 with a revised
Item No. 17: Refer to Specifications. Delete specification section 03 3000 – Cast-in-
Place Concrete. Delete specification section 03 3000 and replace it with the attached specification section 03 3000 with a revised date of 31 July 2025. Revisions are noted with bold, italicized, and struck through text.
ADDENDUM NO. 1 Page 3 of 3 Seay Seay & Litchfield, P.C. 4 August 2025
Item No. 18: Refer to Specifications. Delete specification section 08 1113 – Hollow
Metal Doors and Frames. Delete specification section 08 1113 and replace it with the attached specification section 08 1113 with a revised date of 30 July 2025. Revisions are noted with bold, italicized, and struck through text.
Item No. 19: Refer to Specifications. Delete specification section 10 4400 – Fire
Protection Specialties. Delete specification section 10 4400 and replace it with the attached specification section 10 4400 with a revised date of 30
Item No. 20: Refer to Specifications. Delete specification section 21 1313 – Wet-Pipe
Fire-Suppression Sprinklers. Delete specification section 21 1313 and replace it with the attached specification section 21 1313 with a revised
Item No. 21: Refer to Specifications. Delete specification section 22 0514 – Common
Work Results for Plumbing. Delete specification section 22 0514 and replace it with the attached specification section 22 0514 with a revised
Item No. 22: Refer to Specifications. Delete specification section 23 0500 – General
HVAC Requirements. Delete specification section 23 0500 and replace it with the attached specification section 23 0500 with a revised date of 30
Item No. 23: Refer to Specifications. Delete specification section 28 3111 – Fire
Detection, Evacuation, and Mass Notification. Delete specification section 28 3111 and replace it with the attached specification section 28 3111 with a revised date of 30 July 2025. Revisions are noted with bold, italicized, and struck through text.
End of Addendum #1
This page intentionally left blank
R E
F
EXISTING BASE
SUPPLY
ACCESS TO PROJECT SITE
AND LAYDOWN AREA
RESERVED FOR GOVERNMENT
PARKING ONLY - CONSTRUCTION
PARKING NOT PERMITTED
RESERVED FOR GOVERNMENT
PARKING ONLY - CONSTRUCTION
PARKING NOT PERMITTED
DSP ADDITION
SIMULATOR BUILDING
BLDG 1109
PR
O
JE
C T
S
IT
E
AN
D
LA
YD
O W
N
AR
EA
R
IC
H A
R D
S O
N R
O A
D
C O
NSTRU
C
TIO
N PARKING
AND
LAYD
O W
N AREA
PERIMETER ROAD
P E
R
IM
E T
E R
R O
A D
EXTENTS OF
PERIMETER FENCE
R
IC
H A
R D
S O
N R
O A
D
NO
C
O
NS
TR
UC
TI
O N
PA
RK
IN
G/
A
CC
ES
S
AL
LO
W
ED
NO CONSTRUCTION PARKING/ ACCESS ALLOWED
1 EXISTING FIRE DEPARTMENT ACCESS PATHWAY TO REMAIN OPEN TO THE GREATEST EXTENT
POSSIBLE. COORDINATE WITH BASE FIRE DEPARTMENT PRIOR TO CLOSING ACCESS ROUTE
AS REQUIRED TO CONSTRUCT PARKING LOT. LIMIT DURATION ACCESS DRIVE IS
INACCESSIBLE FOR GOVERNMENT USE TO THE GREATEST EXTENT POSSIBLE.
SITE ACCESS SPECIFIC NOTES Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n W W W .S
SL
A R C H .C O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E
SI
G N
19084
D E
PL
O
Y A
B L
E P
A R
T S
ST
O
R A
G E
F A
C
IL
IT
Y
A0.1
PHASING/ SITE
ACCESS
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A L
10 April, 2025
JLJ/CF/NJ
FEL
1" = 20'-0"A0.1
1 SITE ACCESS
Rev. Description Date
1 ADD #1 7-30-25
HANDICAP ACCESSIBLE EXIT LOCATION
EXIT TRAVEL PATH
FIRE EXTINGUISHER IN SEMI-RECESSED CABINET
FEC
ELECTRIC WATER COOLER - SEE PLUMBING
EWC
2 HR FIRE RATED WALL (UL #U905)
EMERGENCY EXIT SIGNAGE
SYMBOLS LEGEND
FIRE EXTINGUISHER WITH BRACKET
FEB
2 HR FIRE RATED FLOOR/CEILING ASSEMBLY
(UL #G505)
1 HR FIRE RATED WALL (UL #914)
1 HR FIRE RATED FLOOR/CEILING ASSEMBLY
(UL # G717)
DASHED LINE INDICATES LOCATION OF 1-HOUR
RATED WALL (UL # U404) LOCATED ON MEZZANINE
LEVEL SEPARATING WAREHOUSE FROM ADMIN
SPACE
BUSINESS B OCCUPANCY GROUP (IBC 2018)
150 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
STORAGE S-1 GROUP (IBC 2018)
300 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
STORAGE S-1 OCCUPANCY GROUP (IBC 2018)
300 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
STORAGE S-1 OCCUPANCY GROUP (IBC 2018)
500 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
BUSINESS B OCCUPANCY GROUP (IBC 2018)
50 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
BUSINESS B OCCUPANCY GROUP (IBC 2018)
15 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
OCCUPANT LOAD
REQUIRED DOOR WIDTH
STORAGE H-2 GROUP (IBC 2018)
300 SF PER OCCUPANT PER NFPA 101
ORIDINARY HAZARD (NFPA 101)
SMOKE PARTITION AND CEILING ENCLOSURE
22757 SF
Storage S-1
5965 SF
Storage S-1
1723 SF
B (CONCENTRATED)
FEC
FEC
EXIT ACCESS DISTANCE (1/3 DIAGONAL MINIMUM)
178' - 2 3/8"
EXIT
ACCESS DIAGONAL
227' - 2 1/16"
COMMON PATH
67'
COMMON PATH
47'
C O
M M
O N P
AT
H
EXIT TRAVEL DISTANCE
166'
EXIT ACCESS DIAGONAL (W
ITH DSP STORAGE)
281' - 1 5/16"
546 SF
B (CONCENTRATED)
456 SF
B (CONCENTRATED)
305 SF
B (CONCENTRATED)
4448 SF
BUSINESS
(UNCONCENTRATED)
1000 SF
B (CONFERENCE)
1536 SF
HAZARDOUS
STORAGE
194 SF
STORAGE
(IT)
220 SF
STORAGE
(MECHANICAL)
41 OCCUPANTS
7 OCCUPANTS
O C C
U
PA
N
TS
1 OCCUPANT
1 OCCUPANT
OCCUPANT
OCCUPANT
OCCUPANT
OCCUPANT
OCCUPANT
OCCUPANT
2 OCC.
OCCUPANTS
2 OCCUPANTS 2 OCCUPANTS
10 OCCUPANTS
OCCUPANTS
1 OCCUPANT
OCCUPANT
24 OCCUPANTS
12 OCCUPANTS
23 OCCUPANTS
3 OCCUPANTS
35 OCCUPANTS
2 OCCUPANTS
1 OCC.
3 OCCUPANTS2 OCCUPANTS
10 OCCUPANTS
1 OCC
1 OCC
12 OCCUPANTS
1 OCCUPANTS 1 OCCUPANT 1 OCCUPANT 1 OCCUPANT 1 OCCUPANT 1 OCCUPANT 2 OCCUPANTS 1 OCCUPANT 1 OCCUPANT 1 OCCUPANT 1 OCCUPANT
1 OCC 1 OCC
1 OCC
3.3
3.
7.35
4949 7.8
1.
2.25
0.9
0.9 66
1.65
1.65
1.5
1.95
2.7
6.45
1.8
12.15
5.
853939
90 MIN 90 MIN 90 MIN 90 MIN 90 MIN 90 MIN
45 MIN
45 MIN
45 MIN
90 MIN
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E
SI
G N
19084
D E
PL
O
Y A
B L
E P
A R
T S
ST
O
R A
G E
F A
C
IL
IT
Y
LS1.0B
LIFE SAFETY PLAN
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A L
10 April, 2025
JLJ/CF/NJ
FEL
Applicable Codes:
Building Code..............UFC 1-200-01 / 2018 INTERNATIONAL
BUILDING CODE
Structural Code...........3-301-01 Plumbing Code............3-420-01 Mechanical Code.........3-420-01 Fire Code..................3-600-01 Electrical Code...........3-501-01 Energy Code..............1-200-02 Accessibility Code......2010 ADA STANDARDS Life Safety Code........3-600-01 / NFPA 101
IBC Chapter 3 and UFC 3-600-01 Occupancy & Use:
NFPA 101 Chapter 6:
• See Legend on Life Safety Plan
IBC Chapter 4 - Special Detailed Requirements:
• NOT APPLICABLE
IBC Chapter 5 - General Building Heights & Areas:
• Construction Type = II-B, FULLY SPRINKLED, GROUP S-1, B, H-2
SEPARATED
• Allowable Building Height TABLE 504.3
GROUP S-1= 75 FEET ABOVE GRADE PLANE
GROUP B = 75 FEET ABOVE GRADE PLANE
GROUP H-2 = 55 FEET ABOVE GRADE PLANE
• Allowable Number of Stories Above Grade Plane (PER TABLE 504.4)
GROUP S-1 - 3 STORIES ABOVE GRADE PLANE
GROUP B = 4 STORIES ABOVE GRADE PLANE
GROUP H-2 = 1 STORY ABOVE GRADE PLANE
• Tabular Building Area (PER TABLE 506.2)
GROUP S-1 = 70,000 SQUARE FEET
ACTUAL GROUP S-1 AREA = 29,244
GROUP B = 92,000 SQUARE FEET
ACTUAL GROUP B AREA = 8,452
GROUP H-2 = 7,000 SQUARE FEET
ACTUAL GROUP H-2 AREA = 1,453
• Allowable Building Area (PER SECTION 508.4.2)
S-1 = 29,244/70,000 = .42 B = 8,452/92,000 = .09 H-2 = 1,453/7,000 = .21
.42+.09+.21=.72, SUM OF RATIOS IS LESS THAN 1
• Fire Separation Requirements Per Table 508.4
OCCUPANCIES RATING (HR)
B | S-1 0 S-1 | H-2 2
• Incidental Use Areas (PER TABLE 509) See occupancy table.
