TVID_Waterline_Relocation_-_Plans.pdf
PDF 5 MB Posted
- Attached to
- NORTH PIPELINE LATERAL N1 RELOCATION AT NW MARTIN ROAD AND HWY 47 FOR TUALATIN VALLEY IRRIGATION DISTRICT
- Solicitation number
- 2021.165-ITQ
- Issued by
- Washington County, Oregon
About this file
These engineering design documents are for the North Pipeline Lateral N1 Relocation project for the Tualatin Valley Irrigation District (TVID) in Washington County, Oregon. The project involves relocating approximately 150 linear feet of 6-inch diameter asbestos cement waterline with 6-inch diameter restraint ductile iron pipe at the intersection of NW Martin Road and Highway 47. The design plans, prepared by murraysmith in November 2021, include five sheets covering project location maps, general notes, lateral plan and profile, civil details, and erosion and sediment control notes. The project scope requires the contractor to complete all work within 15 calendar days or by March 15, 2022, whichever occurs first.
The design documents specify detailed technical requirements for the waterline relocation, including provisions for utility coordination, potholing existing utilities, polyethylene pipe encasement, and specific installation methods. The project involves connecting to existing 6-inch asbestos cement water lines using transition couplings, installing vertical bends, and ensuring proper backfill and restoration of the site. Erosion and sediment control measures are extensively documented, with requirements for construction entrance, sediment fence installation, and maintenance of disturbed areas. The project is part of a Washington County roadway improvement project, with some related roadway and storm facility work to be completed by others.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH PIPELINE LATERAL N1
RELOCATION AT NW MARTIN
ROAD AND HWY 47
21-3117
NOVEMBER 2021
G P D
X P r o j e c t s
T u a l a t i n
V a l l e y
I r r i g a t i o n
D i s t r i c t M a r t i n
R o a d a t
H w y
C A D
S h e e t s O
R G d w g
G
A M
E L I J E F F E R S O
N s
L M
S
T e c h
888 SW 5TH AVENUE, SUITE 1170
PORTLAND, OREGON 97204
P 503.225.9010
INDEX OF DRAWINGS
LOCATION MAP
SCALE: 1"=500'
GENERAL
COVER SHEET, INDEX OF DRAWINGS, VICINITY AND LOCATION MAPS
GENERAL NOTES, ABBREVIATIONS, SYMBOLS AND LEGEND
G-1
G-2
PROJECT
LOCATION
CIVIL
LATERAL N1 PLAN AND PROFILE
CIVIL DETAILS
C-1
C-2
VICINITY MAP
SCALE: 1"=2000'
PROJECT
LOCATION
ATTENTION: OREGON LAW REQUIRES THE CONTRACTOR TO FOLLOW THE RULES
ADOPTED BY THE OREGON UTILITY NOTIFICATION CENTER. THOSE RULES ARE SET
FORTH IN OAR 952-001-0010 THROUGH OAR 952-001-0090. THE CONTRACTOR MAY
OBTAIN COPIES OF THE RULES BY CALLING THE UTILITY NOTIFICATION CENTER.
(NOTE: THE TELEPHONE NUMBER FOR THE OREGON UTILITY NOTIFICATION CENTER
IS 503-246-6699.)
THIS DESIGN COMPLIES WITH ORS 92.044 (7) IN THAT NO UTILITY INFRASTRUCTURE
IS DESIGNED TO BE WITHIN ONE (1) FOOT OF A SURVEY MONUMENT LOCATION
SHOWN ON A SUBDIVISION OR PARTITION PLAT. NO DESIGN EXCEPTION NOR FINAL
FIELD LOCATION CHANGES SHALL BE PERMITTED IF THAT CHANGE WOULD CAUSE
ANY UTILITY INFRASTRUCTURE TO BE PLACED WITHIN THE PROHIBITED AREA.
CORNELIUS
U
S
O A K
S T
FOREST GROVE
P A C
IF
IC
A
V E
N
W
R
T
I
R
D
Know what'sbelow.
Call before you dig.
