Lake Nona MedGas Example.pdf
PDF 4 MB Posted
- Attached to
- J043--FY25: OVAHCS Medical Gas Testing, Inspection, Certification and Preventative Maintenance.
- Solicitation number
- 36C24825Q0759
About this file
This document is a comprehensive medical gas certification report for the Orlando VA Medical Center - Lake Nona facility, conducted by Mercury Medical on February 25, 2023. The detailed 83-page report documents an extensive medical gas system inspection covering multiple hospital zones, including the hospital, clinic, and various units such as ER, MRI, X-Ray, Operating Rooms, Patient Units, and specialized clinic areas. The certification verifies compliance with NFPA 99, 2018 Edition standards, examining medical gas systems for oxygen, medical air, vacuum, and other critical medical gas infrastructure across different building zones.
The report provides granular testing data for each zone, including outlet pressures, gas quality, flow rates, and system alarm functionality. Key findings include comprehensive testing of medical gas outlets, source equipment, manifolds, and alarm systems across approximately 20 different zone valve blocks (C-ZVB-1 through C-ZVB-25). Minor discrepancies were noted in some areas, such as recommendations to repair/replace oxygen sensors, install WAGD (Waste Anesthetic Gas Disposal) outlets, and address specific alarm system issues. The certification confirms that the medical gas systems generally meet required standards, with systematic documentation of each zone's performance and specific technical measurements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06 36C24825Q0759 0002.pdf | ||
| 36C24825Q0759 0002.docx | DOCX document | |
| 36C24825Q0759 0001.docx | DOCX document | |
| S06 36C24825Q0759 0001.pdf | ||
| Veira Medgas Example.pdf | ||
| S02 36C24825Q0759_final.pdf | ||
| D.5 ATTACHMENT D MEDGAS Equiptment Inventory_By Campus_w-images.xlsx | XLSX spreadsheet | |
| Lake Baldwin MedGas Example.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project:
Attention:
Completed By:
Annual Medical Gas Certification - CLC
Orlando VA Medical Center - Lake Nona
Frank D'Arpa - Medical Gas Certifier - N.I.T.C. #
12313456
THESE DOCUMENTS CONTAIN THE CERTIFICATION REPORTS FOR:
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
02/25/23
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
Fax: (866) 348-9650 1 of 25 Pages
(NFPA 99, 2018 Edition)
Section Results
1 Certificate of Compliance Permanent
2 Medical Air Source Data Tested
3 Medical Vacuum Source Data Tested
4 Manifold Source Data Tested
5 Master Alarm Data Tested
6 Area Alarm Data / Zone Valve Inspection / Tested
Medical Gas Outlets / Filter Analysis
7 Summary Included
CERTIFICATION REPORTS, DATA & FINDINGS
Table of Contents for:
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
Fax: (866) 348-9650
2 of 25 Pages
This certificate is issued - 02/25/23 by Mercury Medical®.
This certificate relates to the work performed pursuant to a request for testing services by -
Orlando VA Medical Center - Lake Nona CLC
In accordance with the terms of that agreement, Mercury Medical® has tested the medical gas piping system of said hospital or a specific area of said - Orlando VA Medical Center - Lake Nona CLC located in - Orlando, FL
And, hereby certifies that as of the time said inspection was performed and except as noted on the data sheets and non compliance-page.
(NFPA 99, 2018 Edition)
1 There are no cross connections found within the medical gas system as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
2 The medical gas alarm systems are functioning within the established limits as required by
NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
3 All valves have been tested for operation and leakage as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
4 All valves, gas outlets and alarms were properly labeled as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
5 Each positive pressure piping system has been purged, analyzed and the piping purity tested as defined by applicable standards as required by NFPA 99, Chapter 5 - Gas and Vacuum Systems.
6 Each positive pressure piping system has been purged, analyzed and the gas dispensed is of proper concentration as required by NFPA 99, Chapter 5 - Gas and Vacuum Systems.
7 Piping systems operations pressure/flows have been tested as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
8 All positive pressure gas systems used for patient application have been tested for particulate contamination as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
9 Medical vacuum outlets were tested as required by NFPA 99, 2018 Edition, Chapter 5 -
Gas and Vacuum Systems.
10 Source equipment was tested in accordance with NFPA 99, 2018 Edition, Chapter 5 -
Gas and Vacuum Systems.
The data sheets accompanying this certificate and final report form, substantiate the certification and provide additional information; they should therefore, be read carefully by all parties. Only those outlets in that portion of the system listed on the attached sheets are included within this certificate.
This certificate shall be rendered void at any time adjustments, modifications or maintenance is performed on the aforementioned systems and/or equipment after this date.
