TE-AE Mass Notification System Inspection Checklist.docx

DOCX document 13 KB Posted

Attached to
Fire Protection Services
Solicitation number
W91151-22-R-0002
Issued by

View the file

Other files

File Type Posted
TE-J Dry Sprinkler Systems Inventory.xlsx XLSX spreadsheet
TE-AG Water Supply Tank Inspection Checklist.docx DOCX document
TE-B Barracks 50 to 150 Devices Inventory.xlsx XLSX spreadsheet
TE-AI Clean Agent System Inspection Checklist.docx DOCX document
TE-AB Chemical System Inspection Checklist.docx DOCX document
TE-O Fire Pumps Inventory.xlsx XLSX spreadsheet
TE-G General Use Fire Alarm Systems Over 200000 SF Inventory.xlsx XLSX spreadsheet
TE-AK ITM FORT HOOD UFC TABLE 4-26-11.docx DOCX document
TE-AF Stand Pipe System Inspection Checklist.docx DOCX document
TE-A Barracks Under 50 Devices Inventory.xlsx XLSX spreadsheet
TE-I Wet Sprinkler Systems Inventory.xlsx XLSX spreadsheet
TE-Z Fire Door Inspection Checklist.xlsx XLSX spreadsheet
TE-T Clean Agent Systems Inventory.xlsx XLSX spreadsheet
TE-R Mass Notification Inventory.xlsx XLSX spreadsheet
TE-N Foam Systems Inventory.xlsx XLSX spreadsheet
TE-H Vehicle Maintenance Facilities Fire Alarm Systems Inventory.xlsx XLSX spreadsheet
TE-C Barracks 151 to 300 Devices Inventory.xlsx XLSX spreadsheet
TE-AA Fire Pump Test Checklist.xlsx XLSX spreadsheet
TE-S Water Supply Tanks Inventory.xlsx XLSX spreadsheet
TE-Q Chemical Systems Inventory.xlsx XLSX spreadsheet
TE-P Fire Doors Inventory.xlsx XLSX spreadsheet
TE-M Stand Pipe Systems Inventory.xlsx XLSX spreadsheet
TE-K Deluge Systems Inventory.xlsx XLSX spreadsheet
TE-L Preaction Systems Inventory.xlsx XLSX spreadsheet
TE-F General Use Facilities Fire Alarm Systems Inventory.xlsx XLSX spreadsheet
TE-E Barracks Over 1000 Devices Inventory.xlsx XLSX spreadsheet
TE-D Barracks 301 to 1000 Devices Inventory.xlsx XLSX spreadsheet
TE-AD Fire Alarm System Inspection Checklist.docx DOCX document
TE-AC Sprinkler System Inspection Checklist.docx DOCX document
Attachment 1 - PWS Fire Protection 2022-2027 V1.docx DOCX document
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL EXHIBIT AE

MASS NOTIFICATION SYSTEM INSPECTION CHECKLIST

Building #:Contact Person:Phone#:
Has Contact Person Been Notified of Test: YesNoTime:
Has Ft. Hood Fire Dept Been Notified: YesNoTime:
Testing/Inspection Conducted By:NICET# Date:

System Information:

Panel Manufacturer:

System Monitoring:

Is this system monitored: Yes No If yes, type of transmitter?

SYSTEM TESTS AND INSPECTION *

TEST RESULTSComments:
QTY PASSEDQTY FAILED

Button Stations

LOC

Remote Mic Speaker/Strobes ______ ______ _______________________ Speakers Strobes Cluster Horn ______ ______ _______________________ Horn ______ ______ _______________________ Horn/Strobe ______ ______ _______________________

Mass Notification Panel

Functional Comments:

Lamps/LEDsYesNoN/A
FusesYesNoN/A
Trouble SignalsYesNoN/A
Zone DisableYesNoN/A
Supervisory SignalYesNoN/A
Ground FaultYesNoN/A

Microphone Yes___ No______ N/A______ ________________________

TransmitterYesNoN/A
BatteriesYesNoN/A

Other:

TECHNICAL EXHIBIT AJ

MASS NOTIFICATION SYSTEM INSPECTION CHECKLIST

Building #: Contact Person: Phone#:

POWER SUPPLIES

Primary (Main): Nominal Voltage:Amps:
Overcurrent Protection: Type:Amps:

Location of Primary Supply Panel:

Has Lockout Been Provide: YesNoIs Circuit Breaker Labeled: YesNo
Secondary:Battery Amp-Hour Rating:

Calculated Battery Back-up Capacity in Hours:

Backup Generator Providing Power to Mass System: YesNo
System Restored to Normal Operation: Date:Time:

Inspectors Signature:

* ALL DEFICIENCIES MUST BE FULLY EXPLAINED ON COMMENT/DEFICIENCY PAGE

COMMENTS/DEFICIENCIES