TE 1 Annex H Facility Maintenance Maintenance of Fort Lee Elevators.docx
DOCX document 88 KB Posted
- Attached to
- Elevator Maintenance and Repair Federal contract opportunity
- Solicitation number
- W91QF5-22-R-0005
About this file
This is a combined synopsis and solicitation for elevator maintenance and repair services at Army Garrison Fort Lee in Virginia. The contractor will be responsible for inspecting, repairing, and maintaining elevators and related equipment at over 475 buildings on the installation. Key requirements include monthly preventative maintenance for each elevator, responding to service calls within four hours, and completing all repairs within five working days. The base period of performance is one year from April 2022 to March 2023, with four optional one-year extensions. The solicitation is set aside for small businesses with a NAICS code of 238290 and size standard of $16.5 million. Quotes are due February 24, 2022 and the contract will be awarded to the lowest priced technically acceptable offer.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Elevator Maintenance Checklist TE 7.docx | DOCX document | |
| Question 2 Elevator Responses.docx | DOCX document | |
| ADDENDUM TO FAR 52.212-1.docx | DOCX document | |
| Site Visit Information.docx | DOCX document | |
| Question 1 Elevator Responses.docx | DOCX document | |
| Section I - Solicitation Clauses Fort Lee Elevator Maintenance revised v1.docx | DOCX document | |
| Section F CLINs.pdf | ||
| Annex A-Overarching PWS Template Maintenance of Fort Lee Elevator Sys..docx | DOCX document | |
| (TE 2) BaseMap - Site Map Main Post.pdf | ||
| (TE 3) EO 13834 (TE 3).doc | DOC document | |
| Section M- Evaluation_Factor_Attachment_FAR PART 12-13 v1.docx | DOCX document | |
| Technical Exhibit 6 Building List TE6.pdf | ||
| (TE 4) Environmental_Special_Conditions 2018.pdf | ||
| Technical Exhibit 5 Annual test TE5.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment TE 1
Facility Maintenance – Vertical
Maintenance of Fort Lee Elevators
07 January 2021
Table of Contents
| 1.0 | General Information | 1 |
| 1.1 | Overview | 1 |
| 1.1.1 Diagnosis and Analysis | 2 | |
| 1.2 | Components | 2 |
| 1.3 | Work Management and Control | 2 |
| 1.3.1 Reporting Requirements | 2 | |
| 1.3.2 Publications and Forms | 3 | |
| 1.3.3 | Facilities Maintenance Instruction | 3 |
| 2.0 Description of Services | 3 | |
| 2.1 Facility Workload | 3 | |
| 2.1.1 BUILDER Sustainment Management System. | 3 | |
| 2.2 Natural Gas Appliance and Equipment | 3 | |
| 2.3 Heating, Ventilation, and Air Conditioning (HVAC) | 3 | |
| 2.3.1 General | 4 | |
| 2.3.2 Seasonal Changeover Requirements | 4 | |
| 2.3.3 Chemical Treatment | 4 | |
| 2.3.4 Building Operations Center | 4 | |
| 2.4 Eye Washes and Safety | 4 | |
| 2.5 Roof Gutters, Drains, and Downspouts | 4 | |
| 2.6 Automatic Doors | 4 | |
| 2.7 Overhead Doors | 4 | |
| 2.8 Gates and Dock Levelers | 4 | |
| 2.9 Air Compressors/Unfired Pressure Vessels | 4 | |
| 2.10 Plumbing | 4 | |
| 2.10.1 Components | 4 | |
| 2.10.2 Leaks | 4 | |
| 2.10.3 Sump Pumps | 5 | |
| 2.10.4 Hot Water Tanks | 5 | |
| 2.10.5 Backflow Preventors | 5 | |
| 2.10.6 Grease Traps. | 5 | |
| 2.10.7 Urinals | 5 | |
| 2.10.8 Wash facilities/racks | 5 | |
| 2.10.9 Oil Water Separators | 5 | |
| 2.11 Sanitary Wastewater Treatment and Collection System | 5 | |
| 2.12 Industrial Wastewater Treatment Plant (IWTP) | 5 | |
| 2.13 Heating/Cooling Plants | 5 | |
| 2.14 | Winterization and De-Winterization | 5 |
