30' -0" 45' -4" 50' -0"
125' -5"
3"
0"
9'
8"
19' -2" 10' -0" 19' -3" 10' -9" 30' -0" 36' -4"
9'
7"
8"
29' -1" 34' -11" 55' -11"
3" 5'
9"
0"
5"
3'
29' -1" 24' -5" 4' -2" 14' -9" 5' -8" 43' -4"
4'
0"
9'
4' -0"7' -3"3' -4"17' -2"28' -9"11' -0"9' -8"7' -7"8' -8"
0'
8"
4'
4'
7"
6"
9'
6" 4'
6"
6"
10' -5" 4' -5" 9' -2" 4' -1" 10' -1"
8'
7'
0"
6"
0"
10' -6" 5' -1" 7' -1"
7' -0"
7'
7'
7'
7'
7' -4"
7' -0" 7' -0" 7' -0" 7' -0"
5"
5'
4'
3' -11" 12' -5"
3'
1"
27' -9" 5' -11" 5' -11"
8'
2"
41' -5"5' -10"
4'
0"
1'
3" 9' -2" 18' -10"
F
F
F F
F
F F FF F
F FF F
F F
F
F
F
F
F F
F
F
F
F
F
F F
F
F F
RAMP DN
6"
1369 SF
CELL
620 SF
CELL
1660 SF
CELL
2424 SF
CELL
546 SF
MECH
24 SF
BATH
20 SF
FOYR
124 SF
STOR
70 SF
STOR
535 SF
KITC
904 SF
DINE
121 SF
ADMN
160 SF
HALL
500 SF
HALL
95 SF
ADMN
100 SF
ADMN
44 SF
BATH
101 SF
HCBA
321 SF
ADMN
92 SF
MECH
49 SF
STOR
136 SF
ADMN
124 SF
FOYR
417 SF
RECP
46 SF
ACON
72 SF
ADMN
73 SF
35 SF
JANC
61 SF
ADMN
440 SF
HALL
15 SF
BATH
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
50 SF
CELL
107 SF
HALL
151 SF
ADMN
71 SF
ADMN
70 SF
ADMN
118 SF
STOR
438 SF
ADMN
116 SF
HALL
51 SF
CELL
51 SF
CELL
51 SF
CELL
51 SF
CELL
30 SF
BATH
122 SF
HALL
113 SF
ENTR
21 SF
XRMP
246 SF
HALL
USAG Humphreys 1056 Floor 1
A B C D E F G H
REVIEWED BY DESIGNED BY
CHECKED BY O&M DIV.
SECURITY DIV.
FIRE SERV. DIV.
SAFETY OFC.
MASTER PLAN DIV. SUBMIT. DATE
USING AGENCY
CHIEF. ENGR. DIV
CA/CI BR. DESIGN BR.
SUBMITTED BY
PROJECT NO.
SCALE
DRAWING NO. REF. NO.
SUNGLIM ENGINEER & CONSTRUCTION CO., LTD.
BY CHK APVDDATESYMBOL ZONE DESCRIPTION
R E V I S I O N
N
1 2 3 4 5 6 7 8 9 10
K
B
C
D
E
F
G
H
J
A
SS
PI
PE
S
PA
CE
4572 4572 4572 4572 4572 4572 4572 4572 1524
15240137169144
38100
RECREATION
(BRAVO BLOCK)
SHOWER SHOWER
TOILET
TOILET
PI
PE
S
PA
CE
RECREATION
(ALPHA BLOCK)
MULTI PURPOSE ROOM
SHOWER TOILET
POST TRIAL
(CHARLIA BLOCK)
MECH.
ROOM
GUARD
LATR
CORRIDOR
JAN.
OFFICE
ISOLATION CELLS
PIPE SPACE
STOR
SHOWER
OFFICE
CORRIDOR
CORRIDOR
ISOLATION CELLS
CO
RR
ID
OR
CORRIDOR
ST
OR
INTERVIEW
TOILET
ADMINISTRATION
IS
OL
AT
IO
N
CE
LL
S
OFFICE
OFFICE
OFFICEOFFICE
OFFICE
OFFICE
OFFICE
CO
RR
ID
OR
CO
RR
ID
OR
PSB OFFICE
LOBBY
MECH.