Frank D'Arpa
CERTIFICATE OF COMPLIANCE
Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
3 of 25 Pages
Section 2
Facility Name: Orlando VA Medical Center - Lake Nona CLC
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification Test Date: 02/25/23
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for Medical Air Compressor Source
Enclosure/Location: Mechanical Room
Package Model # : MTD0303445 Serial #: 4816888-651
Type: Oil Less RPM: 1760
HP: 3 Voltage: 460 FLA: 4.4
Motor Current 1 #1 Leg 4.4 #2 Leg 14 #3 Leg 14
Motor Current 2 #1 Leg 4.3 #2 Leg 14 #3 Leg 13.9
Total Compressors in Package: 2 # Operational: 18
Main Line Pressure is: 50 Capacity: 10.1 SCFM Each
Lead Pressure Switch Cut in: 80 Cut Out: 100
Lag Pressure Switch Cut in: 70 Cut Out: 90
Actual Wired to
Monitors Mfr. Serial # Reading Master
Dewpoint Powerex 0643 -40°F Yes
CO ENMET 1401 O PPM Yes
Filters (Pre) Powerex No
Filters (Post) Powerex No
Dryer 1 Powerex 0008 No
Dryer 2 Powerex 0008 No
Filter Analysis 0 CO2 PPM <25
Comments: Needs new auto drain on tank. Need float drains on condensate canisters
Recommendations:
Discrepancy:
MEDICAL AIR COMPRESSOR SOURCE DATA
13800 Veterans Way
Model #
PDPM1001
Co-Guard
PMD10T00AJ
PMD10T00AJ
Hydro Carbon PPM
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
4 of 25 Pages
Section 3
Address:
Project Name: Annual Medical Gas Certification
Test Date:
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for Vacuum Primary & Backup Source
Enclosure/Location: Mechanical Area
Package Model # : VTD030341 Serial #: 4816888-686
Type: Rotary RPM: 1725
HP: 3-Jan Voltage: 460 FLA: 3.9 SF: 1.115
Motor Current 1 #1 Leg 3.9 #2 Leg #3 Leg
Motor Current 2 #1 Leg 3.9 #2 Leg #3 Leg
Comments:
Recommendations:
Discrepancy:
VACUUM SOURCE DATA
13800 Veterans Way
Orlando, FL 32827
02/09/2021
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
5 of 25 Pages
Section 4
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification - CLC Test Date: 02/25/23
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for Oxygen Primary & Secondary Supply
Enclosure/Location: Manifold room
Manifold Manufacturer is: TRI-TECH
Model #: LLU12OX1L Serial #: 2011022-E-A
Liquid /Gas: Liquid
2 Right Bank: 2
Main Line Manifold Pressure: 55 PSI
Manifold Right Bank Pressure: 285 PSI
Manifold Left Bank Pressure: 196 PSI
Comments: 8 cylinder high pressure back up system
Recommendations:
Discrepancy:
OXYGEN MANIFOLD SOURCE DATA
13800 Veterans Way
Cylinders in Left Bank:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 6 of 25 Pages
Section 5
MASTER ALARM DATA
Facility Name: Orlando VA Medical Center - Lake Nona CLC
Address:
Project Name: Annual Medical Gas Certification Test Date: 02/25/23
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Setpoint
YES NO YES NO
X 40 X
X 40 X
X 12 X
X 60 X
X 60 X
X N/A X
N/A
N/A
N/A
N/A
N/A
Local Visual Local Audible Local Alarm Only
Yes Yes
Yes Yes
Yes Yes
Yes Yes
Local Visual Local Audible Local Alarm Only
Yes Yes
Comments:
Recommendations: Evaluate and repair signals/retest
Discrepancy: Master alarm signals not functioning properly for oxygen system.
13800 Veterans Way
Orlando, FL 32827
Manufacturer: Amico
Enclosure Location: B Unit Nurses
Station
Gas Labeled Functioning
Line Pressure Low Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum
Other
EVAC
Other
Line Pressure High Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Bulk Oxygen Site Switch Setpoint Wired To Master Not Wired To Master
Manifolds Secondary Supply In Use Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Other
Primary Liquid Level Low Yes
Secondary Supply In Use Yes
Medical Air Compressor Wired To Master Not Wired To Master
Dew Point High ( 39F@50psig)
Secondary Liquid Level Low Yes
Secondary Low Head Pressure Yes
Yes
Carbon Monoxide High (<10ppm) Yes
Compressor High Air Temp (Note14) Yes
Lag Compressor Running Yes
Air Receiver High Water (Note15)
Liquid Ring Comp High Water (Note16)
Vacuum Pumps Wired To Master Not Wired To Master
High Temp Yes
Lag Pump Running Yes
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 7 of 25 Pages
Section 6
Floor: Facility Name:
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum
EVAC
Other
O U T L E T S
□ Critical Area (Alarm Required)
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
N - Nitrogen
Yes x Non-Critical Area
Outside 1A207 Dental 1A207 □ (If applicable) Manufacturer/Model -
Alarm Location:
x Area alarm data alarm N/A
Zone Valve Location:
Areas Served
E - EVAC (WAGD)
Medical Air
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
10 - Leaking outlet
20 - Failed Flow Rate Test
30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
2 - Nitrous Oxide
O xy ge n
S C
F M
3.