IBC Chapter 6 Types of Construction:
• Construction Type: II-B
• Fire Ratings (PER TABLE 601) as Follows (Except where noted otherwise)
Primary Structural Frame.............................. 0 HOUR Bearing Walls (Interior & Exterior)...................0 HOUR Non-Bearing Walls and Paritions (Interior)........0 HOUR Floor Construction and Secondary Members...0 HOUR Roof Construction and Secondary Members....0 HOUR
• Required Fire Rating (Per Table 602)
OCCUPANCY FIRE SEPARATION REQUIRED
TYPE (ACTUAL) SEPARATION
S-1 >30'-0" 0 HR
B 27'-6" 0 HR
H-2 >30'-0" 0 HR
UFC 3-600-01(replaces IBC Chapter 9) - Fire Protection Systems:
• SECTION 9-1 - EMERGENCY VEHICLE ACCESS
1. Facility REQUIRES one means of all-weather emergency vehicle ground access in accordance with 9-1.1
2. Facility REQUIRES aerial apparatus access in accordance with 9-1.2
• SECTION 9-2 - FIRE FLOW FOR FACILITIES
1. Fire Flow for sprinkler system is provided in accordance with 9-2.1
• SECTION 9-3 - SERVICE MAINS AND LATERALS
1. Fire hydrants are provided in accordance with 9-3.5.8 A. Hydrants are spaced at 300 ft maximum B. Hydrant to be located within 150' of Fire
Department Connection
• SECTION 9-5 - FIRE PUMPS
1. A fire pump IS required to meet fire protection demand, and is provided in accordance with 9-5 adjacent to building 1201.
2. Existing fire pumps (2-2,000 gpm pumps) and existing 75,000 gallon on site water storage will serve the facility.
• SECTION 9-7 - AUTOMATIC SPRINKLER SYSTEMS
1. Per 9-7.2.1, an automatic sprinkler system IS required
• SECTION 9-10 - STANDPIPE SYSTEMS
1. Per 9-10, a standpipe system IS NOT required
• SECTION 9-17 - PORTABLE FIRE EXTINGUISHERS
1. Per 9-17.1, portable fire extinguishers ARE required
NFPA CHAPTER 8 - Fire and Smoke Protection Features:
• Maximum Exterior Wall Openings (PER SECTION IBC 705)
Fire Separation: Degree of Opening Protection: Allowable Area:
GREATER THAN 25 FT UNPROTECTED, SPRINKLERED , (UP, S) NO LIMIT
• Fire Walls (Per NFPA 8.3.2) No fire walls are present within the scope of the project
• Shaft Enclosure (Per NFPA 8.3.1/7.3.1.2) No shaft enclosure is present
• Opening Protectives (Per NFPA 8.3.4) Type of Assembly Assembly Rating Required Opening Protection (Door/Sidelite)
FIRE BARRIER 2 HOURS 1-1/2 HOUR/2 HOUR
FIRE BARRIER 1 HOUR 3/4 HOUR/ 3/4 HOUR
• Concealed Spaces (Per Section 8.6.11) Not Applicable
• See Legend on Life Safety Plan for Applicable UL Assemblies to be provided.
IBC Chapter 8, UFC 3-600-01, NFPA 101 - Interior Finishes:
• Finish Material Rating Requirements (Per NFPA 101)
BUSINESS (CHAPTER 38)
Exits and Exit Access Corridors
Interior Wall and Ceiling Finish - CLASS A OR B (38.3.3.2.1) Interior Floor Finish - CLASS I OR CLASS II (38.3.3.3.2)
Areas other than Exits and Exit Access Corridors Interior Wall and Ceiling Finish - CLASS A, B, OR C (38.3.3.2.2)
STORAGE (CHAPTER 42)
Exits and Exit Access Corridors
Interior Wall and Ceiling Finish - CLASS A, B, OR C (42.3.3.2) Interior Floor Finish - CLASS I OR CLASS II (42.3.3.3.1)
Areas other than Exits and Exit Access Corridors Interior Wall and Ceiling Finish - CLASS A, B, OR C (42.3.3.2) Interior Floor Finish - NO REQUIREMENT (42.3.3.3.2)
* THE CONTRACTOR SHALL PROVIDE A QUALIFIED FIRE PROTECTION ENGINEER (QFPE) AS DEFINED BY UFC 3-600-01 TO BE THE QFPE FOR THE PROJECT. THE QFPE SHALL WORK FOR THE CONTRACTOR
AND BE RESPONSIBLE FOR PRODUCING, REVIEWING, AND STAMPING ALL SHOP DRAWINGS AND
MATERIAL SUBMITTALS FOR THE FIRE ALARM/MNS SYSTEMS. THE QFPE SHALL PROVIDE INSPECTIONS DURING CONSTRUCTION TO ENSURE SYSTEMS COMPLIANCE. THE QFPE SHALL PERFORM A PRE-FINAL INSPECTION AND PROVIDE A REPORT FOR AHJ REVIEW. THE QFPE MUST ALSO BE INVOLVED IN THE FINAL INSPECTION WITH THE GOVERNMENT AHJ. THE QFPE MUST MONITOR THE INSTALLATION OF THE FIRE ALARMS/MNS SYSTEM AND CERTIFY IN WRITING TO THE GOVERNMENT AHJ THAT THE SYSTEMS
HAVE BEEN CONSTRUCTED AND OPERATE AS INTENDED TO COMPLY WITH UFC 3-600-01AND UFC
4-021-01.*
NFPA Chapter 7 (replaces IBC Chapter 10) - Means of Egress:
• Occupancy Load (PER TABLE 7.3.1.2):
See Occupancy Table
• Egress Capacity Sizing (PER TABLE 7.3.3.1)
See Code Calculations Table(s) See life safety plan for individual room egress analysis
• Minimum Stair Width (PER SECTION 7.3.3.1) See Code Calculations Table(s)
• Number of Means of Egress (PER SECTION 7.4.1) Total Number of Exits Required
Business Occupancy (CHAPTER 38)
GROUND FLOOR - 2 EXITS REQUIRED
Storage Occupancy (CHAPTER 42)
GROUND FLOOR - 1 EXITS REQUIRED
• Common Path of Egress Travel Distance Business Occupancy (CHAPTER 38)
100 ft per 38.2.5.3.1 Storage Occupancy (CHAPTER 42)
100 feet per TABLE 42.2.5 Other (CHAPTER 7)
Mechanical Equipment Rooms, Boiler Rooms, and Furnace Rooms - 100 ft per 7.12.1
• Exit Access Travel Distance Business Occupancy (CHAPTER 38)
300 FT per 38.2.6.3 See life saftey plan for exit access travel distance
Storage Occupancy (CHAPTER 42) 400 feet per TABLE 42.2.5
NFPA Chapter 7 (CONTINUED)
• Corridors
Occupancy Type (B) requires:
NO FIRE RATING REQUIRED FOR CORRIDOR WALLS
See life saftey Plan for locations of rated corridors
Occupancy Type (S-1) requires:
NO FIRE RATING REQUIRED FOR CORRIDOR WALLS PER 42.3.6
See life saftey Plan for locations of rated corridors
Minimum Corridor Width Business Occupancy (CHAPTER 38) 44 inches per 38.2.3.2 Storage Occupancy 36 inches per 7.3.4.1
Dead End Corridors Business Occupancy (CHAPTER 38)
Maximum of 50 feet per 38.2.5.2.1 Storage Occupancy (CHAPTER 42)
Maximum of 100 feet per TABLE 42.2.5
3/32" = 1'-0"LS1.0B
1 DSP LIFE SAFETY PLAN
FIRST FLOOR PLAN CODE CALCULATIONS
Name
Occupancy Calculations Egress Width Calculations
Area (SF) Occupancy Factor (SF per Occupant)
Factor Type
Total Occupant Load (Occupants)
Other Egress Component Width
Calculated Width (Other
Egress Components)
(Inches)
Required Egress Width
(Inches)
B (CONCENTRATED) 1723 SF 50 SF GROSS 35.00 0.2 7.00 44
B (CONCENTRATED) 546 SF 50 SF GROSS 11.00 0.2 2.20 44
B (CONCENTRATED) 456 SF 50 SF GROSS 10.00 0.2 2.00 44
B (CONCENTRATED) 305 SF 50 SF GROSS 7.00 0.2 1.40 44
B (CONFERENCE) 1000 SF 15 SF NET 67.00 0.2 13.40 44
BUSINESS (UNCONCENTRATED) 4448 SF 150 SF GROSS 30.00 0.2 6.00 44
HAZARDOUS STORAGE 1536 SF 500 SF GROSS 4.00 0.2 0.80 44
STORAGE (IT) 194 SF 300 SF GROSS 1.00 0.2 0.20 44
STORAGE (MECHANICAL) 220 SF 500 SF GROSS 1.00 0.2 0.20 44
Storage S-1 22757 SF 500 SF GROSS 46.00 0.2 9.20 44 Storage S-1 5965 SF 500 SF GROSS 12.00 0.2 2.40 44
39149 SF 224.00 44.80
PLUMBING FIXTURE CALCULATIONS
Name Male
Occupancy Female
Occupancy
Plumbing Fixtures Required Water Closets
Required Lavatories Required Drinking Fountains
Req.Men Women Men Women
BUSINESS / STORAGE 58 14 2.9 0.7 2.9 0.7 0.96
58 14
Rev. Description Date
MCJ
M C J
M C J
M C J
M C J
MCJ
GCJ
MCJ
5514 SF
DSP STORAGE
D101
1.1 1.2
A4.1B
A4.1B
A4.1B
32' - 4" 21' - 4" C
O O
R D
W
/ E
XI
S
TI
N G
D O
O R
/8
1' - 7 1/2"
A.1
A.7
24' - 4" 10' - 8"
D101 D102
D104
D105
DS
DS
BD BD
BD BD
BD
BD
102 SF
EGRESS
D102
A5.1B
0.1
A.2
A.3
A.4
A.5
A.6
6' - 0"
N8
N8
N4
DS
A5.1B
0.15
16' - 0"
/2
/ 1 '-0
/2
/ 1
'-0
1.1 1.2
A.1
A.7
DS
DS
A5.1B
0.1
A.2
A.3
A.4
A.5
A.6
NONVENTIILATING
RIDGE CAP
A5.1B
DS
A5.1B
0.15
HVLS FAN - SEE
MECHANICAL
EXPOSED INSULATED METAL ROOF
PANEL - PAINT STRUCTURE IN THIS
AREA
PAINT EXPOSED CEILING
AND STRUCTURAL SYSTEM
IN THIS AREA
SILL
PLAN
HEAD
CONFIRM 1 " REQUIRED CLEAR
SPACE FOR DEFLECTION
PROVIDE FLEXIBLE CLOSURE
STRIPS AS REQUIRED IN DECK
FLUTES
SEE STRUCTURAL FOR TOP OF
WALL BRACING
XX
TAG INDICATES WALL TYPE
OVER CMU MASONRY
**NOTE: IF WALL IS SCHEDULED TO
RECEIVE TILE, PROVIDE CONCRETE
BOARD AND WATERPROOFING FOR
TILE INSTALLATION. REFER TO FINISH
SCHEDULE, INTERIOR ELEVATIONS AND
SECTIONS, AND GYPSUM BOARD
ASSEMBLIES SPECIFICATIONS FOR
TYPES AND OTHER
SUBSTRATE/FURRING REQUIREMENTS**
TYPE N
WALL TAG
# SPECIFIC NOTE TAG
GYPSUM CONTROL JOINT - REFER TO DETAIL 6/A2.4
FLOOR PLAN LEGEND
DOWNSPOUT AND BOOTDS
DOOR TAG
SECTION/DETAIL TAG
X
AX.X
CURTAIN WALL/STOREFRONT TAG
202A
1i
BOLLARDBD
REMOVABLE BOLLARDRB
MASONRY CONTROL JOINT - REFER TO S0.1, PROVIDE
TYPE V SEALANT.
