STRUCTURAL FIRETRAINER SPECIFICATION AND SCOPE OF WORK - MSFA.pdf
PDF 1 MB Posted
- Attached to
- 1501-25-R-RFIN-00002
- Solicitation number
- 3150006366
- Issued by
- Hinds County, Jackson City, Mississippi
About this file
This technical specification document details a proposal by KFT Fire Trainer for a Structural Live Fire Training System for the Mississippi Fire Academy. The comprehensive proposal covers the design, fabrication, and installation of a full-scale fire training simulator with multiple fire scenario props, including a kitchen with flare-up features, double and twin bed props, couch prop, attic fire trainer, hallway flashover, and paint locker fire trainer. The system is designed to provide realistic fire training scenarios using LPG propane vapor, with advanced control systems, safety features, and wireless handheld controls that comply with NFPA 1402 (2019) standards.
The proposal includes a complete project scope covering design, manufacturing, installation, commissioning, documentation, and two days of operator training. KFT will provide five years of preventive maintenance with semi-annual visits, and offers a standard one-year warranty on parts and workmanship. The total project will be managed with milestone payments: 20% upon contract award, 20% at equipment delivery, 30% upon installation and commissioning, and 30% at project handover. The system is designed to be integrated into the existing burn building, with KFT responsible for extending fuel and electrical services to the new training props, and the Owner responsible for primary infrastructure like tank farms, main fuel supply, and electrical service panels.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| NEWSPAPER NOTICE OF INTENT TO CERTIFY SOLE SOURCE-KFT ADVERTISEMENT 2.docx | DOCX document | |
| NOTICE OF INTENT TO CERTIFY SOLE SOURCE KFT 2 LONG FORM.docx | DOCX document | |
| KFT QUOTE 160-9025V6.pdf | ||
| KFT-MFSA SOLE SOURCE JUSTIFICATION.pdf | ||
| SSD KFT 2025-2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TECHNICAL SPECIFICATION
KFT FIRETRAINER
STRUCTURAL FIRE TRAINING SYSTEM
Contents
1. Proposal Introduction
2. Specification for the Structural FireTrainer™
2.1. Systems Components
2.2. Mock-up Construction
2.2.1. Proposed Fireplace Details
2.2.1.1. Kitchen with Extensions and Flare Effect
2.2.1.2. Double Bed with Flashover/Rollover Effect
2.2.1.3. Twin Bed
2.2.1.4. Couch
2.2.1.5. Attic Fire Trainer
2.2.1.6. Hallway Flashover
2.2.1.7. Paint Locker Fire Trainer
2.3. Additional Information
2.3.1. Technical Rooms
2.3.2. Smoke Machines
2.3.3. Safety Systems
3. Fire Scenarios
3.1. Internal Fire Scenarios
4. Control System
4.1. Main Control Unit
4.1.1. Operator Authorization
4.1.2. Remote Access
4.1.3. System Diagnostics
4.1.4. Data Recording
4.2. Handheld Control Units
4.3. Trainer Flames
4.4. Pilot Ignition System
4.5. Combustion Air
4.6. Safety Systems
4.6.1. Emergency Stop Systems
4.6.2. Temperature Monitoring
4.6.3. Gas Detection
4.6.4. Exhaust Ventilation System
5. Civil Work
5.1. Service Trench/Ducts
5.2. Drainage System
6. Fuel Supply System
6.1. Fuel Delivery System
7. Main Power Supply System
7.1. Electrical System
8. Design and Project Management
8.1. Project Schedule
8.2. Manufacturing
8.3. Site Inspection
8.4. Shipping & Storage of Materials
9. Installation
10. Commissioning and Documentation
10.1. Hand Over Documentation
10.2. Training Course
11. Service and Warranty
11.1. Maintenance
11.2. Warranty
12. Relevant Standards and Regulations
13. Commercial Notes
13.1. Terms and Conditions
13.2. Exclusions
13.3. Offer Validity
13.4. Delivery
1. Proposal Introduction
KFT Fire Trainer (KFT) has the pleasure in providing an offer and specification for the supply and installation of a Structural Live Fire Training System as specified during multiple discussions with the Mississippi Fire Academy leadership and training staff.
KFT has successfully installed multiple Live Fire Training Systems in challenging configurations and we are proud to have the knowledge and expertise to fulfil the requirements of such projects. The KFT Live Fire Training System provides distinct design challenges, which we have been successful in overcoming on previous projects. You can be confident and assured that KFT has previous hands-on experiences of such projects and have reference sites for examination.
The Offer Price is based on the Clarifications and information obtained during the upgrade discussions with reference to the LPG Propane fuelled Internal Fireplaces and control system. We have therefore proposed a KFT proven FireTrainer™ System capable of Automatic or Manual Control with local wireless control.
The KFT FireTrainer™ system contains regulatory compliant control and safety systems using the latest generation of technology as described in this brief specification. The complete system will be constructed, assembled and fully tested to the industry’s highest standard.
