This document is a Medical Gas Certification report for the Viera VA Outpatient Clinic in Melbourne, Florida, conducted on January 26, 2023, by Mercury Medical. The comprehensive certification includes testing and inspection of multiple medical gas systems, including medical air compressors, vacuum pumps, oxygen and nitrous oxide manifolds, and medical gas outlets across various facility zones. The report covers critical areas such as zone valve data, alarm systems, outlet functionality, and pressure measurements for oxygen, medical air, nitrous oxide, and vacuum systems.

The certification was performed by Frank D'Arpa (Medical Gas Certifier, N.I.T.C. # 12313456) and follows NFPA 99, 2018 Edition standards. The testing examined multiple critical parameters including line pressures, gas concentrations, outlet performance, alarm functionality, and system integrity across different facility zones like recovery areas, endoscopy rooms, and nurses stations. The report indicates that most systems passed inspection, with some detailed notes on specific outlet and system performance, though no major discrepancies were explicitly highlighted in the summary section.

View the file

Other files

File Type Posted
S06 36C24825Q0759 0002.pdf PDF
36C24825Q0759 0002.docx DOCX document
S06 36C24825Q0759 0001.pdf PDF
36C24825Q0759 0001.docx DOCX document
S02 36C24825Q0759_final.pdf PDF
D.5 ATTACHMENT D MEDGAS Equiptment Inventory_By Campus_w-images.xlsx XLSX spreadsheet
Lake Baldwin MedGas Example.pdf PDF
Lake Nona MedGas Example.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Site Contact Person Contact Title Phone #

EQUIPMENT pick one Air Compressor/System Vacuum Pump/System Other

Maintenance Interval - pick one Quarterly PM Semi-Annual PM Quarterly and Annual PM One-Time PM

Location in facility Temp in equipment room °F

Manufacturer Accessories

Model Number

Serial Number

Drawing, Job Number

Motor Plate Info: Amps SF Rated Voltage HP

Voltage Readings: Lead 1-2 Check here if single phase

Lead 1-3

Lead 2-3

Amperage Readings:

Lead 1

Lead 2

Lead 3

Visual Checks:

Rotation

Oil Level

Hours

Overloads set at

H-O-A Switch

Belt Tension

Pump Temp °F

Max Vac inches hg

Vane Width*

*applies to dry rotary vane pumps only

Pressure Switch Settings:

On

Off

Air Dryer/Air Treatment device info: Bank/Unit 1 Bank/Unit 2 Bank/Unit 1 Bank/Unit 2

Bank in service on arrival Suction pressure (if fitted)

Bank in service at completion (dryers switched) Filter element(s) condition

Tower changeover OK (desiccant dryers) Dew point °F

Other Operating Parameters:

Horn audible Pumps alternate correctly Oil / filter changed

Auto-drains functional Intake filters checked CO monitor operating

Panel lights functional Motor bearings lubed DP monitor operating

Bypass correctly set Gearcase oil level checked Lag alarm operating

Exhaust outlet screen checked for silncer debris (only applies to Rietschle and Busch dry claw vacuum pumps)

All screw terminals tightened in control panel; control panel checked for arcing

OWNER / OWNER'S REPRESENTATIVE DATE

CITY & STATE

CITY & STATE

WO #:

TECH:

Medical Technology Associates, Inc. Corporate Office: 6651 102nd Ave N, Pinellas Park, FL 33782 Tel 877-569-8886 Fax

727-548-8622 Form PM1 - 2015-06

Future service needs and/or service notes:

MTA SERVICE TECHNICIAN DATE

DATE

PO #

CUSTOMER

"" or "Y" = Yes or OK, "X" or "N" = No or Not OK, "-" or "N/A" = Not Applicable NOTE: All fields do not apply to all installations.

Lead Lag 1 Lag 2 Lag 3

FACILITY

PREVENTATIVE MAINTENANCE SERVICE REPORT

AIR COMPRESSOR - VACUUM PUMP

Pump 4Pump 3

Pump 1 Pump 2 Pump 3 Pump 4

Pump 1 Pump 2

NancyH Line

Maintenance Interval - pick one Quarterly PM Semi-Annual PM Quarterly and Annual PM One-Time PM Location in facility Temp in equipment room °F Manufacturer Accessories Model Number Serial Number Drawing, Job or Q Number

Motor Plate Info: Amps SF Rated Voltage HP

Voltage Readings: Lead 1-2 Check here if single phase Lead 1-3 Lead 2-3

Amperage Readings:

Lead 1 Lead 2 Lead 3

Amperage Readings:

Lead 1 Lead 2 Lead 3

Visual Checks: AC 1 AC 2 AC 3 AC 4 AC 5 AC 6 AC 7 AC 8 Rotation Hours Overloads set at H-O-A Switch Belt Tension Pump Temp °F

