Summary Report - Limited Hazardous Materials Assessment Marquette Armory (2022).pdf
PDF 2 MB Posted
- Solicitation number
- RFP - 171 - 220000002999
- Issued by
- Alger County, Menominee City, Michigan
About this file
This document is a Summary Report for a Limited Hazardous Materials Assessment conducted at the National Guard Armory in Marquette, Michigan. The assessment was performed by TriMedia Environmental & Engineering Services, Inc. on behalf of OHM Advisors in preparation for planned renovation activities at the armory. The assessment identified the presence of asbestos-containing materials, including thermal system insulation, floor tiles, and mastics, as well as lead-containing paint in various locations throughout the building. Estimated quantities of asbestos-containing materials range from 130 square feet to 1,500 linear feet. This information is intended to assist OHM Advisors in identifying hazardous materials that will need to be properly abated prior to the renovation project.
The report also notes that if vermiculite is found during the renovations, it must be treated as an assumed asbestos-containing material and managed in accordance with EPA and OSHA regulations. Additionally, any lead-containing paint must be properly addressed during demolition and disposal activities in accordance with MIOSHA requirements. This assessment does not constitute a waste characterization, and a separate waste characterization will be required prior to landfill disposal of any demolished building materials.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
830 W. Washington Street
Marquette, MI 49855
906.228.5125
906.228.5126 Fax
www.trimediaee.com
June 7, 2022
Sent Via Electronic Mail Tracie Williams, PE, LEED AP OHM Advisors 424 Hancock Street Hancock, Michigan 49930
Re: Summary Report – Limited Hazardous Materials Assessment at the National Guard Armory in
Marquette, Michigan TriMedia Project Number 2022-1270
Dear Ms. Williams:
TriMedia Environmental & Engineering Services, Inc. (TriMedia) has prepared this correspondence to summarize results of the limited Hazardous Materials Assessment (HMA) at the Marquette Armory.
The HMA was limited to the interior of the building as planned renovations are not set to impact exterior building materials. The intent of this information and data is to assist OHM Advisors in identifying hazardous materials related to proposed renovation activities. This correspondence also includes a summary of analytical laboratory results.
TriMedia was on-site on May 23, 2022 to conduct sampling to identify the presence of Asbestos- Containing Materials (ACM), metals-containing paint, and other hazardous materials within the identified building. The assessment is intended to identify building contaminants that, if mismanaged during renovation activities, could pose an environmental or health and safety concern. During the assessment, TriMedia identified suspect asbestos and lead-containing building materials.
ASBESTOS SURVEY
TriMedia collected a total of 23 interior samples (29 including sample layers) of suspect asbestos-containing materials to be submitted for laboratory analysis. Each suspect asbestos-containing material sampled was containerized in a laboratory-supplied sealable bag; labeled with a material description, sample location, and a unique sample number; and, shipped under chain of custody to EMSL Analytical, Inc., (EMSL) in Indianapolis, Indiana for analysis under EPA Method 600/R-93/116 utilizing polarized light microscopy techniques.
ASBESTOS RESULTS
Asbestos was detected at concentrations above the regulatory limit for asbestos-containing material in the following sampled materials:
OHM Advisors
Sample # Location Material Concentration Estimated Quantity*
Asb-001 Boiler Room Tank Insulation 15% Amosite 30% Chrysotile
130 SF
Asb-003 Boiler Room Steam Return TSI 50% Chrysotile
Approximately 350 LF of TSI and 65 elbows/fittings.
Asb-004 Boiler Room Elbow, Cold Water
35% Amosite
Asb-005 Boiler Room Fitting, Domestic Cold
25% Amosite 25% Chrysotile
Asb-006 Boiler Room Heat Return TSI 35% Chrysotile
Asb-007 Boiler Room Hot Water Heating Supply
10% Amosite
5% Chrysotile
Asb-008 Boiler Room Domestic Hot TSI 45% Chrysotile
Asb-009 Classroom
Brown Floor Tile & Black Mastic
5% Chrysotile & 3% Chrysotile
1000 SF including Classroom
Asb-011 Classroom
TSI 35% Chrysotile Estimated 250 LF and 20 Elbows between Classroom 125 & 126
Asb-015 Maintenance Bay
TSI 60% Chrysotile Appx 1500 LF
Asb-016 Facilities Office
TSI 55% Chrysotile Appx 120 LF & 20 elbows
Asb-021 Men’s Room TSI 55% Chrysotile Appx 20 LF
Asb-022 Men’s Shower TSI 25% Amosite Appx 50 LF
Asb-023 Entry Corridor Floor Mastic 2% Chrysotile Appx 1400 SF
*Estimated quantities are field estimates and are not meant for bidding purposes.