KFT has a dedicated department covering all aspects of Customer post-sales support. We have a dedicated in-country US based customer support team. In addition to the dedicated US team, KFT is fortunate to be able to draw on support from other KFT offices around the world should the need arise. With unrivalled support systems in place, KFT is confident that in the unlikely event of an equipment failure, the KFT FireTrainer response will be immediate. The KFT Maintenance Department is contactable by Online Request, Telephone, Fax and Email. Action on site will depend on the problem whether it can be solved by remote intervention, user support or Technician visit.
When evaluating the fire training simulation equipment, we encourage you to fully review the type, quantity and quality of equipment that we have offered. As a company committed to the provision of only the highest quality of equipment, we confirm that our offer is fully compliant with the latest codes and regulations.
Failure to comply with the regulations will result in an unsafe installation that may result in failure and injury.
Not all simulators are the same and KFT’s quality and level of experience illustrates a full mission achieving solution capability, particularly related to the provision of field proven equipment within the region.
2. Specification for the Structural FireTrainer™
Based on the specification and clarifications, KFT is proposing to supply a series of Fire Training Mock-ups representative of your requirements to provide Live Fire Training in your existing burn building as required.
The following sections describe the equipment that KFT will be providing. KFT will fit out the Owner’s burn building with Fire Training Simulation Equipment, Control System, Safety System and features in accordance with the RFP requirements unless otherwise noted as Owner Supplied.
2.1. Systems Components
The following Table lists the Fire Trainers Offered by KFT per the Academy requirements.
Item Description Qty 1 Stove prop with flare up feature and overhead cabinet extension fire 1 2 Double bed with flashover 1 3 Twin bed prop 1 4 Sofa prop 1 5 Attic FireTrainer 1 6 New hallway flashover 1 7 New storage rack prop 1
Table 1
The following Table lists the non-fire Trainers Offered by KFT per the Academy requirements. The actual props and quantity to be decided.
Item Description Qty
1 Table prop 2 2 Chair prop 2 3 Cabinet props 2 4 Storage rack prop 2 5 Car prop 2
Table 2
2.2. Mock-up Construction
1) Fire props and mock-ups are constructed of heavy gauge corrosion resistant steel ("Cor-Ten" steel conforming to ASTM A-588) or stainless steel.
2) Steel dimensions, including thickness, are designed to provide support for the units and prevent deformation by heat from the training fires. Components will have the following minimum thicknesses:
a) Support legs, frame, etc.: 0.18" thick
b) Fire prop / mock-up panels: 12 gauge
c) Panels in areas with no heat: 14 gauge
d) Grates: 1-1/2" x 3/16" bars
e) Bolts: 3/8" diameter
3) Burner elements will be constructed of a minimum of 14 gauge 304 stainless steel.
4) Fire props and mock-ups are fully compatible with multiple extinguishing agents including water, foam, and compressed air foam.
5) All welds will meet American Welding Society (AWS) standards.
6) Exposed welds will be ground smooth.
7) Exposed edges of steel will be curved or ground smooth.
8) Trainers, fire props, and mock-ups are tested and adjusted at the factory prior to delivery. (Test reports available upon request.)
9) Trainers and fire props will be designed and fabricated to provide the main fire and up to two (2) fire extensions based on the trainer descriptions in the RFP
10) Unless otherwise described, the burners are provided in a water bath to insulate the fire prop and to evenly distribute the flame across the surface of the fire prop.
11) The fire props include a drain to discharge the water after use to minimize the risk of corrosion and or damage resulting from freezing temperatures.
2.2.1. Proposed Fireplace Details
2.2.1.1. Kitchen with Extensions and Flare Effect
Sample kitchen Range-Top Fire with Extensions
Description:
The kitchen trainer shall simulate a Class B grease spill range top fire and a Class A countertop fire. The fire structure shall consist of an stove fire prop in a kitchen with overhead cabinets. The stove fire and the overhead cabinet fires shall be capable of burning simultaneously.
The stove will also have a flare up feature simulating a spill over grease fire.
The flame generation system shall be located within the fire prop.
The kitchen fire shall be designed for flame-spread to a kitchen cabinet fire prop directly above the stove. The control system shall allow the instructor to select the start point of the fire, flame-spread sequence, and timing of the flame generation and spread. The kitchen range-top fire, and kitchen cabinet fire, shall have a pilot ignition system compliant with NFPA 1402. The kitchen range-top, and kitchen cabinet fires shall be fully operable independently or in conjunction with each other with a full flame range control from incipient through free burn.
Upon initialization by the operator, smoke shall be emitted, and the fire shall begin to grow according to parameters set by the instructor with the wireless controller. The fully involved fire shall reach a height of 4' to 6' above the fire prop and shall cover the majority of the stove and cabinets.
A flare up effect burner shall be mounted inside of the stove prop and shall be mounted in such a way as to be inconspicuous to the trainees.
The flare up feature shall be capable of being controlled by a trigger panel integrated into the stove mock up or by the instructor using the wireless control pendant within the burn room.
Artificial smoke from the Smoke Generation System will be able to emanate from the general area of the fire room.