Pressure Switch Settings:

On Off

Pressure Switch Settings:

On Off

Time to Satisfy Pressure Switch (In Seconds)

Air Dryer/Air Treatment device info:

Pick one: Refrigerant Bank/Unit 1 Bank/Unit 2

Dessicant Bank/Unit 1 Bank/Unit 2 Suction pressure (if fitted) Bank in service on arrival Filter element(s) condition Bank in service at completion (dryers switched) Dew point °F indicated Tower changeover OK (desiccant dryers) Dew point °F actual

Other Operating Parameters:

Horn audible Pumps alternate correctly Auto-drains functional Intake filters checked Panel lights functional Motor bearings lubed Bypass correctly set Gearcase oil level checked

Oil / filter changed CO monitor operating DP monitor operating Lag alarm operating Control Cabinet Filter Clean Scroll Greased as Required

Touch screen functioning Tip seals due for scroll compessors 5000hrs HP and 10000 hrs for SP? __________ All screw terminals tightened in control panel; control panel checked for arcing _________

AC 1 AC 2

PREVENTATIVE MAINTENANCE SERVICE REPORT

AIR COMPRESSOR SYSTEM

AC 4

"" or "Y" = Yes or OK, "X" or "N" = No or Not OK, "-" or "N/A" = Not Applicable NOTE: All fields do not apply to all installations.

Lead

TECH:

Lag 3

FACILITY

AC 3

DATE

PO #

CUSTOMER

Medical Technology Associates, LLC Corporate Office: 6651 102nd Ave N, Pinellas Park FL 33782 Tel 877-569-8886 Fax 877-787-3220 Form PM1a2 - v2023-03

Future service needs and/or service notes:

MTA SERVICE TECHNICIAN DATE

Lag 1 Lag 2

CITY & STATE

CITY & STATE

WO #:

RESPONSIBLE FACILITY AUTHORITY DATE

AC 5 AC 6 AC 7 AC 8

Lag 4 Lag 5 Lag 6 Lag 7

AC 7 AC 8

AC 1 AC 2 AC 3 AC 4

AC 5 AC 6

PREVENTATIVE MAINTENANCE SERVICE REPORT

Amperage Readings:

Lead 1 Lead 2 Lead 3

Amperage Readings:

Lead 1 Lead 2 Lead 3

Visual Checks: AC 9 AC10 AC11 AC12 AC13 AC14 AC15 AC16 Rotation Hours Overloads set at H-O-A Switch Belt Tension Pump Temp °F

Pressure Switch Settings:

On Off

Pressure Switch Settings:

On Off

Time to Satisfy Pressure Switch (In Seconds)

AIR COMPRESSOR SYSTEM

AC 9 AC 10 AC 12

"" or "Y" = Yes or OK, "X" or "N" = No or Not OK, "-" or "N/A" = Not Applicable NOTE: All fields do not apply to all installations.

DATE

AC 9

TECH:

AC 12

FACILITY

AC 11

PO #

CUSTOMER

Medical Technology Associates, LLC Corporate Office: 6651 102nd Ave N, Pinnellas Park, FL 33782 Tel 877-569-8886 Fax 727-548-8622 Form PM1a2 - V2023-03

AC 10 AC 11

CITY & STATE

CITY & STATE

WO #:

AC 13 AC 14 AC 15 AC 16

AC 13 AC 14 AC 15 AC 16

AC 15 AC 16

AC 9 AC 10 AC 11 AC 12

AC 13 AC 14

FACILITY: Va Viera

CITY &

STATE

Viera

CUSTOMER: Va Viera

CITY &

STATE

Melbourne

PO#: NA JOB #: j67107

DATE: 3/4/2023 TECH: Miguel Ruiz

Affidavit j67107 Control # NA

All In One Certification Form - V2022-5.14

Medical Technology Associates Inc.

Certification

Medical Technology Associates

6651 102nd Ave N, Pinellas Park, FL 33782

Tel. (727) 535-3007, Fax (727) 548-8622

Certification

Affidavit #: j67107

Medical Technology Assications, Inc.