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a rb on
D io xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room No.
1 P1A207 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = psig Vacuum = psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Lab Air = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Attached Outlet Data sheet for this zone.
Actual Static
Pressure
H a lo g e n a te d h y d ro c a rb o n s p p m
D e w P o in t
F
Actual Static
PressureGas
DISS AmicoAmico
Gas
P a rt ic u la te m g n o n -M e th a n e
H d ro c a rb o n s p p m
*P/F = Pass/Fail
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 8 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
50 - Unable to test (in use)
60 - Missing parts
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air x Non-Critical Area
B Unit Spring Hill Village - B Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room No.
1 P 1 P 1 P1B012 Good
1 P 1 P 1 P1B014 Good
1 P 1 P 1 P1B016 Good
1 P 1 P 1 P1B018 Good
1 P 1 P 1 P1B020 Good
1 P 1 P 1 P1B022 Good
1 P 1 P 1 P1B024 Good
1 P 1 P 1 P1B027 Good
1 P 1 P 1 P Good1B029
1 P 1 P 1 P1B030 Good
1 P 1 P 1 P1B032 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Attached Outlet Data sheet for this zone.
Amico Amico DISS
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 9 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
Orlando, FL 32827 02/25/23
13800 Veterans Way
B Unit Spring Hill Village - B Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom Number
Notes
1 P 1 P 1 P1B034 Good
1 P 1 P 1 P1B036 Good
1 P 1 P 1 P1B038 Good
1 P 1 P 1 P1B040 Good
*P/F = Pass/Fail
Comments:
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 10 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 48 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
C Unit Spring Hill Village - C Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Notes
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
1 P 1 P 1 P
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
Style
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations: Repair replace oxygen sensor
Discrepancy: Area alarm Oxygen sensor not accurate
Room No.
1C006 Good
1C008 Good
1C010 Good
1C012 Good
1C014 Good
1C016 Good
1C018 Good
1C020 Good
1C022 Good
1C024 Good
1C026 Good
Oultlets Manufacturer
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 11 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
C Unit Spring Hill Village - C Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1C028 Good
1 P 1 P 1 P1C027 Good
1 P 1 P 1 P1C029 Good
1 P 1 P 1 P1C032 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 12 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
D Unit Spring Hill Village - D Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.
Notes
1 P 1 P 1 P1D012 Good
1 P 1 P 1 P1D014 Good
1 P 1 P 1 P1D016 Good
1 P 1 P 1 P1D018 Good
1 P 1 P 1 P1D020 Good
1 P 1 P 1 P1D022 Good
1 P 1 P 1 P1D024 Good
1 P 1 P 1 P1D029 Good
1 P 1 P 1 P1D027 Good
1 P 1 P 1 P1D030 Good
1 P 1 P 1 P1D032 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations: Repair / Replace
Discrepancy: Alarm is off
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 13 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
D Unit Spring Hill Village - D Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1D034 Good
1 P 1 P 1 P1D036 Good
1 P 1 P 1 P1D038 Good
1 P 1 P 1 P1D040 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 14 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
E Unit Spring Hill Village - E Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.
Notes
1 P 1 P 1 P1E004 Good
1 P 1 P 1 P1E006 Good
1 P 1 P 1 P1E008 Good
1 P 1 P 1 P1E010 Good
1 P 1 P 1 P1E012 Good
1 P 1 P 1 P1E014 Good
1 P 1 P 1 P1E016 Good
1 P 1 P 1 P1E018 Good
1 P 1 P 1 P1E020 Good
1 P 1 P 1 P1E022 Good
1 P 1 P 1 P1E024 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 15 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
E Unit Spring Hill Village - E Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1E026 Good
1 P 1 P 1 P1E025 Good
1 P 1 P 1 P1E027 Good
1 P 1 P 1 P1E032 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 16 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
F Unit Oak Tree Village - F Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.
