This federal contract opportunity notice seeks a general contractor to upgrade elevators at the Veterans Affairs Medical Center in Salem, Virginia. The project includes upgrading service elevators 1 through 4 in Building 143, patient elevators 1 through 3 in Building 143, cart lift elevators 1 and 2 in Building 143, and the elevators in Buildings 1, 4, 5, 10, 11, and 76. The work consists of general construction, demolition, civil, structural, architectural, medical gas, fire alarm, fire protection, plumbing, mechanical, electrical and telecommunications associated with the elevator upgrades. The solicitation is set aside 100% for Service-Disabled Veteran-Owned Small Businesses. The agency issuing this opportunity is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALEM VA MEDICAL CENTER

SALEM, VIRGINIA

PROJECT NO. 658-18-103 INDEX OF DRAWINGS

SHEET NO. DRAWING TITLE

GENERAL

GI001 COVER SHEET

NOT TO SCALE

GI002 LEGENDS, SYMBOLS AND ABBREVIATIONS

UPGRADE ELEVATORS

ARCHITECTURAL

AE100

F

A

D

I

ET

D S T

N U

E

TM

AP

R

E NT O

S

A

T SE FO

REM

ACI

N

VE RATE

A

FAI R

F

S

CAMPUS MAP SCOPE OF WORK

SHEET NO.

NOT TO SCALE

GI003 3 GENERAL NOTES

BUILDING 143

F001 FIRE PROTECTION ABBREVIATIONS, LEGEND, AND GENERAL NOTES

F101 FIRE PROTECTION DEMOLITION PLANS

F102 FIRE PROTECTION NEW PLANS

FIRE PROTECTION DETAILSF501

M001

MD101

MH101

LEGEND, ABBREVIATIONS - BLDG 143

ENLARGED HVAC DEMOLITION PLAN - SUBBASEMENT - BLDG 143

ENLARGED HVAC PLAN - SUBBASEMENT - BLDG 143

MH102 ENLARGED HVAC PLAN - PENTHOUSE - BLDG 143

MECHANICAL

FIRE PROTECTION

MH401 HVAC SCHEDULES - BLDG 143

CAMPUS MAP SCOPE OF WORK

AD100

AD200

AS100

AS200

AS201

AS300

CONSTRUCTION BARRIER FLOOR PLANS

DEMOLITION FLOOR PLANS

NEW WORK FLOOR PLANS

INTERIOR CAB ELEVATIONS

FINISH SCHEDULES AND DETAILS

SECTIONS AND DETAILS

E001 GENERAL NOTES AND LEGEND

ELECTRICAL

ED101

EP101

E602

ELECTRICAL DEMOLITION PLANS

ELECTRICAL NEW WORK PLANS

PANEL SCHEDULES

PH101 4 PHASING PLAN

E601 PANEL SCHEDULES

20EP102 ELECTRICAL NEW WORK PLANS

COVER SHEET

GI001

SD

RD

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

AutoCAD SHX Text

SITE

AutoCAD SHX Text

DETAIL MAP

AutoCAD SHX Text

VICINITY MAP

AutoCAD SHX Text

SITE

sdoty Typewritten Text sdoty Typewritten Text sdoty Typewritten Text sdoty Typewritten Text sdoty Typewritten Text sdoty Typewritten Text sdoty Typewritten Text F100 sdoty Typewritten Text 24A sdoty Typewritten Text

CONSTRUCTION BARRIER FLOOR PLANS

sdoty Typewritten Text

BUILDING CODES AND STANDARDS

STRUCT. STRUCTURAL

SUSP. SUSPENDED

WALL TYPE

WALL TYPE INDICATOR

EQUIPMENT INDICATOR

EQUIPMENT NUMBER

A

KEYNOTE INDICATOR

KEYNOTE NUMBER

WINDOW INDICATOR

ROOM NAME

ROOM NUMBER

ROOM NAME

SHEET NUMBER

DETAIL NUMBER

INTERIOR ELEVATIONS

COLUMN NUMBER

COLUMN INDICATOR

00000.001

DETAIL NUMBER

SHEET NUMBER

SECTION INDICATOR

A A100

* MULTIPLE DOORS PER ROOM

DOOR DESIGNATION

DOOR NUMBER

A A100

SHEET NUMBER

DETAIL NUMBER

EXTERIOR ELEVATION

ALT.16

ALTERNATE INDICATOR

ALTERNATE NUMBER

CEILING TYPE

CEILING HEIGHT

NOT ALL SYMBOLS ARE USED IN THIS DRAWING SET

1. VA DESIGN MANUAL (PG-18-0)

2. VA DESIGN, QUALITY, AND STANDARD ALERTS

3. VA DESIGN GUIDES (PG-18-12)

4. VA DESIGN AND CONSTRUCTION PROCEDURES (PG-18-3)

5. PHYSICAL SECURITY DESIGN MANUAL FOR VA FACILITIES

6. VA FIRE PROTECTION DESIGN MANUAL

7. VA BARRIER FREE DESIGN GUIDE (PG-18-3)

8. VA SIGNAGE DESIGN GUIDE

9. VA PARKING DESIGN GUIDE

10. NFPA 101: LIFE SAFETY CODE

11. NFPA 13: STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

12. NFPA 70: NATIONAL ELECTRICAL CODE

13. ASHRAE 62.1: VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

14. ASHRAE 90.1: ENERGY STANDARD FOR BUILDINGS EXCEPT LOW RISE

RESIDENTIAL BUILDINGS

15. VA NATIONAL CAD STANDARD APPLICATION GUIDE

16. NFPA NATIONAL FIRE CODES (EXCEPT NFPA 5000 & 900)

17. VA SEISMIC DESIGN REQUIREMENTS, H-18-8

18. OSHA STANDARDS

19. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN

CONCRETE INSTITUTE AND COMMENTARY (ACI 318)

20. EPA 2005

21. VA MASTER SPECIFICATIONS

22. NEC NATIONAL ELECTRICAL CODE CURRENT REVISION.

23. VA SUSTAINABLE DESIGN MANUAL

CEILING INDICATOR

3 PHOTO DETAIL

NEW WORK NOTE

DEMOLITION NOTE

ROOM

NAME

A

WINDOW

DESIGNATION

4AE1002

PROJECT INFORMATION

RENOVATE ELEVATORS

SALEM VA MEDICAL CENTER

1970 ROANOKE BOULEVARD

SALEM, VA 24153-6404

VA PROJECT NUMBER: 658-18-103

SCOPE OF WORK

SAMPLING AND DETECTING FOR ASBESTOS CONTAINING MATERIAL (ACM) WITHIN THE

AREA AFFECTED BY THIS CONSTRUCTION PROJECT HAVE BEEN COMPLETED. ACM'S

WERE FOUND TO BE PRESENT WITHIN THE CONSTRUCTION LIMITS. SEE REPORT TITLED:

"LIMITED HAZARDOUS MATERIALS SURVEY SVAMC Elevator Upgrade Building 143 H&P Project 20181871. PERFORMED BY MS. MARY BETH WRISTON. VIRGINIA ASBESTOS

INSPECTOR LICENSE NUMBER 3303 003466. CONDUCTED ON DECEMBER 6, 2018

THE CONTRACTOR SHALL BE REQUIRED TO PROPERLY ABATE AND DISPOSE OF THESE

MATERIALS IN ACCORDANCE WITH STATE AND FEDERAL ASBESTOS ABATEMENT

GUIDELINES PRIOR TO ANY INTERIOR WORK.