Complete analytical laboratory results have been enclosed for your records. Sampled materials, locations, and analytical results have been summarized in Table 1: Materials Sampled and Found to Not Contain Asbestos and Table 2: Materials Sampled and Found to Contain Asbestos.
Concrete Masonry Unit (CMU block) construction may contain vermiculite as insulating material.
TriMedia did not identify any vermiculite during the inspection. If vermiculite is found during renovations activities, it must be treated as an assumed ACM Per EGLE regulation. Vermiculite, as an assumed ACM by EGLE must be managed in accordance with provisions stipulated in Environmental Protection Agency (EPA) National Emissions Standards for Hazardous Air Pollutants (NESHAP) 40 CFR Part 61, Subpart M; and AHERA regulations promulgated in 40 CFR Part 763, Subpart E. In addition, OSHA and MIOSHA regulations regarding materials containing <1% asbestos may be applicable to vermiculite.
Roofing and exterior building materials were not sampled as part of the assessment. If renovation plans change and the exterior or roof will be impacted as part of the renovations, they must be sampled or treated as ACM.
METALS CONTAINING PAINT SURVEY
TriMedia collected 8 paint samples throughout the facility and included all layers of paint to the substrate. Samples were collected in laboratory supplied packages, given a unique sample identification number, and shipped under appropriate chain of custody to EMSL Analytical, Inc., (EMSL) in Indianapolis, Indiana. Paint samples were analyzed for lead content through EPA Method SW 846 7000B Flame Atomic Absorption Spectrophotometry.
METALS CONTAINING PAINT RESULTS
Analytical results detected the presence of lead in 3 paint samples ranging from 0.034% to 0.11%.
A summary of sampled materials and locations are provided in Table 3: Metals Containing Paint.
Complete analytical laboratory results of paint samples collected for lead have been enclosed for your records.
OTHER HAZARDOUS MATERIALS
Fluorescent Light bulbs: Approximately 480 fluorescent light bulbs and 40 halogen bulbs were identified in the building. Fluorescent light bulbs typically contain mercury and other trace hazardous materials. If lights are impacted/removed during the renovation activities, unbroken fluorescent light bulbs may be collected and disposed as universal waste.
Light Ballasts: Approximately 120 fluorescent light fixtures/ballasts and 40 halogen light ballasts were identified within the building. Light ballasts manufactured prior to January 1, 1979 may utilize oils containing PCBs. Light ballasts manufactured after January 1, 1979 are generally labelled as “non-PCB”. While TriMedia did not catalog each light fixture for non-PCB markings, all light ballasts that are not clearly marked as “Non-PCB” are must be assumed to contain PCBs and should be disposed of as PCB waste. Non-PCB light ballasts must be disposed of as electronics waste.
Smoke Detectors and Exit Signs and Thermostats: TriMedia identified 0 smoke detectors and 8 exit signs that potentially contain special waste (low activity radioactive material). Eight (8) thermostats which potentially contain mercury were observed throughout the building.
SUMMARY OF FINDINGS AND RECOMMENDATIONS
▪ TriMedia did not sample exterior building materials as part of this assessment.
▪ Asbestos was detected at regulated levels (> 1%) in the 14 of the 23 samples taken in the Marquette Armory. If planned renovations impact ACM they must be removed by a licensed asbestos abatement contractor prior to renovation.
▪ The presence of lead was detected in 3 paint samples.
▪ TriMedia estimates the presence of approximately 4,380 – 5,480 linear feet of asbestos containing thermal systems insulation in the Marquette Armory.
▪ TriMedia identified approximately 1,200 SF of 9x9 ACM floor tile found in classrooms 125 & 126.