FACILITY:

CITY &

STATE

CUSTOMER:

CITY &

STATE

PO#: JOB #:

DATE: TECH:

OXY AIR VAC N2O N2 CO2 WAGD Other

Date

Viera

Melbourne

F. LEAK DETECTION

G. OTHER

A. TOTAL SYSTEM

EVALUATION

B. PATIENT OUTLET

TESTING

C. CONSTRUCTION

CERTIFICATION

D. CONTAMINANT TESTING

E. PARTICULATE MATTER

TESTING

CHECK APPROPRIATE BOX(ES)

MEDICAL GAS PIPING

SYSTEMS (A - G only)

Va Viera

Va Viera

NA

3/4/2023 j67107

Miguel Ruiz

Comments:

6651 102nd Ave N, Pinellas Park, FL 33782 | Tel. (727) 535-3007, Fax (727) 548-8622 | Form 100 - V2022-5.14

3/4/2023 Mccloskey mechanicalDominic Calloway

(Print)

CompanyService Acknowledged By Signature of

Responsible Facility Authority

Acknowledgement of Services certification_zone

Affidavit #: j67107

Medical Technology Associates, Inc.

FACILITY:

CUSTOMER:

PO#:

DATE:

Individual Pressurization (5.1.12.4.3.1) ✔ Pressure Differential (5.1.12.4.3.2)

Oxy P P P P P 50 40 60 P P P P

Vac P P P P P 29 12 NA P P P P

P = Pass; F = Fail, SC = See Comment

NA

Viera

Comments:

Va Viera

Va Viera

3/4/2023

ZONE

VALVE

BOX

Location:

Area Served:

AREA

ALARM

PANEL

Area Served:

Standing

Pressure

Test

Pressure

Gauges

Cross

Connection

Test

Insde room

G108 and G109

System

Line

Pressure

Low

Alarm High Alarm

Audible

Visual

Signals

Test

Switch

Sensor

Location

Pass / Fail

6651 102nd Ave N, Pinellas Park, FL 33782 | Tel. (727) 535-3007, Fax (727) 548-8622 | Form 102 - V2022-5.14

CITY &

STATE

CITY &

STATE

JOB #:

TECH: Miguel Ruiz j67107

Melbourne

Pass /

Fail

CROSS CONNECTION TEST (Check methodology)

Location:Right of entry

G108 and G109

Gas / Vacuum Proper

Labeling

Pass /

Fail

Medical Gas & Vacuum Zone Valve & Alarm Panel certification_field_affidavit

Affidavit #: j67107

Control Number: NA

Medical Technology Associates, Inc.

I, P System Inspection Per NFPA99 2021 5.1.12.3 has been completed.

Miguel Ruiz 3/4/2023 accordance with NFPA99 2021 and attest to the following:

Area Inspected: G108 and G109

Check appropriate box(es)

P

NA

DATE:

FACILITY: Va Viera

CITY &

STATE

Viera

TECH: Miguel Ruiz

P

P = Pass, F = Fail, NA = Not Applicable

P

P

P

NFPA99 2015

Antonio Ayala Certificate #: 12491804

Installer Performed Tests Per NFPA99 2021 Code 5.1.12.2 have been completed.

Verifier cross connection test was successfully completed.

Name: Certificate # :

Pipeline system tested was purged of the test gas Nitrogen (NF).

P

All tested outlets and inlets are labeled and functioning properly for flow and pressures.

All tested alarm panels were located and functioning properly.

All tested valves and zone valve boxes were located properly with tags and labels.

CUSTOMER: Va Viera

CITY &

STATE

Melbourne

PO#: NA

3/4/2023

Associates as of (date) , as a current appointed representative of Medical Technology have conducted tests of the Medical Gas & Vacuum System in

JOB #: j67107

P

P

Any equipment not listed on the attached worksheets is the responsibility of the Contractor and / or Facility.

P

All tested central supply systems were found to be properly located and functioning for their intended use.

If this box is "X'ed" review all notes on the MTA CODE COMPLIANCE WORK SHEET before patient use.

Verifiers 10 minute standing pressure test was successfully completed.

The concentration of the gas delivered at each outlet was tested and is within specified standards.

Category 3

Verifier is ASSE 6030 qualified per NFPA99 2021 5.1.12.4.1.3

Verifier is ASSE 6035 qualified per NFPA99 2021 5.1.12.4.1.4

NFPA99 2018 NFPA99 2021✔ Other

NFPA99 2012Category 1 Category 2

6651 102nd Ave N, Pinellas Park, FL 33782 | Tel. (727) 535-3007, Fax (727) 548-8622 | Form 104 - V2022-5.14

Signed (Contractor):Signed (MTA, Inc.): Signed (Responsible Facility Authority):

supply systems) at a later date.

NA

NA

piping system (including but not limited to inlets / outlets, alarm panels, zone valve boxes, manifolds or central

Medical Technology Associates, Inc will be held harmless from any liability caused by any modification of the

All tested air compressor and vacuum pumps were inspected and are installed correctly.

The above certification applies to the condition of the detailed, itemized list of equipment as of the date noted.

Hold Harmless Clause:

The Contractor and / or Facility are responsible for the identification of all the equipment to be certified.