PARTITION TAG LEGEND
1. THE FIRST CHARACTER IN THE TAG REFERENCES THE PARTITION TYPE
2. THE SECOND CHARACTER IN THE TAG REFERENCES THE THICKNESS OF
THE STRUCTURE (CMU, METAL STUD, WOOD, ETC.)
* REFER TO INTERIOR ELEVATIONS AND ASSOCIATED WALL SECTIONS
AND DETAILS FOR ADDITIONAL FURRING REQUIREMENTS AND FINISHES
NOT SHOWN ON WALL TYPE PLAN SCHEDULE
**NOTE - REFER TO LIFE SAFETY PLAN FOR PARTITION RATINGS**
1 2*
CEILING MATERIAL LEGEND
LIGHT FIXTURE - SEE
ELECTRICAL
SUPPLY DIFFUSER -
SEE MECH.
RETURN DIFFUSER -
SEE MECH.
ROOF PLAN LEGEND
STANDING SEAM METAL ROOF
(LINES FOR SEAMS ON METAL ROOF TYPES,
REFER TO SPECS FOR PANEL SIZES)
DOWNSPOUT + BOOTS (BOOTS NOT SHOWN)
(NOTE: REFER TO ELECTRICAL FOR LIGHTNING
PROTECTION - COORDINATE AS REQUIRED)
DS
VTR VENT TO ROOF - SEE MECHANICAL/ PLUMBING & 5/A5.1B, AND 6/A5.1B
NOTE 1 - LOCATE ALL PENETRATIONS THROUGH METAL ROOF PANELS AT MIDPOINT IN ROOF PANEL
NOTE 2 - REFER TO ELECTIRCAL FOR LIGHTNING PROTECTION - COORDINATE AS REQUIRED
GENERAL NOTES
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n W W W .S
SL
A R C H .C O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E
SI
G N
19084
D E
PL
O
Y A
B L
E P
A R
T S
ST
O
R A
G E
F A
C
IL
IT
Y
A2.1B
PLANS - DSP
STORAGE
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A L
10 April, 2025
JLJ/CF/NJ
FEL
1/8" = 1'-0"A2.1B
1 DSP STORAGE ADDITION - FLOOR PLAN
1/8" = 1'-0"A2.1B
2 DSP STORAGE ADDITION - ROOF PLAN
1/8" = 1'-0"A2.1B
3 DSP REFLECTED CEILING PLAN
GENERAL NOTES:
1. REFER TO EXTERIOR WALL SECTIONS FOR WALL ASSEMBLIES. .
2. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL WALLS ( INCLUDING STRUCTURE, FINISH, AND INSULATION) SHALL EXTEND TO
UNDERSIDE OF ROOF DECK ABOVE.
3. ALL WALLS TO RUN FULL HEIGHT TO STRUCTURE ABOVE. COORDINATE OPENINGS TO ACCOMODATE MECHCANICAL. SEAL ALL
PLUMBING, MECHANICAL, ELECTRICAL, AND FIRE PROTECTION PENETRATIONS.
4. FOR EXTERIOR WALL EXPANSION JOINTS SEE EXTERIOR ELEVATIONS.
DIMENSION NOTES: ALL DIMENSIONS ARE MEASURED AS FOLLOWS:
- INTERIOR STUD WALLS ARE DIMENSIONED TO THE CENTER LINE OF THE WALL
- EXTERIOR WALLS ARE DIMENSIONED TO THE OUTSIDE FACE OF THE STUDS OR CMU.
N8 7 5/8" N4 3 5/8"
TYPE STRUCTURE THICKNESS
Rev. Description Date
(Aluminum Storefront System)
B1
Opening Type B1
75' - 0"
14' - 0"
3' - 9" 3' - 9" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 3' - 9" 3' - 9"
IG-3 IG-3 IG-3 IG-3 L IG-3 IG-3 IG-3 IG-3 L IG-3 IG-3 IG-3 IG-3
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
A3.0B
CR
COILING DOOR
(ELECTRIC OPERATION)
AS SCHEDULED
DOOR WIDTH
A S S
C H
ED
U
LE
D
D O
O R
H
EI
G H T
NL HM INT
HOLLOW METAL
DOOR WITH
NARROW LIGHT
" M
A X
AS SCHEDULED
DOOR WIDTH
A S S
C H
ED
U
LE
D
D O
O R
H
EI
G H T
NL HM EXT
INSULATED HOLLOW
METAL DOOR WITH
NARROW LIGHT
" M A X
D O
O R
H
EI
G H T
A S S
C H
ED
U
LE
D
DOOR WIDTH AS SCHEDULED
DOOR TYPE SCHEDULE
HM F2
HOLLLOW METAL
FRAME 4" HEAD
HM F2 EXT
INSULATED HOLLOW
METAL FRAME 4"
HEAD
0' - 2"
AS SCHEDULED
DOOR WIDTH 0' - 2"
A S S
C H
ED
U
LE
D
D O
O R
H
EI
G H T
0' - 2"
AS SCHEDULED
DOOR WIDTH 0' - 2"
A S S
C H
ED
U
LE
D
D O
O R
H
EI
G H T
HM EXT F3
COILING ROLLING
DOOR FRAME
A S S
C H
ED
U
LE
D
D O
O R
H
EI
G H T
0' - 2"
AS SCHEDULED
DOOR WIDTH 0' - 2"
FRAME TYPE SCHEDULE
CMU WALL
SEE STRUCTURAL FOR CELL JAMB
REINFORCEMENT REQUIREMENTS
MASONRY "T" ANCHOR, SEE
SPECIFICATIONS FOR
SPACING REQUIREMENTS
VARIES - VERIFY
CONT. SEALANT, TYP.
EA. SIDE
HOLLOW MTL. FRAME, SEE
DOOR SCHEDULE, GROUT FILL
HEAD AND JAMBS
SEE DOOR SCHEDULE
CMU WALL
CONT. SEALANT, TYP. EA. SIDE
HOLLOW MTL. FRAME, SEE
DOOR SCHEDULE, GROUT FILL
HEAD AND JAMBS
SEE DOOR SCHEDULE
CMU BOND BEAM, SEE
STRUCTURAL FOR SIZE AND CELL
REINFORCEMENT REQUIREMENTS
HEAD DETAIL
JAMB DETAIL
RADIUS CORNER
SQUARE CORNERS
AT FIRST COURSE
ABOVE FLOOR
VARIES - VERIFY
CMU
CONT. BACKER ROD & SEALANT,
TYP. BOTH SIDES - 3/8" MIN.