Notes
1 P 1 P 1 P1F012 Good
1 P 1 P 1 P1F014 Good
1 P 1 P 1 P1F016 Good
1 P 1 P 1 P1F018 Good
1 P 1 P 1 P1F020 Good
1 P 1 P 1 P1F022 Good
1 P 1 P 1 P1F024 Good
1 P 1 P 1 P1F027 Good
1 P 1 P 1 P1F029 Good
1 P 1 P 1 P1F030 Good
1 P 1 P 1 P1F032 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 17 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
F Unit Oak Tree Village - F Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1F034 Good
1 P 1 P 1 P1F036 Good
1 P 1 P 1 P1F038 Good
1 P 1 P 1 P1F040 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 18 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
G Unit Oak Tree Village - G Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.
Notes
1 P 1 P 1 P1G006 Good
1 P 1 P 1 P1G008 Good
1 P 1 P 1 P1G010 Good
1 P 1 P 1 P1G012 Good
1 P 1 P 1 P1G014 Good
1 P 1 P 1 P1G016 Good
1 P 1 P 1 P1G018 Good
1 P 1 P 1 P1G020 Good
1 P 1 P 1 P1G022 Good
1 P 1 P 1 P1G024 Good
1 P 1 P 1 P1G026 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 19 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
G Unit Oak Tree Village - G Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1G027 Good
1 P 1 P 1 P1G028 Good
1 P 1 P 1 P1G029 Good
1 P 1 P 1 P1G032 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 20 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
H Unit Blue Water Village - H Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.
Notes
1 P 1 P 1 P1H012 Good
1 P 1 P 1 P1H014 Good
1 P 1 P 1 P1H016 Good
1 P 1 P 1 P1H018 Good
1 P 1 P 1 P1H020 Good
1 P 1 P 1 P1H022 Good
1 P 1 P 1 P1H024 Good
1 P 1 P 1 P1H026 Good
1 P 1 P 1 P1H028 Good
1 P 1 P 1 P1H030 Good
1 P 1 P 1 P1H032 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 21 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
H Unit Blue Water Village - H Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1H033 Good
1 P 1 P 1 P1H034 Good
1 P 1 P 1 P1H035 Good
1 P 1 P 1 P1H042 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 22 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
53 Yes 53 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 24 Yes 24 12 N/A X
EVAC
Other
O U T L E T S
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827 02/25/23 x Non-Critical Area
J Unit Blue Water Village - J Unit x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Nurses station □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served □ Critical Area (Alarm Required)
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
50 - Unable to test (in use)
60 - Missing parts
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/FRoom No.
Notes
1 P 1 P 1 P1J004 Good
1 P 1 P 1 P1J006 Good
1 P 1 P 1 P1J008 Good
1 P 1 P 1 P1J010 Good
1 P 1 P 1 P1J012 Good
1 P 1 P 1 P1J014 Good
1 P 1 P 1 P1J016 Good
1 P 1 P 1 P1J020 Good
1 P 1 P 1 P1J021 Good
1 P 1 P 1 P1J022 Good
1 P 1 P 1 P1J023 Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 55 psig 99% Carbon Dioxide = psig
21% Medical Air = 53 psig Vacuum = 24 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Amico Amico DISS n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Attached Outlet Data sheet for this zone.
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 23 of 25 Pages
1st Address:
Building: Test Date:
CLC Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
O U T L E T S
02/25/23
OUTLETS DATA SHEET ATTACHMENT
Orlando VA Medical Center - Lake Nona CLC
13800 Veterans Way
Orlando, FL 32827
J Unit Blue Water Village - J Unit
Alarm Location
Nurses Station
Zone Valve Location
Areas Served O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C ar bo n
D io xi de
S C
V ac uu m
S C
W A G
D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room Number
1 P 1 P 1 P1J024 Good
1 P 1 P 1 P1J026 Good
1 P 1 P 1 P1J028 Good
1 P 1 P 1 P1J030 Good
Recommendations:
Discrepancy:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 24 of 25 Pages
Section 7
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification Test Date: 02/25/23
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Summary
Recom-
SECTION # Comments mendations Discrepancies
2 Medical Air Source -- -- see page(s) : 4
3 Medical Vacuum Source -- see page(s) :
4 Manifold Source -- see page(s) :
7 7
5 Master Alarms -- see page(s) :
11,13 11,13
6 Area Alarms / Zone Valves / -- see page(s) :
Medical Gas Outlets/Filter
Analyis
CERTIFICATION DISCREPANCY SUMMARY
13800 Veterans Way
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 25 of 25 Pages
Project:
Attention:
Completed By:
Annual Medical Gas Certification
Orlando VA Medical Center - Lake Nona
Frank D'Arpa - Medical Gas Certifier - N.I.T.C. #
12313456
THESE DOCUMENTS CONTAIN THE CERTIFICATION REPORTS FOR:
Orlando VA Medical Center - Lake Nona
13800 Veterans Way
Orlando, FL 32827
02/25/2023
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 1 of 83 Pages
(NFPA 99, 2018 Edition)
Section Results
1 Certificate of Compliance Permanent
2 Medical Air Source Data Tested
3 Medical Vacuum Source Data Tested
4 Manifold Source Data Tested
5 Master Alarm Data Tested
6 Area Alarm Data / Zone Valve Inspection / Tested
Medical Gas Outlets / Filter Analysis
7 Summary Included
CERTIFICATION REPORTS, DATA & FINDINGS
Table of Contents for:
Orlando VA Medical Center - Lake Nona
13800 Veterans Way
Orlando, FL 32827
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
2 of 83 Pages
This certificate is issued - 02/25/2023 by Mercury Medical®.