Field Affidavit Inspection / Testing Services

Medical Gas & Vacuum Systems certification_outlet_b

Affidavit #: j67107

Medical Technology Associates, Inc.

W Oxy Y P

W Vac Y NA

W Oxy Y P

6651 102nd Ave N, Pinellas Park, FL 33782 | Tel. (727) 535-3007, Fax (727) 548-8622 | Form 105N - V2022-5.14

Pass

Fail

G108

Adjacent Inlet Test

(Vacuum)

Pressure

>12” Hg

3.0

(SCFM)

>5.0

NA >12

<5.0 >6 NA NA

Operational Pressure Test

(Gases)

Trans Flow Test

(SCFM)

Drop

(PSIG)

NA

Test

Gas

Purge

Test Flow 3.5

(5.0 N2) SCFM

Type of

Gas

Station

W,D,P,C

Location

G109 >5.0

AREA:

FACILITY:

CUSTOMER:

G108 and G109

Va Viera

Va Viera

3/4/2023

Miguel Ruiz

** Station Abbreviations: **W = Wall **D = Hose Drop **P = Pedestal **C = Arm, Boom, Column or Pendant

NA = Not Applicable / ND = None Detected / P = Passed / F = Failed / SC = See Comment

DATE:

TECH:

NA NA >3.0

<5.0 >6 NA

Additional Outlets may be continued on following sheets.

Comments:

Medical Gas & Vacuum Outlets certification_particulate

Affidavit #: j67107

Medical Technology Associates, Inc.

OXYGEN

FACILITY: Va Viera

CITY &

STATE

Viera

CITY &

STATE

Melbourne CUSTOMER: Va Viera

PO#: NA

Pass or Fail

NA

P

JOB #:

TEST CONDITION TEST RESULT

DATE: 3/4/2023 TECH:

NITROUS

OXIDEOXYGEN

MEDICAL

AIR

Miguel Ruiz

NITROGEN /

Instrument j67107

CARBON

DIOXIDE

P = Pass / F = Fail / NA = Not Applicable / ND = None Detected / SC = Source / N = N2 NF

NITROUS

OXIDE

NITROGEN /

Instrument

NA

NA

CARBON

DIOXIDE ZONE LOCATION and ROOM NUMBER

MEDICAL

AIR

G108

NA NANA NA

NA

NA

No Discoloration on filter

SC NA NASource (SC) or N2 NF (N)

< 1.0 MG Particulate Matter P NA

Test Gas Used

Pass or Fail

NAP NA NA NA

6651 102nd Ave N, Pinellas Park, FL 33782 | Tel. (727) 535-3007, Fax (727) 548-8622 | Form 112 - V2022-5.14

Medical Gas Particulate Test

Maintenance Interval - pick one Quarterly PM Semi-Annual PM Quarterly and Annual PM One-Time PM Location in facility Temp in equipment room °F Manufacturer Accessories Model Number Serial Number Drawing, Job or Q Number

Motor Plate Info: Amps SF Rated Voltage HP

Voltage Readings: Lead 1-2 Check here if single phase Lead 1-3 Lead 2-3

Amperage Readings:

Lead 1 Lead 2 Lead 3

Visual Checks:

Rotation Oil Level Hours Overloads set at H-O-A Switch Pump Temp °F Max Vac inches hg Vane Width*

*applies to dry rotary vane pumps only

Pressure Switch Settings:

On Off

Other Operating Parameters:

Horn audible Pumps alternate correctly Panel lights functional Motor bearings lubed Bypass correctly set Gearcase oil level checked Touch screen functioning Intake Filters checked All screw terminals tightened in control panel; control panel checked for arcing _________

Oil / filter changed Exhaust Filters changed Site Glasses Cleaned Check Valves Function Lag alarm operating Control Cabinet Filter Clean

Exhaust outlet screen checked for silncer debris (only applies to Rietschle and Busch dry claw vacuum pumps)

Pump 1 Pump 2 Pump 3 Pump 4

Pump 1 Pump 3Pump 2 Pump 4

PREVENTATIVE MAINTENANCE SERVICE REPORT

VACUUM SYSTEM

Lag 3

FACILITY

DATE

PO #

CUSTOMER

"" or "Y" = Yes or OK, "X" or "N" = No or Not OK, "-" or "N/A" = Not Applicable NOTE: All fields do not apply to all installations.