▪ TriMedia identified approximately 2,500 SF of ACM floor mastic in classrooms 125 & 126 and the main corridor in the entrance of the Armory.
▪ Applicable state, federal and industry regulations for worker and environmental protection must be met when impacting metal-containing paint during building remodeling or demolition.
Specifically, MIOSHA Part 603 – Lead Exposure in Construction.
▪ Information regarding painted surfaces may be provided to contractors who may potentially impact the materials and to other entities who may take possession of the materials. Applicable state, federal and industry regulations for worker and environmental protection must be met when impacting metal-containing paint during building demolition. The State of Michigan has not established a numerical threshold defining “lead-containing paint”. All paint with detection of lead is considered “lead-containing” and there is no provision for recycling usage of concrete products coated with lead-containing paint. Metal bearing lead-containing paint may be recycled. All other materials coated with lead-containing paint, including CMU block, must be deposited in a landfill.
▪ This assessment does not constitute a waste characterization for disposal of demolished building materials. A waste characterization will need to be coordinated with the selected contractor prior to securing landfill disposal acceptance.
▪ All light fixture ballasts, bulbs, thermostats, and exit signs that are impacted by the building renovation should be removed prior to commencement of the renovation and recycled or properly disposed.
TriMedia made every reasonable attempt to access all areas of the building that are planned to be impacted by renovations. However, as with all hazardous material assessments, there exists the potential for discovering additional suspect materials not addressed by this report during renovation activities. In the event suspect materials are identified during on-site activities, they must be sampled before being disturbed or treated as ACM.
TriMedia can assist OHM with project planning, specification development, contractor selection, abatement oversight and air monitoring related to the renovation project. We look forward to the opportunity to assist as the project progresses.
It is hoped this Summary Report meets your needs and expectations. Should you have any questions regarding this correspondence, or the project in general, please do not hesitate to contact the undersigned at (906) 228-5125 or via email at tsorensen@trimedia.com. On behalf of the professional staff at TriMedia, thank you for the opportunity to be of continued service to OHM Advisors.
Sincerely, TriMedia Environmental & Engineering Services, LLC
Andrew Tripp Tim Sorensen Staff Industrial Hygienist Project Manager Asbestos Inspector A48290
AMT/trs/jet mailto:tsorensen@trimedia.com
Enclosures: Table 1: Materials Sampled and Found to Not Contain Asbestos Table 2: Materials Sampled and Found to Contain Asbestos Table 3: Metals-Containing Paint Photo Log EMSL Analytical Report – Asbestos EMSL Analytical Report – Metals Containing Paint cc: TriMedia Project File 2022-1270
Limitations: Information presented in this Summary Report was prepared for OHM Advisors and its authorized parties only.
Any use a third party makes of this report, or any reliance on or decisions to be made based upon, are the responsibility of such third party.
Table 1 Materials Sampled and Found to Not Contain Asbestos
Marquette Armory
TriMedia 2022-1270
Sample #
(Layers)* Material/Description
Asb-002 Boiler Elbow Large hard pack elbow
Asb-005 (1 of 2) Boiler Fitting Domestic cold wrap layer
Asb-010 Classroom 125 Wall Brown covebase and mastic
Asb-012 Corridor Wall Tan covebase and glue
Asb-013 Gym Floor underlayment Gym floor underlay
Asb-014 Maintenance bay Ceiling Ceiling insulation
Asb-017 Facilities office Drop ceiling tile
Asb-018 Bar/club Floor 12x12 off white floor tile
Asb-019 Range/locker room Ceiling Ceiling tile
Asb-020 Men’s room Ceiling Plaster
Asb-023 (1 of 2) Entry corridor Khaki floor tile layer
Location Details
*Material layers separated in lab - not able to be separated in field.
