VA STRATTON 2A FACADE DRAWINGS_FINAL.pdf
PDF 19 MB Posted
- Solicitation number
- 36C24221B0050
About this file
This document provides details on a federal contract opportunity for hospital facade repairs. The solicitation number is 36C24221B0050 and concerns facade repairs phase 2A at a Veterans Health Administration facility. The opportunity was issued by the Department of Veterans Affairs Veterans Health Network 2. The related file contains final drawings for the Stratton VA facility to support the facade repairs phase 2 work. The description notes the opportunity involves facade repairs for an existing hospital. No further information is provided on response dates, award timing, pricing terms, or set-asides.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24221B0050 0002.docx | DOCX document | |
| 36C24221B0050 0001.docx | DOCX document | |
| Wage Determinations.txt | TXT text file | |
| VA STRATTON FACADE PHASE 2B DWG_Pt1.pdf | ||
| VA STRATTON 2A FACADE SPECS_FINAL.pdf | ||
| 36C24221B0050_2.docx | DOCX document | |
| VA STRATTON FACADE PHASE 2B DWG_Pt2.pdf | ||
| VIEWS 03923953 DRAFT CD - VAAR 819 852 -OGC Concur (003).docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE LOCATION
VAMC SIGNATURE BLOCK
DIRECTOR OF MEDICAL CENTER - SIGNATURE BLOCK
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
BUILDING 1
O₂
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
SITE SAFETY & PROPOSED STAGING PLAN
SAFETY NOTES:
LEGEND:
GENERAL NOTES:
O₂
REFERENCE RADIO FREQUENCY EXPOSURE MAPS (NTS):
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
PARTIAL KEY PLAN
OVERHEAD VIEW
LEGEND
GENERAL PROJECT PHASING NOTE:
GENERAL NOTES:
CONSTRUCTION PHASING PLAN
20 WEEKS TOTAL
Description of Required Infection Control Precautions by Class
During Construction Project Upon Completion of
1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with
HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety
Section and Infection Control Department, and thoroughly cleaned by the owner's Environment
Services Department.
1. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
2. Contain construction waste before transportation in tightly covered containers.
3. Cover transport receptacles or carts. Tape covering unless solid lid.
4. Vacuum work area with HEPA filtered vacuums.
5. Wet mop area with disinfectant.
6. Remove isolation of HVAC system in areas where work is being performed.
C l a s
I V
C l a
I
1. Remove or isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with
HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety
Section and Infection Control Department, and thoroughly cleaned by the owner's Environment
Services Department.
1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety
Department and Infection Control Department, and thoroughly cleaned by the owner’s Environmental
Services Department.
2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
3. Vacuum work area with HEPA filtered vacuums.
4. Wet mop area with disinfectant.
5. Remove isolation of HVAC system in areas where work is being performed.
NOTES:
PATIENT RISK GROUP FOR "TYPE D" CONSTRUCTION
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
Class IV
Class III / IV
Class IV
Class IV
DURATION DESCRIPTION
Weeks 1-3 Submittals & Mobilization
Weeks 4-7 PHASE 1 (A-Wing Repairs & Cleaning - AS-101 & AS-102)
Weeks 8-11 PHASE 2 (A-Wing Repairs & Cleaning - AS-103 & AS-104)
Weeks 12-15 PHASE 3 (D-Wing Repairs & Cleaning - AS-201 & AS-202)
Weeks 16-19 PHASE 4 (Core Repairs & Cleaning - AS-301)
Week 20 Project Closeout:
Including: Closeout Documents, demobilization, etc.
Project Duration: 100 Days
Notes:
1. Certain activities may be combined for expediency.
2. All phasing and work is subject to the owner occupancy schedule.
3. All work needs to be coordinated with the COR in advance.
4. There will be no re-mobilization cost permitted. All work must be completed in allotted time frame.
5. Refer to spec section 01 32 16.15 for more information on Project
Scheduling Requirements.
