VA STRATTON FACADE PHASE 2B DWG_Pt1.pdf
PDF 7 MB Posted
- Solicitation number
- 36C24221B0050
About this file
This document package includes construction drawings and specifications for facade repairs at a Department of Veterans Affairs medical center. The drawings detail repair needs across ten elevations, including cracked masonry, failed sealants, deteriorated roof elements, and cleaning of the overall facade. Repairs are divided into four phases to be completed over a 20-week performance period. Infection control protocols are specified depending on the risk level of adjacent patient areas.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24221B0050 0002.docx | DOCX document | |
| 36C24221B0050 0001.docx | DOCX document | |
| Wage Determinations.txt | TXT text file | |
| VA STRATTON 2A FACADE DRAWINGS_FINAL.pdf | ||
| VA STRATTON 2A FACADE SPECS_FINAL.pdf | ||
| 36C24221B0050_2.docx | DOCX document | |
| VA STRATTON FACADE PHASE 2B DWG_Pt2.pdf | ||
| VIEWS 03923953 DRAFT CD - VAAR 819 852 -OGC Concur (003).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE LOCATION
VAMC SIGNATURE BLOCK
DIRECTOR OF MEDICAL CENTER - SIGNATURE BLOCK
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
BUILDING 1
O₂
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
SITE SAFETY & PROPOSED STAGING PLAN
SAFETY NOTES:
LEGEND:
GENERAL NOTES:
O₂
REFERENCE RADIO FREQUENCY EXPOSURE MAPS (NTS):
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
PARTIAL KEY PLAN
OVERHEAD VIEW
LEGEND
GENERAL PROJECT PHASING NOTE:
GENERAL NOTES:
CONSTRUCTION PHASING PLAN
20 WEEKS TOTAL
Description of Required Infection Control Precautions by Class
During Construction Project Upon Completion of
1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with
HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety
Section and Infection Control Department, and thoroughly cleaned by the owner's Environment
Services Department.
1. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
2. Contain construction waste before transportation in tightly covered containers.
3. Cover transport receptacles or carts. Tape covering unless solid lid.
4. Vacuum work area with HEPA filtered vacuums.
5. Wet mop area with disinfectant.
6. Remove isolation of HVAC system in areas where work is being performed.
C l a s
I V
C l a
I
1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with
HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety
Section and Infection Control Department, and thoroughly cleaned by the owner's Environment
Services Department.
1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety
Department and Infection Control Department, and thoroughly cleaned by the owner’s Environmental
Services Department.
2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
3. Vacuum work area with HEPA filtered vacuums.
4. Wet mop area with disinfectant.
5. Remove isolation of HVAC system in areas where work is being performed.
NOTES:
PATIENT RISK GROUP FOR "TYPE D" CONSTRUCTION
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
Class IV
Class III / IV
Class IV
Class IV
CLEANING BRICKWORK / MASONRY PROCEDURE:
PERFORMANCE SPECIFICATION:
FACADE CLEANING (KEYED NOTES 60, 61 & 62)
DURATION DESCRIPTION
Weeks 1-3 Submittals & Mobilization
Weeks 4-7 PHASE 1 (D-Wing Parapet)
Weeks 8-11 PHASE 2 (D-Wing Roof)
Weeks 12-15 PHASE 3 (D-Wing Repairs & Cleaning - AS-201 & AS-202)
Weeks 16-19 PHASE 4 (D-Wing Repairs & Cleaning - AS-203 & AS-204)
Week 20 Project Closeout:
Including: Closeout Documents, demobilization, etc.
Project Duration: 100 Days
Notes:
1. Certain activities may be combined for expediency.
2. All phasing and work is subject to the owner occupancy schedule.
3. All work needs to be coordinated with the COR in advance.
4. There will be no re-mobilization cost permitted. All work must be completed in allotted time frame.
5. Refer to spec section 01 32 16.15 for more information on Project
Scheduling Requirements.
11 4
4 5
ELEVATION D-1
ELEVATION D-2
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
PROVIDE NEW COUNTERFLASHING TO COVER
EXPOSED WOOD
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
REPAIR DAMAGED WINDOW FRAME
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
97 REPLACE MISMATCHED EIFS FINISHED AREA
112 RESECURE MECHANICAL EQUIPMENT
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT, SEE DETAIL 6/AS-602.