P O
R T E R
R D
O A K
S T
FOREST GROVE
P A C
IF
IC
A
V E
R
T
R T E R
R D
24TH AVE
22ND AVE
EROSION CONTROL
EROSION AND SEDIMENT CONTROL NOTES AND DETAILSESC-15
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
G P D
X P r o j e c t s
T u a l a t i n
V a l l e y
I r r i g a t i o n
D i s t r i c t M a r t i n
R o a d
A t
H w y
C A D
S h e e t s O
R G d w g
G
T T E S T E P s
L M
S
T e c h
SHEET
0 1
21-3117
G-2
NOVEMBER 2021
NORTH PIPELINE LATERAL N1
RELOCATION AT NW MARTIN
ROAD AND HWY 47
AS SHOWN
of 5
GENERAL NOTES, ABBREVIATIONS,
SYMBOLS AND LEGEND
BDF
JSD
BVO
1. THIS WORK IS BEING PERFORMED IN RESPONSE TO A WASHINGTON COUNTY ROADWAY
IMPROVEMENT PROJECT. THE DISTRICT WATER LATERAL IS BEING RELOCATED IN ORDER TO
MAINTAIN ADEQUATE COVER AND TO ALLOW FOR FUTURE MAINTENANCE OF DISTRICT FACILITIES.
2. THE CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS OF ORS 757.542 TO 757.562. THE
CONTRACTOR SHALL NOTIFY EACH UNDERGROUND UTILITY AT LEAST 48 BUSINESS DAY HOURS
PRIOR TO EXCAVATING, BORING, OR POTHOLING.
3. NO ADDITIONAL PAYMENT SHALL BE MADE FOR UTILITY RELOCATION COORDINATION OR DELAYS
CAUSED BY UTILITY CONFLICTS. ALL COSTS RELATED TO UTILITY COORDINATION AND RELOCATION, INCLUDING ADDITIONAL POTHOLING, ARE TO BE CONSIDERED INCIDENTAL AND INCLUDED IN THE
PRICE OF THE BID.
4. UTILITIES OR INTERFERING PORTIONS OF UTILITIES THAT ARE ABANDONED IN PLACE SHALL BE
REMOVED BY THE CONTRACTOR TO THE EXTENT NECESSARY TO ACCOMPLISH THE WORK. THE
CONTRACTOR SHALL PLUG OR CAP THE REMAINING EXPOSED ENDS OF ABANDONED UTILITIES.
5. PROVISIONS SHALL BE MADE BY THE CONTRACTOR TO KEEP ALL EXISTING UTILITIES IN SERVICE
AND TO PROTECT THEM DURING CONSTRUCTION. CONTRACTOR SHALL PROPERLY DIVERT ALL STORM
FLOWS AS NECESSARY TO ACCOMPLISH WORK. CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE
CONSTRUCTION DOES NOT INCREASE DITCH OR OVERLAND FLOWS OR FLOODING RISKS.
6. EXISTING AND PROPOSED UTILITY LOCATIONS AND ELEVATIONS ARE SHOWN ON THE PROFILES
(SEE GENERAL NOTE 3). LEADER LINES SHOW ONLY THE APPROXIMATE HORIZONTAL LOCATION OF
THE UTILITY AND DO NOT INDICATE OR IMPLY AN APPROXIMATE DEPTH OR ELEVATION OF THE
UTILITY UNLESS THE UTILITY IS ACTUALLY SHOWN AND/OR AN INVERT ELEVATION IS INDICATED.
7. LOCATIONS OF EXISTING UTILITIES ARE BASED ON INFORMATION SUPPLIED BY UTILITIES. AS
REQUIRED BY STATE LAW, THE CONTRACTOR SHALL OBTAIN UTILITY LOCATES PRIOR TO
COMMENCING CONSTRUCTION. DEFLECT PIPE AS REQUIRED AND WITHIN SPECIFIED AND
MANUFACTURER'S TOLERANCES TO AVOID EXISTING UTILITIES AND TO COMPLETE TIE-INS.
8. BASEMAPPING PROVIDED BY OTHERS. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY
BASEMAPPING CONFLICTS OR DISCREPANCIES FOR RESOLUTION.