HOLLOW METAL FRAME -
SEE DOOR SCHEDULE
FILL WITH GROUT
SEE DOOR SCHEDULE
SILL DETAIL
SEE DOOR SCHEDULE
HOLLOW METAL FRAME BEYOND
ALUMINIUM THRESHOLD SET IN
FULL BED OF SEALANT
SEAL - SEE HARDWARE SCHEDULE
PEJ
CMU
HOLLOW METAL FRAME -
SEE DOOR SCHEDULE
FILL WITH GROUT
SEE DOOR SCHEDULE
LINE OF THRESHOLD
BEYOND
CONTINUOUS BACKER ROD &
SEALANT
3/8" MIN. (BOTH SIDES)
JAMB DETAIL
HEAD DETAIL
CMU BOND BEAM, SEE
STRUCTURAL FOR SIZE AND
CELL REINFORCEMENT
REQUIREMENTS
WALL GIRT - SEE STRUCTURAL
BASE TRIM
INSULATED METAL WALL
PANEL
BUTYL SEALANT
WALL GIRT - SEE STRUCTURAL
INSULATED METAL WALL
PANEL
BUTYL SEALANT
CONTINUOUS BENT PLATE EMBEDDED IN
CONCRETE - SEE STRUCTURAL
PRE-MOULDED EXPANSION JOINT
PAVING - SEE CIVIL
Slope
0' - 2"
M in im um
/2 in ch
HOLLOW METAL FRAME
CONT. BACKER ROD AND SEALANT (BOTH SIDES TYP..)
HEAD DETAIL
C L
OVERHEAD COILING DOOR
SILL DETAIL
CMU JAMB, SEE STRUCTURAL FOR
REINFORCEMENT REQUIREMENTS
HOLLOW METAL FRAME
OVERHEAD COILING DOOR
CONT. BACKER ROD AND SEALANT
CONT. BACKER ROD AND SEALANT AT HMF
JAMB DETAIL
WALL GIRT - SEE STRUCTURAL
INSULATED METAL WALL PANEL
BUTYL SEALANT
BASE TRIM
WALL GIRT - SEE STRUCTURAL
INSULATED METAL WALL PANEL
BUTYL SEALANT
BASE TRIM
PNT1: Color: SW 7064
PNT2: Color: SW 7004
PNT3: Color: SW 7065
PNT4: Color: SSW HC-166
PNT5: Color: SW 7600
RB1: Manufacturer: Roppe Color: P123 Charcoal Style B: Cove Height: 4" Length: Roll
RESILIENT BASE
FINISH SCHEDULE LEGEND
PAINT
SC: Sealed Concrete - See Spec 09 91 23
CONCRETE
PNT3: Refer to Paint Colors
INTERIOR HOLLOW METAL FRAMES
PNT3: Refer to Paint Colors
INTERIOR HOLLOW METAL DOORS
NOTES:
1. PAINT EXPOSED STRUCTURE, PIPING, CONDUIT, ETC. THE COLOR
INDICATED IN FINISH SCHEDULE. EXPOSED SIDE OF ROOF PANEL
TO REMAIN AS PREFINISHED, TOUCH-UP PAINT AS REQUIRED.
A
INSULATED METAL WALL PANEL
BASE TRIM
COMPOSITE TRANSLUCENT WALL PANEL
FULL BED OF SEALANT
0' - 8 1/2"
GLAZED OPENING - SEE OPENING SCHEDULE
BACKER ROD W/ SEALANT
SHIM AS REQUIRED - 3/8” MIN
WALL GIRT - SEE STRUCTURAL
INSULATED METAL WALL PANEL
BASE TRIM
GLAZED OPENING - SEE OPENING SCHEDULE
WALL GIRT - SEE STRUCTURAL
BACKER ROD W/ SEALANT
SHIM AS REQUIRED - 3/8” MIN
FULL BED OF SEALANT
PREFINISHED AULUMINUM SUBSILL FLASHING SET IN FULL BED OF SEALANT
2" OVERLAP AT HORIZONTAL JOINTS. SET IN FULL BED OF TYPE V SEALANT,
PROVIDE END DAMS AT ENDS
INSULATED METAL WALL PANEL
BACKER ROD W/ SEALANT
SHIM AS REQUIRED - 3/8” MIN
GLAZED OPENING - SEE OPENING SCHEDULE
WALL GIRT - SEE STRUCTURAL
SIGN TYPE: A
WAYFINDING ID MOUNTED ADJACENT TO DOOR
6"
EXIT
SIGNAGE SCHEDULE
NOTE: ALL SIGNS SHALL COMPLY
WITH NFPA 101 AND ANSI A117.1
SIGN TYPE: B
WAYFINDING ID MOUNTED ADJACENT TO DOOR
6"
NO EXIT
A
INSULATED METAL WALL PANEL
BASE TRIM
FULL BED OF SEALANT
GLAZED OPENING - SEE OPENING SCHEDULE
BACKER ROD W/ SEALANT
SHIM AS REQUIRED - 3/8” MIN
WALL GIRT - SEE STRUCTURAL
BACKER ROD W/ SEALANT
LOUVER, SEE SECTION 08 91 00
PREFINISHED AULUMINUM SUBSILL FLASHING
SET IN FULL BED OF SEALANT
INSULATED METAL WALL PANEL
BACKER ROD W/ SEALANT
GLAZED OPENING - SEE OPENING SCHEDULE
WALL GIRT - SEE STRUCTURAL
PREFINISHED AULUMINUM SUBSILL FLASHING
BACKER ROD W/ SEALANT
LOUVER, SEE SECTION 08 91 00
0' - 8 1/2"
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E
SI
G N
19084
D E
PL
O
Y A
B L
E P
A R
T S
ST
O
R A
G E
F A
C
IL
IT
Y
A3.0B
DSP SCHEDULES
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A L
10 April, 2025
JLJ/CF/NJ
FEL
DSP DOOR AND FRAME SCHEDULE
DOOR
NO.
DOOR
FRAME
TYPE
GLAZING
TYPE
DETAILS
SIGN
TYPE COMMENTSWIDTH PANEL NO.
PANEL 1
WIDTH
PANEL 2
WIDTH HEIGHT THICKNESS TYPE HEAD DETAIL
JAMB
DETAIL
SILL
DETAIL
FIRST FLOOR FFE
D101 14' - 0" 1 14' - 0" 0' - 0" 14' - 0" 0' - 0 7/8" CR HM EXT F3 3/A3.0B 3/A3.0B 3/A3.0B - D102 3' - 0" 1 3' - 0" 7' - 0" 0' - 1 3/4" NL HM EXT HM EXT F2 IG-3 2/A3.0B 2/A3.0B 2/A3.0B A D104 3' - 0" 1 3' - 0" 7' - 0" 0' - 1 3/4" NL HM INT HM F2 S-1 1/A3.0B 1/A3.0B 1/A3.0B A,B,B Install 1 Type B sign to existing adjacent door D105 3' - 0" 1 3' - 0" 7' - 0" 0' - 1 3/4" NL HM EXT HM EXT F2 IG-3 2/A3.0B 2/A3.0B 2/A3.0B A
DSP FINISH SCHEDULE
NO. ROOM NAME
FLOOR
FINISH BASE FINISH
WALL FINISH
CEILING FINISH
WINDOW MILLWORK TOILET
PARTITIONS NOTESNORTH WALL EAST WALL SOUTH WALL WEST WALL SILL CASEWORK COUNTERTOP
FIRST FLOOR FFE
D101 DSP STORAGE SC PNT1 PNT1 PNT1 PNT1 NOTE 1 / PNT1 - - - - PAINT ALL EXPOSED STRUCTURE D102 EGRESS SC RB1 PNT1 PNT1 PNT1 PNT1 NOTE 1 / PNT1 - - - - PAINT ALL EXPOSED STRUCTURE
3" = 1'-0"A3.0B
1 DSP HM AT CMU, INSET
3" = 1'-0"A3.0B
2 DSP HM FRAME DETAILS - INSULATED METAL WALL PANEL ON CMU
3" = 1'-0"A3.0B
8 DSP OVERHEAD COILING DOOR HEAD AND JAMB DETAIL - INSULATED METAL PANEL
3" = 1'-0"A3.0B
5 DSP STOREFRONT HEAD @ INSULATED METAL WALL PANEL
3" = 1'-0"A3.0B
6 DSP STOREFRONT @ INSULATED METAL WALL PANEL
3" = 1'-0"A3.0B
7 DSP STOREFRONT SILL @ INSULATED METAL WALL PANEL
3" = 1'-0"A3.0B
3 DSP STOREFRONT HEAD W/ LOUVERS @ INSULATED METAL WALL PANEL
3" = 1'-0"A3.0B
4 DSP STOREFRONT SILL W/ LOUVERS @ INSULATED METAL WALL PANEL
Rev. Description Date
TYPICAL HSS GIRT TO C.M.U. WALL DETAIL
HSS GIRT. SEE
PLAN FOR SIZE
CMU WALL
L3x3x1/4x0'-6" W/ (2)3/4"Ø
EXP. BOLTS TOP & BOT.
3/16
TYP.
TYPICAL HSS GIRT TO BUILDING COLUMN DETAIL
3/16
TYP.
HSS GIRT. SEE
PLAN FOR SIZE
BUILDING
COLUMN
COPE GIRT AROUND
COL. FLANGE AS
REQUIRED
L3x3x1/4x0'-6"
TOP & BOTTOM
TYPICAL SLAB CONSTRUCTION
W.W.F.
JOINT DETAIL-(C.J.)
ALTERNATE SLAB CONSTRUCTION
JOINT DETAIL (SAWED JOINT)
W.W.F.
6"
SAW CUT 1/8"x1" DEEP
SAWED JOINT. FILL
JOINT W/ SEALANT.
NOTE:
IF SAWED JOINTS ARE USED,
JOINTS MUST BE SAWED SAME
DAY AS SLAB POUR.
WOOD FORMED
KEYED JOINT
1/
2" 6"
6" 6"
HARD RUBBER KEY MASONRY
CONTROL JOINT @ 25'-4" MAX.,
FULL HT. DISCONTINUE @ TOP &
BOT. OF U-BLOCK BOND BEAMS.