| 2.15 Chemical Treatment of Water Systems | 5 | |
| 2.16 | Lift Stations | 5 |
| 2.17 | Maintenance Cycles | 5 |
| 2.18 | Electrical. | 5 |
| 2.18.1 | General | 5 |
| 2.18.2 | Description of Equipment | 5 |
| 2.18.3 | Action After Maintenance or Repair | 6 |
| 2.18.4 | Emergency Fixtures | 6 |
| 2.19 Auxiliary Generators | 6 | |
| 2.19.1 Perform PM of Auxiliary Generators. | 6 | |
| 2.19.2 Temporary Generator. | 6 | |
| 2.20 Grounding Point Checks | 6 | |
| 2.20.1 Grounding Points, Lightning Protection and Cathodic Protection Maintenance. | 6 | |
| 2.21 Security Systems | 6 | |
| 2.22 Fire Alarm/Suppression Systems | 6 | |
| 2.22.1 Fire Alarm Systems | 6 | |
| 2.22.2 | Sprinkler and Hood Suppression Systems | 7 |
| 2.23 Playgrounds | 7 | |
| 2.24 PM for Barracks Buildings | 7 | |
| 2.24.1 Unscheduled Task. | 7 | |
| 2.24.2 Scheduled Tasks Scheduled Inspections. | 7 | |
| 2.25 | Elevator Maintenance. | 7 |
| 2.25.1 Elevator Inspection and Certification | 7 | |
| 2.25.2 Out of Service Time. | 7 | |
| 2.25.3 Preventive Maintenance Requirements and Scheduled Maintenance Requirements. | 7 | |
| 2.26 | Swimming Pools and Hot Tubs | 7 |
| 2.26.1 | Circulation, Heating, and Filtration Systems | 7 |
| 2.27 Keys and Locks | 7 | |
| 2.27.1 Key Control | 8 | |
| 2.27.2 Lock Combinations | 8 | |
| 2.28 Food Service Equipment (FSE) | 8 | |
| 2.29 Dining Facility (DFAC) Maintenance | 8 | |
| 2.29.1 General | 8 | |
| 2.29.1 Action After Maintenance or Repair | 8 | |
| 2.29.1 Lubricants | 8 | |
| 2.29.1 Contractor Provided Training | 8 | |
| 2.29.1 Reconfigurationof Fire Suppresion Systems | 8 | |
| 2.29.1 Weekly Inspections | 8 | |
| 2.29.1 Kitchen Exhaust Systems and Hoods | 8 | |
| 2.29.1 Maintenance/Inspection of Fire Suppression Systems | 8 | |
| 2.29.1 Pest Control | 8 | |
| 2.30 Crane and Load Scales Maintenance and Load Testin | 8 | |
| 2.30.1 General | 8 | |
| 2.30.2 Preventive Maintenance Plan | 8 | |
| 2.30.3 Crane Operator Training | 8 | |
| 2.30.4 Load Scales | 8 | |
| 2.31 Glass and Glazing | 8 | |
| 2.32 Aircraft Arresting System (ASS) | 8 | |
| 2.32.1 Certification and Training | 8 | |
| 3.0 | Work Capability Levels | 9 |
| 4.0 | Self-Help Program | 9 |
| 4.1 Scope of Services | 9 | |
| 4.2 Operation of Self-Help Supply Stores | 9 | |
| 4.2.1 Hours of Operation l | 9 | |
| 4.2.2 Location and Set up | 9 | |
| 4.3 Self-Help Training Plan | 9 | |
| 4.3.1 Scheduled Training | 9 | |
| 4.3.2 Training Certification | 9 | |
| 4.3.3 Additional Training Courses | 9 | |
| 4.4 Work Management and Control | 9 | |
| 4.4.1 Publications and Forms | 9 | |
| 4.4.2 Authorization | 9 | |
| 4.4.3 Facility Manager | 9 | |
| 4.5 Self-Help Center Warehousing | 9 | |
| 4.5.1 Labeling of Supplies | 9 | |
| 4.5.2 Supplies and Materials Inventory | 9 | |
| 4.6 Customer Identification and Record Keeping | 9 | |
| 4.7 Display Area | 9 | |
| 4.8 Issue of Items | 9 | |
| 4.8.1 Supplies and Materials | 10 | |
| 4.8.2 Tools and Equipment | 10 | |
| 5.0 | OPERATION AND MAINTENANCE OF ENERGY CONSERVATION SYSTEMS | 10 |
| 5.1 General | 10 | |
| 5.1.1 Replacement of Solar Panel | 10 | |
| 5.1.2 Roof Leaks | 10 | |
| 5.1.3 Occupancy Sensors | 10 | |
| 5.1.4 Replacement Standard | 10 | |
| 5.2 Preventive Maintenance Requirement | 10 | |
| 5.2.1 Monthly Inspections and Maintenance PV | 10 | |
| 5.2.2 Washing of Photo Voltaic Systems | 10 | |
| 5.2.3 Solar Day Lighting Electrical Systems | 11 | |
| 5.2.4 Sensor Adjustment. Adjustment | 11 | |
| 5.2.5 Efficient Upgrade | 11 | |
| 6.0 | SIGN SHOP OPERATIONS | 11 |