THE BUILDING SHALL BE OCCUPIED THROUGH OUT THE CONSTRUCTION PROCESS. THE

CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT OCCUPIED

AREAS DURING ABATEMENT AND DEMOLITION. PERFORM AIR SAMPLING WITHIN

BUILDING TO ENSURE OCCUPIED AREAS ARE SUITABLE FOR USE BY THE OWNER.

COORDINATE ANY DISRUPTIONS TO DAILY OPERATIONS WITH PROJECT ENGINEER.

THE OWNER HAS PERFORMED SURVEYS OF THE EFFECTED PORTIONS OF THE BUILDING

WHERE WORK ON THE ELEVATOR SYSTEMS WILL BE PERFORMED. THE SURVEYS WERE

CONDUCTING IN COMPLIANCE WITH THE REQUIREMENTS OF THE ENVIRONMENTAL

PROTECTION AGENCY (EPA) NATIONAL EMISSION STANDARDS FOR HAZARDOUS AIR

POLLUTANTS (NESHAP) AS DETAILED IN 40 CFR, PART 61, SUBPART M REGULATIONS.

ASBESTOS INFO

BUILDING SUMMARY

OCCUPANCY CLASSIFICATION: INSTITUTIONAL (1-2)

USE: HEALTHCARE / HOSPITAL

CONSTRUCTION TYPE: TYPE II-B (FULLY SPRINKLERED)

FIRE RESISTANCE RATING FOR BUILDING ELEMENTS (HOURS)

BEARING WALL EXTERIOR - 2

BEARING WALL INTERIOR - 2

NON-BEARING WALL - 0

PRIMARY STRUCTURAL FRAME - 2

FLOOR CONSTRUCTION - 2

ROOF CONSTRUCTION - 1

THIS DESIGN EFFORT INCLUDES DESIGN /RENOVATION OF ELEVATORS IN BUILDINGS 1, 2, 2A, 4,5,10, 11, 76, AND 143 (THIS BID 143 ONLY). THE ORDER OF PRIORITY SHALL BE: BUILDING 2A, BUILDING 143 (TO INCLUDE ALL PASSENGER ELEVATORS AND DUMBWAITERS), BUILDING 2, BUILDING 10, BUILDING 11, BUILDING 4, BUILDING 5, BUILDING 76, AND BUILDING 1. THE ELEVATORS HAVE BEEN NOTED AS PAST LIFE EXPECTANCY AND NEED OF REPLACEMENT AND UPGRADE. A COMPLETE DESIGN PACKAGE SHALL

PROVIDE FULLY FUNCTIONAL ELEVATORS IN RESPECTIVE BUILDINGS TO ENSURE THE MEDICAL

CENTER REMAINS CAPABLE OF PROVIDING SAFE, HIGH QUALITY CARE TO OUR VETERAN POPULATION.

INFECTIOUS CONTROL NOTES

INFECTIOUS CONTROL PROCEDURES

1. CONTRACTOR SHALL PROVIDE EVERYTHING NEEDED FOR INFECTIOUS

CONTAINMENT/CONTROL SYSTEM. SOME ITEMS MAY INCLUDE, BUT NOT LIMITED TO;

CONSTRUCTION ZONE SIGNS, HEPA FILTERS, AIR SCRUBBERS, ETC. CONTACT RESIDENT

ENGINEER, FACILITY INFECTIOUS CONTROL RISKS ASSESSMENT TEAM (ICRA) FOR FULL

PROCEDURE REQUIREMENTS.

2. IT IS RECOMMENDED THAT THE CONTRACTOR UTILIZES MOVEABLE CONTAINMENT SYSTEM,

CONSTRUCTED OF A MINIMUM 6ML POLY OR PREFABRICATED ZIP WALL THAT CAN BE SEALED

TO WORK AREAS. THE INTEGRITY OF THE BARRIER WALLS MUST ASSURE A COMPLETE SEAL

OF THE CONSTRUCTION AREA FROM ADJACENT AREAS.

3. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT CONTAINMENT/CONTROL

SYSTEM PLAN TO COR FOR APPROVAL, INCLUDING PERIODIC STATUS REPORTS, AND SUBMIT

TO THE VA RESIDENT ENGINEER AND FACILITY ICRA TEAM FOR REVIEW FOR COMPLIANCE

WITH CONTRACT REQUIREMENTS. ALL PERSONNEL INVOLVED IN THE CONSTRUCTION SHALL

BE EDUCATED AND TRAINED IN INFECTION PREVENTION MEASURES ESTABLISHED BY THE

MEDICAL CENTER AND SHALL FOLLOW INFECTION CONTROL PROCEDURES.

4. IN EACH CONSTRUCTION AREA, THE CONTRACTOR SHALL UTILIZE A 120V HEPA FILTER

EQUIPPED AIR SCRUBBER MACHINE.

5. DO NOT REMOVE CONSTRUCTION BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT

IS SIGNED OFF BY COR AND VA'S INFECTION CONTROL DEPARTMENT.

6. PROVIDE DUST “STICKY” MAT AT ENTRANCE/EXIT OF CONSTRUCTION AREA AND REPLACE OR

CLEAN WHEN NO LONGER EFFECTIVE.

7. ALL FURNITURE AND EQUIPMENT SHALL BE PROTECTED DURING DEMOLITION AND

CONSTRUCTION.

MEDICAL WASTE

1. HOSPITAL STAFF SHALL ENSURE THE REMOVAL OF ANY MEDICAL WASTE,

INCLUDING SHARP CONTAINERS, FROM AREAS TO BE RENOVATED, PRIOR TO THE

START OF THE PROJECT.

2. INFECTION CONTROL SHALL BE NOTIFIED BY FACILITIES MANAGEMENT STAFF

IMMEDIATELY IF UNEXPECTED MEDICAL WASTE IS ENCOURAGED.

ENVIRONMENTAL CONTROL

1. ISOLATE HVAC SYSTEM IN AREA WERE WORK IS TO BE DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

MAINTAIN NEGATIVE AIR PRESSURE AT ALL TIMES WITH NO DISRUPTION OF THE AIR

SYSTEMS OF THE ADJACENT AREAS. INSTALL HEPA (HIGH EFFICIENCY PARTICULATE

ACCUMULATOR) FILTER VACUUM SYSTEM RATED AT 95% CAPTURE OF 0.3 MICRONS

INCLUDING (EFFECTIVE FOR POLLEN, MOLD SPORES

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

LEGENDS, SYMBOLS

AND ABBREVIATIONS

GI002

SDRD

DEFINITIONS:

CUTTING: REMOVAL OF IN-PLACE CONSTRUCTION NECESSARY TO PERMIT INSTALLATION

OR PERFORMANCE OF OTHER WORK.

PATCHING: FITTING AND REPAIR WORK REQUIRED TO RESTORE SURFACES TO ORIGINAL

CONDITIONS AFTER INSTALLATION OF OTHER WORK.

REMOVE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF

THEM OFF-SITE, UNLESS INDICATED TO BE SALVAGED OR REMOVED AND REINSTALLED.

SALVAGE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND DELIVER THEM TO

OWNER READY FOR REUSE.

REMOVE AND REINSTALL: DETACH ITEMS FROM EXISTING CONSTRUCTION, PREPARE

THEM FOR REUSE, AND REINSTALL THEM WHERE INDICATED.

EXISTING TO REMAIN: EXISTING ITEMS OF CONSTRUCTION THAT ARE NOT TO BE

REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE REMOVED, REMOVED AND

SALVAGED, OR REMOVED AND REINSTALLED.