RAKE JOINT
CLEAN & CAULK
CMU SASH BLOCK
NOTE:
M.C.J. DETAIL
SIMILAR @
INTERIOR
C.M.U. WALLS
VERT. REINF. SAME SIZE
AS WALL REINF. EA. SIDE
OF M.C.J. FULL HT. OF
WALL, TYP.
FILL CELLS W/ CONC. FULL
HT. @ EA. VERT. BAR, TYP.
CAULK JOINTBRICK WHERE OCCURS
(@ EXTERIOR WALLS)
TYPICAL MASONRY CONTROL JOINT (M.C.J.)
8"
4" 2' - 0"
8" 8" 8"
SEE PLAN
FOR EL.
FILL ALL CELLS
W/ CONC. BELOW
FIN. FLOOR
FIN. FLOOR
(2)#5 CONT. TOP &
BOT. W/ #4 @ 24"O.C.
TURN VAPOR
BARRIER UP WALL
TO BREAK BOND
6x6-W1.4xW1.4 W.W.F.
0'-0"
#4 @ EA. JAMB & @
48"O.C., CENTERED. FILL
CELLS SOLID W/ CONC.
FULL HT. OF WALL ONLY @
#4.
CONT. HORIZ. MAS-
ONRY JOINT REINF.
@ 16"O.C., VERT.
1'
0"
SP
LI
C
E
D
IA
F.
S.
SE
E
PL
AN
TYPICAL FOOTING STEP DETAIL - (F.S.)
CONT. REINF.
MIN.
1' - 0"
CONT. REINF.
SEE SECTIONS FOR
TRANSVERSE REINF.
SAME SIZE & NUMBER
AS CONT. REINF.
TYP.
2' - 0"
(8)#8 VERT.
#4 TIES SPACED
@ 2@2", R@6"
FROM TOP, 1 1/2"
CLEAR SIDES.VIEW A-A
2'
0"
2' - 0"
SEE PLAN
FOR EL.
SCH. REINF.
D
EP
TH
SC
H
SCH. SIZE
24"x24" CONC. PIER W/
(8)#8 VERT. & #4 TIES
SPACED @ 2@2", R@
6" FROM TOP, 1 1/2"
CLEAR SIDES.
CENTERLINE BASE
PLATE, PIER, & FTG.
BELOW
COORDINATE W/
METAL BLDG. MFR.
FRAME COL., BASE
PLATE, & ANCHOR BOLTS
BY METAL BLDG. MFR.
(USE (4)3/4"Øx24" GRADE
55 HEADED, MIN.)
FIN. GRADE.
SEE SITE PLAN
PROVIDE 3/8" PEJ. W/
SEALANT WHERE
CONC. ABUTS WALL
O.S.F. OF END
WALL COLUMN
A-A
8"
FIN. FLOOR
6x6-W2.9xW2.9 W.W.F.
+0'-0"
TOP OF PIER
8"
2" 6"
HOOK (2)#9 AROUND
ANCHOR BOLTS
FILL CAVITY W/ CONC.
BELOW FIN. GRADE
S2.1B
SEE PLAN
FOR EL.
FIN. FLOOR
SCH. REINF.
6x6-W2.9xW2.9 W.W.F.
+0'-0"
D
EP
TH
SC
H
SCH. SIZE
16"x16" CONC. PIER W/
(4)#8 VERT. & #4 TIES
SPACED @ 2@2", R@6"
FROM TOP, 1 1/2"
CLEAR SIDES.
CENTERLINE BASE PLATE,
PIER, & FTG. BELOW
TOP OF PIER
6" 2"
ENDWALL COL., BASE
PLATE, & ANCHOR BOLTS
BY METAL BLDG. MFR.
(USE (4)3/4"Øx24" GRADE
55 HEADED, MIN.)
8"FIN. GRADE.
SEE SITE PLAN
PROVIDE 3/8" PEJ. W/
SEALANT WHERE
CONC. ABUTS WALL
O.S.F. OF END
WALL COLUMN
8"
COORDINATE W/
METAL BLDG. MFR.
FILL CAVITY W/ CONC.
BELOW FIN. GRADE
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n W W W .S
SL
A R C H .C O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
19084
D E
PL
O
Y A
BL
E
P A
RT
S
ST
O
RA
G
E F
A
CI
LI
TY
09-06-21
S0.1B
GENERAL NOTES -
SCHEDULES -
TYPICAL DETAILS -
DPS STORAGE
D A
N N
E
LL
Y F
IE
LD
M
O N
TG
O
M E
RY
A
L.
09/06/2021
FOUNDATION:
1. THE BEARING STRATA OF ALL FOOTINGS AND GRADE BEAMS SHALL BE
INSPECTED AND APPROVED BY THE SOILS TESTING LABORATORY PRIOR
TO PLACING THE REINFORCING STEEL AND CONCRETE.
2. ALL FOOTINGS SHALL BEAR ON AN UNDISTURBED SOIL STRATA OR
COMPACTED FILL CAPABLE OF SUSTAINING THE LOADS.
3. FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING OF
P = 2500 PSF. THE TESTING AGENCY SHALL VERIFY THAT THE SOILS ARE
CAPABLE OF SUSTAINING 2500 PSF PRIOR TO CONCRETE PLACEMENT.
4. ELEVATIONS SHOWN ON PLAN ARE TOP OF FOOTINGS AND ARE MINIMUM
DEPTH. DIFFERENT OR UNUSUAL CONDITIONS SHALL BE REPORTED TO
THE ARCHITECT AND/OR ENGINEER.
5. ALL FOOTING REINFORCEMENT SHALL BE HELD SECURELY FROM THE
GROUND. CONCRETE BLOCK AND BROKEN TILE SHALL NOT BE USED.
CONCRETE OR CLAY BRICK MAY BE USED.
6. DOWEL ALL FOOTINGS AND WALLS WHERE THEY ABUT WITH SAME STEEL
AS VERTICAL.
7. PROVIDE PREFORMED EXPANSION JOINT WHERE SHOWN.
8. IN FOOTINGS PROVIDE CORNER BARS AT ALL EXTERIOR BUILDING CORNERS.
9. DO NOT BACK FILL BEHIND FOUNDATION WALLS UNTIL TOP AND BOTTOM
SLABS HAVE BEEN POURED AND ATTAINED THEIR DESIGN STRENGTHS.
10. BACK FILL BOTH SIDES OF FOUNDATION WALLS AT SAME TIME TO
PREVENT OVERTURNING.
11. BACK FILL BEHIND ALL RETAINING WALLS AND BASEMENT WALLS SHALL
BE AN APPROVED GRANULAR MATERIAL.
CONCRETE:
1. ALL CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH AT 28 DAYS OF
F'c = 4000 PSI AND A MAXIMUM WATER-CEMENT RATIO OF 0.53.
ALL CONCRETE FOR EXTERIOR APPLICATIONS SHALL CONTAIN
ENTRAINED AIR. SEE SPECS FOR ADDITIONAL INFORMATION.
2. REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60.
3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A1064.
4. UNLESS NOTED OTHERWISE PROTECTIVE COVERING OF REINFORCEMENT
SHALL BE AS FOLLOWS ( SEE DETAILS ) : FOOTINGS AND GRADE BEAMS
3" CLEAR BOTTOM AND SIDES, 2" CLEAR TOP. CONCRETE SLABS
3/4" CLEAR. WALLS 1 1/2" CLEAR SIDES. BEAMS 1 1/2" CLEAR TO
STIRRUPS. CONCRETE COLUMNS 1 1/2" CLEAR TO TIES.
5. LAP ALL CONCRETE WALL VERTICAL REINFORCING AND CONCRETE BEAM
HORIZONTAL REINFORCING WITH CLASS B LAP SPLICES. LAP ALL OTHER
CONTINUOUS BARS WITH CLASS A SPLICES UNLESS NOTED OTHERWISE.
6. PLACING PLANS AND DETAILS SHALL BE IN ACCORDANCE WITH THE
LATEST "A.C.I. DETAILING MANUAL".
7. STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR THE ARCHITECT
AND/OR ENGINEER'S REVIEW.
8. DO NOT RUN CONDUITS, RACEWAYS, OR PIPES IN CONCRETE SLABS, BEAMS,
OR COLUMNS WITHOUT SPECIFIC APPROVAL FROM BLACKBURN DANIELS O'BARR.
MASONRY:
1. PROVIDE MASONRY HORIZONTAL JOINT REINFORCEMENT 16" O.C.
VERTICAL IN ALL CONCRETE BLOCK WALLS. REINFORCEMENT SHALL BE
FOR TOTAL WIDTH OF CAVITY WALLS.
2. WHERE CONCRETE OR STEEL BEAMS BEAR ON CONCRETE BLOCK WALLS, BLOCK
CELLS SHALL BE FILLED WITH CONCRETE 1'-4" WIDE TO FOUNDATION AND
REINFORCED WITH A #5 EACH CELL UNLESS NOTED OR DETAILED OTHERWISE.
3. CONCRETE OR GROUT FOR BLOCK FILL SHALL HAVE 3/8 INCH MAXIMUM
SIZE COARSE AGGREGATE AND SUFFICIENT WATER SO THE CONCRETE
WILL FLOW INTO THE BLOCK CELLS WITHOUT LEAVING VOIDS. HEIGHT
OF LIFT WHEN FILLING CELLS SHALL NOT EXCEED 4'-0".
4. CONCRETE OR GROUT FILL FOR C.M.U. SHALL HAVE A 28 DAY COMPRESSIVE
STRENGTH OF F'c = 3000 PSI. ON 16" AND DEEPER U-BLOCKS, FILL
CELLS FULL HEIGHT OF LINTEL AT SAME TIME.