2.2.1.2. Double Bed with Flashover/Rollover Effect
Sample Double Bed Fire
The double bed trainer will simulate a Class A bed fire. The fire structure shall consist of a fire prop resembling a double (full-size) bed.
The flame generation system is located within the fire prop.
The control system allows a full flame range control from incipient through free burn.
Upon initialization by the operator, smoke is emitted, and the fire shall begin to grow according to parameters set by the instructor with the wireless controller. The fully involved fire shall reach a height of 4' to 6' above the fire prop and shall cover the majority of the bed surface.
Artificial smoke from the Smoke Generation System will be able to emanate from the general area of the fire.
A flashover/rollover effect burner shall be mounted near the ceiling level above the bed fire prop and shall be mounted in such a way as to be inconspicuous to the trainees. The flashover/rollover effect shall not rely on any training fire's main flame for ignition and shall be compliant with NFPA 1402.
Flashover/rollover fires shall only be capable of being controlled by the instructor using the wireless control pendant within the burn room. The rollover shall simulate a buildup of igniting heat and gases at the ceiling, simulating rollover conditions. When the instructor initiates flashover/rollover, it shall provide a burst of flame that engulfs the ceiling area in the burn room.
2.2.1.3. Twin Bed
Sample Twin Fire
The twin bed trainer will simulate a Class A bed fire. The fire structure shall consist of a fire prop resembling a twin-size bed.
Description:
The flame generation system is located within the fire prop.
The control system allows a full flame range control from incipient through free burn.
Upon initialization by the operator, smoke is emitted, and the fire shall begin to grow according to parameters set by the instructor with the wireless controller. The fully involved fire shall reach a height of 4' to 6' above the fire prop and shall cover the majority of the bed surface.
Artificial smoke from the Smoke Generation System will be able to emanate from the general area of the fire.
2.2.1.4. Couch
Sample Couch Fire
The couch trainer will simulate a Class A couch fire. The fire structure shall consist of a fire prop resembling a residential couch/sofa.
Description:
This Fire Point will be specifically designed to simulate Class A fires in the living room area of a residential or business structure replicating the burning of these materials. The mockup will consist of a sofa, loveseat, and ottoman.
The water bath will form part of the structure of the sofa and will be where the burner element is positioned. The water bath includes a drain point for manual draining of the water for maintenance and in winter. Water acts as a diffusion media for the propane creating a realistic scenario.
The Fire Burner will be installed inside the sofa structure of the Mockup. The Mockup will replicate the size, layout, and configuration of a residential sofa. The Mockup will be placed in a suitable position in the office area of the training structure.
This Fire Burner will contain three sets of independently controlled burner elements located in the Base Unit in the structure. The control system allows the instructor to select the start point of the fire, flame-spread sequence and timing of the flame generation and spread.
the fire room.
2.2.1.5. Attic Fire Trainer
Sample Attic Fire
The attic trainer will be sized to occupy the space shown on the Construction Drawings (length x width).
It will replicate a Class A Fire within an attic, including simulated bottom chords of trusses at floor that are 6" tall.
Description:
The flame generation system is located within the fire prop.
The control system allows a full flame range control from incipient through free burn.
Upon initialization by the operator, smoke is emitted, and the fire shall begin to grow according to parameters set by the instructor with the wireless controller. The fully involved fire shall reach a height of 4' to 6' above the fire prop and shall cover the majority of the bed surface.
2.2.1.6. Hallway Flashover
Sample Flashover Fire
The standalone flashover/rollover effect trainer is mounted near the ceiling in the hallway where indicated in the drawings. The flashover/rollover effect trainer is mounted in such a way as to be inconspicuous to the students. The flashover/rollover fire has its own pilot and the hallway includes a full set of NFPA-compliant safety systems including unburned gas detection.
Flashover/rollover fires is only capable of being controlled by the instructor using the wireless control pendant within the burn hallway.
The rollover simulates a buildup of igniting heat and gases at the ceiling, simulating rollover conditions.
When the instructor initiates flashover/rollover, it is capable of providing a burst of flame that engulfs the ceiling area in the burn hallway.
The flashover/rollover effect is capable of lasting 15 or more seconds when the flashover button is continuously pressed by the instructor.
Additionally, the instructor will be able to deliver short bursts of flame across the ceiling, gradually building up the fire to simulate realistic rollover development.
2.2.1.7. Paint Locker Fire Trainer
Sample Paint Locker Prop
The paint locker trainer will simulate a Class B fire occurring at a storage area desk found within a residential garage, The fire structure will consist of a simulated storage rack with paint cans.
Description:
The flame generation system is located within the fire prop base.
The control system allows a full flame range control from incipient through free burn.
Upon initialization by the operator, smoke is emitted, and the fire shall begin to grow according to parameters set by the instructor with the wireless controller. The fully involved fire shall reach a height of 4' to 6' above the fire prop and shall cover the majority of the rack surface.
2.2.2 Scope of Work
The scope of work for upgrading the fire training props within the burn building will include to following.
Design, fabricate and install a new structural fire training system to be integrated into the existing burn building.
Demolition:
- Remove the existing fire training props including the burn room mock ups, control cabinets and connecting hardware between both including piping, conduit, duct work and cabling.