| 6.1 General | 11 | |
| 6.1.1 Sign Design | 11 | |
| 6.1.2 Type of Paint l | 11 | |
| 6.1.3 Traffic Sign Material Specification | 11 | |
| 6.1.4 Traffic Signs | 11 | |
| 6.1.5 Informational Signs | 11 | |
| 6.1.6 Directional Signs | 11 | |
| 6.1.7 Inspect and Survey | 11 | |
| 7.0 | Utility Systems | 11 |
| 7.1 Electric Distribution System | 11 | |
| 8.0 | Uninterruptible Power Supply (UPS Systems) | 11 |
| 9.0 | Area Lighting | 11 |
| 9.1 Traffic Controls General | 11 | |
| 9.2 Repair and Maintain Traffic Signals and Flashers | 11 | |
| 9.3 Preventive Maintenance Requirements | 11 | |
| 9.4 School Flashing Lights | 11 | |
| 9.5 Airfield Lights | 12 | |
| 10.0 Utility Marking | 12 | |
| 11.0 Pumps and Pumping Stations | 12 | |
| 12.0 Natural Gas and Propane Distribution System | 12 | |
| 13.0 Propane Tanks and Distribution Systems | 12 | |
| 14.0 Water Distribution Systems | 12 | |
| 14.1 Secondary System | 12 | |
| 14.2 Water Lines | 12 | |
| 14.3 Backflow Prevention Program | 12 | |
| 14.4 Wastewater Collection System | 12 | |
| 14.5 Mains and Service Lines | 12 | |
| 14.6 Replacing Pipe | 12 | |
| 14.7 Sewage Lift Station for Septic Systems | 12 | |
| 14.8 Manholes | 12 | |
| 14.9 Sanitary System Maintenance | 12 | |
| 14.10 Ordinances | 12 | |
| 14.11 The Contractor shall perform the work IAW the following | 12 | |
| 15.0 Storm Water Collection System | 12 | |
| 15.1 Provide and Install storm drain markers | 12 | |
| 15.2 Inspect storm drains and gutters | 12 | |
| 15.3 Excavation and Backfilling | 13 | |
| 15.4 Excavation and Backfilling Barricades | 13 | |
| 15.5 Storm Water Collection Main Repair | 13 | |
| 15.6 Catch Basins | 13 | |
| 15.7 Storm Sewers/System | 13 | |
| 16.0 Preventive Maintenance | 13 | |
| 16.1 Maintain the Storm Water Collection System | 13 | |
| 16.2 Schedule and Inspect Storm Water Collection System | 13 | |
| 16.3 Storm Sewers | 13 | |
| 16.4 Notice of Storm Drainage Service Disruption | 13 | |
| 16.5 Compliance | 13 | |
| 16.6 The Contractor shall perform the work IAW the following | 13 | |
| 17.0 Reporting Requirements | 13 | |
| 17.1 Current Storm Water Management Plan | 13 | |
| 17.2 Installation Storm Water Management Plan (SWMP) | 13 | |
| 17.3 Storm Water Management System Maintenance Plan (SWMSMP) | 13 | |
| 17.4 Storm Water Management System Maintenance Inspection Form | 13 | |
| 17.5 Integrated Contingency Plan (ICP) for Spill Control and Response | 13 | |
| 17.6 Safeguard the Wastewater and Storm Water Systems | 13 | |
| 17.7 Certified Plant Operator | 13 | |
| 17.8 Cleaning and Inspection Logs | 14 | |
| 18.0 Training | 14 | |
| 19.0 Certification | 14 | |
| 20.0 Other Utility Systems | 14 | |
| 21.0 Fuel Storage and Distribution Systems | 14 | |
| 21.1 Monthly and Annual Inspections on Above Ground Tanks | 14 | |
| 22.0 Fuel-Powered Pump Maintenance | 14 | |
| 23.0 Emergency/Backup Generators | 14 | |
| 24.0 Other Water Distribution Systems | 15 | |
| 25.0 Water Standpipes | 15 | |
| 26.0 Other Sanitary Wastewater Collection Systems | 15 | |
| 27.0 Fireloop System Hydrants | 15 | |
| 27.1 Flow Testing | 15 | |
| 27.2 Backflow Preventers | 15 | |
| 28.0 Training of Personnel | 15 | |
| 28.1 Licenses | 15 | |
| 28.2 Water Stop Boxes | 15 | |
| 28.3 Water Testing and Disinfecting | 15 | |
| 29.0 Monitoring Systems | 15 | |
| 30.0 Golf Courses | 16 | |
| 31.0 Athletic Fields | 16 |
Annex H (CLS 411 Facilities Maintenance Vertical) to OPORD 18-011: IMCOM Enterprise Base Operations (BASOPS) Performance Work Statement (PWS) Templates (U)