5. ANCHOR ALL MASONRY WALLS TO STEEL COLUMNS WITH STRAP ANCHORS
AT 16" O.C. VERTICALLY UNLESS SHOWN OTHERWISE.
6. UNLESS INDICATED OTHERWISE PROVIDE KEYED RUBBER MASONRY
CONTROL JOINTS AT A MAXIMUM SPACING OF 25'-4". JOINT SHALL
BE DISCONTINUOUS AT BOND BEAM.
7. PROVIDE REINFORCING BAR SUPPORTS TO CENTER VERTICAL
REINFORCING IN MASONRY WALLS.
8. PROVIDE 48 DIAMETER LAP SPLICE IN VERTICAL MASONRY REINFORCING.
9. PROVIDE CORNER BARS IN U-BLOCK BOND BEAMS AT CORNERS, TYPICAL.
10. ALL CMU SHALL BE PLACED IN A RUNNING BOND PATTERN UNLESS NOTED
OTHERWISE.
11. VERTICAL REINFORCING SHALL BE CONTINUOUS THROUGH BOND BEAMS AND
LINTELS (CUT OUT OR NOTCH BOTTOM OF U-BLOCKS AS REQUIRED -- DO NOT
SUBSTITUTE BLOCK WITH KNOCK-OUT WEBS WHERE STANDARD U-BLOCK IS
INDICATED). FOR BOND BEAMS AT TOP OF WALL, EXTEND VERTICAL
REINFORCING TO 1" CLEAR TOP OF BOND BEAM.
STRUCTURAL STEEL:
1. ALL STRUCTURAL STEEL W AND WT SHAPES SHALL CONFORM TO ASTM
A992 (GRADE 50). OTHER SHAPES SHALL CONFORM TO ASTM, A36,
LATEST EDITION (EXCEPT STEEL JOISTS AND TUBE SECTIONS).
2. STRUCTURAL STEEL TUBE SECTIONS SHALL CONFORM TO ASTM A500,
GRADE B, Fy = 46.0 KSI.
3. HEADED STUDS SHALL BE TYPE B SHEAR CONNECTORS (Fu = 65 KSI).
4. STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR THE ARCHITECT
AND/OR ENGINEER'S REVIEW.
5. THE CONTRACTOR SHALL VERIFY ALL SH0P DRAWINGS DIMENSIONS WITH
STRUCTURAL AND ARCHITECTURAL PLANS AND DETAILS.
6. BOLTED CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS
CONFORMING TO ASTM A325. USE 3/4 INCH DIAMETER MINIMUM.
UNLESS NOTED OTHERWISE, ALL BOLTS SHALL BE TIGHTENED AS FULLY
PRETENSIONED BEARING CONNECTIONS.
7. CONNECTIONS NOT SHOWN ON DRAWINGS SHALL BE DESIGNED
BY THE FABRICATOR. WHERE POSSIBLE USE DOUBLE ANGLE
CONNECTIONS. USE MAXIMUM NUMBER OF BOLTS FOR DEPTH
OF BEAM WITH SINGLE ROW OF BOLTS. WHERE DOUBLE ANGLE
CONNECTIONS ARE NOT POSSIBLE, FABRICATOR SHALL DESIGN
CONNECTION FOR CAPACITY EQUIVALENT TO DBL-ANGLE CONNECTION
WITH MAX NO. BOLTS UNLESS DETAILED OTHERWISE.
8. FOR DBL-ANGLE CONNECTIONS, MIN ANGLE THICKNESS SHALL BE 5/16"
FOR 3/4 INCH DIAMETER BOLTS AND 3/8" FOR 7/8 INCH DIAMETER BOLTS
AND LARGER.
9. UNLESS SHOWN OTHERWISE PROVIDE 1/2 X 7 1/2 X 7 1/2 BEARING
PLATES ON 1 INCH GROUT WITH 2-3/4" DIAMETER ANCHOR BOLTS
UNDER ALL STEEL BEAMS THAT BEAR ON MASONRY WALLS.
10. OPEN WEB STEEL JOIST SHALL CONFORM TO THE SPECIFICATIONS OF
THE AISC AND SJI AND TO THE LATEST OSHA STEEL ERECTION STANDARD.
11. UNLESS SHOWN OTHERWISE PROVIDE BRIDGING, BEARING SEATS, AND
STABILIZER PLATES IN ACCORDANCE WITH ABOVE SPECIFICATIONS AND
STANDARD.
12. ALL BRIDGING SHALL BE SECURELY ANCHORED AT END OF EACH RUN.
WELD TO STEEL BEAM OR ANCHOR TO MASONRY WALL WITH 3/8 "
ANCHOR BOLTS.
13. WHERE JOISTS CAN NOT BEAR 2 1/2 INCHES ON STEEL BEAMS,
STAGGER LOCATION OF JOISTS TO PROVIDE 2 1/2 INCHES MINIMUM
BEARING.
14. ROOF JOISTS AND BRIDGING SHALL BE DESIGNED FOR A NET UPLIFT
OF 15 PSF. SHELTER ROOF JOISTS SHALL HAVE A MINIMUM TOP CHORD
THICKNESS OF 1/4".
15. ANY MEMBER CALLED OUT TO BE BENT TO RADIUS SHALL BE FABRICATED OUT
OF PLATE WITH EQUIVALENT SECTION PROPERTIES IF BENDING TO RADIUS
IS IMPRACTCAL.
PRE-ENGINEERED METAL BUILDING:
1. THE COMPLETE DESIGN OF METAL BUILDING INCLUDING ALL
COMPONENTS SHOWN OR NOT SHOWN ON THE DRAWINGS SHALL BE
ACCOMPLISHED BY THE BUILDING MANUFACTURER.
2. THE DESIGN SHALL BE MADE BY A REGISTERED ENGINEER, REGISTERED
IN THE STATE OF ALABAMA AND HE SHALL AFFIX HIS REGISTRATION
NUMBER TO ALL SHOP DRAWINGS AND CALCULATIONS.
3. THE BUILDING AND ALL OF ITS COMPONENTS SHALL BE DESIGNED FOR
THE FOLLOWING DEAD AND LIVE LOADS;
a.) ACTUAL WEIGHT OF STEEL STRUCTURE.
b.) 10 PSF DEAD (COLLATERAL) LOAD IN ADDITION TO ACTUAL WEIGHT OF
STRUCTURE AND ROOFING MATERIALS.
c.) 20 PSF ROOF LIVE LOAD.
d.) ANY ADDITIONAL LOADS AND REACTIONS THAT ARE SHOWN ON
THE DRAWINGS.
e.) WIND LOADING AS REQUIRED BY INTERNATIONAL BUILDING CODE.
4. NO LIVE LOAD REDUCTION SHALL BE TAKEN FOR THE DESIGN OF THE
RIGID FRAMES.
5. WHERE MEMBER SIZES AND GAGES ARE SHOWN THEY SHALL BE
CONSIDERED A MINIMUM SIZE. THE MANUFACTURER SHALL NOT USE
SMALLER SIZE OR LIGHTER GAGES, OR OMIT FRAMING WHERE
INDICATED. HE SHALL USE ONLY LARGER SIZE AND HEAVIER GAGES
IF HIS DESIGN INDICATES THESE ARE REQUIRED TO MEET THE
LOADING CRITERIA
6. THE DEFLECTION OF GIRTS SHALL BE LIMITED TO 1/240 OF THE SPAN
AND DEFLECTION OF PURLINS SHALL BE LIMITED TO 1/240 OF THE
SPAN. DEFLECTION OF RIGID FRAMES AND END WALL COLUMNS
SHALL BE LIMITED TO 1/240 OF THE SPAN. DEFLECTIONS
SHALL BE BASED ON TOTAL LOAD (DEAD PLUS LIVE LOADS).
TOTAL RIGID FRAME DRIFT SHALL BE LIMITED TO
H/240, WHERE H IS EQUAL TO THE EAVE HEIGHT.
7. COLUMN BASES SHALL BE DESIGNED AS PINNED CONNECTIONS.
MOMENTS AT COLUMN BASE PLATES ARE NOT ACCEPTABLE.
8. LOCATE PORTAL FRAMES ONLY WHERE INDICATED ON PLAN. PORTAL FRAME
COLUMNS SHALL BE NESTED TIGHT TO WEB OF RIGID FRAME COLUMN.
COLD-FORMED STEEL STUDS:
1. PROVIDE COLD FORMED STEEL STUDS WHERE INDICATED ON THE PLAN.
ALL SIZES AND GAGES SHOWN SHALL BE CONSIDERED MINIMUM.
2. LIGHT STEEL GALVANIZED (G-60) METAL STUDS, OF SIZES SHOWN
COMPLETE WITH ALL ACCESSORIES REQUIRED. 16 GA AND HEAVIER
MEMBERS SHALL MEET ASTM A-1003/A1003M, GRADE D WITH 50 KSI
YIELD.
3. PROVIDE SHOP DRAWINGS PREPARED BY COLD FORMED METAL FRAMING
MANUFACTURER. SUBMIT FOR APPROVAL SHOWING PLANS, SECTIONS,
ELEVATIONS, LAYOUTS, PROFILES, PRODUCT COMPONENTS, AND INDICATING
SPACING OF MEMBERS, PROPOSED METHODS OF FRAMING LINTELS,
DOORWAY FRAMING, ETC. SHOW CONNECTION DETAILS WITH SCREW TYPE
AND LOCATIONS AND ALL OTHER FASTENER REQUIREMENTS. INCLUDE
CATALOG DATA ON ALL PRODUCT MATERIAL.
4. MANUFACTURER SHALL SUBMIT SHOP DRAWINGS AND DESIGN CAL-
CULATIONS INCLUDING ALL CONNNECTIONS. DESIGNS SHALL BE SIGNED
BY A REGISTERED PROFESSIONAL ENGINEER, REGISTERED IN THE
STATE OF ALABAMA.