9. ALL EXISTING CASINGS, PIPE, VALVES AND FITTINGS TO BE ABANDONED SHALL BE REMOVED AS
SHOWN AND AS DIRECTED BY THE ENGINEER. PIPES ARE TO BE REMOVED AND DISPOSED OF AT THE
CONTRACTOR'S EXPENSE. GROUT PLUGS SHALL BE WATER TIGHT AND EXTEND 12 INCHES INTO
PIPES OR AS SPECIFIED. DUCTILE IRON CAPS SHALL BE RESTRAINED. ALL RESULTING TRENCHES
BENEATH PROPOSED PAVEMENT, SIDEWALKS, OR STRUCTURES SHALL BE BACKFILLED AND
COMPACTED WITH GRANULAR MATERIAL AS SPECIFIED. TRENCHES IN OTHER AREAS SHALL BE
BACKFILLED AND COMPACTED WITH SELECT NATIVE MATERIAL.
10. ALL BURIED GASKETS AND BURIED RUBBER FOR PIPES, VALVES, FITTINGS, COUPLINGS, AND
SPECIALS TO BE NITRILE BUTADIENE RUBBER WITHOUT EXCEPTION, SEE SPECIFICATIONS.
11. ALL CONCRETE TO BE 3000 PSI MINIMUM 28-DAY COMPRESSIVE STRENGTH UNLESS OTHERWISE
SPECIFIED.
12. FINAL LOCATIONS OF ALL AIR RELIEF VALVES, WATER MAIN GUARD POSTS, AND TEST STATIONS
SHALL BE FIELD LOCATED BY ENGINEER.
13. ALL PIPING, VALVES, TEES, BENDS, FITTINGS, AND NEW SERVICE INSTALLATIONS COMPLETE TO
BE RESTRAINED JOINT UNLESS OTHERWISE SPECIFICALLY IDENTIFIED. R RESTRAINED JOINT; SP
STANDARD PUSH-ON JOINT. R STATIONS AT ENDS OF RESTRAINED PIPE SECTIONS IDENTIFY
MINIMUM RESTRAINED LENGTHS FROM FITTING OR DEAD END. MAINTAIN MINIMUM RESTRAINED
LENGTHS. PROFILES INDICATE RESTRAINED JOINT AND STANDARD PUSH-ON JOINT FOR PIPING, VALVES AND FITTINGS.
14. CONTRACTOR SHALL PROVIDE TEMPORARY TAPS, BLOW-OFFS AND THRUST RESTRAINT AS
REQUIRED TO FACILITATE FLUSHING AND TESTING OF WATER LINE.
15. CONTRACTOR TO OBTAIN AND COMPLY WITH COUNTY AND STATE PERMITS AND REQUIREMENTS
FOR WORK IN AND RESTORATION OF ROADWAYS.
16. SURVEY DATA HAS BEEN COMPILED BASED ON THE FOLLOWING: HORIZONTAL DATUM:
OREGON COORDINATE REFERENCE SYSTEM, PORTLAND ZONE NAD83 (2011) EPOCH 2010.00.
VERTICAL DATUM: NGVD29.
17. ALL PLANTERS, BUILDINGS, STRUCTURES, LOTS, SWALES, DITCHES, CURBS, SIDEWALKS, FENCES, WALLS, MAILBOXES, SIGNS, GUY WIRES, PIPING AND UTILITIES DISTURBED DURING
CONSTRUCTION SHALL BE RESTORED TO EXISTING CONDITION UNLESS OTHERWISE SPECIFIED.
18. PROVIDE POLYETHYLENE ENCASEMENT IN ACCORDANCE WITH ANSI/AWWA C105/A21.5 FOR ALL
METALLIC PIPING AND SERVICE LINES WITHIN 10'-0" OF AN EXISTING GAS MAIN AND AS OTHERWISE
SPECIFIED. CONTRACTOR TO COORDINATE WITH GAS COMPANY FOR MOVING/DEFLECTING GAS
MAINS AS REQUIRED.