CLEANING BRICKWORK / MASONRY PROCEDURE:
PERFORMANCE SPECIFICATION:
FACADE CLEANING (KEYED NOTES 60, 61 & 62)
ELEVATION A-6
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
PROVIDE NEW COUNTERFLASHING TO COVER
EXPOSED WOOD
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
GENERAL NOTES:
QUOTATION & REPAIR:
ELEVATION A-8
50 50
60 60
50 31
ELEVATION A-7
11 1111
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
TYPICAL DETAIL3
GENERAL NOTE:
ELEVATION A-9
71 71
15 15
11 11
11 11
ELEVATION A-10
2 71
62 13
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
TYPICAL DETAIL3
GENERAL NOTE:
ELEVATION A-12
ELEVATION A-11
71 72
72 71
50 50
31 31
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
TYPICAL DETAIL3
GENERAL NOTE:
ELEVATION D-1
4 3
3 10
15 15
30 503
ELEVATION D-2A
94 96
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
TYPICAL DETAIL3
GENERAL NOTE:
ELEVATION D-2C
ELEVATION D-2B
AMBULANCE
ENTRANCE
111111 3 11
3 72
A
A
A-A
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
CONTRACTOR CANNOT BLOCK
ACCESS TO THE AMBULANCE
BAY AT ANY TIME. NO ILSM WILL
BE GRANTED TO DO SO EVEN
FOR A SHORT PERIOD OF TIME.
LARGE BRICK AREA REPAIR DETAIL4
TYPICAL DETAIL3
GENERAL NOTE:
CORE RA3
ELEVATION CORE-4
ELEVATION CORE-5
1 31
DO NOT BLOCK DOORWAY AT ANY TIME.
DOOR MUST REMAIN ACCESSIBLE AT ALL
TIMES.
ELEVATION CORE-6
1 1
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601
REPAIR CRACKS IN CONCRETE.
REPAIR SPALLED CONCRETE
NOT USED
NOT USED
REPAIR EXPOSED WOOD AND FASTENERS ON STUCCO
REMOVE VEGETATION ON BUILDING95
96 REPAIR MARRED STUCCO FINISH
100% CONSTRUCTION DOCUMENTS
MASONRY
SEALANT
SEAL ROUND ANCHORS
STONE
KEYED NOTE LEGEND
ROOF EQUIPMENT
1 REPLACE CRACKED, BROKEN OR SPALLED MASONRY
REPOINT OPEN MASONRY JOINTS, STEP CRACKS OR
UNBOUNDED & MISSING MORTAR
REMOVE ABANDONED ANCHORS/FASTENERS & FILL VOID
PATCH STONE UNIT
REPLACE STONE UNIT & BRICK
PATCH CRACKED STONE UNIT
REPAIR SPALLED STONE OR INSUFFICIENT PAST STONE REPAIR
REPLACE OR ADD NEW SEALANT
REMOVE & REPLACE MORTAR & SEALANT
SEAL CRACKS IN EXPOSED CONCRETE IN LIGHT WELLS
REPAIR SPALLED CONCRETE DUE TO REINFORCEMENT
DETERIORATION
CONCRETE
ROOF REPAIR AREA
REPAIR PITCH POCKET
ROOF
CLEAN & REPAINT CORROSION AT EXPOSED METAL
ELEMENTS (COLUMNS, STAIRS & LADDERS, RAILINGS, ETC.)