GENERAL NOTES:

1. DEPICTION OF EXISTING CONDITIONS BASED ON ORIGINAL CONSTRUCTION

DOCUMENTS AND LIMITED FIELD OBSERVATIONS. EXISTING ELEMENTS AND

CONDITIONS CONCEALED BY IN-PLACE EQUIPMENT AND FINISHES WERE NOT

OBSERVED OR INVESTIGATED. ONCE CUTTING AND SELECTIVE DEMOLITION WORK IS

COMPLETE, REPORT ANY CONFLICTS TO COR/RE.

2. VAMC EQUIPMENT SUPPLIER TO REMOVE EXISTING UNMOUNTED AND MOUNTED

EQUIPMENT PRIOR TO CONSTRUCTION. ONCE OWNER & EQUIPMENT SUPPLIER HAS

REMOVED EQUIPMENT, PHOTOGRAPHICALLY DOCUMENT ENTIRE AREA OF NEW WORK.

TAKE NOTE OF ANY DAMAGED SURFACES OR ELEMENTS. PREPARE WRITTEN AND

PHOTOGRAPHIC REPORT OF SURVEY AND SUBMIT TO OWNER AND DESIGNER.

3. PROTECT ALL EXISTING FINISHES AND ELEMENTS TO REMAIN. REPAIR OR REPLACE

DAMAGED SURFACES TO MATCH ADJACENT FINISHES.

1. PATIENT/STAFF CIRCULATION SHALL BE COORDINATED WITH THE VA. PROVIDE TEMPORARY BARRIERS

TO ENSURE THE SAFE PASSAGE OF PEOPLE AROUND THE CONSTRUCTION AREA. CONDUCT

OPERATIONS TO PREVENT DAMAGE OF FALLING DEBRIS OR OTHER CAUSE TO ADJACENT SPACES.

2. DO NOT CLOSE OR OBSTRUCT CORRIDOR OR OCCUPIED SPACES WITHOUT PERMISSION FROM COR, PROVIDE ALTERNATE ROUTES AROUND CLOSED OR OBSTRUCTED TRAFFIC.

3. UTILITY OUTAGE SHALL BE DETERMINED BY CONTRACTOR AND COORDINATED WITH THE VA AT LEAST

TWO WEEKS IN ADVANCE.

4. CONSTRUCTION PERIOD TESTING REQUIREMENTS AS PER VA STANDARD CRITERIA.

5. INSPECTION REQUIREMENTS AS PER VA CRITERIA.

6. STAGGING/STORAGE AREAS AND CONSTRUCTION ROUTES FOR DELIVERY AND REMOVAL OF

MATERIALS SHALL BE COORDINATED AND APPROVED BY THE COR.

7. PROMPTLY REPAIR DAMAGE CAUSED TO ALL AREAS BY DEMOLITION/CONSTRUCTION OPERATIONS AT

NO COST TO THE VA.

8. MAINTAIN EXITING UTILITIES; KEEP IN SERVICE AND PROTECT AGAINST DAMAGE DURING DEMOLITION

AND CONSTRUCTION OPERATIONS.

9. DO NOT INTERRUPT EXISTING UTILITY SERVICE TO OCCUPIED SPACES EXCEPT WHEN AUTHORIZED BY

COR.

10.CONTRACTOR SHALL PROVIDE CONSTRUCTION ZONE SIGNS, NEGATIVE PRESSURE ZONE WITH

HEPA FILTERS, AIR SCRUBBERS STICKY MATS, DUST BARRIER; SEAL AIR OUTLETS, SEAL DOORS

BETWEEN CONSTRUCTION ZONE AND HOSPITAL. CONTRACTOR SHALL CONTACT COR FOR A

COMPLETE LIST OF INFECTION CONTROL PROCEDURES.

11.PROVIDE TEMPORARY ENCLOSURES AND OTHER SUITABLE METHODS AS NECESSARY TO LIMIT THE AMOUNT OF DUST AND DIRT RISING AND SCATTERING IN THE AIR TO THE LOWEST LEVELS OF AIR POLLUTION PRACTICAL FOR THE CONDITION OF WORK. WRAP EITHER DUCT OR OPENINGS OR OUTLET

WITH BLUE CELLOPHANE TO PREVENT DUST FROM ENTERING. COMPLY WITH GOVERNMENT

REGULATIONS.

12.CONTRACTOR SHALL PROVIDE NON-DESTRUCTIVE IMAGING AT ALL REQUIRED PENETRATIONS AT

EXISTING FLOORS AND ROOFS.

CLEANING

1. THE CONSTRUCTION ZONE AND ADJACENT AREAS SHALL BE MAINTAINED IN A CLEAN AND

SANITARY MANNER BY THE CONTRACTORS AND SHALL BE SWEPT AND MOPPED DAILY OR

MORE FREQUENTLY AS NEEDED TO MINIMIZE DUST GENERATION.

2. ALL EQUIPMENT, TOOLS, MATERIAL, ETC. TRANSPORTED THROUGH OCCUPIED AREAS SHALL

BE MADE FREE FROM DUST AND MOISTURE BY VACUUMING AND WIPE DOWN. USING HEPA

VACUUM, CLEAN INSIDE THE BARRIER AND VACUUM CEILING TILE PRIOR TO REPLACEMENT.

ALL TRANSITION AREAS FROM CONSTRUCTION TO THE OCCUPIED MEDICAL CENTER SHALL BE

VACUUMED AND WET MOPED AT THE END OF EACH WORKDAY.

3. ALL DEBRIS SHALL BE REMOVED AS IT IS GENERALIZED DURING LOW TRAFFIC HOURS OR

AFTER HOURS IN A CLEAN, COVERED, SEALED CART; APPROVED BY THE COR. NO DEBRIS

SHALL BE HAULED THROUGH PATIENT-CARE AREAS WITHOUT PRIOR APPROVAL OF THE COR

AND THE MEDICAL CENTER. WHEN, APPROVED, DEBRIS SHALL BE HAULED IN ENCLOSED DUST

PROOF, TIGHTLY FITTED CONTAINERS, USING SPECIFIC TRAFFIC PATTERNS DAILY. PROJECT

SUPERINTENDENT SHALL OVERSEE THIS AFTER APPROVAL FROM RESIDENT ENGINEER.

1. CLOTHING SHALL BE FREE FROM DUST AND DEBRIS PRIOR TO EXITING THE CONSTRUCTION

ZONE.

2. PERSONAL PROTECTIVE EQUIPMENT, INCLUDING FACE SHIELD, GLOVES AND N95

RESPIRATORS SHALL BE UTILIZED AS APPROPRIATE.

3. ALL CONSTRUCTION PERSONNEL ENTERING STERILE/INVASIVE PROCEDURE AREAS, SHALL

WEAR A DISPOSABLE JUMPSUIT, HEAD COVERED AND SHOE COVERINGS WHICH MUST BE

REMOVED PRIOR TO EXITING THE WORK AREA. CONTACT FOR SPECIFIC INSTRUCTIONS.

PROJECT COMPLETION

1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS

ASSOCIATED WITH CONSTRUCTION.

2. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.

3. WET MOP WORK AREA WITH DISINFECTANT.

4. REMOVE ISOLATION OF HVAC SYSTEMS IN AREAS WHERE WORK IS BEING PERFORMED.

5. WIPE CASEWORK AND HORIZONTAL AND VERTICAL SURFACES AT COMPLETION OF PROJECT.

SUBMITTALS

1. CONTRACTOR IS TO REVIEW INFECTIOUS CONTROL PROCEDURES PROVIDED BY THE VA'S

INFECTION CONTROL DEPARTMENT, INCLUDING LOCATION AND DETAILS OF BARRIERS PRIOR

TO START OF PROJECT.