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
4/1-AS-501 &
8A, 8B &
8C/1-AS-602
5/1-AS-501, 9 &
9A/1-AS-602 &
2-4/1-AS-602A
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
5&6/1-AS-602A
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
4&7/1-AS-603
101/1-AS-503
& 11/1-AS-603
103/1-AS-503 &
3,4&7/1-AS-603
110/AS-503 &
10/AS-603
111/1-AS-503 &
3-5/1-AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED.
71/1-AS-502
73/1-AS-502
82/1-AS-503
112/1-AS-503
94/1-AS-503
96/1-AS-503
97/1-AS-503 &
1/1-AS-602A
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED.
NOT USED
95/1-AS-503
LARGE BRICK AREA REPAIR DETAIL3
GENERAL NOTES:
ELEVATION D-3
979797
DEDUCT ALTERNATE
DEDUCT ALTERNATE
ELEVATION D-4
2 3
11 11
15 72
97 97 97 97 97 97 97 97 97
DEDUCT ALTERNATE
DEDUCT ALTERNATE
DEDUCT ALTERNATE
11 10
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
REPAIR DAMAGED WINDOW FRAME
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
97 REPLACE MISMATCHED EIFS FINISHED AREA
112 RESECURE MECHANICAL EQUIPMENT
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT, SEE DETAIL 6/AS-602.
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
4/1-AS-501 &
8A, 8B &
8C/1-AS-602
5/1-AS-501, 9 &
9A/1-AS-602 &
2-4/1-AS-602A
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
5&6/1-AS-602A
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
4&7/1-AS-603
101/1-AS-503
& 11/1-AS-603
103/1-AS-503 &
3,4&7/1-AS-603
110/AS-503 &
10/AS-603
111/1-AS-503 &
3-5/1-AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED.
71/1-AS-502
73/1-AS-502
82/1-AS-503
112/1-AS-503
94/1-AS-503
96/1-AS-503
97/1-AS-503 &
1/1-AS-602A
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED.
NOT USED
95/1-AS-503
TYPICAL DETAIL3
GENERAL NOTE:
GENERAL NOTES:
QUOTATION & REPAIR:
TYPICAL DETAIL3
ELEVATION D-6
ELEVATION D-5
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
REPAIR DAMAGED WINDOW FRAME
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
97 REPLACE MISMATCHED EIFS FINISHED AREA
112 RESECURE MECHANICAL EQUIPMENT
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT, SEE DETAIL 6/AS-602.
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
4/1-AS-501 &
8A, 8B &
8C/1-AS-602
5/1-AS-501, 9 &
9A/1-AS-602 &
2-4/1-AS-602A
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
5&6/1-AS-602A
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
4&7/1-AS-603
101/1-AS-503
& 11/1-AS-603
103/1-AS-503 &
3,4&7/1-AS-603
110/AS-503 &
10/AS-603
111/1-AS-503 &
3-5/1-AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED.
71/1-AS-502
73/1-AS-502
82/1-AS-503
112/1-AS-503
94/1-AS-503
96/1-AS-503
97/1-AS-503 &
1/1-AS-602A
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED.
NOT USED
95/1-AS-503
GENERAL NOTES:
ELEVATION D-7
11 1111
11 1
3 15
ELEVATION D-8
2 50
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
REPAIR DAMAGED WINDOW FRAME
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
97 REPLACE MISMATCHED EIFS FINISHED AREA
112 RESECURE MECHANICAL EQUIPMENT
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT, SEE DETAIL 6/AS-602.
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
4/1-AS-501 &
8A, 8B &
8C/1-AS-602
5/1-AS-501, 9 &
9A/1-AS-602 &
2-4/1-AS-602A
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
5&6/1-AS-602A
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
4&7/1-AS-603
101/1-AS-503
& 11/1-AS-603
103/1-AS-503 &
3,4&7/1-AS-603
110/AS-503 &
10/AS-603
111/1-AS-503 &
3-5/1-AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED.
71/1-AS-502
73/1-AS-502
82/1-AS-503
112/1-AS-503
94/1-AS-503
96/1-AS-503
97/1-AS-503 &
1/1-AS-602A
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED.
NOT USED
95/1-AS-503
GENERAL NOTE:
GENERAL NOTES:
ELEVATION D-9
3 15
11 11
10 11
A
A
ELEVATION D-10
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
REPAIR DAMAGED WINDOW FRAME
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
97 REPLACE MISMATCHED EIFS FINISHED AREA
112 RESECURE MECHANICAL EQUIPMENT
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT, SEE DETAIL 6/AS-602.