This certificate relates to the work performed pursuant to a request for testing services by -
Orlando VA Medical Center - Lake Nona
In accordance with the terms of that agreement, Mercury Medical® has tested the medical gas piping system of said hospital or a specific area of said - Orlando VA Medical Center - Lake Nona located in - Orlando, FL
And, hereby certifies that as of the time said inspection was performed and except as noted on the data sheets and non compliance-page.
(NFPA 99, 2018 Edition)
1 There are no cross connections found within the medical gas system as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
2 The medical gas alarm systems are functioning within the established limits as required by
NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
3 All valves have been tested for operation and leakage as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
4 All valves, gas outlets and alarms were properly labeled as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
5 Each positive pressure piping system has been purged, analyzed and the piping purity tested as defined by applicable standards as required by NFPA 99, Chapter 5 - Gas and Vacuum Systems.
6 Each positive pressure piping system has been purged, analyzed and the gas dispensed is of proper concentration as required by NFPA 99, Chapter 5 - Gas and Vacuum Systems.
7 Piping systems operations pressure/flows have been tested as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
8 All positive pressure gas systems used for patient application have been tested for particulate contamination as required by NFPA 99, 2018 Edition, Chapter 5 - Gas and Vacuum Systems.
9 Medical vacuum outlets were tested as required by NFPA 99, 2018 Edition, Chapter 5 -
Gas and Vacuum Systems.
10 Source equipment was tested in accordance with NFPA 99, 2018 Edition, Chapter 5 -
Gas and Vacuum Systems.
The data sheets accompanying this certificate and final report form, substantiate the certification and provide additional information; they should therefore, be read carefully by all parties. Only those outlets in that portion of the system listed on the attached sheets are included within this certificate.
This certificate shall be rendered void at any time adjustments, modifications or maintenance is performed on the aforementioned systems and/or equipment after this date.
Frank D'Arpa
CERTIFICATE OF COMPLIANCE
Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
3 of 83 Pages
Section 2
Facility Name: Orlando VA Medical Center - Lake Nona
Address:
Project Name: Annual Medical Gas Certification
Test Date:
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
This data is for BULK OXYGEN Primary Supply
Enclosure/Location: Bulk Oxygen Pad
Bulk Supplier: Air Liquide
Main Tank Pressure Setting: 120 PSI Reserve Liquid
Low Setting -
100 PSI 30
Reserve Type Liquid/Gas: Gas Reserve Size: 1500
OR # of "H" Bottles:
Main Liquid Level Low Setting: 35
Emergency Fill Box: X Secured: X
Yes No Yes No
Main Tank
Mfr./Date: Model #: 6000 Gal SN: 26247
Reserve Tank
Mfr./Date: Model #: 1500 Gal SN: 26352
Delivery Pressure: 50 PSI
Comments:
Recommendations:
Discrepancy:
BULK OXYGEN SITE DATA
13800 Veterans Way
Orlando, FL 32827
02/25/2023
Reserve Pressure:
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
Fax: (866) 348-9650
4 of 83 Pages
Bulk Oxygen
Site Data
Section 3
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification Test Date: 02/25/2023
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
This data is for MEDICAL AIR COMPRESSOR Source
Enclosure/Location: Mechanical Room
Package Model # : MSH150655183181 Serial #: 3/15/20012 5183181-925
Type: Scroll RPM: 1725
HP: 15 Voltage: 480 FLA: 14.1
Motor Current 1 #1 Leg 13.9 #2 Leg 14 #3 Leg 14
Motor Current 2 #1 Leg 13.9 #2 Leg 14 #3 Leg 13.9
Total Compressors in Package: 18 # Operational: 18
Main Line Pressure is: 52 Capacity: N/A SCFM Each
Lead Pressure Switch Cut in: 80 Cut Out: 100
Lag Pressure Switch Cut in: 70 Cut Out: 90
Actual Wired to
Monitors Mfr. Serial # Reading Master
Dewpoint Powerex N/A -61° Yes
CO ENMET Yes
Filters (Pre) YES No