- Remove existing burn room ventilation fans.
- Remove existing wiring between control cabinets and mock ups in each burn room.
- Remove existing transition plates in each burn room. This is the steel plate integrated into the exterior CMU wall that the utility lines (propane, electrical, water, air) mount to before connecting to the burn props.
- Remove the existing CAT 5 LAN cable that connects the burn building to the control room.
- KFT will reuse the existing conduit and propane piping as they are in very good condition and do not need to be replaced.
Design:
Design new fire training mockups (Couch, storage rack, stove with flareup and overhead cabinets, double bed with flashover, twin bed, attic prop, hallway flashover) Design new fire generation system Design new non-fire training props (car, stove, storage rack, table, chair) Design Facility Interface Drawing (FID) that integrates the fire training props, all control cabinets and utility runs into the burn building.
Design new commercial doors Design new forcible entry doors Design new water cooling system Design new standpipe system
Fabrication:
Fabricate new fire training mockups as listed above Fabricate new non-fire training props Fabricate new commercial doors Fabricate new forcible entry doors Fabricate new water cooling system Fabricate new standpipe system
Installation:
- Install a bi-directional hallway flashover in the first floor of the burn building (Room 106).
o Installation includes new exterior control cabinet and utility runs through non burn room (Room 101) to hallway flashover.
o Install thermal lining cover to protect utility run along the ceiling in Room 101.
- Install thermal lining in the first floor hallway in the burn area of the flashover (Room 106).
- Install additional thermal lining in the existing second floor burn room (Room 204).
- Install steel reinforcements in second floor burn room doorway (Room 204).
- Install new burn props into existing burn rooms.
o New/replacement props:
Couch (Room102) New storage rack in garage (Room 103). New Prop, not a replacement.
Stove with flare up and overhead cabinets (Room 105) Double bed with flashover (Room202) Twin bed (Room 204) Attic prop (Room 301) o New mineral oil (Type II) smoke generators in all burn rooms o New transition plates for each mockup o New ventilation fans for each burn room
- Install new fire generation system:
o New mechanical control cabinets for each burn room o New electronic control cabinets for each burn room o New Type II smoke generators for each burn room o New software to control all systems. Software is integrated into software for the existing containerized burn building as well.
o New ventilation fans that fit into existing wall openings for each burn room. KFT will create a new opening for the storage rack prop in Room 103.
o Install new CAT 6 LAN cable between the control room and burn building o Install new electrical cables between the new control cabinets and the new burn props in each burn room o Install new mechanical (LPG) piping between the mechanical control cabinet and the new burn props in each burn room o Install new combustion air ducting between the new mechanical control cabinet and the new burn props in each burn room o Install new mechanical, electrical and smoke generator cabinets for the new storage rack prop in room 103 o Modify the existing fuel control station to comply with the 2019 version of NFPA 1402.
Eliminating the high and low pressure switches
- Install new non-fire props o Install one (1) non fire car prop in the existing garage burn room (Room 103) o Install four (4) non fire burn props to serve as obstacles within burn rooms. Props included:
table, chair, sofa, storage shelf. Location to be determined (TBD) o Install five (5) new doors with magnets. Location TBD o Install two (2) forcible entry doors. Locations TBD o Replace existing stand pipe on rear of burn building with a new standpipe o Install new water cooling line, along exterior of building, to each burn room o Install new magnets on existing burn building doors
Project Completion
- Integrate new fire training system into the existing PC in control room
- Complete Acceptance Testing with MSFA Staff
- Provide new Operation & Maintenance manuals
- Provide two days of Operations & Maintenance training (classroom and field)
- Provide warranty letter to MSFA Staff
- Develop plan for scheduling maintenance visits per the agreed upon annual maintenance contract
2.3. Additional Information
At KFT we use a modular design and construction methodology. This allows for some modification to the final position of features during the design review phase with the Owner.
This methodology also allows for adaptation and modification in the future. Should training needs change or grow, the KFT units are readily adaptable to suit such requirements.
When evaluating the fire training simulation equipment, we encourage you to fully review the type, quantity and quality of equipment that we have offered. As a company committed to the provision of only the highest quality equipment, we confirm that our offer is fully compliant with the latest codes and regulations. Failure to comply with the regulations will result in an unsafe installation that may result in failure and injury.
Not all simulators are the same. KFT quality and level of experience illustrates a full mission achieving solution, particularly related to the provision of field proven equipment.
2.3.1. Technical Rooms
The technical rooms will be used to house the KFT process control equipment. It is a safe area where the process equipment is protected from the live fire training environment and does not take up valuable training space of the users. KFT will populate the technical areas with the control equipment to support the KFT supplied equipment as listed in Table 1.
2.3.2. Smoke Machines
To enhance the training environment KFT Fire Trainer will integrate smoke machines into the Fire Training System.