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
4/1-AS-501 &
8A, 8B &
8C/1-AS-602
5/1-AS-501, 9 &
9A/1-AS-602 &
2-4/1-AS-602A
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
5&6/1-AS-602A
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
4&7/1-AS-603
101/1-AS-503
& 11/1-AS-603
103/1-AS-503 &
3,4&7/1-AS-603
110/AS-503 &
10/AS-603
111/1-AS-503 &
3-5/1-AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED.
71/1-AS-502
73/1-AS-502
82/1-AS-503
112/1-AS-503
94/1-AS-503
96/1-AS-503
97/1-AS-503 &
1/1-AS-602A
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED.
NOT USED
95/1-AS-503
GENERAL NOTE:
GENERAL NOTES:
RA 30
RA 28
RA 27
RA 29
ROOF #5D
CORE
ROOF #4A
CORE
ROOF #3C
CORE
ROOF #3C
CORE
ROOF #5C
R
O
O
F
D
N
O
T
N
S
C
O
P
E
NOT IN SCOPE
D-WING ROOF PLAN
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
REPAIR DAMAGED WINDOW FRAME
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
97 REPLACE MISMATCHED EIFS FINISHED AREA
112 RESECURE MECHANICAL EQUIPMENT
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
REMOVE & REBUILD PARAPET WALL & BRICK VENEER
PATCH STONE UNIT, SEE DETAIL 6/AS-602.
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
WINDOWS
NOT USED.
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
NOT USED
111 AIR TERMINAL / CABLING / GROUNDING IS DAMAGED /
BROKEN OR MISSING, PROVIDE NEW
PROVIDE NEW SCUPPER
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR PONDING AREAS ON ROOF
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
4/1-AS-501 &
8A, 8B &
8C/1-AS-602
5/1-AS-501, 9 &
9A/1-AS-602 &
2-4/1-AS-602A
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
5&6/1-AS-602A
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
4&7/1-AS-603
101/1-AS-503
& 11/1-AS-603
103/1-AS-503 &
3,4&7/1-AS-603
110/AS-503 &
10/AS-603
111/1-AS-503 &
3-5/1-AS-604
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED.
71/1-AS-502
73/1-AS-502
82/1-AS-503
112/1-AS-503
94/1-AS-503
96/1-AS-503
97/1-AS-503 &
1/1-AS-602A
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED.
NOT USED
95/1-AS-503
GENERAL NOTES:
LEGEND
AREA OF WORK
RA-30 STAIRWELL ELEVATIONS
RA-29 STAIRWELL ELEVATIONS
NOTE:
| Sheets and Views |
| 2B (1) 1-GI-001-_TS |
| 2B (2) 1-GI-002-1-GI-002 |
| 2B (3) 1-AS-001-1-AS-001 |
| 2B (4-8) 1-AS-201 THRU 1-AS-205 (D WING FACADE)-1-AS-201 |
| 2B (4-8) 1-AS-201 THRU 1-AS-205 (D WING FACADE)-1-AS-202 |
| 2B (4-8) 1-AS-201 THRU 1-AS-205 (D WING FACADE)-1-AS-203 |
| 2B (4-8) 1-AS-201 THRU 1-AS-205 (D WING FACADE)-1-AS-204 |
| 2B (4-8) 1-AS-201 THRU 1-AS-205 (D WING FACADE)-1-AS-205 |
| 2B (9) 1-AS-401 (D WING ROOF)-1-AS-401 |
| 2B (10) 1-AS-501 DEFICIENCY EXAMPLES-1-AS-501 |
| 2B (11) 1-AS-502 DEFICIENCY EXAMPLES-1-AS-502 |
| 2B (12) 1-AS-503 DEFICIENCY EXAMPLES-1-AS-503 |
| 2B (13) 1-AS-601 SCAFFOLDING DETAILS-1-AS-601 |
| 2B (14) 1-AS-602 DETAILS-1-AS-602 |
| 2B (15) 1-AS-602A DETAILS-1-AS-602A |
| 2B (16) 1-AS-603 ROOF DETAILS-1-AS-603 |
| 2B (17) 1-AS-604 ROOF DETAILS-1-AS-604 |
| 2B (18) 1-MH-101 (MECHANICAL SHEETS)-1-MH-101 |
File details come from the government source that posted it. Updated .