Table 2 Materials Sampled and Found to Contain Asbestos
Marquette Armory
TriMedia 2022-1270
Sample #
(Layers) Material/Description
Asbestos
Concentration Estimated Quantity
Asb-001 Boiler room Tank insulation
15% Amosite
30% Chrysotile 130 SF
Asb-003 Boiler Steam return TSI air cell 50% Chrysotile
Asb-004 Boiler Elbow Small elbow cold water pipe 35% Chrysotile
Asb-005 (1 of 2) Boiler Fitting Domestic cold
25% Amosite
5% Chrysotile
Asb-006 Boiler Heat return TSI air cell 35% Chrysotile
Asb-007 Boiler Hot water heating supply TSI
10% Amosite
25% Chrysotile
Asb-008 Boiler Domestic hot TSI 45% Chrysotile
Asb-009 (2) Classroom 125 Floor Brown 9x9 tile and black mastic layers
5% Chrysotile
2% Chrysotile*
1000 SF
(includes Rm 126)
Asb-011 Classroom 126 Corner into ceiling TSI 35% Chrysotile
250 LF and 20
Elbows between
Classroom 125 &
Asb-015 Maintenance bay TSI TSI 60% Chrysotile 1500 LF
Asb-016 Facilities office TSI 55% Chrysotile
120 LF
20 elbows
Asb-021 Bathroom TSI TSI 55% Chrysotile 20 LF
Asb-022 Men’s room TSI 25% Amosite 50 LF
Asb-023 (1 of 2) Entry corridor Khaki floor mastic layer 2.1% Chrysotile* 1400 SF
*Material layers separated in lab - not able to be separated in field.
Location Details
**Polarized Light Microscopy (PLM) - Point count performed by EPA 600/R93/116 Method with gravimetric reduction and 400 point count
350 LF of TSI and
65 elbows/fittings.
***Estimated quantities are field estimates and are not meant for bidding purposes.
Table 3 Metals Containing Paint
Marquette Armory
TriMedia 2022-1270
Sample # Color Lead
Concentration
Paint-001 Grey Boiler Floor 0.110%
Paint-002 Mint green paint with white base Boiler Wall <0.0080%
Paint-003 Light blue Classroom Wall <0.0080%
Paint-004 White paint Maintenance bay Wall entry <0.0080%
Paint-006 Pink Facilities office Wall <0.0080%
Paint-006 Paint layers grey/blue, light blue, tan Basement Handrail 0.065%
Paint-007 White with black layer Basement Wall 0.034%
Paint-008 Blue grey paint tan layer under Bar Club <0.0080%
Note: "<" (less than) result signifies that the analyte was not detected at or above the reporting limit.
Location
Marquette Armory
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-001
Description: Boiler Room - Tank
Insulation 15% Amosite and
30% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-002
Description: Boiler Room - Elbow ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-003
Description: Boiler Room Steam
Return TSI AirCell
50% Chrysotile
Photo Log
Hazardous Material Assessment
TriMedia Project 2022-1270 Page 1 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-004
Description: Boiler Room - Small
Elbow on Cold Water Pipe
35% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-005
Description: Boiler Room -Fitting
25% Amosite and 5% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-006
Description: Boiler Room - Heat
Return TSI Aircell
35% Chrysotile
Photo Log
TriMedia Project 2022-1270 Page 2 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-007
Description: Boiler Room - Hot water supply TSI
10% Amosite and 25% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-008
Description: Boiler - Domestic Hot TSI
- 45% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-009
Description: Classroom 125
9x9 Brown Floor Tile with Mastic
Layer 5% Chrysotile and 2%
Chrysotile
Photo Log
TriMedia Project 2022-1270 Page 3 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-010
Description: Classroom 125- Wall
Cove Base - ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-011
Description: Classroom 126 Corner
Pipe - TSI
45% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-012
Description: Corridor Tan Covebase -
ND
Photo Log
TriMedia Project 2022-1270 Page 4 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-013
Description: Gym Floor
Underlayment - ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-014
Description: Maintenance Bay Ceiling
Insulation - ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-015
Description: Maintenance Bay - TSI
60% Chrysotile
Photo Log
TriMedia Project 2022-1270 Page 5 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-016
Description: Facilities Office - TSI
55% Chrysotile
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-017
Description: Facilities Office Ceiling -
ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-018
Description: Bar/Club 12x12 Off
White Flooring - ND
Photo Log
TriMedia Project 2022-1270 Page 6 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-019
Description: Range/Locker Room
Ceiling Tile - ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-020
Description: Men's Room Ceiling
Plaster - ND
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-021
Description: Bathroom TSI
55% Chrysotile
Photo Log
TriMedia Project 2022-1270 Page 7 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-022
Description: Men's Room TSI
25% Amosite
Taken By: AMT
Date Taken: 5/23/2022
Sample: Asb-023
Description: Entry Cooridor Kahki
Floor Tile Layer - ND
Masitc Layer 2.1% Chrysotile
Photo Log
TriMedia Project 2022-1270 Page 8 of 8
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint -001
Description: Grey Paint Boiler Room
Floor 0.110% wt
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint -002
Description: Mint Green Boiler Room -below detection
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint-003
Description: Light Blue Classroom
Walls - below detection
Photo Log
TriMedia Project 2022-1280 Page 1 of 3
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint-004
Description: White Paint
Maintenance Bay - below detection
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint-006
Description: Basement Handrails
Layers - Grey/Blue, Light Blue/ Tan lead content 0.065 % wt
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint-006 Pink
Description: Facility Walls below detection
Photo Log
TriMedia Project 2022-1280 Page 2 of 3
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint-007
Description: Basement Wall
White with Black Layer
Lead Detection 0.034% wt
Taken By: AMT
Date Taken: 5/23/2022
Sample: Paint-008
Description: Blue Grey with Tan underlayer - below detection
Photo Log
TriMedia Project 2022-1280 Page 3 of 3
EMSL Analytical, Inc.