All trainers will include a smoke generation system that provides simulated smoke obscuration into and throughout the burn room. The trainer control system controls the smoke emission. The smoke will create obscuration of less than one-foot visibility at the three foot level within the burn room while the flames are active. This smoke is non-toxic, safe for use with open flame, and safe at the operating temperatures readily found within the burn room.
a) Each fire trainer will include an integral smoke generation system that produces realistic smoke effects for the burn room and floor containing the operated trainer using hypoallergenic theatrical smoke fluid.
b) Each smoke generation system will include a fluid reservoir and distribution center capable of delivering artificial smoke as required.
c) Each smoke generation system will be programmable with an operator controlled variable discharge. Each system will provide the operator the ability to vary discharge duration and intervals between cycles from the main control touch panel without the use of any external equipment.
d) Each smoke generation system will provide low visibility training environments during fire conditions. The smoke generation system meets all applicable codes and standards and is suitable for the application. Smoke fluid is non-combustible, non-toxic, and safe for use for personnel, the training building, and the equipment. There will be no environmental impact caused using the smoke generation system.
e) The smoke generation system has the ability to totally fill the entire burn room of the operated fire trainer.
f) All components of the smoke generation system have been designed and fabricated to meet the conditions of the training building and burn room environment.
g) The reservoir for the smoke solution is easily accessed for filling and designed to minimize the risk of contaminating the control cabinet and controls should the reservoir leak or become overfilled.
h) The reservoir for the smoke solution is fully removable from the control cabinet.
i) The smoke solution is protected from freezing under harsh weather conditions
j) The smoke generation system has been designed and fabricated to work with the fire training control system, including the following:
i) Respond to pre-programmed commands from the fire training control system to produce smoke before and during operation of the trainers.
ii) Respond to manual command for smoke during non-fire trainer use (search and rescue training and similar scenarios).
iii) Respond to manual commands to produce additional smoke before and during fire training scenarios.
iv) Shut down smoke generation upon automatic commands from the control system and upon manual command.
k) Additional, optional smoke machines (if requested) for rooms that do not have trainers can be connected to the trainer controls, so that all rooms in the burn building can be filled with smoke.
2.3.3. Safety Systems
In accordance with NFPA 1402 (2019) KFT will provide regulatory compliant Safety Systems for the Live Fire Training Areas, including Gas Detection, Temperature Monitoring, E-Stops and Extract ventilation. These systems will be described fully in the Control System description in Section 4.
3. Fire Scenarios
The proposed fire scenarios will be a series of LPG vapor fuelled Fires. The Fire Training scenarios will be designed to represent the chosen fire type and will be fabricated to the highest quality and latest standards.
Table 1 lists the proposed scenarios.
Each fire generation area or fireplace operates on the same principle. A fuel source is ignited by an ignition source to produce a pilot flame and when the pilot flame is confirmed by the operator, a main flame is ignited from the pilot flame. KFT provides dedicated combustion air to the Mock-up area to ensure effective combustion of the LPG propane is achieved in a safe manner.
The control of the fuel for the pilot and the main flame is from the HMI (Human Machine Interface) control screen and the wireless controls.
The LPG Vapor main flames are ignited from the electronic pilot burner ignition.
The failure of the pilot flame to light or failing during operation will automatically inhibit the operation of the fire scenario. This is a critical safety feature and is required by regulation when igniting LPG Fire Scenarios. This will be communicated to the operator via the HMI.
All flame producing components are located within the fire prop structure to produce flame growth in and around the fire prop structure consistent with the represented fire.
All trainer fire props and mock-ups are fully integrated with all burners and pilot systems built in.
All fires are generated from multiple similarly configured modular hardware sets Training fires and effect fires will be instructor controlled. The control system, however, will automatically monitor all trainer safety systems and shall stop all training fires and begin building ventilation as appropriate for the specific safety system alarm or malfunction.
A wireless handheld control unit shall be used to control the training fire with a minimum of three height settings (low, medium, and high). Continuous and full range control over fire heights is available.
For flashover/rollover effects, an on/off control will be provided Control racks are capable of being remotely located above, below, or to the side of the multiple burn rooms controlled from each control module No fire burn room will be supplied without being a fully independent, dedicated pilot burner. This includes all extension fires and flashovers.
Flashover fires will not require any extension burners in order for the flames to extend across the ceiling. Flashover fire generation systems are compliant with NFPA 1402.
The fire scenarios listed in Table 1 will be provided as per the specification.
Trainers are capable of being "computer run", including agent detection and programmable training scenarios run by the computer, in addition to "instructor run", with an instructor running all scenarios with manual controls.
3.1. Internal Fire Scenarios
The internal fire scenarios will be a series of LPG Propane Fuelled Fire Scenarios. The Fire Training scenarios will be designed to represent the chosen fire type and will be fabricated to the highest quality and latest standards.
Please note alternate Fire Scenario Options are available from our extensive library of solutions. If you require either an alternate or additional fire please advise. These may be available at no extra cost depending on the fire type, quantity and location.
4. Control System
KFT proposes to supply you with a state-of-the-art control system to control the Fire Scenarios. The following sections describe the control components behind the control system and the features it offers. It is a proven control system that offers you a reliable and repeatable LPG Propane fuelled fire scenarios with several important safety features. The system should be enabled prior to use via a security key. In addition to this, the control system also comprises a local control feature where a wireless controller can locally control features of the training area.