2. CONTRACTOR SHALL SUBMIT PRODUCT DATA FOR REVIEW.

PRODUCTS AND MATERIALS

1. CONSTRUCTION BARRIERS SHALL CONSIST OF 6 MILL. THICK FIRE RETARDANT PLASTIC

SHEETS, OR PREFABRICATED ZIP WALLS WITH 120V HEPA FILTER EQUIPPED AIR SCRUBBER.

2. DISINFECTANT AS APPROVED BY VA HOSPITAL.

1. DESIGNATED ENTRY AND EXIT PROCEDURES SHALL BE COORDINATED WITH THE VA (IN

CONJUNCTION WITH ANY NECESSARY INTERIM LIFE SAFETY MEASURES) FOR THE PROJECT.

2. ALL EGRESS PATHWAYS SHALL BE FREE OF DEBRIS.

3. UNAUTHORIZED PERSONNEL SHALL NOT BE ALLOWED TO ENTER THE CONSTRUCTION AREA.

4. ONLY DESIGNATED ELEVATORS SHALL BE USED FOR CONSTRUCTION DURING SCHEDULED

TIMES.

5. WHEN USING DEMOLITION CHUTES, CHUTE OPENINGS SHALL BE SEALED WHEN NOT IN USE.

THE CHUTE AND DAMPER SHALL BE SPRAYED WITH WATER, AS NECESSARY, TO MAINTAIN

DUST CONTROL.

6. ANY CEILING ACCESS PANELS OPENED FOR INVESTIGATION BEYOND SEALED AREAS SHALL BE

CLOSED IMMEDIATELY WHEN UNATTENDED.

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

GENERAL NOTES

GI003

SDRD

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

PHASING PLAN

PH101

SD

CAMPUS MAP

v.a. medical center, salem, va no scale

FF

EE

DD

AA

BB

T

NN

Z

U Y

W

X

V

Q

P

O

N

LL

OO

PP

KK

K

JJ

J

HH

M

R

S

GG

F

E

A

G

C

D

B

CC

To City of Salem

To City of Roanoke

Navy Way

Patriot Blvd.

Ai r F or ce

C irc le

Garden Sq.

Marine Corps Drive

Roanoke Blvd.

Patriot Circle

Ar my

R oa d

Co as t G ua rd La ne

MM

Patriot Circle

Patriot Circle

Patriot Circle

BUILDING FUNCTIONS

1 DIRECTOR, POLICE

2 EXTENDED CARE, NUCLEAR MED, DENTAL, K.T., P.T., O.T.

2A ADMISSIONS, EMER. RM., PATHOLOGY, RADIOLOGY IMAGING

4 MAIN KITCHEN, CANTEEN, MEDICAL MEDIA

5 AUDITORIUM

7 LONG TERM EXTENDED PSYCHIATRIC, SOCIAL WORK

8 SUBSTANCE ABUSE, ACUTE PSYCHIATRIC

9 SUBSTANCE ABUSE, P.T.S.D.

10 CENTRALIZED FEE

17 LEASED SPACE

18 OFFICES

29 SWIMMING POOL

34 STORAGE

77 CREDIT UNION, EDUCATION ,

ENVIRONMENTAL MGMT,

STUDENT QUARTERS

80 GREENHOUSE (WEST)

T85 SHEET METAL SHOP

121 GREENHOUSE

130 GRANDSTAND

131 ELECTRICAL SUBSTATION

133 GOLF CLUBHOUSE

138 EMERGENCY GENERATOR BLDG

139 EMERGENCY GENERATOR BLDG

140 EMERGENCY GENERATOR BLDG

141 EMERGENCY GENERATOR BLDG

142 EMERGENCY GENERATOR BLDG

143 MAIN HOSPITAL, OUTPATIENT,

INPATIENT, CLINICAL NURSING UNIT.

144 CHAPEL

145 PLUMBING SHOP

146 CHAPEL OFFICES

148 MOTOR VEHICLE SHOP

150 SMOKING SHELTER

151 SMOKING SHELTER

11 MENTAL HYGIENE, DAY TREATMENT,

PSYCHIATRY/PSYCHOLOGY ADMIN.

12 HOPTEL, PROSTHETICS, AFGE, EMP. HEALTH, C & P

13 BOILER/ CHILLED WATER PLANT

14 LAUNDRY

15 SOILED LINEN, VET. INDUST., ENG./MED. REC. STOR.

16 VISN 6 OFFICES, ADR, AC SHOP, LANDSCAPE

19 OFFICES

23 SEWAGE PUMP HOUSE

25 DUPLEX HOUSE (LEASE)

26 6-CAR GARAGE

27 5-CAR GARAGE

28 5-CAR GARAGE

35 IMPLEMENT SHED

46 FLAGPOLE

72 STORAGE

74 FMS, LOGISTICS, SAFETY, HRM, IRS

75 WHEELCHAIR CLINIC, REGION OFFICE STO, FISCAL, FITNESS CNTR

76 RESEARCH, NATIONAL AFGE, CARPENTRY & ELECTRIC SHOPS,

TRANSITIONAL LVG

153 EMERGENCY GENERATOR BLDG

154 EMERGENCY GENERATOR BLDG

155 PUMP HOUSE

156 EMERGENCY GENERATOR BLDG

157 EMERGENCY GENERATOR BLDG

158 SMOKING SHELTER

159 SMOKING SHELTER

160 OPEN FRONT SMOKING SHELTER

161 SMOKING SHELTER

162 ROANOKE CITY WATER MAIN BLDG

163 SALEM WATER MAIN BLDG

164 GREENHOUSE

165 OPEN SMOKING SHELTER

168 CENTER FOR TRAUMATIC STRESS

170 ACUTE INPATIENT PSYCHIATRIC UNIT

171 POLICE SUB STATION

172 WVWA PUMP HOUSE

173 CITY OF SALEM PUMP HOUSE

174 WATER TOWER

175 NEW BOILER PLANT

176 SALT SHED

152 SMOKING SHELTER

Building

Parking Lot

Connecting Corridor

Underground Service Tunnel

2A

H

L

I

REPLACING: 1 HYDRAULIC ELEVATOR

6 TRACTION ELEVATORS

2 HYDRAULIC CART LIFTS

SOUTH BIRD'S EYE VIEW

NORTH BIRD'S EYE VIEW

"EE"

"1"

CAMPUS MAP SCOPE OF WORK

AE100

DR

ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

'E'

NOTE: BOTH FLOORS ARE

THE SAME FOR CART LIFT E.

NOTE:

BASEMENT AND

SUB-BASEMENT

FOR BANK C ARE

THE SAME AS

FIRST FLOOR

D

NOTE: SUB-BASEMENT FOR BANK C IS

THE SAME AS THE BASEMENT PLAN

GENERAL NOTES

LEGEND & ABBREVIATIONS

ABBREVIATION SYMBOL DESCRIPTION ABBREVIATION DESCRIPTION

ABOVE FINISHED FLOOR AFF

A/C ABOVE CEILING

AIR HANDLING UNIT AHU

AP

BTUH

ACCESS PANEL

BRITISH THERMAL UNITS PER HOUR

CUBIC FEET PER MINUTE CFM

CLG CEILING

DOWN DN

DWGS DRAWINGS

EXHAUST AIR EA

EF EXHAUST FAN

ELECTRIC ELEC

EX. EXISTING

GALLONS PER MINUTE GPM

HVAC HEATING VENTILATING & AIR CONDITIONING

MAXIMUM MAX

MIN MINIMUM

TRANSFER GRILLE TG

TYP TYPICAL

VARIABLE AIR VOLUME UNIT VAV

CTE CONNECT TO EXISTING

HWS

HWR

MBV

GV

CV

RL/RS/RHG

D

MOV

FD

MLD/MD

HOT WATER SUPPLY

HOT WATER RETURN

METERED BALANCING VALVE

GATE VALVE

CHECK VALVE

CONDENSATE DRAIN LINE

MOTOR OPERATED (2-WAY) VALVE

STRAINER

UNION

FIRE DAMPER

SINGLE LINE DUCT

FLEXIBLE DUCT

DUCT TRANSITION

ROUND

PIPE UP

PIPE OR DUCT DOWN

DIRECTION OF FLOW

MANUAL DAMPER

ROUND DUCT

FLAT OVAL WIDTH X DEPTH

RECTANGULAR DUCT WIDTH X DEPTH

MISSING)

RECTANGULAR ELBOWS WITH VANES EVEN IF SYMBOL IS

VANED ELBOW ( PROVIDE ALL SQUARE OR

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

HWS

HWR

OR

WXD"

WXD

MITERED ELBOWS.