1.0 General Information.
| 1.1 | Overview. The Contractor shall inspect, repair and maintain all existing buildings elevators and their components listed in Facilities List (TE 6, Real Property per Category Code (CATCODE) Unit of Measure). |
| a. | The following paragraphs describe all facets involved in the management of building and structure maintenance; they include terms used to classify work; provide information on the level of effort that will be required at Fort Lee in terms of workload and trade distributions; and describe the way in which work will be received, managed, and documented. The contractor is responsible for the maintenance and repair of all buildings elevators (TE 6, Real Property per Category Code (CATCODE) Unit of Measure). Work will include elevators and other trades that relate to the maintenance and repair of real property facilities. The Contractor shall perform both PMOs Preventive Maintenance and DMOs on all real property listed in TE 6. |
| b. | There is a wide variety of facilities at Fort Lee with a wide variety of installed equipment. Although other sections of this PWS detail the requirements for some of these types of equipment, all of this real property installed equipment for buildings elevators is the responsibility of the contractor. |
| 1.1.1 | Diagnosis and Analysis. The Contractor shall provide follow-up analysis and diagnosis of equipment failure as requested or shown in section 1.1.1 (b) |
| a. | The primary aim is to identify the factors that contributed to and/or resulted in the failure of maintenance, service, repair and/or operation of real property, infrastructure, and systems at Fort Lee, and to identify and implement actions to prevent repeated future failure due to the same failure reasons. The contractor shall: |
| i. | Provide a detailed description and explanation of the failure |
| ii. | Identify the root cause or causes of the problem |
| iii. | Provide possible actions and solutions to prevent future occurrences, an explanation of the pros and cons of these actions, a cost analysis of these actions, and the contractor’s recommended action |
| iv. | The selection and implementation of the appropriate action |
| v. | Review, documentation, and analysis of the outcome |
| vi. | Change in procedures, training, PWS, etc. as needed |
| b. | The Contractor shall provide additional analysis or diagnosis when: |
| i. | Directed by the Contracting Officer (KO), Contracting Officer Representative (COR). |
| ii. | After catastrophic, unusual, or unforeseen events that result in adverse maintenance, repair, and service requirements |
1.2 Components. The Contractor shall perform preventive maintenance (PM) and repairs. Facilities and components covered under this Common Level of Support (CLS) include, but are not limited to, the following:
a. Dining Facilities
b. Administrative buildings
c. Training facilities
d. Childcare facilities
e. Medical facilities and clinics
f. Schools, chapels, and recreational facilities
g. Childcare facilities
h. Installed building equipment
1.3 Work Management and Control.
1.3.1 Reporting Requirements. The Contractor shall furnish, with each invoice submitted, reports on the condition of the equipment monthly and provide annual reports. Reports shall be submitted electronically to KO/COR within five (5) business days after the end of the month in which the work was performed. Each report shall include a resume of the services performed by the Contractor, parts replaced, and deficiencies noted that will require future corrections and recommendations relative to methods for improving the operational effectiveness of the equipment. Specific equipment items will be clearly identified in the report. The format of the report is subject to approval of the Contracting Officer. On a monthly basis, the Contractor shall provide the monthly/annual maintenance checklist (TE 7) for each elevator serviced/maintained during the past month. This report shall include any deficiencies noted and shall be submitted electronically to the Contracting Officer Representative (COR). The Contractor shall reproduce as many copies of Technical Exhibit 7 as necessary at his own expense, for use during performance of this contract requirement.
All repairs and parts that are incidental to normal continuous and safe operation of the listed systems are covered by this contract.
1.3.1.1 Service Plan.
a. Within 30 calendar days of the start of the contract, the Contractor shall submit electronically to the KO/COR a Service Plan organized by Functional Area. The Service Plan shall describe all preventive maintenance services to be performed and their frequencies as reflected by this Contract, standard operating procedures/orders, and proposed staffing. As part of the Service Plan, the Contractor shall submit detailed management plans for high risk utility systems (elevators). These management plans shall include, at a minimum, specific maintenance tasks and frequencies, specific instructions for accomplishment of tasks, required special tools and equipment, personnel requirements, safety requirements, emergency procedures, personnel training requirements, and documentation procedures. The Contractor shall submit the plan annually for Contracting Officer approval.
b. Snow and Ice Removal. N/A
c. Freeze Plan. N/A
1.3.1.2 Emergency Utilities Operating Procedures. N/A
| 1.3.1.3 | Other Emergency Services to include, but not be limited to: N/A |
| • | Command-Directed operations support N/A |
| • | Natural disasters N/A |
| • | Emergency work for the security or protection of Government property N/A |
| • | Emergency work due to loss of operation of kitchen equipment N/A |
| • | Emergency work due to a malfunction in fire alarm or fire sprinkler systems N/A |
| • | Response to emergency DMOs N/A |
1.3.2 Publications and Forms. See Annex A—Overarching Performance Work Statement (PWS) paragraphs 2 and 2.1
1.3.3 Facilities Maintenance Instruction. N/A
2.0 Description of Services. The Contractor shall develop and implement (after KO/COR approval) a Comprehensive PM and Repair Program. PM consists primarily of inspection, cleaning, lubrication, adjustment, calibration, and minor part and component replacement on building elevators, its component equipment included at facilities which are listed in TE 6 Real Property per Category Code (CATCODE) Unit of Measure IAW the PM tasks. The Contractor shall submit the Comprehensive PM and Repair Program for this service within 30 days after receipt of approval to start. Work that is outside the scope of a PMO shall be accomplished through a DMO.