The system has been used successfully and with complete safety in both Fire Training Buildings, Aircraft and Maritime Simulators throughout the world without a single safety incident. Per specification the system can be operated in Manual mode.
Per the request of the Mississippi Fire Academy Leadership Team, a bypass feature will be provided which allows the training cadre to select changes to the standard KFT provided controls. Specifically, the academy would like to raise the high temperature emergency stop setting from the current 500 degrees Fahrenheit to the previous standard of 700 degrees.
Additionally, the academy would like to enable all fire controls from the central control room rather than a local wireless pendant with each fire training instructor. KFT will provide a training system that is compliant with the 2019 edition of NFPA 1402, if the Academy leadership selects to raise the temperature setting to 700 degrees or control all fires from the central control room vs a pendant that is local to the individual burn room, this will be accomplished with either a password protected or physical key switch to change the setting above. Additionally, the switch will require acknowledging that the NFPA 1402 standards are being bypassed.
4.1. Main Control Unit
Sample Operator Control Screen
1) Each fire burn room will have a control unit with all necessary controls & equipment to:
a) Provide automatic and manual control over each fire and effect (smoke, sound- if this option is added)
b) Provide individual control of each fire (including main fire, extensions, and flashover)
c) Monitor the entire burn trainer for safety conditions
d) Shut down the burn trainer automatically on safety or fault conditions
e) Shut down the system manually
f) Record and archive all event data from the fire trainer and room
g) Provide password protected instructor access
h) Provide system diagnostics, both locally and via remote access.
i) Provide three levels of fire, low, medium and high, with an ability to be updated at a later date to include multiple pre-programmed and custom developed training scenarios
j) Control units utilize a PLC (programmable logic controller). The PLC has its control components distributed among all fire control equipment as necessary to provide individual control of the fire as well as a safety interface to monitor the entire trainer for safety conditions and shut down trainer operation, if required. This includes monitoring the trainer's gas detection and emergency stop systems and monitoring and controlling the trainer's gas supply and ventilation system. Flame size is controlled from the handheld control unit. Flame height range shall be incipient through free burn without limitation.
k) We can confirm that the Fire Training Simulation equipment and control system we are providing is readily expandable in the future. Control units allow for future upgrades to a centralized computer workstation using a Microsoft operating system to simultaneously control, link and monitor all burn rooms within the fire training tower. The Control systems use the latest PLC’s and I/O. This allows the system to be expanded to additional devices as the training unit and equipment expands.
REMOTE
CONTROL
PANEL
CONTROL
Sample Futue Control System Operator Screen with advanced Settings
l) All control units, devices, and equipment have been designed and constructed for reliable operation in the harsh conditions of the fire training building.
m) Control units are programmed for fail safe operation and automatically shut down the gas and start the ventilation exhaust system on activation of safety devices, on system fault, and when emergency stop is initiated. All fail-safe events are recorded and archived.
n) Control units include an LCD touch panel. The panel provides high quality legibility in various lighting conditions. The screen and user interface are sized to allow all information for each scenario to be displayed on a single screen. The local display shall be durable and provided with replaceable protective covers.
o) All controls are designed and sized for quick, simple operation with minimal user input.
p) Controls allow the instructor to set up, initiate and monitor the scenario, and to constantly monitor safety conditions.
2) Controls allow the operator to control the following aspects of the training scenario:
a) Flame size and height measured from the top of the exposed burner or surface of water if submerged: automatic and manual control of flame heights (low, medium, high). Low will be 1' to 2' above the fire prop. Medium will be 2' to 4' above the fire prop. High shall be 4' to 8' above the fire prop.
b) KFT will provide a wireless controller for local control of the training system where the operator can be positioned close to the training unit and the trainees. It is a robust unit with feedback that operates using industrial grade switches.
c) Each fire trainer will have a dedicated control unit. The control unit allows full control of smoke enhancement, fire growth, ventilation, and man-down capability. The smoke enhancement switch shall allow the instructor to obscure the area to suit the capability of trainees. The fire growth switch shall control fire generation. The man- down switch shall control the instant on and off capability of the fire while the clear switch shall allow the instructor to ramp ventilation to 100 percent if the area needs to be cooled or smoke needs to be cleared. The Wireless Unit is described in section 4.2 Handheld Control Units.
3) Each control unit shall display, record, and archive the following information at a minimum:
a) Pilot light confirmation
b) Main flame confirmation
c) Flashover confirmation
d) Elapsed time of the training scenario
e) Gas level(s) in the burn room
f) Temperature in the burn room
g) Smoke generation status
h) Exhaust fan status (including fan speed)
i) Agent detector amounts and locations
j) Safety warning messages (with problem and corrective action)
k) Diagnostic message (with problem and recommended corrective action)
l) Alerts shall be indicated on the handheld control units via flashing light(s) or messages
m) When the system is logged off, all systems are disabled with the exception of the gas detection and ventilation systems. The gas detection system continuously monitors the atmosphere and the ventilation system shall automatically operate to safely exhaust the detected gas from the building.
n) The ventilation exhaust system can be activated manaully at all times
4.1.1. Operator Authorization
1) Each of the gas fueled burner controls incorporates an electronic security system to prohibit unwanted and unauthorized use, data retrieval, data manipulation, diagnostics, programming, or other operation.