6340 CastlePlace Dr. Indianapolis, IN 46250
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162211497EMSL Order:
Customer ID: TRIC50
Customer PO:
Project ID:
Attention: Phone:Andrew Tripp (906) 278-5125
Fax:TriMedia Environmental & Engineering Svs (906) 228-5126
Received Date:830 W. Washington 05/25/2022 9:50 AM
Analysis Date:Marquette, MI 49855 05/27/2022
Collected Date:
Project: 2022-1270
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
Asb-001
162211497-0001
15%
30%
Amosite
Chrysotile
Non-fibrous (Other)35%Cellulose20%Gray/White
Fibrous
Homogeneous
Boiler Room - Tank
Insulation
Asb-002
162211497-0002
None DetectedNon-fibrous (Other)30%Cellulose
Glass
40%
30%
Gray/White
Fibrous
Homogeneous
Boiler Elbow - Large
Hard Pack Elbow
Asb-003
162211497-0003
50% ChrysotileNon-fibrous (Other)25%Cellulose25%Gray/White
Fibrous
Homogeneous
Boiler Steam Return -
TSI Air Cell
Asb-004
162211497-0004
35% AmositeNon-fibrous (Other)35%Cellulose30%Gray/White
Fibrous
Homogeneous
Boiler Elbow - Small
Elbow Cold Water
Pipe
Asb-005-Fitting
162211497-0005
25%
5%
Amosite
Chrysotile
Non-fibrous (Other)35%Cellulose35%Gray
Fibrous
Homogeneous
Boiler Fitting -
Domestic Cold
Asb-005-Wrap
162211497-0005A
None DetectedNon-fibrous (Other)2%Cellulose98%White
Fibrous
Homogeneous
Boiler Fitting -
Domestic Cold
Asb-006
162211497-0006
35% ChrysotileNon-fibrous (Other)65%Gray/White
Fibrous
Homogeneous
Boiler Heat Return -
TSI Air Cell
Asb-007
162211497-0007
10%
25%
Amosite
Chrysotile
Non-fibrous (Other)30%Cellulose35%Gray/Tan/White
Fibrous
Homogeneous
Boiler Hot Water
Heating Supply - TSI
Asb-008
162211497-0008
45% ChrysotileNon-fibrous (Other)40%Cellulose15%Gray/White
Fibrous
Homogeneous
Boiler Domestic Hot -
TSI
Asb-009-Floor Tile
162211497-0009
5% ChrysotileNon-fibrous (Other)95%Gray/Red
Non-Fibrous
Homogeneous
Classroom 125 Floor
- Brown 9x9 Tile
Black Mastic
Asb-009-Mastic
162211497-0009A
3% ChrysotileNon-fibrous (Other)97%Black/Yellow
Non-Fibrous
Homogeneous
Classroom 125 Floor
- Brown 9x9 Tile
Black Mastic
Asb-010-Cove Base
162211497-0010
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Classroom 125 Wall -
Brown Covebase and
Mastic
Asb-010-Mastic
162211497-0010A
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Classroom 125 Wall -
Brown Covebase and
Mastic
Asb-011
162211497-0011
35% ChrysotileNon-fibrous (Other)35%Cellulose30%Gray/White/Blue
Fibrous
Homogeneous
Classroom 126
Corner into Ceiling -
TSI
Asb-012-Cove Base
162211497-0012
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Corridor Wall - Tan
Covebase and Glue
Asb-012-Glue
162211497-0012A
None DetectedNon-fibrous (Other)100%Brown/Yellow
Non-Fibrous
Homogeneous
Corridor Wall - Tan
Covebase and Glue
Initial report from: 05/27/2022 17:05:57
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 5/27/2022 5:05 PM
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