5. MINIMUM CONNECTION OF THE TRACK TO THE FOUNDATION SHALL BE
(2)-0.157IN DIAMETER X 1-1/2" EMBEDMENT HILTI X-U ANCHORS
AT EACH STUD. FOLLOW ALL MANUFACTURERS RECOMMENDED EDGE
DISTANCES AND SPACING REQUIREMENTS.
CODES:
ALL PARTS SHALL BE FURNISHED AND ERECTED ACCORDING TO THE
APPLICABLE CODES AND SPECIFICATIONS OF THE FOLLOWING:
AMERICAN CONCRETE INSTITUTE (ACI)
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AMERICAN WELDING SOCIETY (AWS)
OSHA STEEL ERECTION STANDARD (OSHA)
STEEL JOIST INSTITUTE (SJI)
INTERNATIONAL BUILDING CODE (IBC 2015) (ICC)
DESIGN LIVE LOADS:
ROOF.......20 PSF.
MEZZANINE..150 PSF
OFFICES
RISK CATEGORY (PER IBC 2015/ASCE 7-10)..........II
WIND.......INTERNATIONAL BUILDING CODE (PER ASCE 7-10)
ULTIMATE DESIGN WIND SPEED (Vult).........115 MPH NOMINAL DESIGN WIND SPEED (Vasd)..........90 MPH
WIND EXPOSURE.............................C
INTERNAL PRESSURE COEFFICIENTS............+/-0.18
COMPONENTS AND CLADDING ULTIMATE WIND PRESSURES:
NOTE: MULTIPLY ALL VALUES SHOWN BELOW BY 0.6 TO GET ALLOWABLE DESIGN
PRESSURES.
ROOF:TRIBUTARY AREA A = 10 SF
ZONE 1: -49.7PSF/31.3PSF
ZONE 2: -86.5PSF/31.3PSF
ZONE 3: -128.0PSF/31.3PSF
WALL:TRIBUTARY AREA A = 10 SF
ZONE 4: -58.9PSF/54.3PSF
ZONE 5: -72.7PSF/54.3PSF
CORNER ZONE = 5 FT
SEISMIC....INTERNATIONAL BUILDING CODE (PER ASCE 7-10)
SEISMIC IMPORTANCE FACTOR.................Ie=1.0 MAPPED SPECTRAL ACCELERATION (SHORT-TERM).Ss=0.134
MAPPED SPECTRAL ACCELERATION (1-SECOND)...S1=0.075
SITE CLASS................................C
SHORT-PERIOD SPECTRAL RESPONSE ACCEL......Sds=0.107g 1-SECOND SPECTRAL RESPONSE ACCEL..........Sd1=0.085g
SEISMIC DESIGN CATEGORY...................B
SEISMIC FORCE-RESISTING SYSTEM............STEEL FRAME
NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
DESIGN BASE SHEAR (ULTIMATE)..............35k SEISMIC RESPONSE COEFFICIENT..............Cs=0.035
RESPONSE MODIFICATION FACTOR..............R=3
ANALYSIS PROCEDURE........................ASCE 7 (SECT 12.8)
SNOW.......INTERNATIONAL BUILDING CODE
GROUND SNOW LOAD..........................Pg=5 PSF
SPECIAL INSPECTIONS
1. ALL SPECIAL INSPECTIONS REQUIRED BY CHAPTER 17 OF THE IBC 2015 SHALL
BE
PERFORMED BY A DESIGNATED TESTING EGENCY OR AGENCIES RESPONSIBLE
FOR SPECIAL INSPECTIONS.
SEISMIC REQUIREMENTS FOR SPECIAL INSPECTIONS:
1. THE FOLLOWING STRUCTURAL COMPONENTS ARE DESIGNATED AS SEISMIC
SYSTEMS AND/OR PART OF THE SEISMIC-FORCE-RESISTING SYSTEM OF THE
BUILDING AND ARE SUBJECT TO THE REQUIREMENTS OF SECTIONS 1705.12
AND 1705.13 OF IBC 2015 AND PROJECT SPECIFICATIONS:
X-BRACING
PRE-ENG TRUSSES AND TRUSS-COLUMN CONNECTIONS
SHEAR WALLS (INCL. ANCHORAGE TO FOUNDATION)
THESE SPECIFIC COMPONENTS ARE IN ADDTION TO ALL GENERAL COMPONENTS
LISTED IN SECTIONS 1705.12 AND 1705.13 OF IBC 2015 AND ARE SUBJECT
TO ALL SPECIAL INSPECTIONS AND TESTING AS REQUIRED BY CHAPTER 17 OF
IBC 2015, PROJECT SPECIFICATIONS, AND SCHEDULE OF SPECIAL INSPECTIONS.
SPECIAL INSPECTION REPORTS SHALL BE SUBMITTED AS PER THE STATEMENT
OF SPECIAL INSPECTIONS.
2. OTHER ARCHITECTURAL, MECHANICAL, OR ELECTRICAL COMPONENTS
AND THEIR ANCHORAGES MAY ALSO BE DESIGNATED AS SEISMIC SYSTEMS.
SEE OTHER DISCIPLINE'S DRAWINGS AND SPECIFICATIONS.
3. ALL SPECIAL INSPECTIONS AS REQUIRED BY CHAPTER 17 OF THE IBC 2015 SHALL
BY PERFORMED. REFER TO TABLES SHOWN IN CHAPTER 17 FOR ALL APPLICABLE
COMPONENTS THAT REQUIRE SPECIAL INSPECTIONS.
WIND REQUIREMENTS FOR SPECIAL INSPECTIONS:
1. THE FOLLOWING STRUCTURAL COMPONENTS ARE DESIGNATED AS WIND
SYSTEMS AND/OR PART OF THE MAIN WINDFORCE-RESISTING SYSTEM
OF THE BUILDING AND ARE SUBJECT TO THE REQUIREMENTS OF SECTION
1705.11 OF IBC 2015 AND PROJECT SPECIFICATIONS:
ROOF DIAPHRAGM SYSTEM AND ATTACHMENT
LOAD-BEARING CMU (SHEAR) WALLS
JOIST CONNECTIONS TO SHEAR WALLS
SHEAR WALL ANCHORAGE TO FOUNDATION
THESE SPECIFIC COMPONENTS ARE IN ADDTION TO ALL GENERAL COMPONENTS
LISTED IN SECTION 1705.11 OF IBC 2015 AND ARE SUBJECT TO ALL
SPECIAL INSPECTIONS AND TESTING AS REQUIRED BY CHAPTER 17 OF IBC
2015, PROJECT SPECIFICATIONS, AND SCHEDULE OF SPECIAL INSPECTIONS.
SPECIAL INSPECTION REPORTS SHALL BE SUBMITTED AS PER THE STATEMENT
OF SPECIAL INSPECTIONS.
2. OTHER ARCHITECTURAL COMPONENTS AND THEIR ANCHORAGES MAY
ALSO BE DESIGNATED AS WIND-RESISTING COMPONENTS. SEE OTHER
DISCIPLINE'S DRAWINGS AND SPECIFICATIONS.
3. ALL SPECIAL INSPECTIONS AS REQUIRED BY CHAPTER 17 OF THE IBC 2015 SHALL
BY PERFORMED. REFER TO TABLES SHOWN IN CHAPTER 17 FOR ALL APPLICABLE
COMPONENTS THAT REQUIRE SPECIAL INSPECTIONS.
GENERAL NOTES
3/4" = 1'-0"
SECTION1
3/4" = 1'-0"
DETAILA 3/4" = 1'-0"
DETAILB
FOOTING SCHEDULE - DPS
Type Mark Width Length Depth Reinforcing
F-G 6'-0" 6'-0" 1'-2" (6)#4 E.W. TOP - (6)#5 E.W. BOT.
F-M 8'-6" 8'-6" 1'-6" (9)#5 E.W. TOP - (9)#6 E.W. BOT.
F-P 9'-6" 9'-6" 1'-8" (10)#5 E.W. TOP - (10)#6 E.W. BOT.
Lintel Schedule - DPS Mark or Location Max. Span Type Size Reinforcing Remarks
8" C.M.U. 4'-0" U-BLOCK 8x16 #5 TOP & BOTTOM 8" HIGH U-BLOCK Rev. Description Date
1 Addendum #1
08.01.25
EF
156 SF
COMM
164 SF
ELECTRICAL
265 SF
CUST.
SERVICE
93 SF
ASSET
MANAGEMENT
83 SF
OPERATIONS
COMPLIANCE
324 SF
F-35 SEGREGATED
STORAGE
190 SF
BATTERY STORAGE
190 SF
HEF STORAGE
190 SF
FLAMMABLE
STORAGE
190 SF
CORROSIVE
STORAGE
190 SF
DRUM STORAGE
ALIS WORKSTATION
TA
N K
S
TO
R A G
E
83 SF
CUST. SUPPORT
NCOIC
98 SF
MATERIAL
MANAGEMENT
286 SF
OPEN OFFICE
111A
105 106
101B
101A
100B
146147
144 143 142 141 140 139
125 SF
GAS MASK WASH
ROOM
145B
DSP STORAGE
M
AT
C H
LI
N
E
- N
EW
D
PS
M
AT
C
H
LI
N E
- E
XI
ST
IN
G B
AS
E
SU
PP
LY
M
AT
C
H
LI
N E
- N
EW
D
PS
M
AT
C H
LI
N
E
- E
XI
ST
IN
G
B
AS
E
SU
PP
LY
EXISTING ALARM
HORN AND STROBE
EXISTING FDC
F F
EXISTING CONTROL
RISER SERVING
BASE SUPPLY AND
NEW DPS
EXISTING UNDERGROUND
WATER SERVICE FEEDING
BASE SUPPLY AND NEW
DPS
BFP
F F
F
F
F
F
F
FNEW DPS WET PIPE SPRINKLER
ZONE BOUNDARY
NEW DPS WET PIPE SPRINKLER
ZONE BOUNDARY
EXISTING WET PIPE SPRINKLER
SYSTEM FEED MAIN SERVING
BASE SUPPLY. FIELD VERIFY
EXACT LOCATION.
