Ft Hamilton PMCS Reports 2024 Redacted_Redacted.pdf

PDF 3 MB Posted

Attached to
ICIDS Maintenance Services Fort Hamilton NY
Solicitation number
W15QKN26QA137
Issued by

About this file

This document is a series of Integrated Intrusion Detection System (ICIDS) Preventive Maintenance Checks and Services (PMCS) records for Fort Hamilton, covering the inspection period of May 20-24, 2024. The records document facility point of contact information and comprehensive maintenance inspection results across 17 separate buildings and security zones at the installation.

The PMCS records detail voltage measurements for backup batteries, test points (TP1, TP3, TP9), and CMOS batteries across all facilities, with readings consistently falling within acceptable operational ranges (backup batteries ranging from 12.3 to 13.6 volts DC). All inspected facilities passed functional tests including RADC tamper detection, AC power fail detection, 24-hour alarm reception (where applicable), sensor tamper detection, sensor restoration to normal status, exit delay verification, remote access security, and alarm clearing procedures. All sensor and RADC interior visual inspections returned "Good" condition ratings. Facilities inspected include critical security areas such as the EOC (Building 1148, Zone 12), SCIF (Building 114E), MEPS (Building 116, Zone 15), arms rooms (Buildings 212A-212F), NEC facilities (Buildings 206A and 301D), and administrative buildings. The primary facility point of contact across all inspections is Maryann Tighe (maryann.t.tighe.civ@army.mil, 718-630-4691). One corrective action was documented: Building 212B required installation of a 12V 7-amp battery (customer-provided). No additional corrective actions or maintenance issues were noted for the remaining facilities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ICIDS Preventive Maintenance Checks and Services

Installation: Ft Hamilton

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 1148 Name: Maryann Tighe

Facility Name: EOC Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number: 12

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.6 vdc Notes:

TPl DC Voltage: 13.7 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Name:

Maryann Tighe

Email Address: Email Address: ---• Phone Number: Phone Number:

SECURITY2000 TECHNICIAN POINT OF CONTACT

Name: -------------

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 114C Name: Maryann Tighe

Facility Name: ID office Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number:

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 13.1 vdc Notes:

TPl DC Voltage: 13.6 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name:

Email Address: Email Address: ---• Phone Number: Phone Number:

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 114E Name: Maryann Tighe

Facility Name: SCIF Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number:

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.9 vdc Notes:

TPl DC Voltage: 13.2 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.1 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Notes: No 24 hr points

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Name:

Email Address: Email Address: ---• Phone Number: Phone Number:

Name: ----------- Emai

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 116 Name: Maryann Tighe

Facility Name: MEPS Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number: 15

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.7 vdc Notes:

TPl DC Voltage: 13.6 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.1 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Name:

Maryann Tighe

Email Address: Email Address: ---• Phone Number: Phone Number:

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 200 Name: Maryann Tighe

Facility Name: PX Shopette Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number: 24

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.6 vdc Notes:

TPl DC Voltage: 13.6 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name:

Email Address: Email Address: ---• Phone Number: Phone Number:

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 206A Name: Maryann Tighe

Facility Name: DOIM NEC Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number: 25

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.5 vdc Notes:

TPl DC Voltage: 13.7 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.1 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Notes: No 24 hr points

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Name:

Maryann Tighe

Email Address: Email Address: ---• Phone Number: Phone Number:

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Bui lding Number: 2078 Name: Maryann Tighe

Facility Name: Community Club Cash Rm Email Address: mar~ann.t.t ighe.civ@arm~.mil

Phone Number: 718-630-4691

Zone Number: 26

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.8 vdc Notes:

TPl DC Voltage: 13.8 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.0vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Name:

Maryann Tighe

Email Address: Email Address: ---• Phone Number: Phone Number:

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 212A Name: Maryann Tighe

Facility Name: 16th Co Arms Rm Email Address: mar~ann.t.tighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 43

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.7 vdc Notes:

TPl DC Voltage: 13.5 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.3vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct: Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Emai l Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.tighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

I Name Emai l Address: ---1

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 2128 Name: Maryann Tighe

Facility Name: 133rd arms rm 1388 Email Address: maryann.t.t ighe.civ@army.mil

Phone Number: 718-630-4691

Zone Number: 44

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 13.6 vdc Notes: Installed 12v7amp Battery customer provided

TPl DC Voltage: 13.7 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.1 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Maryann Tighe Name:

Email Address: maryann.t.tighe.civ@army.mil Email Address:

Phone Number: 718-630-4691 Phone Number:

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 212D Name: Maryann Tighe

Facility Name: 107th arms rm 1348 Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 46

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.6 vdc Notes:

TPl DC Voltage: 13.5 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Email Address: ---1

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 212E Name: Maryann Tighe

Facility Name: 107th arms rm 1358 Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 47

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.7 vdc Notes:

TPl DC Voltage: 13.6 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 212F Name: Maryann Tighe

Facility Name: 642nd arms rm 1378 Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 48

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.6 vdc Notes:

TPl DC Voltage: 13.5 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.0 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 230 Name: Maryann Tighe

Facility Name: Museum Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 32

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 13.1 vdc Notes:

TPl DC Voltage: 13.7 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 301A Name: Maryann Tighe

Facility Name: Post Office Email Address: mar~ann.t.tighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 38

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.8 vdc Notes:

TPl DC Voltage: 13.6 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.lvdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct: Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Emai l Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.tighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Emai l Address: ---1

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 301D Name: Maryann Tighe

Facility Name: NEC Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 303

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.9 vdc Notes:

TPl DC Voltage: 13.6 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.3 vdc Notes:

CMOS Battery Voltage: 4.3 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Notes: There are no 24 hr points

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 412 Name: Maryann Tighe

Facility Name: Youth Center Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 42

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.7 vdc Notes:

TPl DC Voltage: 13.5 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.0vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

Inspection Date: 5/20/24 to 5/24/24

Start Time:

End Time:

FACILITY LOCATION FACILITY POINT OF CONTACT

Building Number: 207A Name: Maryann Tighe

Facility Name: Museum Archives Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691

Zone Number: 28

PMCS RECORD

Sensor Visual Inspection: Good

RADC Interior Visual Inspection: Good

Backup Battery Voltage : 12.3 vdc Notes:

TPl DC Voltage: 13.7 vdc Notes:

TP3 DC Voltage: 4.9 vdc Notes:

TP9 DC Voltage: 3.2 vdc Notes:

CMOS Battery Voltage: 4.2 vdc Notes:

RADC Tamper Received: Pass Notes:

AC Power Fail Received : Pass Notes:

24 Hour Alarms Received: Pass Notes:

Sensor Tampers Received: Pass Notes:

Sensors Restored to Normal: Pass Notes:

Exit Delay Correct : Pass Notes:

Remote Access/ Secure: Pass Notes:

All Alarms Cleared: Pass Notes:

Addit ional Notes/ Corrective Actions:

PHYSICAL SECURITY POINT OF CONTACT ALARM OPERATOR POINT OF CONTACT

Name: Maryann Tighe Name: Maryann Tighe

Email Address: mar~ann.t.tighe.civ@arm~.mil Email Address: mar~ann.t.t ighe.civ@arm~.m il

Phone Number: 718-630-4691 Phone Number: 718-630-4691

File details come from the government source that posted it. Updated .