2.1 Facility Workload. N/A
2.1.1 BUILDER Sustainment Management System. N/A
2.2 Natural Gas Appliance and Equipment. N/A
2.3 Heating, Ventilation, and Air Conditioning (HVAC). N/A
2.3.1 General.N/A
2.3.1.1 Work Area/System Description. N/A
2.3.1.2 Inventory List. N/A
2.3.1.3 Work Performance. N/A
2.3.1.4 High Occupancy and Critical Facilities.
2.3.1.4 Priority 1 DMOs. N/A
2.3.1 Seasonal Changeover Requirements. N/A
2.3.2 Chemical Treatment. N/A
2.3.3 Building Operations Center. N/A
2.3.4.1 System Controls. N/A
2.3.5 Related Components and Accessories. N/A
2.4 Eye Washes and Safety Showers. N/A
2.5 Roof Gutters, Drains, and Downspouts. N/A
2.6 Automatic Doors. N/A
2.7 Overhead Doors. N/A
2.8 Gates, fences, barriers and Dock Levelers. N/A
2.9 Air Compressor Maintenance & Repair. N/A
2.9.1 Refrigerated Air dryer. N/A
2.9.2 Compressor storage tanks. N/A
2.10 Plumbing. N/A
2.10.1 Components. N/A
2.10.2 Leaks. N/A
2.10.2.1 Gas Leaks. N/A
2.10.3 Sump Pumps and Septic Tanks. N/A.
2.10.4 Hot Water Tanks. N/A
2.10.5 Backflow Preventors. N/A
2.10.6 Grease Traps. N/A
2.10.7 Urinals. N/A
2.10.8 Wash facilities/racks. N/A
2.10.9 Oil Water Separators. N/A
2.11 Sanitary Wastewater Treatment and Collection System (Septic Tanks). N/A
2.12 Industrial Wastewater Treatment Plant (IWTP). N/A.
2.13 Heating/Cooling Plants. N/A
2.14 Winterization and De-Winterization. N/A
2.15 Chemical Treatment of Water Systems. N/A
2.16 Lift Stations. N/A
2.17 Maintenance Cycles. N/A
2.18 Electrical. N/A
2.18.1 General. N/A
2.18.2 Description of equipment. N/A
2.18.3 Action After Maintenance or Repair. N/A
2.18.4 Emergency Fixtures. N/A
2.19 Auxiliary Generators. N/A
2.19.1 Perform PM of Auxiliary Generators. N/A
2.19.2 Temporary Generators. N/A
2.20 Grounding Point Checks. N/A
2.20.1 Grounding points, Lighting Protection and Cathodic Protection Maintenance. N/A
2.21 Security Systems. N/A
2.22 Fire Alarm/Suppression Systems. N/A
2.22.1 Fire Alarm Systems. N/A
2.22.1.1 Turnover/Fire Testing Schedule. N/A
2.22.1.2 Preventive Maintenance Requirements N/A
| a. | N/A |
| b. | N/A |
| c. | N/A |
| d. | N/A |
2.22.2 Sprinkler and Hood Suppression Systems. N/A
2.22.3 The Contractor shall perform the work IAW the following: N/A
a. National Fire Protection Association
b. UFC 3-600-01
c. UFC 3-601-02
d. Environmental Laws and Directives
e. AR 420-1
f. Manufacturer’s Specifications and Instructions
g. National Fire Codes (NFPA 17, 17A, 25, 96, 2001)
h. Federal, State and Local EPA Requirements
2.23 Playgrounds. N/A
2.24 PM for Barracks Buildings. N/A
2.24.1 Unscheduled Tasks. N/A
2.24.2 Scheduled Tasks Scheduled Inspections. N/A
2.25 Elevator Maintenance. The contractor shall inspect, test, repair and maintain all elevators, stairwell lifts and escalator at the facilities on Ft. Lee, Virginia. A list of facilities with elevators and escalator is at TE 6, List of Facilities with Elevators. The Contractor shall coordinate directly with the COR for scheduling of all work and access to the buildings and elevators.
2.25.1 Elevator Inspection and Certification. Inspection and testing shall be performed with a Contractor-provided certified inspector. Inspection and testing shall be IAW the following:
a. State of Virginia Department of Licensing and Regulatory Affairs for Elevators
b. ASME A17.1, A17.2, A17.3, (State of Virginia)
c. NFPA standards
d. National Electrical Codes (NEC)
e. Certificate of Elevator Inspection GSA Form 55 and Acknowledgment of Elevator Inspection Certificate GSA Form 55A or a form approved by KO/COR (TE 5), Certificate of Elevator Inspection GSA Form 55 and 55-A)
The Contractor shall obtain an annual State of Virginia elevator certificate of operation. The Contractor shall post a notice inside each elevator noting the date of the completed annual certification and note that certificates are on file and available upon request. The Contractor shall create a schedule of inspection, testing, maintenance, repair and certification within 30 days of the contract start date and submit to the KO/COR/ACOR for approval. The Contractor shall coordinate any scheduled shutdown with the affected building occupants after written approval is provided by the KO/COR/ACOR. In the event that an unscheduled shutdown of an elevator occurs, the Contractor shall notify the KO/COR/ACOR within two (2) hours.