ZONE
DPS-1
FF
F
F FFF
F
F
F
EXISTING STUB-OUT
FOR DPS BUILDING
FIRE SPRINKLER CONTRACTOR SHALL INSTALL PIPING, IN WAREHOUSE
AREAS, AS REQUIRED TO PROVIDE COMPLETE PROTECTION OF ALL
STORED ITEMS AND ACCESS ISLES. ROUTE SPRINKLER PIPING, OFFSET
FROM THE CENTER OF ISLES, SO AS NOT TO INTERFERE WITH REQUIRED
LIGHTING. STORAGE AREAS SHALL BE PROTECTED TO A MAXIMUM
HEIGHT OF 30'-0" AFF, BASED ON PLASTICS COMMODITIES.
PROTECTION OF STORAGE AREAS SHALL BE PROVIDED USING "ESFR"
SPRINKLERS. MINIMUM TEMPERATURE RATING OF SPRINKLERS IN
WAREHOUSE AREAS SHALL BE 150° F.
BUILT-IN SLEEVE WITH
FIRE STOP SEALANT
AND ESCUTCHEONS
BUILT-IN SLEEVE WITH
FIRE STOP SEALANT
AND ESCUTCHEONS
1 2
8"
F
F
8"
EXISTING TEST HEADER
PRV
EXISTING SHUT-OFF
VALVE
F F
EXISTING STUB-OUT
FOR DPS BUILDING
F
F
CONNECT TO EXISTING
F EXISTING PIPING TO REMAIN
UNIFIED FACILITIES CRITERIA UFC
LEGEND
DUCTILE IRON PIPEDIP
MECHANICAL JOINTMJ
FIRE DEPARTMENT CONNECTIONFDC
UNDERGROUNDUG
GALLONS PER MINUTEGPM
POUNDS PER SQUARE INCHPSI
SQUARE FEETSF
SPRINKLER SYSTEM ZONE BOUNDARY
UNDERWRITERS LABORATORYU.L.
NOTE LEGEND NUMBER
WET PIPE SYSTEM CONTROL ASSEMBLY
F FIRE SPRINKLER PIPING
FACTORY MUTUALFM
GENERAL NOTES:
1. FIRE SPRINKLER CONTRACTOR SHALL BE LICENSED THROUGH THE OFFICE
OF THE STATE OF ALABAMA FIRE MARSHAL.
2. SEE SPECIFICATIONS FOR SPRINKLER OCCUPANCY HAZARD
CLASSIFICATIONS, SPRINKLER DENSITY REQUIREMENTS, SPRINKLER
MINIMUM AREA REQUIREMENTS, AND HOSE STREAM DEMAND
REQUIREMENTS.
3. ALL WET SYSTEM FIRE SPRINKLER PIPING SHALL BE INSTALLED WITHIN
BUILDING INSULATION ENVELOPE. SEE ARCHITECTURAL PLANS FOR THE
LOCATION AND EXTENT OF THE BUILDING INSULATION ENVELOPE.
4. ALL TAMPER SWITCHES, FLOW SWITCHES, AND ALARM HORN / STROBE,
SHALL BE FURNISHED AND INSTALLED BY THE FIRE SPRINKLER
CONTRACTOR. REQUIRED ELECTRICAL CONNECTIONS, AND
CONNECTIONS TO THE BUILDING FIRE ALARM SYSTEM, SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR. ALL FLOW AND TAMPER
SWITCHES SHALL BE CONNECTED TO A CONSTANTLY MONITORED
LOCATION. PROVIDE SURGE PROTECTIONS DEVICES (SPDS) FOR
COMMUNICATION EQUIPMENT AND SPECIALIZED ELECTRICAL
EQUIPMENT SUCH FIRE ALARM AND DETECTION SYSTEMS (ANTENNAS),
ELECTRICAL POWER FOR FIRE ALARM CONTROL PANELS (FACP) AND
MASS NOTIFICATIONS SYSTEMS (MNS) ARE AREAS OF REQUIREMENT OF
AFI 32-1065 AND NFA 780. SPDS SHALL BE UL1283 AND UL1449 RATED.
5. NO PIPING SHALL BE INSTALLED ABOVE ELECTRICAL EQUIPMENT AND/OR
DATA EQUIPMENT. MAINTAIN ALL REQUIRED CLEARANCES.
6. ALL EXPOSED SPRINKLER PIPING SHALL BE INSTALLED AS HIGH AS
POSSIBLE.
7. THESE DRAWINGS ARE FOR ENGINEERING INTENT ONLY. FOR NEW OR
MODIFIED SYSTEMS, WORKING (SHOP) DRAWINGS AND CALCULATIONS
MUST BE PREPARED BY A QUALIFIED FIRE PROTEC TION ENGINEER (QFPE)
THAT HAS OBTAINED NATIONAL INSTITUTE FOR CERTIFICATION IN
ENGINEERING TECHNOLOGIES, AUTOMATIC SPRINKLER SYSTEMS, LEVEL III
CERTIFICATION OR SPECIAL HAZARDS SUPPRESSION SYSTEMS LEVEL IV
CERTIFICATION, AS APPLICABLE TO THE PROJECT. THE QUALIFIED FIRE
PROTECTION ENGINEER (QFPE) MUST REVIEW THE SHOP DRAWINGS,
HYDRAULIC CALCULATIONS AND MATERIAL SUBMITTALS. THE SHOP
DRAWINGS MUST BEAR THE REVIEW STAMP OF THE QFPE PRIOR TO
SUBMITTING THE FIRE EXTINGUISHING SYSTEM SHOP DRAWINGS TO THE
DESIGNATED FIRE PROTECTION ENGINEER (DFPE).
8. BRAND NAMES AND MODEL NUMBERS ARE GIVEN FOR ILLUSTRATIVE
PURPOSES ONLY. EQUIPMENT, FULFILLING REQUIREMENTS OF THE PLANS
AND SPECIFICATIONS, MAY BE SUBMITTED FOR REVIEW AND APPROVAL.
9. THE FIRE SPRINKLER CONTRACTOR SHALL PROVIDE A "STATEMENT OF
COMPLIANCE" TO THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE
REQUESTING FINAL APPROVAL OF THE INSTALLATION, AS PER SECTION
901.2.1 IN THE INTERNATIONAL FIRE CODE, 2019 EDITION.
10. A COPY OF AS-BUILT DRAWINGS, MANUFACTURER'S OPERATION AND
MAINTENANCE LITERATURE, AND NFPA 25 SHALL BE PROVIDED TO THE
OWNER AS A PART OF THE SYSTEMS ACCEPTANCE.
1. FIRE PROTECTION SYSTEM SHALL BE A WET PIPE SYSTEM, AND SHALL COMPLY WITH "UFC
3-600-01" (REV. 5.6.2021), "NFPA 13" (2019), AND INTERNATIONAL BUILDING CODE (2021).
2. DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH "UFC 3-600-01" (REV.
5.6.2021).
3. OCCUPANCY CLASSIFICATION SHALL BE PER "UFC 3-600-01" (REV. 5.6.2021).
4. SYSTEMS SHALL BE INTERFACED WITH BUILDING ALARM SYSTEM.
5. ROUTE PIPING TO MINIMIZE OBSTRUCTION TO OTHER WORK.
6. BUILDING SHALL BE SUPERVISED PER "UFC 3-600-01" (REV. 5.6.2021).
7. THE SPRINKLER CONTRACTOR SHALL DESIGN AND INSTALL AN APPROVED, COMPLETE,
OPERATIONAL SPRINKLER SYSTEM. PROVIDE COVERAGE TO ENTIRE AREA INCLUDING
OVERHANGS. SYSTEM SHALL MEET ALL APPLICABLE CODES AND ORDINANCES.
COORDINATE HEADS WITH LIGHTS, MECHANICAL EQUIPMENT, CEILING SYSTEMS, ETC.
8. CUTTING OF STRUCTURAL AND / OR ARCHITECTURAL MEMBERS SHALL BE DONE ONLY
WITH THE WRITTEN APPROVAL OF THE ARCHITECT.
9. CONTRACTOR SHALL PROVIDE OFFSETS AS REQUIRED FOR PROPER INSTALLATION,
COORDINATION WITH OTHER TRADES, AND / OR TO MAINTAIN PROPER CLEARANCES.
VERIFY STRUCTURAL, MECHANICAL, AND ELECTRICAL INSTALLATIONS AND AVOID ANY /
ALL OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING, AND/OR
SPRINKLER LOCATIONS.
10. ALL WALL AND FLOOR PENETRATIONS FOR FIRE PROTECTION PIPING SHALL BE FULLY
SLEEVED AND SEALED. FIRE STOP ALL PENETRATIONS OF SMOKE / FIRE WALLS, CEILINGS,
FLOORS, ROOFS, ETC. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF FIRE RATED
STRUCTURES.
11. PROVIDE STOCK OF EXTRA SPRINKLERS IN ACCORDANCE WITH "UFC 3-600-01" (REV.
5.6.2021).
12. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN ACCORDANCE
WITH "UFC 3-600-01" (REV. 5.6.2021). FOR ALL PROJECTS, DESIGN OF SUPPORTS FOR FIRE
PROTECTION SYSTEMS SHALL COMPLY, AS A MINIMUM, WITH SEISMIC CRITERIA AS
OUTLINED IN UFC REQUIREMENTS.
13. TEMPERATURE RATINGS, OF…