E. INSTALL TURNING VANES IN ALL 45 AND 90 DEGREE

SPIN-IN COLLAR WITH SCOOP AND DAMPER.

TO RECTANGULAR OR SQUARE DUCT WITH A

D. FLEXIBLE OR ROUND DUCT SHALL BE CONNECTED

DIMENSIONS.

C. DUCT SIZES SHOWN ARE ACTUAL INSIDE

SENSORS 48 INCHES ABOVE FINISHED FLOOR.

SPACE THERMOSTATS, HUMIDISTATS AND

B. UNLESS OTHERWISE INDICATED, INSTALL ALL

PRIOR TO INSTALLATION.

A. COORDINATE ALL WORK WITH OTHER TRADES

DESIGN CONDITIONS

UNIT AREA

INSIDE OUTSIDE

HEAT. COOLING HEAT. COOLING

DB F WB F DB F DB F WB F

72.7 92.2 16.8 62.5 75.0 70.0 BUILDING 143 AHU-S4

DB F

S-15

CR-15 LOW PRESSURE STEAM CONDENSATE RETURN

S-15

DUCT MOUNTED SMOKE DETECTOR

SKD SKD

ETR EXISTING TO REMAIN

UH

HP HEAT PUMP

ROOF HOOD

UNIT HEATER

RH

M001SNS SNS

LEGEND, ABBREVIATIONS - BLDG

AHU-PS1-1 T0 PS1-5 BUILDING 143 70.0 75.0 62.5 16.8 92.2 72.7

CR-15

D

REFRIGERANT LINE SET RL/RS/RHG

AHU-PS2-1 T0 PS2-5 BUILDING 143 70.0 75.0 62.5 16.8 92.2 72.7

CO CLEAN OUT

LOW PRESSURE STEAM (15 PSIG AND BELOW)

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Fax: 251.990.3716

Phone: 251.990.5778

Fairhope, AL 36532

766 Middle St, Corporate Office:

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

V e te ra n s

A ff a ir s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

/3

/2

:2

:2

A

M

Revisions: Date:

BUILDING 143

UPGRADE ELEVATORS

SALEM VA MEDICAL CENTER

658-18-103

PLAN - SUBBASEMENT - BLDG 143

ENLARGED HVAC DEMOLITION

SNS SNS MD101

1 ENLARGED HVAC DEMOLITION PLAN - SUB-BASEMENT

MD101

DEMOLITION PLAN NOTESDEMOLITION PLAN NOTES

DRAWINGS FOR MORE INFORMATION.

4. ELEVATOR EQUIPMENT. REFER TO EQUIPMENT

PENETRATION.

ARCHITECTURAL FOR INFORMATION ABOUT WALL

APPROXIMATELY 18"X36" IN SIZE. REFER TO

DISPOSED OF PROPERLY. TRANSFER GRILLE IS

3. EXISTING TRANSFER GRILLE TO BE REMOVED AND

INFORMATION ABOUT WALL PENETRATION.

32"X32" IN SIZE. REFER TO ARCHITECTURAL FOR

DISPOSED OF PROPERLY. FAN IS APPROXIMATELY

2. EXISTING EXHAUST FAN SHALL BE REMOVED AND

REMAIN.

1. EXISTING SUBBASEMENT EXHAUST FAN SHALL

EXISTING TO BE REMOVED

EXISTING TO REMAIN

SCALE: 1/4" = 1'-0"

SF-100

04 - Vertical Space

ELEVATOR

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Fax: 251.990.3716

Phone: 251.990.5778

Fairhope, AL 36532

766 Middle St, Corporate Office:

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

V e te ra n s

A ff a ir s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

/3

/2

:2

:2

A

M

Revisions: Date:

BUILDING 143

UPGRADE ELEVATORS

SALEM VA MEDICAL CENTER

658-18-103

SNS SNS MH101

MH101

ENLARGED HVAC PLAN - SUB-BASEMENT

SUBBASEMENT - BLDG 143

ENLARGED HVAC PLAN -

PLAN NOTES

RL/RS/RHG

AHU

S4

D

HP

S4

LOCATION.

FIELD VERIFY DRAIN

DRAIN LOCATED IN AIR WELL.

ROUTE CONDENSATE TO

SCALE: 1/4" = 1'-0"

2/MH401 FOR DETAIL.

4. INSTALL UNIT ON EQUIPMENT PAD. REFER TO

UNIT. ROUTE TO EXTERIOR AS SHOWN.

3. CONDENSATE DRAIN FULL SIZE OF CONNECTION AT

RECOMMENDATIONS.

IN ACCORDANCE WITH MANUFACTURER'S

OUTDOOR UNIT. SIZE AND INSTALL REFRIGERANT LINE

2. ROUTE REFRIGERANT LINE OUT ASSOCIATED

MANUFACTURER'S RECOMMENDATIONS.

1. MOUNT UNIT ON WALL IN ACCORDANCE WITH

EXISTING TO REMAIN

NEW WORK

SF-100

04 - Vertical Space

ELEVATOR

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Fax: 251.990.3716

Phone: 251.990.5778

Fairhope, AL 36532

766 Middle St, Corporate Office:

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

V e te ra n s

A ff a ir s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

/3

/2

:2

:2

A

M

Revisions: Date:

BUILDING 143

UPGRADE ELEVATORS

SALEM VA MEDICAL CENTER

658-18-103

MECH

SJ 100CS 1

STAIR

NO 1

ELEVATOR

ELEVATOR

ELEVATOR

ELEVATOR ELEVATOR ELEVATOR

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Fax: 251.990.3716

Phone: 251.990.5778

Fairhope, AL 36532

766 Middle St, Corporate Office:

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

V e te ra n s

A ff a ir s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

/3

/2

:2

:2

A

M

Revisions: Date:

BUILDING 143

UPGRADE ELEVATORS

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

1 ENLARGED HVAC PLAN - PENTHOUSE

MH102

PENTHOUSE - BLDG 143

ENLARGED HVAC PLAN -

MH102SNS SNS

CO

AHU

PS1-5

AHU

PS1-3AHU

PS2-4

AHU

PS2-2

HP

PS1

PLAN NOTES

RL/RS/RHG

RL/RS/RHG

R L /R

S /R

H G

D

D

HP

PS2

AHU

PS2-5

AHU

PS2-3

AHU

PS2-1

AHU

PS1-4

AHU

PS1-2

AHU

PS1-1

R L /R

S /R

H G

RL/RS/RHG

RL/RS/RHG

RL/RS/RHG

RL/RS/RHG

RL/RS/RHG

RL/RS/RHG

RL/RS/RHG

RL/RS/RHG

RECOMMENDATIONS.