2.25.1.2 For any elevators located in Virginia, licensing and regulatory requirements apply.
2.25.2 Out of Service Time. Elevators shall not be out of service for more than 24 hours at any one time. When parts are ordered, the KO/COR will be notified on the status and due delivery date. If the Contractor knows that the elevator is going to be down more than seven calendar days, the KO/COR shall be informed in writing/email detailing the specific problem and indicating why the elevator will be down for more than seven days. The Contractor shall post a Status of Repairs on the elevator door indicating the “repair by” date.
Emergency Service Calls. In the case of an elevator being shut down between scheduled maintenance or if an emergency occurs, the Contractor shall respond to a service call from the Government within four (4) hours. The Government reserves the right to contract with other sources for services whenever the above time limit is exceeded. The Contractor shall provide emergency service after normal working hours seven (7) days a week including holidays. Calls will be made by the COR or the Fort Lee Designated Call Center for service required after duty hours. All service calls after normal duty hours and on weekends and holidays are Emergency Service Calls. The Contractor shall furnish the Contracting Officer and the COR with the names and telephone numbers of qualified maintenance personnel and company officials who can be contacted to respond to an emergency after normal duty hours. When called in under an emergency service call, the Contractor shall remain on site until the emergency has ended. Any repairs required to return the elevator to service after the emergency has ended shall be completed within five (5) working days. If the elevator cannot be returned to service, a written report/proposal shall be submitted to the COR by 11:00 AM the next working day describing the corrective action required to return the elevator to service.
2.25.3 Preventive Maintenance Requirements and Scheduled Maintenance Requirements. Includes monthly preventative maintenance; repairs; parts and supplies; inspections and reports. Monthly preventative maintenance includes but is not limited to the following: lubricate equipment, adjust parts and components, re-lamp signals, and examine all elevator equipment for optimum operation. All maintenance and work shall be performed in accordance with industry standards and equipment manufacturer’s specifications. The Contractor shall provide for each elevator; one (1) scheduled monthly Preventive Maintenance (PM)/Inspection per month and one (1) annual PM per year in accordance with (IAW) Technical Exhibit (TE) 7 for each elevator listed on TE 6. Monthly PM’s shall be performed on no more than six (6) elevators during any eight (8) hour period. The Contractor shall ensure an elevator mechanic is on site from 8:00 AM until 4:30 PM Mondays, Tuesdays, Thursdays and Fridays, except on federal holidays, to perform maintenance and respond to customer calls for repairs. All repairs shall be during regulars working hours. The Contractor shall also provide annual inspections in conjunction with their regularly scheduled PM’s on the elevator systems listed in TE 6. This work shall be performed in accordance with the Performance Requirement Summary which summarizes the services, associated standards, and the Acceptable Quality Levels (AQL). Contractor shall perform all repairs and provide all parts that are incidental to normal continuous and safe operation of the listed elevators. Parts and repairs not covered by this contract are the hoist way enclosures, hoist way vents, cab floor covering, main jack casing, cylinder, underground piping and connections. Projected annual workload for these contract requirements are presented in Technical Exhibit 4.
2.25.3.1 Periodic Inspections, Testing, and Reports. The Contractor shall perform annual inspection/testing and make a formal report in accordance with industry standards. Schedule for Annual inspections shall be submitted for approval to the KO/COR within 30 calendar days of the start of the contract. The Contractor shall also fill out DA Form 7485-R and submit the completed form to the KO/COR within 10 calendar days after completion of each Annual test. The Contractor shall perform Annual Testing and Certification of elevators IAW paragraph 2.25.1.
2.25.3.2 General PM Requirements. The following items shall be provided by the contractor to support the maintenance and repair services.
a. The Contractor shall keep each log book in the machine room of each elevator, maintain log book to include records of scheduled maintenance services, annual service, testing, service calls, repairs and parts replaced. Information shall contain description of work, dates, problems, and corrective measures taken, persons requesting services/repairs, time completed, and the name of the mechanics performing the work. The log book shall be hard bound. Existing log book may be continued if the book is in good condition. Retain previous log books and records in a binder or other suitable document container. Log books will become Government property.