ROOM
ARMS
STOR
STORAGE
KITCHEN
DINING AREA
CSB OFFICE
STORAGE
USAG HUMPHREYS, KOREA
INSTL AIR CONDITIONER IN PSB OFFICE AND PUT
CEILING WINDOW IN CLOSE CONFINEMENT, S-1056
V7-10002 & 4-3J
25 JUN. 2014
SCOPE OF WORK ("K" WORK)
1. REPLACE EXIST SPLIT TYPE AIR CONDITIONING UNIT.
(ISOLATION CELL, PSB OFFICE, CSB OFFICE & LOBY)
SEE PARTIAL FLOOR PLAN
SEE PARTIAL FLOOR PLAN
SEE PARTIAL FLOOR PLAN
SEE PARTIAL FLOOR PLAN
EXST GROUND FLOOR PLAN1
M1 SCALE = 1 : 200-
M2M1
M2M1
M3M1
M4M1
HP-001SHEET 5 OF 13
MECHANICAL
EXST GROUND FLOOR PLAN
AND SCOPE OF WORK
A B C D E F G H
REVIEWED BY DESIGNED BY
CHECKED BY O&M DIV.
SECURITY DIV.
FIRE SERV. DIV.
SAFETY OFC.
MASTER PLAN DIV. SUBMIT. DATE
USING AGENCY
CHIEF. ENGR. DIV
CA/CI BR. DESIGN BR.
SUBMITTED BY
PROJECT NO.
SCALE
DRAWING NO. REF. NO.
EP-001SHEET 6 OF 13
SUNGLIM ENGINEER & CONSTRUCTION CO., LTD.
BY CHK APVDDATESYMBOL ZONE DESCRIPTION
R E V I S I O N
USAG HUMPHREYS, KOREA
MECHANICAL
INSTL AIR CONDITIONER IN PSB OFFICE AND PUT
CEILING WINDOW IN CLOSE CONFINEMENT, S-1056
PARTIAL FLOOR PLAN
(ISOLATION CELLS & LOBBY)
ISOLATION
CELLS #1
PIPE SPACE
SHOWER
CORRIDOR
CORRIDOR
ISOLATION
CELLS #2
ISOLATION
CELLS #3
ISOLATION
CELLS #4
ISOLATION
CELLS #5
ISOLATION
CELLS #10
ISOLATION
CELLS #9
ISOLATION
CELLS #8
ISOLATION
CELLS #7
ISOLATION
CELLS #6
M2 SCALE = 1 : 100M1
EXST/REMOVAL FLOOR PLAN
V7-10002 & 4-3J
AS SHOWN25 JUN. 2014
ISOLATION
CELLS #1
PIPE SPACE
SHOWER
CORRIDOR
CORRIDOR
ISOLATION
CELLS #2
ISOLATION
CELLS #3
ISOLATION
CELLS #4
ISOLATION
CELLS #5
ISOLATION
CELLS #10
ISOLATION
CELLS #9
ISOLATION
CELLS #8
ISOLATION
CELLS #7
ISOLATION
CELLS #6
REMOVE EXST A/C UNIT
(IN-DOOR UNIT) REMOVE EXST A/C UNIT
W/CON'C PAD (OUT-DOOR UNIT)
M2 SCALE = 1 : 100M1
EXST/NEW FLOOR PLAN
(TYP. OF 3EA)
LOBBY
M2 SCALE = 1 : 100M1
EXST/NEW FLOOR PLAN
1321457245724572
T
TEMPERATURE CONTROLLER
D RL RG
D RL RG
D RL RG
RL
RG
D
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT INDOOR UNIT
CENTRAL
CONTROLLER
OUTDOOR INDOOR
M2 NOT TO SCALEM2
CONTROL DIAGRAM (EQUIP #1)
D : 20∅
RL : 12.7∅
RG : 6.35∅
D : 20∅
RL : 12.7∅
RG : 6.35∅
SEQUENCE OF OPERATION
CONTRACTOR SHALL INSTALL THE CONTROL HARDWARE TO PERFORM THIS SEQUENCE OF OPERATION. UNLESS OTHERWISE SPECIFIED, ALL INTEGRATED FUNCTIONS SHALL BE PROVIDED BY MANUFACTURER’S OPERATING MANUALS.
A. SYSTEM ON-OFF SWITCH THRU CONTROLLER
(1) ON: WITH THE CONTROLLER “ON-OFF-AUTO: SWITCH IN THE “ON POSITION, THE SYSTEM WILL START FAN AND IT SHALL
RUN CONTINOUSLY.
(2) OFF: WITH THE CONTROLLER “ON-OFF-AUTO” SWITCH IN THE “OFF” POSITION, THE SYSTEM WILL STOP.
(3) AUTO: WITH THE SIRELESS CONTROLLER “ON-OFF-AUTO” SITHCH IN THE “AUTO” POSITION. THE SYSTEM SHALL RUN
ACCORDING TO THE HEAT-COOL OPERATION OF THE THERMOSTAT.