Filters (Post) YES No
Dryer 1 YES No
Dryer 2 YES No
Filter Analysis <25 CO2 PPM <1
Recommendations:
Discrepancy:
MEDICAL AIR COMPRESSOR SOURCE DATA
13800 Veterans Way
Model #
PDPM1001
Hydro Carbon PPM
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
5 of 83 Pages
Address:
Project Name: Annual Medical Gas Certification
Test Date:
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for VACUUM Primary & Backup Source
Enclosure/Location: Mechanical Room
Package Model # : CUPT15055122708 Serial #: 1/30/2012 5122708-687
Type: Claw RPM: 1725
HP: 15 Voltage: 460 FLA: 14.1 SF: 1.15
Motor Current 1 #1 Leg 14 #2 Leg 14 #3 Leg 14.1
Motor Current 2 #1 Leg 14 #2 Leg 14 #3 Leg 13.9
Motor Current 3 #1 Leg 13.9 #2 Leg 14 #3 Leg 14
Total Vac Pumps in Package: 3 # Operational: 2
Source Line Vacuum is: 23 " Hg Capacity: N/A SCFM Each
Lead Pressure Switch Cut in: 18 Cut Out: 23
Lag Pressure Switch Cut in: 12 Cut Out: 21
Comments:
Recommendations: Repair / Replace/Evaluate
Discrepancy: 1 out of 3 vacuum pumps functioning
VACUUM SOURCE DATA
13800 Veterans Way
Orlando, FL 32827
02/25/23
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
6 of 83 Pages
Address:
Project Name: Annual Medical Gas Certification
Test Date:
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for VACUUM Primary & Backup Source
Enclosure/Location: Mechanical Room
Package Model # : CUPT15055122708 Serial #: 1/30/2012 5122708-704
Type: Oil-less RPM: 1725
HP: 5 Voltage: 460 FLA: 14 SF: 1.15
Starter Mfr: Schneider Heater Size: LC1D18 Fuse Size: 1-1/4
Motor Current 1 #1 Leg 6.1 #2 Leg 6.0 #3 Leg 14.1
Motor Current 2 #1 Leg 6.1 #2 Leg 6.0 #3 Leg 13.9
Total Vac Pumps in Package: 2 # Operational: 1
Source Line Vacuum is: 20 " Hg Capacity: N/A SCFM Each
Lead Pressure Switch Cut in: 20 Cut Out: 25
Lag Pressure Switch Cut in: 18 Cut Out: 23
Comments:
Recommendations:
Discrepancy:
WAGD SOURCE DATA
13800 Veterans Way
Orlando, FL 32827
02/25/23
11300 49th Str. No.
Clearwater, FL 33762
Ph: (800) 990-6372
7 of 83 Pages
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification Test Date: 02/25/2023
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for NITROGEN Primary & Secondary Supply
Enclosure/Location: Manifold room
Manifold Manufacturer is: Amico
Model #: M2HD-D-HH-U-NIT Serial #: 2011022-E-A
Liquid /Gas: Gas
12 Right Bank: 12
Main Line Manifold Pressure: 167 PSI
Manifold Right Bank Pressure: 400 PSI
Manifold Left Bank Pressure: 2239 PSI
Comments:
Recommendations:
Discrepancy:
NITROGEN MANIFOLD SOURCE DATA
13800 Veterans Way
Cylinders in Left Bank:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 8 of 83 Pages
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification Test Date: 02/25/2023
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for CARBON DIOXIDE Primary & Secondary Supply
Enclosure/Location: Manifold room
Manifold Manufacturer is: Amico
Model #: M3A-DL-HHH-U-CO2 Serial #: 20210913-0003
Liquid /Gas: Gas
4 Right Bank: 4
Main Line Manifold Pressure: 52 PSI
Manifold Right Bank Pressure: 200 PSI
Manifold Left Bank Pressure: 200 PSI
Comments:
Recommendations:
Discrepancy:
CARBON DIOXIDE MANIFOLD SOURCE DATA
13800 Veterans Way
Cylinders in Left Bank:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 9 of 83 Pages
Address:
Orlando, FL 32827
Project Name: Annual Medical Gas Certification Test Date: 02/25/2023
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456 This data is for NITROUS OXIDE Primary & Secondary Supply
Enclosure/Location: Manifold room
Manifold Manufacturer is: Amico
Model #: M2HD-D-HH-U-N2O Serial #: 20101208-C-A
Liquid /Gas: Gas
6 Right Bank: 6
Main Line Manifold Pressure: 51 PSI
Manifold Right Bank Pressure: 260 PSI
Manifold Left Bank Pressure: 300 PSI
Comments:
Recommendations:
Discrepancy:
NITROUS OXIDE MANIFOLD SOURCE DATA
13800 Veterans Way
Cylinders in Left Bank:
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 10 of 83 Pages
Facility Name: Orlando VA Medical Center - Lake Nona
Address:
Project Name: Annual Medical Gas Certification Test Date: 02/25/2023
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Setpoint
YES NO YES NO