6340 CastlePlace Dr. Indianapolis, IN 46250
Tel/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com / indianapolislab@emsl.com
162211497EMSL Order:
Customer ID: TRIC50
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
Asb-013
162211497-0013
None DetectedNon-fibrous (Other)45%Cellulose55%Brown/Black
Fibrous
Homogeneous
Gym Floor
Underlayment - Gym
Floor Underlay
Asb-014
162211497-0014
None DetectedNon-fibrous (Other)10%Glass90%Brown/Tan
Fibrous
Homogeneous
Maintenance Bay
Ceiling - Ceiling
Insulation
Asb-015
162211497-0015
60% ChrysotileNon-fibrous (Other)20%Cellulose20%Gray/White
Fibrous
Homogeneous
Maintenance Bay TSI
- TSI
Asb-016
162211497-0016
55% ChrysotileNon-fibrous (Other)15%Cellulose30%Gray/White
Fibrous
Homogeneous
Facilities Office - TSI
Asb-017
162211497-0017
None DetectedPerlite
Non-fibrous (Other)
10%
5%
Cellulose
Min. Wool
55%
30%
Gray/White
Fibrous
Homogeneous
Facilities Office - Drop
Ceiling Tile
Asb-018-Floor Tile
162211497-0018
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Bar/Club Floor -
12x12 Off-White Floor
Tile
Asb-018-Mastic
162211497-0018A
None DetectedNon-fibrous (Other)100%Black/Yellow
Non-Fibrous
Homogeneous
Bar/Club Floor -
12x12 Off-White Floor
Tile
Asb019
162211497-0019
None DetectedPerlite
Non-fibrous (Other)
10%
15%
Cellulose
Min. Wool
35%
40%
Gray/White
Fibrous
Homogeneous
Range/Locker Room
Ceiling - Ceiling Tile
Asb-020
162211497-0020
None DetectedQuartz
Non-fibrous (Other)
15%
85%
Gray/White
Non-Fibrous
Homogeneous
Men's Room Ceiling -
Plaster
Asb-012
162211497-0021
55% ChrysotileNon-fibrous (Other)15%Cellulose30%Gray/White
Fibrous
Homogeneous
Bathroom TSI - TSI
Asb-22
162211497-0022
25% AmositeNon-fibrous (Other)75%Gray/White
Fibrous
Homogeneous
Men's Room - TSI
Asb-023-Floor Tile
162211497-0023
None DetectedNon-fibrous (Other)100%Brown/White
Non-Fibrous
Homogeneous
Entry Corridor - Khaki
Floor Tile and Mastic
Asb-023-Mastic
162211497-0023A
2% ChrysotileNon-fibrous (Other)98%Black/Yellow
Non-Fibrous
Homogeneous
Entry Corridor - Khaki
Floor Tile and Mastic
Analyst(s)
Sydney Bell (29) Asbestos Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN NVLAP Lab Code 200188-0, AZ0939, CA 2575, CO AL-15132, TX 300262
Initial report from: 05/27/2022 17:05:57
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 5/27/2022 5:05 PM
Asb-021
JTresedder Highlight
JTresedder Highlight
JTresedder Highlight
6340 CastlePlace Dr., Indianapolis, IN 46250 Phone/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com indianapolislab@emsl.com
162211497 CustomerID: TRIC50 CustomerPO:
ProjectID:
EMSL Order:
Attn: Andrew Tripp TriMedia Environmental & Engineering Svs 830 W. Washington Marquette, MI 49855
Received: 05/25/22 9:50 AM
2022-1270
Fax: (906) 228-5126 Phone: (906) 278-5125
Project:
6/1/2022Analysis Date:
Collected:
SAMPLE ID APPEARANCE
NON- ASBESTOS
% NON-FIBROUS
(%) Matrix Organic Acid
ASBESTOS