B. HEAT-COOL OPERATION
(1) HEAT-COOL: “HEAT” OR “COOL” MODE SHALL BE AUTO CHANGED BY THE CONTROLLER.
C. SAFETIES
(1) THE UNIT SHALL RUN SUBJECT TO THE UNIT MANUFACTURER’S SAFETIES.
D. ZONE TEMPERATURE CONTROL
(1) THE HEAT PUMP BUILT-IN CONTROL SHALL CYCLE THE FAN TO MAINTAIN ROOM TEMPERATURE AT 24 DEGREE C (75 DEGREE F), ADJUSTABLE, THE TEMPERATURE SENSOR LACETED IN THE ROOMS SERVED SHALL MONITOR THE SPACE TEMPARAUTRUE.
A B C D E F G H
REVIEWED BY DESIGNED BY
CHECKED BY O&M DIV.
SECURITY DIV.
FIRE SERV. DIV.
SAFETY OFC.
MASTER PLAN DIV. SUBMIT. DATE
USING AGENCY
CHIEF. ENGR. DIV
CA/CI BR. DESIGN BR.
SUBMITTED BY
PROJECT NO.
SCALE
DRAWING NO. REF. NO.
EP-002SHEET 7 OF 13
SUNGLIM ENGINEER & CONSTRUCTION CO., LTD.
BY CHK APVDDATESYMBOL ZONE DESCRIPTION
R E V I S I O N
USAG HUMPHREYS, KOREA
MECHANICAL
INSTL AIR CONDITIONER IN PSB OFFICE AND PUT
CEILING WINDOW IN CLOSE CONFINEMENT, S-1056
PARTIAL FLOOR PLAN
(PSB OFFICE)
V7-10002 & 4-3J
AS SHOWN25 JUN. 2014
M3 SCALE = 1 : 100M1
EXST/REMOVAL FLOOR PLAN
PI
PE
S
PA
CEST
OR PSB OFFICE
REMOVE EXIST WINDOW TYPE
A/C UNIT & BLOCK-UP OPEN'G
PI
PE
S
PA
CEST
OR PSB OFFICE
M3 SCALE = 1 : 100M1
EXST/NEW FLOOR PLAN
D RL
RG
A B C D E F G H
REVIEWED BY DESIGNED BY
CHECKED BY O&M DIV.
SECURITY DIV.
FIRE SERV. DIV.
SAFETY OFC.
MASTER PLAN DIV. SUBMIT. DATE
USING AGENCY
CHIEF. ENGR. DIV
CA/CI BR. DESIGN BR.
SUBMITTED BY
PROJECT NO.
SCALE
DRAWING NO. REF. NO.
EP-003SHEET 8 OF 13
SUNGLIM ENGINEER & CONSTRUCTION CO., LTD.
BY CHK APVDDATESYMBOL ZONE DESCRIPTION
R E V I S I O N
USAG HUMPHREYS, KOREA
MECHANICAL
INSTL AIR CONDITIONER IN PSB OFFICE AND PUT
CEILING WINDOW IN CLOSE CONFINEMENT, S-1056
V7-10002 & 4-3J
AS SHOWN25 JUN. 2014
M4 SCALE = 1 : 100M1
EXST/REMOVAL FLOOR PLAN 2
M4 SCALE = 1 : 100M1
EXST/NEW FLOOR PLAN
MECH.
ROOM
ARMS
STOR
CSB OFFICE
REMOVE EXIST WINDOW TYPE
A/C UNIT & BLOCK-UP OPEN'G
2134 3251
MECH.
ROOM
ARMS
STOR
CSB OFFICE
M4 NOT TO SCALE-
REFREGERANT LIQUID PIPING DETAIL (TYP.)
OUTDOOR UNIT
FLEXIBLE PIPE CONNECTOR (TYP.)
MOISTURE INDICATOR AND SIGHT GLASS
FILTER DRYER
D
RGRL
VALVE (TYP.)
RL : 12.7∅
RG : 6.35∅
D : 20∅
PARTIAL FLOOR PLAN (CSB OFFICE)
AND REFRIGERANT LIQUID PIPING DETAIL
A B C D E F G H
REVIEWED BY DESIGNED BY
CHECKED BY O&M DIV.
SECURITY DIV.
FIRE SERV. DIV.
SAFETY OFC.
MASTER PLAN DIV. SUBMIT. DATE
USING AGENCY
CHIEF. ENGR. DIV
CA/CI BR. DESIGN BR.
SUBMITTED BY
PROJECT NO.
SCALE
DRAWING NO. REF. NO.