19. CONTRACTOR SHALL PLACE 5 MIL PLASTIC SHEETING BETWEEN THRUST BLOCKS AND PIPE
FITTINGS.
20. CONTRACTOR SHALL INSTALL THE NECESSARY EROSION AND SEDIMENT CONTROL BMP'S
REQUIRED TO CONTAIN ALL SEDIMENT LADEN WATERS ONSITE. BMP MATERIALS AND INSTALLATION
METHODS SHALL CONFORM TO CLEAN WATER SERVICES STANDARDS.
21. CONTRACTOR TO PROTECT AND MAINTAIN ALL EXISTING STORM WATER FACILITIES AND
STRUCTURES INCLUDING OUTFALLS, RIPRAP, AND INLETS. ANY DAMAGE TO STORM WATER
FACILITIES SHALL BE REPLACED AT CONTRACTOR EXPENSE.
GENERAL NOTES
RESTRAINED PIPE JOINT & FITTINGS
N
SELECT NATIVE BACKFILL
G
SELECT GRANULAR BACKFILL
R
STANDARD PUSH PIPE JOINT & FITTINGS SP
SHEET FROM WHICH
DETAIL IS TAKEN *
SHEET WHERE SECTION
IS SHOWN *
SECTION AND DETAIL DESIGNATIONS
SECTION DESIGNATIONS DETAIL DESIGNATIONS
SCALE:
DETAIL
A
SCALE:
SECTION
A
* NOTE: IF PLAN AND SECTION FOR DETAIL CALL-OUT AND DETAIL ARE SHOWN
ON THE SAME DRAWING, DRAWING NUMBER IS REPLACED WITH A DASH.
SECTION LETTER
DESIGNATION
SHEET FROM WHICH
SECTION IS TAKEN *
SECTION LETTER
DESIGNATION
DETAIL
NUMBER
VALVE
CHAIN LINK FENCE
SURFACE ELEVATION
SIDEWALK
176.63 176.63
AIR RELEASE ASSEMBLY
TREE DECIDUOUS
FIRE HYDRANT ASSEMBLY
PULL BOX/JUNCTION BOX
CATCH BASIN/FIELD INLET
LIGHT POST
BENCHMARK
SIGN
WATER METER
CLEAN-OUT
GUY WIRE
THRUST BLOCK
UTILITY POLE
MANHOLE
PROPOSED
STRUCTURE OR FACILITY
EDGE OF PAVEMENT/AC
CONTOUR MINOR
TREE/BUSH LINE
SANITARY SEWER LINE
DRAINAGE DITCH
SANITARY SEWER FORCE MAIN
EASEMENT/PROPERTY LINE
ROCK WALL
CONTOUR MAJOR
CURB
GUARDRAIL
CULVERT
CENTERLINE
STORM DRAIN
CABLE TELEVISION
TELEPHONE/TELEMETRY
TOPOGRAPHIC LEGEND
GAS
WATERLINE
EXISTING
S/W
TREE TO BE REMOVED
X
MAILBOX
ABANDON PIPE
EDGE OF GRAVEL
TREE CONIFEROUS
RIGHT-OF-WAY
TEMPORARY SILT FENCE
12"DI W
10"W
E
4"G
T
CATV
8"SS
6"FM
8"SD
E
4"G
T
CATV
8"SS
6"FM
8"SD
18"D
ELECTRICITY UNDERGROUND
ELECTRICITY OVERHEAD
OVHD
REMOVE PIPE/ STRUCTURE
& AND
@ AT
AC ASBESTOS CEMENT
APPROX APPROXIMATE
ARV AIR RELEASE VALVE
AVE AVENUE
AWWA AMERICAN WATER WORKS ASSOCIATION
BMP BEST MANAGEMENT PRACTICE
BPA BONNEVILLE POWER ADMINISTRATION
CL CLASS
C/L CENTER LINE
CMP CORRUGATED METAL PIPE
CONC CONCRETE
CONN CONNECTION
CPLG COUPLING
DEFL DEFLECTION
DI DUCTILE IRON
DIA DIAMETER
ELEV ELEVATION
EXIST EXISTING