IN ACCORDANCE WITH MANUFACTURER'S

OUTDOOR UNIT. SIZE AND INSTALL REFRIGERANT LINE

7. ROUTE REFRIGERANT LINE OUT ASSOCIATED

BLOCK.

6. TURN OUT CONDENSATE DRAIN OVER SPLASH

BUILDING.

5. INSTALL UNIT ON EQUIPMENT RAILS ON ROOF OF

MANUFACTURER'S RECOMMENDATIONS.

UNUSED PORTS. INSTALL IN ACCORDANCE WITH

4. REFRIGERANT HEADER. CAP, SEAL, AND INSULATE

UNIT. ROUTE TO EXTERIOR AS SHOWN.

3. CONDENSATE DRAIN FULL SIZE OF CONNECTION AT

RECOMMENDATIONS.

ACCORDANCE WITH MANUFACTURER'S

HEADER. SIZE AND INSTALL REFRIGERANT LINE IN

2. ROUTE REFRIGERANT LINE TO REFRIGERANT

RECOMMENDATIONS.

ACCORDANCE WITH MANUFACTURER'S

1. HANG UNIT FROM EXISTING STRUCTURE IN

5 5

1"

1"

3/4"

3/4"

1"

SCALE: 1/4" = 1'-0"

2.34m

2D

DX COIL

RA

48" [1200mm] AFF.

ROOM TEMPERATURE SENSOR, WALL MOUNTED

OR BEND OVER END 5D

WELD HEAD TO PLATE

FLOOR

[75mm] MIN.)

PIPE SLEEVE (5D, 3"

BOLT (TYP)

ANCHOR

CONCRETE BASE

EQUIPMENT BASE PLATE

DOWEL BASE TO FLOOR

O.C. EACH WAY IN THE BASE &

PROVIDE #3 BARS 12" [300mm]

BOLT NUT & WASHER

TYPICAL ANCHOR

SYMBOL

TYPE

TOTAL CFM

LOCATION

REMARKS

CHARACTERISTICS

ELECTRICAL

208V 1PH

SUBBASE 143

95.0

62.5

75.0

24,000

WALL MOUNT

17.0

70.0

91.5

PRESSURE, IN. H 0

EXTERNAL STATIC

BTU/HR

TOTAL CAPACITY,

22,635 CAPACITY, BTU/HR

SENSIBLE

17.0

2.5

18,000

AIR, CFM

MINIMUM OUTSIDE

BTU/HR

TOTAL CAPACITY

MINIMUM COP

H E

A T I

N G

C O

O L I

N G

DUCTLESS HEAT PUMP

AHU-S4 HP-S4

MINIMUM SUCTION

COND. AMBIENT

AMBIENT AIR

SEER

MINIMUM

SYMBOL

19.0

195,820

16.0

95.0

C O

O L I

N G

3.5

141,375

17.0

LOCATION

REMARKS

CHARACTERISTICS

ELECTRICAL

460V 3PH

PENTHOUSE 143

VRF HEAT PUMPS

HP-PS1

TONNAGE, TONS

MINIMUM NOMINAL

COND. AMBIENT

(INTEGRATED) EER

MINIMUM

H E

A T I

N G

AFTER LINE LOSSES

CAPACITY, BTU/HR

AFTER LINE LOSSES

CAPACITY, BTU/HR

AMBIENT AIR

MINIMUM COP AT

TYPE

TOTAL CFM

LOCATION

REMARKS

CHARACTERISTICS

ELECTRICAL

208V 1PH

PENTHOUSE 143

31,165

32,500

FULL

1,235

HP-PS1

BTU/HR

TOTAL CAPACITY,

OUTSIDE AIR, CFM

43,160

CAPACITY, BTU/HR

SENSIBLE

BTU/HR

TOTAL CAPACITY,

SYMBOL

VRF AIR HANDLERS

UNIT

ASSOCIATED OUTDOOR

PRESSURE, IN. H20

EXTERNAL STATIC

FULL/PARTIAL

DEMAND TYPE,

C O I

L

C O

O L I

N G

C O I

L

H E

A T

CEILING

CASSETTE

AHU-PS1-1

208V 1PH

31,165

32,500

FULL

1,235

HP-PS1

43,160

CEILING

CASSETTE

AHU-PS1-2

31,165

32,500

FULL

1,235

HP-PS1

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS1-3

31,165

32,500

FULL

1,235

HP-PS1

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS1-4

FAN

T-1

TT

PC

3. ALARM IF SPACE TEMPERATURE OUTSIDE OF RANGES.

2. MODULATE CONDENSER TO MAINTAIN SPACE SET POINT AND FAN SHALL CYCLE W/TEMPERATURE.

1. FAN COIL UNIT SHALL OPERATE CONTINUOUSLY

DUCTLESS SPLIT SYSTEM SEQUENCE OF OPERATION (HEAT PUMP)

RL/RS/RHG

FILTER

1 CONTROL DIAGRAM AND SEQUENCE

DUCTLESS SPLIT SYSTEM HEAT PUMP

SCALE: NTSMH401

PENTHOUSE 143 PENTHOUSE 143 PENTHOUSE 143 1

1 1 1

HVAC SCHEDULES - BLDG 143

SNS SNS MH401

PROGRAMMBALE WIRED THERMOSTAT.

LOW AMBIENT CONTROL, AND

PROVIDE UNIT WITH WIND BAFFLE FOR

UNIT SHALL HAVE A MCA/MCB OF 18A/20A.

DAIKIN AND LG ARE APPROVED EQUAL.

BASIS OF DESIGN IS MITSUBISHI PKA/PUZ.

SIMPLE WIRED THERMOSTAT.

EQUAL. UNIT SHALL HAVE A MCA/MCB OF 1.3A/15A. PROVIDE UNIT WITH

BASIS OF DESIGN IS MITSUBISHI PLFY. DAIKING AND LG ARE APPROVED

31,165

32,500

FULL

1,235

HP-PS1

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS1-5

PENTHOUSE 143

31,165

32,500

FULL

1,235

HP-PS2

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS2-1

PENTHOUSE 143

31,165

32,500

FULL

1,235

HP-PS2

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS2-2

PENTHOUSE 143

31,165

32,500

FULL

1,235

HP-PS2

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS2-3

PENTHOUSE 143

31,165

32,500

FULL

1,235

HP-PS2

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS2-4

PENTHOUSE 143

31,165

32,500

FULL

1,235

HP-PS2

208V 1PH

43,160

CEILING

CASSETTE

AHU-PS2-5

PENTHOUSE 143

19.0

195,820

16.0

95.0

3.5

141,375

17.0

460V 3PH

PENTHOUSE 143

HP-PS2

HEADER KIT, AND TWINNING KIT.

PROVIDE UNIT WITH LOW AMBIENT KIT,

20A/25A(MOD1) - 12A/15A(MOD2).

UNIT SHALL HAVE A MCA/MCB OF

DAIKIN AND LG ARE APPROVED EQUAL.

BASIS OF DESIGN IS MITSUBISHI PUHY.

SCALE: NTSMH401

L

W

A

A

D

D m m

5D

EQUIPMENT BASE PLATE.

GREATER THAN THE

SHALL BE 6" [150mm]

L & W DIMENSIONS

NOTE:

m m

M

IN

L

CONCRETE EQUIPMENT BASE2

SCH 40 PVC OR

FLATHEAD SCREWS

FASTEN TO WALL W/

ADJACENT WALL AREAS

FINISH PAINT TO MATCH

SIZED AS REQD; SEAL W/

CUT TO TIGHTLY FIT

ESCUTCHEON PLATE

MOUNT SLEEVE AND PROVIDE ESCUTCHEON PLATE.