SC-001SHEET 9 OF 13
SUNGLIM ENGINEER & CONSTRUCTION CO., LTD.
BY CHK APVDDATESYMBOL ZONE DESCRIPTION
R E V I S I O N
USAG HUMPHREYS, KOREA
MECHANICAL
INSTL AIR CONDITIONER IN PSB OFFICE AND PUT
CEILING WINDOW IN CLOSE CONFINEMENT, S-1056
EQUIPMENT SCHEDULE AND
CON'C PAD DETAILS
V7-10002 & 4-3J
AS SHOWN25 JUN. 2014
ITEM NO. Q'TY DESCRIPTION
1 3 EA INVERTER TYPE INDOOR UNIT
INDOOR WALL MOUNTED UNIT FOR HEAT AND COOLING,
WIRE AND WIRELESS REMOTE COTROLLER
COOLING CAPACITY : 3.6KW (3,096KCAL/H)
HEATING CAPACITY : 4.0KW (3,440KCAL/H)
CONSUMPTION OF ELECTRICAL POWER : 0.021KW
ELEC. : 1PH, 220V, 60HZ
DIMENSION : 1,050W x 320H x 228D
"CARRIER MODEL #MMK-AP0123H" OR APPROVED EQUAL
1 EA INVERTER TYPE OUTDOOR UNIT
COOLING CAPACITY : 12.4KW (10,664KCAL/H)
HEATING CAPACITY : 12.5KW (10,750KCAL/H)
CONSUMPTION OF ELECTRICAL POWER (C/H) : 2.98KW / 2.82KW
ELEC. : 1PH, 220V, 60HZ
DIMENSION : 900W x 1,340H x 320D
"CARRIER MODEL #MCY-MAP0401HT2K" OR APPROVED EQUAL
2 1 EA INVERTER TYPE INDOOR AND OUTDOOR UNIT
INDOOR WALL MOUNTED UNIT FOR HEAT AND COOLING,
WIRELESS REMOTE CONTROLLER
COOLING / HEATING CAPACITY :
2,500W (2,151KCAL/H) / 2,800W (2,410KCAL/H)
CONSUMPTION OF ELECTRICAL POWER (C/H) : 0.78KW / 0.82KW
ELEC. : 1PH, 220V, 60HZ
DIMENSION :
INDOOR UNIT : 705W x 250H x 207D OUTDOOR UNIT : 780W x 550H x 290D
"CARRIER MODEL #CSV-Q071S" OR APPROVED EQUAL
3 1 EA INVERTER TYPE INDOOR AND OUTDOOR UNIT
INDOOR FLOOR MOUNTED UNIT FOR HEAT AND COOLING,
WIRELESS REMOTE CONTROLLER
COOLING / HEATING CAPACITY :
7,200W(6,195KCAL/H) / 8,200W(7,076KCAL/H)
CONSUMPTION OF ELECTRICAL POWER (C/H) : 2.3KW / 2.25KW
ELEC. : 1PH, 220V, 60HZ
DIMENSION :
INDOOR UNIT : 520W x 1,810H x 368D OUTDOOR UNIT : 900W x 820H x 320D
"CARRIER MODEL #CPV-Q185VW" OR APPROVED EQUAL
ITEM NO. Q'TY DESCRIPTION
4 1 EA INVERTER TYPE INDOOR AND OUTDOOR UNIT
INDOOR WALL MOUNTED UNIT FOR HEAT AND COOLING,
WIRELESS REMOTE CONTROLLER
COOLING / HEATING CAPACITY :
4,500W (3,872KCAL/H) / 5,500W (4,732KCAL/H)
CONSUMPTION OF ELECTRICAL POWER (C/H) : 1.41KW / 1.52KW
ELEC. : 1PH, 220V, 60HZ
DIMENSION :
INDOOR UNIT : 790W x 275H x 235D OUTDOOR UNIT : 780W x 550H x 290D
"CARRIER MODEL #CSV-Q115U" OR APPROVED EQUAL
150 (W1) 150
(D 1)
300 150
150 (W1) 150
WWF, 150x150-∅4.8x∅4.8
NFSM
M2M2
CONCRETE PAD PLAN1
SCALE = 1 : 30M2
SECTION DETAIL2
SCALE = 1 : 30M1 M2M2
(W)
(W)
(D
EQUIP.
NO.
EQUIPMENT DIMENSION
W1 D1
PAD DIMENSION
W D
1 900 320 1,200 620
780 290 1,080 5902
EQUIPMENT PAD SCHEDULE
UNIT : mm
25 CHAMFER
3 900 320 1,200 620
780 290 1,080 5904
EQUIPMENT SCHEDULE