TECH:

Medical Technology Associates, LLC Corporate Office: 6651 102nd Ave N, Pinellas Park, FL 33782 Tel 877-569-8886 Fax 877-787-3220 Form PM1b2 v2023-03

Future service needs and/or service notes:

MTA SERVICE TECHNICIAN DATE

CITY & STATE

CITY & STATE

WO #:

Lead

RESPONSIBLE FACILITY AUTHORITY DATE

Lag 1 Lag 2

Amperage Readings:

Lead 1 Lead 2 Lead 3

Visual Checks:

Rotation Oil Level Hours Overloads set at H-O-A Switch Pump Temp °F Max Vac inches hg Vane Width*

*applies to dry rotary vane pumps only

Pressure Switch Settings:

On Off

VACUUM SYSTEM

PREVENTATIVE MAINTENANCE SERVICE REPORT

Pump 5 Pump 6 Pump 7 Pump 8

Pump 5 Pump 6 Pump 8Pump 7

FACILITY

DATE

PO #

CUSTOMER

"" or "Y" = Yes or OK, "X" or "N" = No or Not OK, "-" or "N/A" = Not Applicable NOTE: All fields do not apply to all installations.

TECH:

Medical Technology Associates, Inc. Corporate Office: 6651 102nd Ave N, Pinellas Park, FL 33782 Tel 877-569-8886 Fax 727-548-8622 Form PM1b2 - 2023-03

CITY & STATE

CITY & STATE

WO #:

Lag 4 Lag 5 Lag 6 Lag 7

Project:

Attention:

Completed By:

Annual Medical Gas Certification

William Glover

Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

THESE DOCUMENTS CONTAIN THE CERTIFICATION REPORTS FOR:

Viera VA Outpatient Clinic 2900 Veterans Way

Melbourne, FL 32940

01/26/2023

11300 49th Str. No.

Clearwater, FL 33762

Ph: (800) 990-6372 Fax: (866) 348-9650 1 of 31 Pages

(NFPA 99, 2018 Edition)

Section Results 1 Certificate of Compliance Permanent 2 Medical Air Source Data Tested 3 Medical Vacuum Source Data Tested 4 Manifold Source Data Tested 5 Master Alarm Data Tested 6 Area Alarm Data / Zone Valve Inspection / Tested

Medical Gas Outlets / Filter Analysis 7 Summary Included

CERTIFICATION REPORTS, DATA & FINDINGS

Table of Contents for:

Viera VA Outpatient Clinic 2900 Veterans Way

Melbourne, FL 32940

11300 49th Str. No.

Clearwater, FL 33762

Ph: (800) 990-6372 Fax: (866) 348-9650

2 of 31 Pages

This certificate is issued - 01/26/2023 by Mercury Medical®.

This certificate relates to the work performed pursuant to a request for testing services by - Viera VA Outpatient Clinic

In accordance with the terms of that agreement, Mercury Medical® has tested the medical gas piping system of said hospital or a specific area of said - Viera VA Outpatient Clinic located in - Melbourne, FL

And, hereby certifies that as of the time said inspection was performed and except as noted on the data sheets and non compliance-page.

(NFPA 99, 2018 Edition) 1 There are no cross connections found within the medical gas system as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

2 The medical gas alarm systems are functioning within the established limits as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

3 All valves have been tested for operation and leakage as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

4 All valves, gas outlets and alarms were properly labeled as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

5 Each positive pressure piping system has been purged, analyzed and the piping purity tested as defined by applicable standards as required by NFPA 99, Chapter 5 - Gas and Vacuum Systems.

6 Each positive pressure piping system has been purged, analyzed and the gas dispensed is of proper concentration as required by NFPA 99, Chapter 5 - Gas and Vacuum Systems.

7 Piping systems operations pressure/flows have been tested as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

8 All positive pressure gas systems used for patient application have been tested for particulate contamination as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

9 Medical vacuum outlets were tested as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

10 Source equipment was tested in accordance with NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.

The data sheets accompanying this certificate and final report form, substantiate the certification and provide additional information; they should therefore, be read carefully by all parties. Only those outlets in that portion of the system listed on the attached sheets are included within this certificate.

This certificate shall be rendered void at any time adjustments, modifications or maintenance is performed on the aforementioned systems and/or equipment after this date.

Frank D'Arpa

CERTIFICATE OF COMPLIANCE

Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

11300 49th Str. No.

Clearwater, FL 33762

Ph: (800) 990-6372

3 of 31 Pages

Section 2

Facility Name: Viera VA Outpatient Clinic

Address:

Melbourne, FL 32940

Project Name: Annual Medical Gas Certification Test Date: 01/26/2023

Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for MEDICAL AIR COMPRESSOR Source

Enclosure/Location: Mechanical Room Critical Care Branch: EQDP-38, 40, 42

Package Model # : MTSD03034KS Serial #:

Type: Scroll RPM: 1400

HP: 3 Voltage: 460

Total Compressors in Package: 2 # Operational: 2

Main Line Pressure is: 52 Capacity: 9.5 SCFM @ 50 PSI

Lead Pressure Switch Cut in: 98 Cut Out: 110

Lag Pressure Switch Cut in: 105 Cut Out: 115

Actual Wired to Monitors Mfr. Serial # Reading Master

Dewpoint Powerex (H)05/20/16 69°F Yes CO Enmet 300-3195 0 Yes Dryers Powerex 0087 Pre Filters Wilkerson FRP96639 Pre Filters Wilkerson MSP96647

Filter Analysis 250 CO2 PPM 0

Recommendations:

Discrepancy:

F1803SHLO

A1804BL00

Hydro Carbon PPM

PMD10T00AJ

MEDICAL AIR COMPRESSOR SOURCE DATA

2900 Veterans Way

Model #

PDPM1001AJ

Co-Guard

(H)05/20/16-5926690-771

11300 49th Str. No.

Clearwater, FL 33762

Ph: (800) 990-6372

4 of 31 Pages

Section 3

Address:

Project Name: Annual Medical Gas Certification Test Date:

Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for VACUUM Primary & Backup Source

Enclosure/Location: Med Gas room (dock) Critical Care Branch: EQDF 13, 15, 17

Package Model # : 1DRB7.5T200 Serial #: 125309812

Type: Rotary Lubed RPM: 1760

HP: 7.5 Voltage: 460 FLA: SF:

Total Vac Pumps in Package: 2 # Operational: 2

Source Line Vacuum is: 29 " Hg Capacity: 43 SCFM Each @19 IN

Lead Pressure Switch Cut in: 19 Cut Out: 24

Lag Pressure Switch Cut in: 16 Cut Out: 20

Comments:

Recommendations:

Discrepancy:

VACUUM SOURCE DATA

2900 Veterans Way Melbourne, FL 32940

01/26/2023

11300 49th Str. No.

Clearwater, FL 33762

Ph: (800) 990-6372

5 of 31 Pages

Section 4

Address:

Melbourne, FL 32940

Project Name: Annual Medical Gas Certification Test Date: 01/26/2023

Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for Oxygen Primary & Secondary Supply

Enclosure/Location: Med Gas Room (dock) Critical Care Branch: LLD 16

Manifold Manufacturer is: Amico

Model #: MTLTDHHUOXY Serial #: 981123-D

Liquid /Gas: Gas

6 Right Bank: 6

Main Line Manifold Pressure: 52 PSI

Manifold Right Bank Pressure: 600 PSI

Manifold Left Bank Pressure: 2200 PSI

Comments:

Recommendations:

Discrepancy:

OXYGEN MANIFOLD SOURCE DATA

2900 Veterans Way

Cylinders in Left Bank:

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 6 of 31 Pages

Address:

Melbourne, FL 32940

Project Name: Annual Medical Gas Certification Test Date: 01/26/2023

Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for Nitrous Oxide Primary & Secondary Supply

Enclosure/Location: Med Gas Room (dock) Critical Care Branch: LLD 14

Manifold Manufacturer is: Amico

Model #: MTLTDHHUOXY Serial #: 981123-D

Liquid /Gas: Gas

2 Right Bank: 2

Main Line Manifold Pressure: 51 PSI

Manifold Right Bank Pressure: 400 PSI

Manifold Left Bank Pressure: 680 PSI

Comments:

Recommendations:

Discrepancy:

NITROUS OXIDE MANIFOLD SOURCE DATA

2900 Veterans Way

Cylinders in Left Bank:

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 7 of 31 Pages

Address:

Melbourne, FL 32940

Project Name: Annual Medical Gas Certification Test Date: 01/26/2023

Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for Nitrogen Primary & Secondary Supply

Enclosure/Location: Med Gas Room (dock) Critical Care Branch: LLD 18

Manifold Manufacturer is: Amico

Model #: M2HD-D-HH-NIT Serial #: 981127-D

Liquid /Gas: Gas

2 Right Bank: 2

Main Line Manifold Pressure: 173 PSI

Manifold Right Bank Pressure: 1800 PSI

Manifold Left Bank Pressure: 1500 PSI

Comments:

Recommendations:

Discrepancy:

NITROGEN MANIFOLD SOURCE DATA

2900 Veterans Way

Cylinders in Left Bank:

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 8 of 31 Pages

Section 5

MASTER ALARM DATA

Facility Name: Viera VA Outpatient Clinic

Address:

Project Name: Annual Medical Gas Certification Test Date: 01/26/2023 Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Critical Care Branch: LLD CKT 18 _________________________________ Setpoint

YES NO YES NO

X 40 X X 40 X X 40 X X 140 X

X 12 X

X 60 X X 60 X X 60 X X 195 X

N/A N/A N/A N/A N/A N/A

Local Visual Local Audible Local Alarm Only

X X X

X X X

X X X

X X X Local Visual Local Audible Local Alarm Only

X X X

X X

Comments:

Recommendations:

Discrepancy:

Vacuum Pumps Wired To Master Not Wired To Master

High Temp X Lag Pump Running X

X

Lag Compressor Running X

Air Receiver High Water (Note15)

Liquid Ring Comp High Water (Note16)

Medical Air Compressor Wired To Master Not Wired To Master

Dew Point High ( 39F@50psig)

Secondary Liquid Level Low

Secondary Low Head Pressure

X

Carbon Monoxide High (<10ppm) X

Compressor High Air Temp (Note14)

Bulk Oxygen Site Switch Setpoint Wired To Master Not Wired To Master

Manifolds Secondary Supply In Use Oxygen Medical Air

Nitrous Oxide Nitrogen

Carbon Dioxide Other

Primary Liquid Level Low

Secondary Supply In Use

Other

EVAC

Other

Line Pressure High Oxygen Medical Air

Nitrous Oxide Nitrogen

Carbon Dioxide

Line Pressure Low Oxygen Medical Air

Nitrous Oxide Nitrogen

Carbon Dioxide Vacuum

2900 Veterans Way Melbourne, FL 32940

Manufacturer: Amico Alert 1

Enclosure Location: Biomed Gas Labeled Functioning

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 9 of 31 Pages

Section 5

MASTER ALARM DATA

Facility Name: Viera VA Outpatient Clinic

Address:

Project Name: Annual Medical Gas Certification Test Date: 01/26/2023 Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Critical Care Branch: LLD CKT 18 Setpoint

YES NO YES NO

X 40 X X 40 X X 40 X X 140 X

X 12 X

X 60 X X 60 X X 60 X X 195 X

N/A N/A N/A N/A N/A N/A

Local Visual Local Audible Local Alarm Only

X X X

X X X

X X X

X X X Local Visual Local Audible Local Alarm Only

X X X

X X

Comments:

Recommendations:

Discrepancy:

2900 Veterans Way Melbourne, FL 32940

Manufacturer: Amico Alert 1

Enclosure Location: Biomed Gas Labeled Functioning

Line Pressure Low Oxygen Medical Air

Nitrous Oxide Nitrogen

Carbon Dioxide Vacuum

Other

EVAC

Other

Line Pressure High Oxygen Medical Air

Nitrous Oxide Nitrogen

Carbon Dioxide

Bulk Oxygen Site Switch Setpoint Wired To Master Not Wired To Master

Manifolds Secondary Supply In Use Oxygen Medical Air

Nitrous Oxide Nitrogen

Carbon Dioxide Other

Primary Liquid Level Low

Secondary Supply In Use

Medical Air Compressor Wired To Master Not Wired To Master

Dew Point High ( 39F@50psig)

Secondary Liquid Level Low

Secondary Low Head Pressure

X

Carbon Monoxide High (<10ppm) X

Compressor High Air Temp (Note14) X

Lag Compressor Running X

Air Receiver High Water (Note15)

Liquid Ring Comp High Water (Note16)

Vacuum Pumps Wired To Master Not Wired To Master

High Temp X Lag Pump Running X

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 10 of 31 Pages

Section 6

Floor: Facility Name:

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 29 Yes

EVAC

Other

O U T L E T S

Yes 2 - Nitrous Oxide 10 - Leaking outlet 20 - Failed Flow Rate Test

Yes 30 - Failed Pressure Test 40 - Can't insert; won't lock 50 - Unable to test (in use) 60 - Missing parts

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

N - Nitrogen Yes E - EVAC (WAGD)

Medical Air

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide x Non-Critical Area Outside E504 E504 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023

Ox yg en

SC

FM

3.

M ed ica l A ir

SC

Ni tro us

Ox ide

SC

Ni tro ge n

SC

FM

Ca rb on

Di ox ide

SC

Va cu um

SC

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Notes

Room No.

1 P 1 P 1 P 1 PE504 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = 28 psig 99% Nitrous Oxide = 50 psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Gas

Pa rti cu la te m g no n-

M et ha ne

H yd ro ca rb on s pp m

*P/F = Pass/Fail AmicoAmico

Attached Outlet Data sheet for this zone.