% TYPESDESCRIPTION
NON- ASBESTOS
% Fibrous
Test Report: Polarized Light Microscopy (PLM) - Point Count Performed by EPA 600/R- 93/116 Method with Gravimetric Reduction and 400 Point Count
Asb-009-Mastic 162211497-0009A
Black/Yellow 61.0Classroom 125 Floor - Brown 9x9 Tile Black Mastic
Non-Fibrous Homogeneous
0.0 Chrysotile2.0Non-fibrous (other)37.0
Asb-023-Mastic 162211497-0023A
Black/Yellow 52.8Entry Corridor - Khaki Floor Tile and Mastic
Non-Fibrous Homogeneous
0.0 Chrysotile2.1Non-fibrous (other)45.1
Asbestos Laboratory Manager or other approved signatory
Test Report PLMPCGrav-7.26.0 Printed: 6/1/2022 3:17:12 PM 1
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Some samples may contain
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN NVLAP Lab Code 200188-0
Maggie Hayden (2)
Initial report from 06/01/2022 15:17:12 http://www.EMSL.com mailto:indianapolislab@emsl.com
OrderID: 162211497
OrderID: 162211497
JTresedder Typewritten Text
JTresedder Typewritten Text
ConcentrationAnalyzed Weight RDL LeadClient SampleDescription Collected
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
EMSL Analytical, Inc.
6340 CastlePlace Dr., Indianapolis, IN 46250 Phone/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com indianapolislab@emsl.com
Attn: Andrew Tripp TriMedia Environmental & Engineering Svs 830 W. Washington Marquette, MI 49855
Received: 5/25/2022 09:50 AM
2022-1270
Fax: (906) 228-5126 Phone: (906) 278-5125
Project:
Collected:
162211545 CustomerID: TRIC50 CustomerPO:
ProjectID:
EMSL Order:
Site: BOILER, FLOOR Desc: GREY
0.11 % wt5/26/2022 0.2533 g 162211545-0001
0.0080PAINT-001 % wt
Site: BOILER, WALL Desc: MINT GREEN PAINT WITH WHITE BASE
<0.0080 % wt5/26/2022 0.2521 g 162211545-0002
0.0080PAINT-002 % wt
Site: CLASSROOM, WALL Desc: LIGHT BLUE
<0.0080 % wt5/26/2022 0.2526 g 162211545-0003
0.0080PAINT-003 % wt
Site: MAINTENANCE BAY, WALL ENTRY Desc: WHITE PAINT
<0.0080 % wt5/26/2022 0.2513 g 162211545-0004
0.0080PAINT-004 % wt
Site: FACILITIES OFFICE, WALL Desc: PINK
<0.0080 % wt5/26/2022 0.2524 g 162211545-0005
0.0080PAINT-005 % wt
Site: BASEMENT, HANDRAIL Desc: PAINT LAYERS GREY/BLUE, LIGHT BLUE, TAN
0.065 % wt5/26/2022 0.2506 g 162211545-0006
0.0080PAINT-006 % wt
Site: BASEMENT, WALL Desc: WHITE WITH BLACK LAYER
0.034 % wt5/26/2022 0.2592 g 162211545-0007
0.0080PAINT-007 % wt
Site: BAR, CLUB Desc: BLUE GREY PAINT TAN LAYER UNDER
<0.0080 % wt5/26/2022 0.2521 g 162211545-0008
0.0080PAINT-008 % wt
Page 1 of 1Test Report PB w/RDL-2.0.0.0 Printed: 5/31/2022 8:22:11 AM
Aleksandrea Kuchenbrod, Inorganic Chemistry Lab Manager or other approved signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
* Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN AIHA-LAP, LLC-ELLAP 157245, OH E10040
Initial report from 05/31/2022 08:22:11 http://www.EMSL.com mailto:indianapolislab@emsl.com
OrderID: 162211545
OrderID: 162211545