2) All access is password protected with individually assigned user names and defined passwords. Multiple levels of password protection are available at the touchpanel.
3) The operating system allows Administrator level control by the Owner and also includes the following:
i) Add and remove users
ii) Create and assign passwords.
iii) Control access levels for each user.
iv) View and print logs and training data.
v) Perform system maintenance.
vi) Backup the operating system, logs, and data files.
4.1.2. Remote Access
1) The operating system includes the ability to permit remote access by KFT including the following:
a) Integral access via the internet
b) Monitoring system diagnostics programs
c) Correcting system software conflicts and problems
d) Upgrading operating systems
e) Backup of the operating system
f) Provide a telephone number for 24-hour access to technical support.
2) KFT will maintain online technical support available for diagnosis of the installed fire burner units and related controls.
3) The operating system shall include the ability for the administrator(s) to obtain access via the internet to conduct initial diagnosis and data retrieval from locations remote from the trainer and fire training building.
4.1.3. System Diagnostics
1) The control system includes integral diagnostic programs. The diagnostics provide the following:
a) Display all system status and error messages on the control screen of the main control cabinet serving the specific trainer.
b) Display instructions on the main control screen to allow the operator and maintenance personnel to identify the problem and correct system malfunctions.
2) The diagnostics program tests and identifies problems with the following systems at a minimum:
a) Program Logic Controller (PLC) system
b) Gas regulator and control system
c) Gas sensors and monitoring system
d) Temperature sensors and monitoring system
e) Ventilation exhaust fans
f) Pilot flame valve and monitor
g) Main flame valve and monitor
h) Handheld control unit
i) Extinguishing agent sensors
j) Smoke generation system
3) The diagnostics program shall notify the Operator when to perform routine diagnostics including:
a) Gas sensor range checks
b) Sensor replacement
c) System adjustments
4.1.4. Data Recording
1) The fire training system provides monitoring and recording of all system functions including:
a) Password logging from all users and administrators
b) Operator input and commands at main control panel
c) Operator input and commands from hand held devices
d) Program Logic Controller (PLC) functions
e) Inputs from safety device and monitors
f) Event messages
g) Error messages
h) Alarms
i) Operator display messages
j) System run timers and counters
k) System fault counters
2) The system stores all information on an integral hard drive and a removable flash drive.
3) Information is tracked by date, time, operator, event, and action.
4) The information is accessible and viewable from the main operator control screen at all times.
5) The information stored on the removable flash drive does not require the use of special equipment or software for removal or viewing.
4.2. Handheld Control Units
In local manual mode, the wireless controller will provide the operator with full control over the training system including:
1) Magnetic Mounting for all handheld units.
2) System uses wireless handheld control units.
3) Wireless handheld control units have a minimum 20-foot range of the designated fire prop within training building structure.
4) All wireless control units allow the control to be used with operation of all switches and controls while wearing NFPA 1971 compliant structural fire-fighting gloves.
5) All handheld control units are designed to withstand frequent exposure to heat, water, steam, vibration, and shock resulting in being dropped from an elevation of approximately three feet above a concrete floor. The handheld units are encased in a non-metallic case to minimize the absorption of heat.
6) All handheld control units have with an Operator Present (“dead man”) switch that requires the instructor to maintain throughout the training exercise. Release of this switch results in a flame shutdown of the associated fire trainer(s).
7) Wireless handheld control unit’s fail-safe and shut down the associated fires if signal is lost during scenario.
8) Handheld control units permit the instructor to immediately shut down the training scenario.
9) Handheld control units permit the instructor to control the following aspects:
a) System on and off
b) Pilot light
c) Flame size and height for the full range of the system.
d) Smoke generation.
10) Handheld control units shall permit the instructor to turn on the ventilation exhaust system.
11) KFT will describe the frequency range used to establish and maintain communication between the wireless handheld controls and the assigned fire prop. The wireless communications frequency shall not be influenced by portable radios, mobile telephones, or other wireless communication that could be present in or about the training facility by commonly used or existing equipment.
12) Wireless handheld controls shall incorporate an ergonomic design to minimize hand or arm fatigue.
13) The wireless handheld controls shall be provided with a lanyard to allow the control to remain in contact with the instructor while not actually in use.
Wireless Controller (Side view) Wireless Controller (Operator View)
4.3. Trainer Flames
1) Each training fire includes a flame initiation system designed and fabricated to provide the following:
a. System initiates and maintains a pilot for ignition of the main flame.
b. Main flame burner element realistically distributes gas and produce flame.
c. Control valves adjust gas flow to the main burner elements.
d. Safety interlock valves are connected to the main control system.
e. The main flame is extinguishable only by the operator's control system and not by the application of extinguishing agents.