REPAIR ROOF DRAIN
DESCRIPTIONREPAIR
PROCEDURE
& DETAILS
1/1-AS-501 &
1/1-AS-602
LINTELS /
SHELF ANGLES
RESET DISPLACED LINTEL
METAL WORK
CLEANING
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
GENERAL FACADE CLEANING62
MISCELLANEOUS
DAMAGED / CORRODED LINTEL AND PLATE
STEEL FILLER STRIP
NOT USED
NOT USED
2/1-AS-501 &
2/1-AS-602
3/1-AS-501
10/1-AS-501
& 6/1-AS-602
11/1-AS-501
& 7/1-AS-602
13/1-AS-501
& 16/1-AS-602
15/1-AS-501
& 16/1-AS-602
30/1-AS-501 &
10-12/1-AS-602
31/1-AS-501
& 3/1-AS-602
41/1-AS-502 &
4,5&13/1-AS-602
42/1-AS-502 &
9/1-AS-603
50/1-AS-502
60/1-AS-502
61/1-AS-502
62/1-AS-502
70/1-AS-502
72/1-AS-502
90/1-AS-503
100/1-AS-503 &
3&4/1-AS-603
101/1-AS-503
& 8/1-AS-603
110/AS-503 &
7/AS-603
32 REMOVE & REPLACE BACKER ROD & SEALANT32/1-AS-501 &
3A/1-AS-602
51 NOT USED
71/1-AS-502
73/1-AS-502
94/1-AS-503
96/1-AS-503
52/1-AS-502
COPING
20 RESET DISPLACED COPING STONE20/1-AS-501
NOT USED
95/1-AS-503
UPPER ELEVATION CORE-8
GENERAL NOTES:
QUOTATION & REPAIR:
PARTIAL CORE ROOF PLAN
AREA OF WORK
GENERAL ROOFING NOTES:
Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
REPLACE CRACKED OR SPALLED MASONRY
STEP CRACKS, UNBONDED AND MISSING MORTAR
ABANDONED ANCHORS/FASTENERS AND FILL VOID
REPOINT OPEN MASONRY JOINT,
RESET DISPLACED COPING STONE
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
GENERAL MORTAR NOTES:
INSUFFICIENT PAST STONE REPAIR
SPALLED STONE OR
PATCH STONE UNIT
REPLACE OR ADD NEW SEALANT
BACKER ROD & SEALANT
REMOVE & REPLACE
MORTAR & SEALANT
REMOVE & REPLACE
REPAIR PROCEDURE:
REPLACE STONE UNIT & BRICK
REPAIR PROCEDURE:
PATCH CRACKED STONE UNIT
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
RESET DISPLACED LINTEL
FIRE ESCAPES,BALCONIES, RAILINGS, ETC.)
FLASHING TO COVER EXPOSED WOOD
CLEAN ALGAE & DIRT BUILDUP
CLEAN CORROSION STAINING ON SURFACE
CONCRETE IN LIGHT WELLS
REINFORCEMENT DETERIORATION
REPAIR SPALLED CONCRETE
EXPOSED METAL ELEMENTS (COLUMNS,
CLEAN & REPAINT CORROSION AT
SEAL CRACKS IN EXPOSED
REPAIR SPALLED CONCRETE DUE TO
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
SECTION VIEWPLAN VIEW
CONCRETE REPAIR NOTES:
PROVIDE NEW COUNTER-
AND PLATE STEEL FILLER STRIP
DAMAGED/ CORRODED LINTEL
REPAIR CRACKS IN CONCRETE
REPAIR PROCEDURE:
REPAIR PROCEDURE:
REPAIR PROCEDURE:
GENERAL FACADE CLEANING
Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
SEAL AROUND ANCHORS
REPAIR PROCEDURE:
FASTENERS ON STUCCO
REPAIR EXPOSED WOOD AND
REPAIR MARRED STUCCO FINISH
REPAIR PROCEDURE:
REPAIR PROCEDURE:
ROOF REPAIR AREA
REPAIR PROCEDURE:
REPAIR ROOF DRAIN
REPAIR PROCEDURE:
REMOVE VEGETATION ON BUILDING
REPAIR PROCEDURE:
REPAIR PITCH POCKET
SCAFFOLD PLANKS:
ERECTION, ALTERATION AND DISMANTLING:
SUPERVISION:
CERTIFICATES OF COMPETENCY:
SCAFFOLDING REGISTER AND INSPECTION OF SCAFFOLDS:
PROTECTION AND MAINTENANCE:
DUTIES OF PRINCIPALS, CONTRACTORS, SCAFFOLDING
ERECTORS AND USERS OF SCAFFOLDS:
SCAFFOLDING OVER VERANDAHS, GANTRIES OR ROOFS:
LIFTING APPLIANCES MOUNTED ON SCAFFOLDING:
SUSPENDED SCAFFOLDS:
TYPES OF SUSPENDED SCAFFOLDS:
MECHANICAL OPERATION:
ANCHORAGES:
BRACKETS AND PARAPET HOOKS:
WORKING PLATFORMS, GUARDRAILS, MIDRAILS AND TOEBOARDS:
SAFETY HARNESSES AND LIFELINES:
ANTI-TILT SWITCH DEVICES:
ACCESS, WARNING NOTICES AND PROTECTION OF THE PUBLIC:
ENGINEER’S CERTIFICATE:
SCAFFOLD REGISTER:
INSPECTION RECORD:
COUNTERWEIGHTING OF OUTRIGGERS:
FOUNDATIONS:
SUSPENDED SCAFFOLDS:
SIDEWALK SHEDS:
REQUIRED TRAINING:
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
GENERAL NOTE:
SECTION AT PARAPET WALL
8A
SCUPPER
MORTAR & SEALANT
WARD WING AREA
REPLACE
ROD & SEALANT
3A
REPLACE BACKER
ROTATED STONE REPAIR
EXPANSION JOINT AT CORNER
SECTION AT PARAPET WALL
PATCH STONE UNIT DETAIL
MASONRY REPAIR DETAIL
CRACKED OR SPALLED
MASONRY REPAIR DETAIL
CRACKED OR SPALLED
BRICK JOINT REPOINTING DETAIL
BRICK JOINT REPOINTING DETAIL
REPLACE STONE UNIT DETAIL
DETAIL AT BASE OF PARAPET WALL
9A
STONE DIMENSIONS DETAIL
SECTION
VIEW
PLAN
VIEW
DUTCHMAN REPAIR NOTES:
DUTCHMAN REPAIR DETAIL
DETAIL AT STONE/BRICK SUPPORT
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
TYPICAL CONCRETE WALL
PENETRATION DETAIL
TYPICAL SECTION AT SCUPPER
8B
TYPICAL SCUPPER ROOF VIEW
8C
FIRE RATED MASONRY PARTITION
CONDUIT PENETRATION IN
PENETRATION DETAIL
EXTERIOR WALL
NOTES:
TYPICAL SECTION AT WINDOW LINTEL
ALPHAGUARD BIO BASE COAT
W/ REINFORCEMENT
ALPHAGUARD BIO TOP COAT
(3) THREE PLIES TREMCO ROOF MEMBRANE
SET IN COLD ADHESIVE MENDED WITH
EXISTING ROOF SURFACE AND TERMINATED AT CLEAT
ON PARAPET WALL. REFER TO ROOF PLANS.
TERMINATION BAR
TWO PIECE COUNTERFLASHING
BASE FLASHING - TRA ELASTOMERIC MEMBRANE
PROVIDE & INSTALL NEW POLYISO
INSULATION, THICKNESS AND
SLOPE TOP MATCH EXISTING
EXISTING CONCRETE DECK
TREMSEAL D
R-MER WALL PAN, REMOVED AND RE-INSTALLED
MIN. 22 GA HAT SECTION CLIP
60 MIL. SELF ADHERING UNDERLAYMENT
R-MER WALL PAN CLIP
ALPHAGUARD BIO BASE
W/ REINFORCEMENT
ALPHAGUARD BIO TOP COAT
EXISTING TREMCO
BUILT-UP ROOF
MEMBRANE
EXISTING CLAMPING RING AND
ROOF DRAIN DOME TO BE
REMOVED & REPLACED WITH
NEW OR PAINTED AS NOTED.
ALL DOMES SHALL BE METAL &
PAINTED BLACK.
EXISTING 2.5" +/-
RIGID INSULATION
EXISTING 4" +/-
CONCRETE DECK
REPLACE BOLTS WITH S.S. TYPE
WATER CUT-OFF MASTIC
TREMSEAL PITCH
POCKET SEALER, OR
EQUIVALENT.
COMPLETELY FILL
POCKET TO PREVENT
PONDING OF WATER.