x 40 x x 40 x x 40 x x 135 x x 40 x x 12 x x 12 x x 60 x x 60 x x 60 x x 195 x x 60 x
N/A
N/A x N/A x x N/A x x N/A x
N/A
Local Visual Local Audible Local Alarm Only x x x x x x x x
Local Visual Local Audible Local Alarm Only x x x x
Comments: Dental Air in lag
Recommendations:
Discrepancy:
13800 Veterans Way
Orlando, FL 32827
Manufacturer: Amico Alert II
Enclosure Location: Biomed 1st Floor Gas Labeled Functioning
Line Pressure Low Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum
Other
EVAC
Other
Line Pressure High Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Bulk Oxygen Site Switch Setpoint Wired To Master Not Wired To Master
Manifolds Secondary Supply In Use Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Other
Primary Liquid Level Low Yes
Secondary Supply In Use Yes
Medical Air Compressor Wired To Master Not Wired To Master
Dew Point High ( 39F@50psig)
Secondary Liquid Level Low Yes
Secondary Low Head Pressure Yes
Yes
Carbon Monoxide High (<10ppm) Yes
Compressor High Air Temp (Note14) Yes
Lag Compressor Running Yes
Air Receiver High Water (Note15)
Liquid Ring Comp High Water (Note16)
Vacuum Pumps Wired To Master Not Wired To Master
High Temp Yes
Lag Pump Running Yes
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 11 of 83 Pages
Facility Name: Orlando VA Medical Center - Lake Nona
Address:
Project Name: Annual Medical Gas Certification Test Date: 02/25/2023
Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Setpoint
YES NO YES NO
x 40 x x 40 x x 40 x x 135 x x 40 x x 12 x x 12 x x 60 x x 60 x x 60 x x 195 x x 60 x
N/A
N/A
N/A x
N/A x
N/A x
N/A
Local Visual Local Audible Local Alarm Only x x x x x x x x
Local Visual Local Audible Local Alarm Only x x x x
Comments: Dental Air in lag
Recommendations:
Discrepancy:
Vacuum Pumps Wired To Master Not Wired To Master
High Temp Yes
Lag Pump Running Yes
Lag Compressor Running Yes
Air Receiver High Water (Note15)
Liquid Ring Comp High Water (Note16)
Medical Air Compressor Wired To Master Not Wired To Master
Dew Point High ( 39F@50psig)
Secondary Liquid Level Low Yes
Secondary Low Head Pressure Yes
Yes
Carbon Monoxide High (<10ppm) Yes
Compressor High Air Temp (Note14) Yes
Bulk Oxygen Site Switch Setpoint Wired To Master Not Wired To Master
Manifolds Secondary Supply In Use Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Other
Primary Liquid Level Low Yes
Secondary Supply In Use Yes
Other
EVAC
Other
Line Pressure High Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Line Pressure Low Oxygen
Medical Air
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum
13800 Veterans Way
Orlando, FL 32827
Manufacturer: Amico Alert II
Enclosure Location: Security 2nd Floor Gas Labeled Functioning
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 12 of 83 Pages
1st Address:
Building: Test Date:
Hospital Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 50 Yes
50 Yes
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 21 Yes
EVAC
Other 35 Yes
O U T L E T S
□ Critical Area (Alarm Required)
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona
13800 Veterans Way
Orlando, FL 32827 02/25/2023
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
N - Nitrogen
Yes
□ Non-Critical Area
Outside Biomed 1H107 □ (If applicable) Manufacturer/Model -
Alarm Location:
□ Area alarm data alarm N/A
Zone Valve Location:
Areas Served
E - EVAC (WAGD)
Medical Air Yes
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
10 - Leaking outlet
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
Yes 50 - Unable to test (in use)
60 - Missing parts
2 - Nitrous Oxide
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room No.
1 P 1 P 1 PStation 1 Good
1 P 1 P 1 PStation 2 Good
1 P 1 P 1 P GoodStation 3
1 P 1 P 1 P GoodStation 4
1 P 1 P 1 P GoodStation 5
1 P 1 P 1 P GoodStation 6
1 P 1 P 1 PStation 7 Good
1 P 1 P 1 P GoodStation 8
1 PLab Air
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 50 psig 99% Carbon Dioxide = psig
21% Medical Air = 50 psig Vacuum = 21 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Lab Air = 35 psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Attached Outlet Data sheet for this zone.