Work covering routine cleaning and refinishing of the interior of cars and the exterior of hoist way doors and frames is not included in this contract. However, cleaning of equipment spaces, hoist ways, and daily cleanup of job sites in conjunction with preventative maintenance, inspection services, and repairs is included in this contract. Provide a metal waste can with cover in each elevator
2.26 Swimming Pools and Hot Tubs. N/A
2.26.1 Circulation, Heating, and Filtration Systems. N/A
2.27 Keys and Locks. N/A
2.27.1 Key Control. N/A
2.27.2 Lock Combinations. N/A
2.28 Food Service Equipment (FSE). See Section 2.29 below. N/A
2.29 Dining Facility (DFAC) Maintenance N/A
2.29.1 General. The Contractor shall perform maintenance and repair of dining facilities (DFAC) and food service equipment at Fort Lee. DFACs are Critical Facilities, work shall be coordinated with the DFAC manager to eliminate or minimize disruption of DFAC operations. A list of DFAC’s is in TE 6. Monthly hood wash shall be performed at the minimum of 25 days apart. N/A
2.29.2 Description of equipment. For each DFAC, the Contractor shall update and furnish to the KO/COR, two (2) copies of the Contractor updated DFAC equipment inventory list electronically using a spreadsheet format of installed DFAC Equipment within 30 calendar days of contract start and shall keep these lists current. The list shall include a preventive maintenance schedule for equipment (such as cleaning refrigeration coils, testing gas safety equipment, etc.). At a minimum, the preventive maintenance schedule shall include manufacturers recommended maintenance for equipment and NFPA 96 requirements. N/A
2.29.3 Action After Maintenance or Repair. After completion of a maintenance or repair task, the Contractor shall ensure that the equipment or area is safe, operational, and clean so that food preparation can commence without effort beyond normal by food service personnel. Contractor shall report results to the DFAC manager and the KO/COR. N/A