FIN FINISHED
G GAS
GALV GALVANIZED
GR GRADE
GV GATE VALVE
HWY HIGHWAY
IE INVERT ELEVATION
INSTL INSTALL
IPS IRON PIPE SIZE
MAX MAXIMUM
MATL MATERIAL
MIN MINIMUM
MJ MECHANICAL JOINT
NO. NUMBER
ORIG ORIGINAL
OVHD OVERHEAD
% PERCENT
PROP PROPOSED
PVC POLYVINYL CHLORIDE
RD ROAD
REQ'D REQUIRE
SD STORM DRAIN
SLP SLOPE
SS SANITARY SEWER
ST STREET
STA STATION
STL STEEL
TRANS TRANSITION
TYP TYPICAL
US UNITED STATES
VERT VERTICAL
W WATER
W/ WITH
ABBREVIATIONS
SYMBOLS
6"AC W
P
V
C
S
D
C
O
C
O
C
O
C
C
S
S
C
O
S
D
C
O
S
D
P
P
C
O
6"AC W
A1+00
A2+00
6"DI W
STA A1+00
CONNECT TO EXIST 6"AC W
FURNISH & INSTALL:
1-6" AC/DI TRANS CPLG
(ROMAC STYLE 501),
SEE NOTES 3 AND 4
STA A2+58
CONNECT TO EXIST 6"AC W
FURNISH & INSTALL:
1-6" AC/DI TRANS CPLG
(ROMAC STYLE 501),
SEE NOTES 3 AND 4
6" AC W
6" AC W
0+00 0+20 0+40 0+60 0+80 1+00 1+20 1+40 1+60 1+80 2+00 2+20 2+40 2+60 2+80 3+00 3+20 3+40 3+60 3+80
EXIST GR @
C/L PIPE
PROP GR
@ C/L PIPE
(BY OTHERS)
E X I S T
C O
N C
S S
S E E
N
O T E
E X I S T
C M
P
S D
E X I S T
W
E X I S T
G
E X I S T
P V C
S S
OVHD BPA
E
X
I
T
X
I
X I S T
A R V
X
R
D
I
C
L
W
S
L
P
F
F
T
SLP=-0.041 FT/FT
SLP=-0.240 FT/FT
SLP=-0.041 FT/FT
S
L P
F T F T
S L P
F T F T
REMOVE AND DISPOSE OF EXIST AC W, SEE NOTE 6
S T A
A
C O
N N
E C T
X I S T
A C
W
I E
A P P R O
X
C O
N F I
E V
S E E
N
O T E
S T A
A
F U
R N
I
H
S T A L L
V E R T
B E N
D
M
J
I E
S T A
A
F U
R N
I
H
S T A L L
V E R T
B E N
D
M
J
I E
S T A
A
V E R T
D
E F L
U
P
I E
S T A
A
C O
N N
E C T
T O
E X I S T
A C
W
I E
A P P R O
X
C O
N F I
E V
S E E
N
O T E
E X I S T
C O
N C
S S
G
E X I S T
P V C
S D
S E E
N
O T E
E X I S T
C O
N C
S S
E X I S T
C O
N C
S S
M I N
T Y P
10'
MIN
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
G P D
X P r o j e c t s
T u a l a t i n
V a l l e y
I r r i g a t i o n
D i s t r i c t M a r t i n
R o a d
A t
H w y
C A D
S h e e t s O
R C d w g
C
T T E S T E P s
L M
S
T e c h
SHEET
0 1
21-3117
C-1
NOVEMBER 2021
NORTH PIPELINE LATERAL N1
RELOCATION AT NW MARTIN
ROAD AND HWY 47
AS SHOWN
of 5
LATERAL N1 PLAN AND PROFILE
BDF
MBE
BVO
SCALE: 1"=20'
PLAN
SCALE: 1"=20' HORIZ, 1"=5' VERT
PROFILE
NOTES:
1. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE RESTRAINED WITH AN
APPROVED JOINT RESTRAINT SYSTEM, SEE SPECIFICATIONS.
2. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE POLYETHYLENE ENCASED, SEE
SPECIFICATIONS.
3. CONTRACTOR TO CONFIRM OUTSIDE DIAMETER OF EXISTING ASBESTOS CEMENT
PIPE PRIOR TO ORDERING TRANSITION COUPLINGS.
4. END CONNECTIONS TO EXISTING ASBESTOS CEMENT PIPE SHALL BE MADE AT AN
EXISTING JOINT UNLESS OTHERWISE APPROVED BY THE ENGINEER. CONTRACTOR
SHALL POTHOLE AND VERIFY EXACT TIE-IN LOCATIONS.
5. WHERE VERTICAL BENDS ARE NOT SPECIFIED, CONTRACTOR TO BEND/DEFLECT
PIPE TO ACHIEVE VERTICAL CURVES SHOWN. THE MAXIMUM ALLOWABLE
DEFLECTION SHALL NOT EXCEED 75% OF THE MAXIMUM INSTALLED DEFLECTION
ANGLE RECOMMENDED BY THE PIPE MANUFACTURER.
6. REMOVE AND DISPOSE OF ALL EXISTING ASBESTOS CEMENT PIPE AND
APPURTENANCES BETWEEN END CONNECTIONS.
7. PROPOSED GUARDRAIL INSTALLATION BY OTHERS ON EAST SIDE OF NW MARTIN
ROAD TO AVOID IMPACTS TO EXISTING ASBESTOS CEMENT WATER LATERAL.
8. CONTRACTOR TO PROTECT AND MAINTAIN EXISTING STORM WATER PIPE DURING
WATERLINE RELOCATION.
9. CONTRACTOR TO POTHOLE EXISTING SANITARY SEWER PIPE PRIOR TO STARTING
WATERLINE RELOCATION.
EXIST ARV
R
T
PROP ROADWAY AND
STORM FACILITY WORK TO
BE COMPLETED BY OTHERS
PROP GUARDRAIL INSTALLATION
BY OTHERS, SEE NOTE 7
SEE NOTE 8
SEE ESC NOTE 1
ESC NOTES:
1. CONTRACTOR TO INSTALL CONSTRUCTION ENTRANCE OFF OF US 47 TO
ACCESS THE SITE, SEE SHEET ESC-1.
2. CONTRACTOR TO SURROUND CONSTRUCTION FOOTPRINT FOR WATERLINE
RELOCATION WITH SEDIMENT FENCE, SEE SHEET ESC-1.
SEE NOTE 9
APPROX. WORK BOUNDARIES
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
G P D
X P r o j e c t s
T u a l a t i n
V a l l e y
I r r i g a t i o n
D i s t r i c t M a r t i n
R o a d
A t
H w y
C A D
S h e e t s O
R C d w g
C
T T E S T E P s
L M
S
T e c h
SHEET
0 1
21-3117
C-2
NOVEMBER 2021
NORTH PIPELINE LATERAL N1
RELOCATION AT NW MARTIN
ROAD AND HWY 47
AS SHOWN
of 5
CIVIL DETAILS
BDF
JSD
BVO
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
G P D
X P r o j e c t s
T u a l a t i n
V a l l e y
I r r i g a t i o n
D i s t r i c t M a r t i n
R o a d
A t
H w y
C A D
S h e e t s O
R E S C d w g
E S C
T T E S T E P s
L M
S
T e c h
SHEET
0 1
21-3117
ESC-1
NOVEMBER 2021
NORTH PIPELINE LATERAL N1
RELOCATION AT NW MARTIN
ROAD AND HWY 47
AS SHOWN
of 5
EROSION AND SEDIMENT CONTROL
NOTES AND DETAILS
BDF
EJJ
BVO
| Sheets and Views |
| 1 21-3117-OR-G - G-1 |
| 2 21-3117-OR-G - G-2 |
| 3 21-3117-OR-C - C-1 |
| 4 21-3117-OR-C - C-2 |
| 5 ESC-1 |
File details come from the government source that posted it. Updated .