NOTE: WHERE PIPING IS EXPOSED AT FINISH WALLS, FLUSH

2 TYP FOR MASONRY

OR CONCRETE WALL

TYP FOR NON-INSULATED

PIPE

PIPE AND CONDUIT

NOTES:

WHERE EXPOSED

AND JACKET

INSULATION

ESCUTCHEON PLATE:

3/4" PLYWOOD

EACH PIPE

PAINT ALL SIDES

SPACE BETWEEN PIPE

CAULK AND SEAL ANNULAR

AND SLEEVE

SPACE BETWEEN PIPE

CAULK AND SEAL ANNULAR

AND SLEEVE

INTERIOR

SCH 40 PVC OR

GALV STEEL SLEEVE

SECURE TO PARTITION

INSULATION

PIPE W/OR W/OUT

EXTERIOR

SECURE TO PARTITION

GALV STEEL SLEEVE

SCALE: NTSMH401

3 PIPE PENETRATION THRU WALL DETAIL

PLAN

SECTION B-B

SECTION A-A (BASE NOT POURED WITH SLAB)

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Fax: 251.990.3716

Phone: 251.990.5778

Fairhope, AL 36532

766 Middle St, Corporate Office:

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

V e te ra n s

A ff a ir s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

/3

/2

:2

:2

A

M

Revisions: Date:

BUILDING 143

UPGRADE ELEVATORS

SALEM VA MEDICAL CENTER

658-18-103

ELECTRICAL NOTES

1. MATERIALS, EQUIPMENT, AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF THE AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM), LATEST EDITION OF THE NATIONAL ELECTRIC CODE (NEC). THE UNDERWRITERS LABORATORY (UL), THE NATIONAL ELECTRIC MANUFACTURER'S ASSOCIATION (NEMA), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), AND OTHER NATIONALLY RECOGNIZED AGENCIES AS WELL AS APPLICABLE LOCAL CODES.

2. ANYTHING DRAWN OR SPECIFIED SHALL NOT BE CONSTRUED TO CONFLICT WITH ANY LOCAL, MUNICIPAL OR STATE LAW, REGULATION OR ORDINANCE WHICH GOVERNS THE INSTALLATION OF ANY ELECTRICAL OR RELATED WORK. ITEMS SHALL NOT BE INSTALLED IN CONFLICT WITH THE NEC. RESOLVE ANY AND ALL CONFLICTS BEFORE INSTALLATION AT NO ADDITIONAL EXPENSE TO THE OWNER.

3. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND LABELED FOR THE QUALIFIED USE. VERIFY CIRCUIT BREAKER INTERRUPT CAPACITY NEEDED FOR EACH PANEL WITH LOCAL UTILITY. FOR BID PURPOSES, ASSUME 25,000 AIC FOR SERVICE ENTRANCE EQUIPMENT, 14,000 AIC FOR 480/277V EQUIPMENT , AND 10,000 AIC FOR 208/120V EQUIPMENT. BALANCE THE POWER EQUALLY (+/- 10%) ON ALL PHASES.

4. THE SYSTEMS SHOWN ON DRAWINGS SHALL BE PROVIDED TO SERVE ALL FIXTURES, EQUIPMENT, AND AREAS WITHIN THE CONTRACT LIMIT LINES AS SET FORTH BY THE ARCHITECTURAL SOLUTION FOR THE PROJECT. THE BIDDING AND CONTRACT REQUIREMENTS, GENERAL REQUIREMENTS, AND GENERAL PROVISIONS SHALL APPLY TO THIS SECTION. SYSTEMS SHALL INCLUDE ALL EQUIPMENT, APPURTENANCES, SAFETY DEVICES, AND

CONTROLS NECESSARY FOR THE INTENDED SERVICE.

5. ALL PERMITS AND FEES REQUIRED FOR THE WORK SHALL BE SECURED AND PAID FOR BY THE ELECTRICAL CONTRACTOR AND INCLUDED IN BID

PRICE.

6. BIDDERS SHALL BE LICENSED CONTRACTORS IN ACCORDANCE WITH LOCAL AND STATE LAWS.

7. ALL EQUIPMENT SHALL BE NEW AND UNUSED. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS, EXCEPT WHERE THESE SPECIFICATIONS REQUIRE A HIGHER QUALITY INSTALLATION THAN RECOMMENDED BY THE

MANUFACTURER.

8. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE ON SITE. REPLACE ANY AND ALL CONTRACTOR-SUPPLIED DEFECTIVE DEVICES, ITEMS OR SYSTEMS AT CONTRACTOR'S OWN EXPENSE BEFORE COMPLETION OF THE PROJECT.

9. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED OR FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLING MANUFACTURER'S GUARANTEED EQUIPMENT. THIS CONTRACTOR'S GUARANTEE SHALL EXIST FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL OWNER ACCEPTANCE OF THE WORK AND SHALL APPLY TO DEFECTS IN MATERIAL AND TO DEFECTIVE WORKMANSHIP OF ANY

KIND.

10. VERIFY FINAL LOCATIONS FOR ROUGH-INS WITH FIELD MEASUREMENTS AND WITH THE REQUIREMENTS OF THE ACTUAL EQUIPMENT TO BE

CONNECTED. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS.

11. SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATIONS OF ELECTRICAL MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK.

GIVE PARTICULAR ATTENTION TO LARGE EQUIPMENT REQUIRING POSITIONING PRIOR TO CLOSING-IN THE BUILDING. COORDINATE THE CUTTING AND PATCHING OF BUILDING COMPONENTS TO ACCOMMODATE INSTALLATION OF ELECTRICAL EQUIPMENT AND MATERIALS.

12. COORDINATE THE INSTALLATION OF ELECTRICAL MATERIALS AND EQUIPMENT ABOVE CEILINGS WITH SUSPENSION SYSTEM, MECHANICAL EQUIPMENT AND SYSTEMS, AND STRUCTURAL COMPONENTS. COORDINATE ELECTRICAL EQUIPMENT AND MATERIALS INSTALLATION WITH OTHER

BUILDING COMPONENTS.

13. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, INSTALL ELECTRICAL SERVICES AND OVERHEAD EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM POSSIBLE. INSTALL ELECTRICAL EQUIPMENT TO FACILITATE MAINTENANCE AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH MINIMUM OF INTERFERENCE WITH OTHER

INSTALLATIONS.

14. COORDINATE CONNECTION OF ELECTRICAL SYSTEMS WITH EXTERIOR UNDERGROUND AND OVERHEAD UTILITIES AND SERVICES. COMPLY WITH REQUIREMENTS OF GOVERNING REGULATIONS, FRANCHISED SERVICE COMPANIES, AND CONTROLLING AGENCIES. PROVIDE REQUIRED

CONNECTION FOR EACH SERVICE.

15. DO NOT ENDANGER OR DAMAGE INSTALLED WORK THROUGH PROCEDURES AND PROCESSES OF CUTTING AND PATCHING. ARRANGE FOR REPAIRS REQUIRED TO RESTORE OTHER WORK, BECAUSE OF DAMAGE CAUSED AS A RESULT OF ELECTRICAL INSTALLATIONS.

16. BIDDERS SHALL THOROUGHLY ACQUAINT THEMSELVES WITH THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED. THEY SHALL EXAMINE ALL SERVICES, EQUIPMENT, SURFACES, ETC., WHICH THIS WORK IS IN ANY WAY DEPENDENT UPON, AND BRING ANY DISCREPANCIES DETERMINED OR OMISSIONS FOUND IN THE DRAWINGS TO THE OWNER'S ATTENTION BEFORE SUBMITTING BID.