2.29.4 Lubricants. N/A
2.29.5 Contractor Provided Training. N/A
2.29.6 Reconfiguration of Fire Suppression Systems. N/A
2.29.7 Weekly Inspections. N/A
2.29.8 Kitchen Exhaust Systems and Hoods. N/A
2.29.9 Maintenance/Inspection of Fire Suppression System. N/A
2.29.10 Pest Control. N/A
2.30 Crane and Load Scales Maintenance and Load Testing. N/A
2.30.1 General. N/A
2.30.2 Preventive Maintenance Plan. N/A
2.30.3 Crane Operator Training. N/A
2.30.4 Load scales. N/A
2.31 Glass and Glazing. N/A
2.32 Aircraft Arresting System (AAS). N/A
2.32.1 Certification and Training. N/A
3.0 Work Capability Levels. N/A
4.0 Self-Help Program. N/A
4.1 Scope of Services. N/A
4.2 Operation of Self-Help Supply Stores.
4.2.1 Hours of Operation: N/A
4.2.2 Location and Set up. N/A
4.3 Self-Help Training Plan. N/A
4.3.1 Scheduled Training. N/A
4.3.2 Training Certification. N/A
4.3.3 Additional Training Courses. N/A
4.4 Work Management and Control.
4.4.1 Publications and Forms. N/A
4.4.2 Authorization. N/A
4.4.3 Facility Manager. N/A
4.5 Self-Help Center Warehousing. N/A
4.5.1 Labeling of Supplies. N/A
4.5.2 Supplies and Materials Inventory. N/A.
4.6 Customer Identification and Record Keeping. N/A
4.7 Display Area. N/A
4.8 Issue of Items. N/A
4.8.1 Supplies and Materials. N/A
4.8.2 Tools and Equipment. N/A
5.0 Operation and Maintenance of Energy Conservation Systems
5.1 General. N/A
5.1.1 Replacement of Solar Panel. N/A
5.1.2 Roof Leaks. N/A
5.1.3 Occupancy Sensors. N/A
5.1.4 Replacement Standard. N/A
5.2 Preventive Maintenance Requirements. N/A
5.2.1 Monthly Inspections and Maintenance PV. N/A
5.2.2 Washing of Photo Voltaic Systems. N/A
5.2.3 Solar Day Lighting Electrical Systems. N/A
5.2.4 Sensor Adjustment. N/A
5.2.5 Efficient Upgrade. N/A
6.0 Sign Shop Operations
6.1 General. N/A
6.1.1 Sign Design. N/A
6.1.2 Type of Paint. N/A
6.1.3 Traffic Sign Material Specification. N/A
6.1.4 Traffic Signs. N/A
6.1.5 Informational Signs. N/A
6.1.6 Directional Signs. N/A.
6.1.7 Inspect and Survey. N/A
7.0 Utility Systems. N/A
7.0.1 Electric Distribution System. N/A
8.0 Uninterruptible Power Supply (UPS) Systems. N/A
9.0 Area Lighting. N/A
9.1 Traffic Controls General. N/A
9.2 Repair and Maintain Traffic Signals and Flashers. N/A
9.3 Preventive Maintenance Requirements. N/A
9.4 School Flashing Lights. N/A
9.5 Airfield Lights. N/A
10.0 Utility Marking. N/A.
11.0 Pumps and Pumping Stations. N/A
12.0 Natural Gas and Propane Distribution System. N/A
13.0 Propane Tanks and Distribution Systems. N/A
14.0 Water Distribution Systems. N/A
14.1 Secondary System. N/A
14.2 Water Lines. N/A
14.3 Backflow Prevention Program. N/A
14.4 Wastewater Collection System. N/A
14.5 Mains and Service Lines. N/A
14.6 Replacing Pipe. N/A
14.7 Sewage Lift Station for Septic Systems. N/A
14.8 Manholes. N/A
14.9 Sanitary System Maintenance. N/A
14.10 Ordinances. N/A
14.11 The Contractor shall perform the work IAW the following: N/A
15.0 Storm Water Collection System. N/A
15.1 Storm Drain Markers. N/A
15.2 Inspect Storm Drains and Gutters. N/A
15.3 Excavation and Backfilling N/A
15.4 Excavation and Backfilling Barricades. N/A
15.5 Storm Water Collection Main Repair. N/A
15.6 Catch Basins. N/A
15.7 Storm Sewers/System. N/A
16.0 Preventive Maintenance. N/A
16.1 Maintain the Storm Water Collection System. N/A
16.2 Schedule and Inspect Storm Water Collection System. N/A
16.3 Storm Sewers. N/A
16.4 Notice of Storm Drainage Service Disruption. N/A
16.5 Compliance. N/A
16.6 The Contractor shall perform the work IAW the following: N/A
17.0 Reporting Requirements.
17.1 Current Storm Water Management Plan. N/A
17.2 Installation Storm Water Management Plan (SWMP). N/A
17.3 Storm Water Management System Maintenance Plan (SWMSMP). N/A
17.4 Storm Water Management System Maintenance Inspection Form. N/A
17.5 Integrated Contingency Plan (ICP) for Spill Control and Response. N/A
17.6 Safeguard the Wastewater and Storm Water Systems. N/A
17.7 Certified Plant Operator. N/A.
17.8 Cleaning and Inspection Logs. N/A
18.0 Training
18.1 Anti-Terrorism (AT) Level I Training.
IAW AR 525-13, Antiterrorism, all Contractor employees, including sub-contractor employees, requiring access to Army installations, facilities, or controlled access areas shall complete Antiterrorism (AT) Level I awareness training within 30 calendar days after contract start date or effective date of incorporation of the requirement into the contract, whichever applies. The Contractor shall submit certificates of completion for each affected contract employee and subcontractor employee to the KO or designated Government Representative/COR within 30 calendar days after completion of training by all employees and subcontractor personnel on a recurring annual basis. AT Level I awareness training is available at the following site: http://jko.jten.mil.
18.2 iWATCH Training.
The Contractor shall brief the local iWATCH program (training standards provided by the Rock Island’s ATO) to all of Contractor’s employees and associated subcontractors. This training is used to inform employees of the types of behavior to watch for and instruct employees to report suspicious activity to the Fort Lee, Police Department and the COR. The Contractor shall complete the training within 30 calendar days after contract award and within 30 calendar days of new employees commencing performance and send to the KO or designated Government representative/COR via both electronic and paper copy within 30 calendar days of completion.
18.3 Operational Security (OPSEC) Awareness Training.
IAW AR 530-1, Operations Security, Contractor employees shall complete Level I OPSEC Awareness training within 30 calendar days after contract award and within five (5) calendar days of new employees commencing performance. Completion certificates will be made available to Government within ten (10) business of completion or upon request from the Government. All Contractor personnel shall complete Level I OPSEC Awareness training annually. Level I OPSEC training is available at the following website: http://cdse.edu/catalog/elearning/GS130.html.
19.0 Certification. The Contractor shall inspect, repair, and maintain elevator systems and components associated with facilities listed in real property records as required throughout this contract utilizing properly trained, skilled, and qualified employees or subcontractor personnel. The Contractor shall furnish, in writing, to the Contracting Officer evidence of qualifications for each of his maintenance and service employees prior to commencing work under this contract. Mechanic’s qualifications shall consist of a recognized Commonwealth of Virginia Journeymans Licsense for the elevator industry followed by four (4) years of experience as a repair mechanic with an established company that has repaired and installed equipment of similar type to that covered under this contract. All employees assigned by the Contractor to perform the work under this contract shall be physically able to do the assigned work.
20.0 Other Utility Systems. N/A
21.0 Fuel Storage and Distribution Systems. N/A
21.1 Monthly and Annual Inspections on Above Ground Tanks. N/A
22.0 Fuel-Powered Pump Maintenance. N/A
23.0 Emergency/Backup Generators (not attached to building). N/A.
24.0 Other Water Distribution Systems. N/A
25.0 Water Standpipes. N/A
26.0 Other Sanitary Wastewater Collection Systems. N/A
27.0 Fireloop System Hydrants. N/A
27.1 Flow Testing. N/A.
27.2 Backflow Preventers. N/A
28.0 Training of Personnel. N/A
28.1 Licenses.
28.2 Water Stop Boxes. N/A
28.3 Water Testing and Disinfecting. N/A
29.0 Monitoring Systems. N/A
30.0 Golf Courses. N/A
31.0 Athletic Fields. N/A