Actual Static Pressure

H al og en at ed hy dr oc ar bo ns p pm

D ew

P oi nt

F

Actual Static PressureGas

Ohmeda

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 11 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 29 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside E505 E505 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 P 1 PE505 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = 28 psig 99% Nitrous Oxide = 50 psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 12 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 29 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside E507 E507 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 P 1 PE507 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = 29 psig 99% Nitrous Oxide = 50 psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 13 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside E508 E508 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 P 1 PE508 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = 29 psig 99% Nitrous Oxide = 50 psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 14 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside E509 E509 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 P 1 PE509 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = 29 psig 99% Nitrous Oxide = 50 psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 15 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside E512 E512 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 P 1 PE512 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = 28 psig 99% Nitrous Oxide = 50 psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 16 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside E513 E513 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 P 1 PE513 Not in use

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = psig 99% Carbon Dioxide = psig 21% Medical Air = psig Vacuum = psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ N/A N/A N/A N/A

Comments: Not in use

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 17 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 51 Yes Nitrogen Carbon Dioxide Vacuum 25 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Hallway B118, B121, B208, B209

B313, B316 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 PB118 Good 1 P 1 P 1 PB121 Good 1 P 1 P 1 PB208 Good 1 P 1 P 1 PB209 Good 1 P 1 P 1 PB315 Good 1 P 1 P 1 PB316 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 29 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 18 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes

Nitrous Oxide 50 Yes Nitrogen Carbon Dioxide Vacuum 29 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Nurses Station B332, B412, B410, B414 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air N - Nitrogen

Yes 2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 PB332 Good 2 P 2 P 2 PB410 Good 2 P 2 P 2 PB412 Good 2 P 2 P 2 PB414 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 29 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 19 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes 50 Yes

Nitrous Oxide Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside C104 C102, C108, C122, C123 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air Yes N - Nitrogen

2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

2 P 2 P 2 PC102 Good 1 P 1 P 1 PC108 Good 1 P 1 P 1 PC122 Good 1 P 1 P 1 PC123 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 28 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 20 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes 50 Yes

Nitrous Oxide Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside C115 C115 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air Yes N - Nitrogen

2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 PC115 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 28 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 21 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes 50 Yes

Nitrous Oxide Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside C117 C117, C116 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air Yes N - Nitrogen

2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 PC117 Good 1 P 1 P 1 PC116 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 28 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 22 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes 50 Yes

Nitrous Oxide Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area Outside C119 C119, C120 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air Yes N - Nitrogen

2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

1 P 1 P 1 PC119 Good 1 P 1 P 1 PC120 Good

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 28 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments:

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 23 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes 50 Yes

Nitrous Oxide Nitrogen Carbon Dioxide Vacuum 28 Yes

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023 x Non-Critical Area C406 C406 □ (If applicable) Manufacturer/Model -

Alarm Location: _____________________ x Area alarm data alarm N/A

Zone Valve Location:

Areas Served □ Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Yes E - EVAC (WAGD) Medical Air Yes N - Nitrogen

2 - Nitrous Oxide

20 - Failed Flow Rate Test Yes 30 - Failed Pressure Test

40 - Can't insert; won't lock 50 - Unable to test (in use)

60 - Missing parts

Ox yg en

SC

M ed ica l A ir

SC

Ni

SC

Ni tro ge n

SC

FM

Ca ide

SC

Va cu um

W

AG

D

Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.

Notes

NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above

StyleOultlets Manufacturer

99% Oxygen = 52 psig 99% Carbon Dioxide = psig 21% Medical Air = 50 psig Vacuum = 28 psig 99% Nitrous Oxide = psig EVAC = psig 99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F

□ P P P P

Comments: Not in use

Recommendations:

Discrepancy:

Amico Amico Ohmeda no n-

M et ro ca rb on s pp m

H al og en oc ar bo ns p pm

D ew

P oi nt

F

Attached Outlet Data sheet for this zone.

*P/F = Pass/Fail

Gas Actual Static Pressure Gas

Actual Static Pressure

Pa rti cu la te m g

11300 49th Str. No.

Clearwater, FL 33762

Fax: (866) 348-9650 24 of 31 Pages

1st Address:

Building: Test Date:

Main Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456

Notes/Legend:

Setpoints | Functioning

PSIG

or Hg Low High Yes No

Oxygen 52 Yes 52 40 60 52 Yes 50 40 60

Nitrous Oxide Nitrogen Carbon Dioxide Vacuum 26 Yes 26 12 N/A

EVAC

Other

O U T L E T S

ZONE / ALARM / OUTLETS DATA SHEET

Viera VA Outpatient Clinic 2900 Veterans Way Melbourne, FL 32940 01/26/2023

□ Non-Critical Area C321 Recovery 1-5

C321 X (If applicable) Manufacturer/Model -

Alarm Location: Amico LED

Nurses Station □ Area alarm data alarm N/A

Zone Valve Location:

Areas Served x Critical Area (Alarm Required)

ALARM DATA O - Oxygen Zone Valve Value Data A - Medical Air

10 - Leaking outlet

Zone Gases Installed Correctly

Gauges Present

Alarm PSIG or Hg

V - Vacuum C - Carbon Dioxide

Ye…