17. VERIFY MECHANICAL EQUIPMENT SWITCH AND CONNECTION REQUIREMENTS, ITEM BY ITEM, WITH THE MECHANICAL CONTRACTOR, BEFORE

WIRING EQUIPMENT. RESOLVE ALL DISCREPANCIES WITHOUT FURTHER COST TO OWNER.

18. ALL WIRING SHALL BE IN CONDUIT, 3/4" MINIMUM WITH STEEL COMPRESSION FITTINGS.

19. ALL WIRING SHALL BE THHN/THWN COPPER (NO. 12 AWG MINIMUM) UNLESS OTHERWISE NOTED. WIRE AND CONDUIT SIZES ARE SHOWN ON THE

PANEL SCHEDULE.

20. ALL PANELS, CONTROL DEVICES AND MISCELLANEOUS ELECTRICAL APPARATUS SHALL BE CLEARLY MARKED FOR EASY IDENTIFICATION AND SAFETY. USE BLACK PLASTIC OR BAKELITE NAME PLATE ENGRAVED WITH WHITE LETTERS 1/4" HIGH. PUNCHED TAPE IS NOT ACCEPTABLE.

21. PANELS SHALL BE PROVIDED WITH A TYPEWRITTEN DIRECTORY AFFIXED TO INSIDE OF PANEL DOOR WITH A CLEAR PLASTIC SLEEVE. . THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE FOR CIRCUIT ALLOCATION ONLY. DO NOT SCALE DRAWINGS.

22. ELECTRICAL CONTRACTOR SHALL FURNISH RECORD SET OF DRAWINGS WITH ANY DEVIATIONS MARKED IN RED INK.

23. ALL MOTORS SHALL MEET VIRGINIA ENERGY EFFICIENCY CODE COMPLIANCE.

ELECTRICAL LEGEND

GENERAL NOTES & LEGEND

E001

RD JP

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

DEMOLITION NOTES

GENERAL DEMOLITION NOTES

ED101

RD JP

SCALE: 1/8" = 1'-0"

0 4' 8' 16' on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

NOT TO SCALE

NEW WORK NOTES

GENERAL NEW WORK NOTES

EP101

RD JP

SCALE: 1/8" = 1'-0"

0 4' 8' 16' on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

GENERAL NEW WORK NOTES

NEW WORK NOTES

EP102

RD JP

SCALE: 1/8" = 1'-0"

0 4' 8' 16' on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

2019.07.29

PANEL SCHEDULES

E601

RD JP

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

PANEL SCHEDULES

E602

RD JP

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Date

Project No.

Drawing No.

Location Sheet of

FINAL SUBMISSION

V et er an s A ffa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

DESIGN/BUILD

1/

/2

9:

:2

A

M

Revisions: Date:

UPGRADE ELEVATORS

BUILDING 143

SALEM VA MEDICAL CENTER

658-18-103

FIRE PROTECTION ABBREVIATIONS

1. THE FIRE ALARM SCOPE OF WORK FOR THE PROJECT INVOLVES MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM SERVING THE ELEVATORS IN BUILDING 143. THERE ARE 7 ELEVATORS WHICH CONSIST OF 6 TRACTION

ELEVATORS AND 1 HYDRAULIC ELEVATOR.

2. SYSTEMS SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AS WELL AS THE FOLLOWING CODES AND STANDARDS:

CRITERIA IN VA-PG-18-10 FIRE PROTECTION DESIGN MANUAL (DECEMBER 2015)

IBC - INTERNATIONAL BUILDING CODE, 2018

NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION

NFPA 70 - NATIONAL ELECTRIC CODE, 2017 EDITION

NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE, 2019 EDITION

NFPA 101 - LIFE SAFETY CODE, 2018 EDITION

ASME A17.1 - SAFETY CODE FOR ELEVATOR AND ESCALATORS, 2016 EDITION

3. FOR ELEVATOR RELATED FIRE ALARM SYSTEM PROGRAMMING, SEE MATRIX OF OPERATIONS ON SHEET F501.

4. PRIOR TO PERFORMING WORK ON THE ALARM SYSTEM, THE CONTRACTOR MUST FIELD LOCATE THE FIRE ALARM CONTROL PANELS SERVING ALL AREAS AFFECTED.

5. TWO WEEKS PRIOR TO FINAL INSPECTION, CONTRACTOR SHALL DELIVER TO THE COTR 3 SETS OF AS-BUILT DRAWINGS AND ONE SET OF THE AS-BUILT DRAWING COMPUTER FILES SHOWING ALL NEW AND/OR

EXISTING CONDUIT USED FOR THE FIRE ALARM SYSTEM.

6. FINAL FIRE ALARM SYSTEM TESTING SHALL BE WITNESSED BY THE COTR.

7. FILE A "RECORD OF COMPLETION" PREPARED IN ACCORDANCE WITH NFPA 72, AND THE FIRE ALARM TEST REPORT, WITH THE COTR.

8. TAMPER SWITCHES AND FLOW SWITCHES SHALL BE INSTALLED UNDER DIVISION 21, BUT SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM BY THE FIRE ALARM CONTRACTOR.

9. FIRE AND SMOKE STOP ALL PENETRATIONS THROUGH RATED ASSEMBLIES. PROVIDE THROUGH-PENETRATION FIRESTOP SYSTEM PER UL 1479 AND SPECIFICATIONS.

10. ALL NEW FIRE ALARM WIRING SHALL BE CLASS B AND INSTALLED IN METALLIC CONDUIT.

11. EXISTING FIRE ALARM CONDITIONS ARE SHOWN AS ACCURATELY AS POSSIBLE. THESE DRAWINGS WERE PREPARED FROM INFORMATION TAKEN FROM THE ORIGINAL BUILDING DRAWINGS AND FIELD SURVEY INFORMATION COMPILED BY THE ENGINEERING DESIGN TEAM FOR THE PURPOSE OF ENGINEERING DESIGN CONCEPT. THERE IS THE POSSIBILITY THAT CONDITIONS SHOWN ARE NOT EXACTLY AS EXISTING.

CONTRACTOR SHALL VERIFY ALL DIMENSIONS, LOCATIONS AND CONDITIONS AT THE SITE AND DOCUMENT THAT ON THEIR SUBMITTALS.

FIRE ALARM GENERAL NOTES

FIRE SUPPRESSION GENERAL NOTES

1. THE FIRE PROTECTION SCOPE OF WORK INVOLVES MODIFICATIONS TO THE EXISTING FIRE SUPPRESSION SYSTEM SERVING THE ELEVATORS BEING RENOVATED.

2. SYSTEMS SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AS WELL AS THE FOLLOWING CODES AND STANDARDS:

CRITERIA IN VA-PG-18-10 FIRE PROTECTION DESIGN MANUAL (DECEMBER 2015)

IBC - INTERNATIONAL BUILDING CODE, 2018

NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION

NFPA 70 - NATIONAL ELECTRIC CODE, 2017 EDITION

NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE, 2019 EDITION

NFPA 101 - LIFE SAFETY CODE, 2018 EDITION

ASME A17.1 - SAFETY CODE FOR ELEVATOR AND ESCALATORS, 2016 EDITION

3. DRAWINGS ARE FOR REFERENCE PURPOSES ONLY. SHOP DRAWINGS ARE TO BE SUBMITTED FOR APPROVAL.

4. ALL MATERIALS AND EQUIPMENT USED FOR MODIFICATIONS SHALL BE NEW OR RELOCATED.

5. PRIOR TO PERFORMING WORK ON THE SPRINKLER SYSTEM, THE CONTRACTOR MUST FIELD LOCATE THE ZONE…