METAL PITCH PAN
MINIMUM 4'' HEIGHT w/
METAL HOOD
EXISTING
CONCRETE DECK
EXISTING INSULATION
TREMSEAL D
EXISTING PITCH
POCKET ENCLOSURE
MEMBRANE SPLICE
COMPATIBLE WITH
EXISTING ROOFING
EXISTING BUILT-UP
ROOF MEMBRANE
ENGINEERING LLPFE PROJECT NO: 19-092
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
NOT USED
NOT USED
ROOF DRAIN DETAIL
ROOF REPAIR DETAIL
TREMCO PARAPET WALL/
PITCH POCKET DETAIL
FIELD TIE-IN DETAIL
GARLAND ROOFING
GENERAL NOTES:
GARLAND ROOF & PONDING REPAIR:
¾” ”
ROOFING FIELD TIE-IN DETAIL
COPING/GARLAND
ROOFING FIELD TIE-IN DETAIL
BLDG WALL/GARLAND
NOTES:
TYPICAL SECTION AT LOUVER LINTEL
Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
PIPING SUPPORT ON ROOF
COOPER B-LINE
COOPER B-LINE COOPER B-LINE
COOPER B-LINE
DURABLOK BASE DETAILS
CONSTRUCTION SIGN
SAFETY SIGN
TERMINAL DETAIL
ADHESIVE AIR
SPLICE
TERMINAL DETAIL
TYPICAL RE-INSTALLATION DETAIL
MINIMUM CLASS 1 MATERIAL REQUIREMENTS
LEGEND & SCHEDULE OF
EQUIPMENT TYPICAL OF
MANUFACTURER "HARGER"
Middletown, NY 10940 t 845-343-1481; fx 855-320-8735
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704; fx 855-320-8735 www.fellp.com
100% CONSTRUCTION DOCUMENTS
GENERAL NOTES (DETAILS 1&3/1-MH-101):
TEMPORARY LOUVER SNORKEL/ EXTENSION DETAILS - TYPICAL1
TYPICAL AC UNIT DETAIL2
GENERAL NOTES:
FRONT VIEWS SIDE VIEW
TEMPORARY LOUVER SNORKEL/ EXTENSION @ ROOF LEVEL (TYPICAL)3
GENERAL EQUIPMENT PROTECTION NOTES:
TEMPORARY BRIDGING OVER EQUIPMENT - TYPICAL4
AIR INTAKE LOUVER PROTECTION FOR USE WITH MAST SCAFFOLDING SYSTEM::
| Sheets and Views |
| 2A (1) 1-GI-001-_TS |
| 2A (2) 1-GI-002-1-GI-002 |
| 2A (3) 1-AS-001-1-AS-001 |
| 2A (4-7) 1-AS-101 THRU 1-AS-104 (A WING FACADE)-1-AS-101 |
| 2A (4-7) 1-AS-101 THRU 1-AS-104 (A WING FACADE)-1-AS-102 |
| 2A (4-7) 1-AS-101 THRU 1-AS-104 (A WING FACADE)-1-AS-103 |
| 2A (4-7) 1-AS-101 THRU 1-AS-104 (A WING FACADE)-1-AS-104 |
| 2A (8 -9) 1-AS-201 THRU 1-AS-202 (D WING FACADE)-1-AS-201 |
| 2A (8 -9) 1-AS-201 THRU 1-AS-202 (D WING FACADE)-1-AS-202 |
| 2A (10) 1-AS-301 (CORE FACADE & ROOF)-1-AS-301 |
| 2A (11) 1-AS-501 DEFICIENCY EXAMPLES-1-AS-501 |
| 2A (12) 1-AS-502 DEFICIENCY EXAMPLES-1-AS-502 |
| 2A (13) 1-AS-503 DEFICIENCY EXAMPLES-1-AS-503 |
| 2A (14) 1-AS-601 SCAFFOLDING DETAILS-1-AS-601 |
| 2A (15) 1-AS-602 DETAILS-1-AS-602 |
| 2A (16) 1-AS-603 ROOF DETAILS-1-AS-603 |
| 2A (17) 1-AS-604 ROOF DETAILS-1-AS-604 |
| 2A (18) 1-MH-101 (MECHANICAL SHEETS)-1-MH-101 |
File details come from the government source that posted it. Updated .