Actual Static
Pressure
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
Actual Static
PressureGas
DISS AmicoAmico
Gas
P a rt ic u la te m g n o n -M e th a d ro c a rb o n s p p m
*P/F = Pass/Fail
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 13 of 83 Pages
1st Address:
Building: Test Date:
Hospital Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 54 Yes 54 40 60 X
55 Yes 55 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 22 Yes 22 12 N/A X
EVAC
Other
O U T L E T S
50 - Unable to test (in use)
60 - Missing parts
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
□ Non-Critical Area
Outside Exam 9 1A705, 1A707, 1A709, 1A711
1A713, 1A715, 1A717, 1A721
1A109A, 1A109D x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Outside Exam 21 □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served x Critical Area (Alarm Required)
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona
13800 Veterans Way
Orlando, FL 32827 02/25/2023
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room No.
2 P 2 P 3 P1A705 Good
2 P 2 P 3 P1A707 Good
2 P 2 P 3 P1A709 Good
2 P 2 P 3 P1A711 Good
2 P 2 P 3 P1A713 Good
2 P 2 P 3 P1A715 Good
2 P 2 P 3 P1A717 Good
2 P 2 P 3 P Good1A721
2 P 2 P 3 P1A109A Good
2 P 2 P 3 P1A109D Good
NOTE: Oxygen and Medical Air outlets serving critical care areas will be tested at 6 SCFM for 3 seconds prior to the minimum requirements listed above
StyleOultlets Manufacturer
99% Oxygen = 54 psig 99% Carbon Dioxide = psig
21% Medical Air = 54 psig Vacuum = 23 psig
99% Nitrous Oxide = psig EVAC = psig
99% Nitrogen = psig Other = psig *P/F *P/F *P/F *P/F
□ P P P P
Comments:
Recommendations:
Discrepancy:
Attached Outlet Data sheet for this zone.
Amico Amico DISS
*P/F = Pass/Fail
Gas
Actual Static
Pressure Gas
Actual Static
Pressure
P a rt ic u la te m g n o n -M e th a d ro c a rb o n s p p m
H a lo g e n a d ro c a rb o n s p p m
D e w P o in t
F
11300 49th Str. No.
Clearwater, FL 33762
Fax: (866) 348-9650 14 of 83 Pages
1st ER Address:
Building: Test Date:
Hospital Technician: Frank D'Arpa - Medical Gas Certifier - N.I.T.C. # 12313456
Notes/Legend:
Setpoints | Functioning
PSIG
or Hg Low High Yes No
Oxygen 55 Yes 55 40 60 X
56 Yes 56 40 60 X
Nitrous Oxide
Nitrogen
Carbon Dioxide
Vacuum 22 Yes 22 12 N/A X
EVAC
Other
O U T L E T S
50 - Unable to test (in use)
60 - Missing parts
20 - Failed Flow Rate Test
Yes 30 - Failed Pressure Test
40 - Can't insert; won't lock
10 - Leaking outlet
Zone Gases Installed
Correctly
Gauges
Present
Alarm PSIG or Hg
V - Vacuum
C - Carbon Dioxide
Yes E - EVAC (WAGD)
Medical Air Yes N - Nitrogen
2 - Nitrous Oxide
ALARM DATA O - Oxygen
Zone Valve Value Data A - Medical Air
□ Non-Critical Area
Outside 1A-118 1A-118,1A-120,1A-122, 1A-116,1A-112
1A-109A, 1A-109C, 1A-110, 1A-108
1A-106,1A-104,1A-102, 1A-101 x (If applicable) Manufacturer/Model -
Alarm Location: AMICO
Outside Exam 21 □ Area alarm data alarm N/A
Zone Valve Location:
Areas Served x Critical Area (Alarm Required)
ZONE / ALARM / OUTLETS DATA SHEET
Orlando VA Medical Center - Lake Nona
13800 Veterans Way
Orlando, FL 32827 02/25/2023
O xy ge n
S C
M ed ic al
A ir
S C
N itr ou s
O xi de
S C
N itr og en
S C
C a xi de
S C
V ac u um
S C
W A
G D
S C
Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F Qty *P/F
Notes
Room No.
2 P 2 P 3 P1A-118 Good
2 P 2 P 3 P1A-120 Good
2 P 2 P 3 P1A-122 Good
2 P 2 P 3 P1A-116 Good
2 P 2 P 3 P1A-112…