2) The flame control systems include separate automatic shut off valves interlocked to the safety control system. This valve shall stop the flow of gas at all emergency shutdown events or on the loss of electrical power.
3) The flame control system has been designed and will be fabricated to adjust the gas flow based on programmed control systems and/or at Operator's control, including flame height.
4) The burner is immersed in a water bath.
5) The water tray/pan is constructed of stainless steel and is not visible from the outside of the fire prop.
6) The tray is fitted with a drain valve and be designed for ease of cleaning.
4.4. Pilot Ignition System
1) Each fire trainer (main burners, extensions, and rollover element) is equipped with a flame pilot per NFPA 1402.
2) Pilot and pilot burners are inextinguishable.
3) The pilot is designed to function in the training building and burn room environment and to provide a continuous pilot flame during the application of extinguishing agents.
4) Pilots are controlled with a commercial, continuous self-check ignition device. This device will only allow main flame gas flow if pilot flame is confirmed.
5) The pilot has been designed and located to assure ignition of all burner elements.
6) The pilot flame is not visible during training.
7) The pilot monitor includes the following.
a) Each pilot is monitored independently.
b) Each pilot is continuously monitored.
c) The pilot monitor reports status to the main control unit and records pilot attempt, confirmed, and failures.
d) In the event of pilot failure or extinguishing, the fuel delivery system and all safety valves will close. An error indicator is displayed on the control unit and handheld units.
DEADMAN
SWITCH
E S T O P
E S T O P
F I R E P L A C E
5 8
4.5. Combustion Air
1) Each fire prop shall include adequate combustion air to ensure reliable combustion of the main flame gas source.
2) Each fire prop shall include a sensor to measure and confirm airflow.
3) The control system shall continuously monitor the combustion air supply.
4) If the system detects inadequate combustion air, the flame and smoke shall automatically shut down and an error message shall be displayed on the control unit. The handheld unit shall signal an error.
5) The system shall automatically check the combustion air sensor and shut down the flame and smoke generator automatically if the sensor fails
6) The combustion air supply shall be clean air per the requirements of NFPA 1402.
All the gas control equipment adheres to current NFPA standards. It is important that the correct specification of equipment is used for the installation of the gas pipe work as well as certified gas installation engineers. Failure to adhere to regulations and codes of practice may result in sub-standard pipe work installation that is dangerous and may cause serious injury.
4.6. Safety Systems
The control system relies on a series of controls and procedures to ensure the safe operation of the equipment. KFT provides a training course for operators to ensure their competency prior to use of the equipment. An operation and maintenance manual is also supplied to ensure the knowledge of the equipment and its fitness for purpose are maintained.
Before the system can be used it needs to be activated by a key at the main control panel. This ensures no unauthorised operation of the equipment unless the key is present. A number of other systems are included in order to ensure the safety of the trainers and trainees:
4.6.1. Emergency Stop Systems
1) Each burn room includes an emergency shutdown control.
2) Each shutdown control is hard wired.
3) Shutdown controls are independent of the control system.
4) The emergency stop will be a normally closed circuit and open upon activation of the button.
5) The emergency stop button activates the following events:
a) Close all burner control valves throughout the building.
b) Secure the gas supply to the associated prop.
c) Initiate the ventilation exhaust system at full until manual reset of the system.
d) Identify the location of the emergency stop event on the control display.
e) Record the time, location, and system status of all equipment.
f) The emergency stop control shall require manual reset before restart of any system.
4.6.2. Temperature Monitoring
1) Each burn room (room with a fire trainer) will include a temperature monitoring system with at least one temperature sensor (more if room size and conditions require them) that monitors room temperature during trainer operation.
2) The temperature monitoring system ensures student safety while allowing realistic interior firefighting experience in flame size, spread and heat development. The temperature monitoring system shall be adjustable and calibrated for the specific trainer and specific room or area of the assigned burner.
3) Temperature sensors are appropriate for the training building environment and burn rooms.
4) Temperature sensors are mounted at five feet (5'-0") above the floor level.
5) The temperature monitoring system continuously monitors, displays, records, and archives temperature levels within each burn room during operations.
6) The temperature monitoring system automatically initiates the ventilation exhaust system when temperature levels exceed programmed levels. The ventilation system continues to run until temperature levels are reduced below the programmed levels.
7) When temperatures exceed programmed levels, a warning message is displayed on the control system.
4.6.3. Gas Detection
1) The safety control system will include a gas detection system per NFPA 1402.
2) Gas detection sensors will be provided within each burn room plus each equipment room per
NFPA 1402.
3) The gas detection system will operate independently of the training control system.
4) The gas detection system will verify safe gas levels within the burn room prior to system operation, prior to pilot and flame initiation, and during all burn events.
5) The gas detection system will constantly monitor, record, and display the gas concentration levels at each sensor.
6) The gas sensors will provide continuous, reliable operation within the training building and burn room environment.
7) Each burn room will include not less than one (1) gas detector to monitor the entire burn room and equipment room (if applicable). The detection system and sensors will meet the following requirements:
a) Requirements of NFPA 1402.
b) Each sensor will be monitored independently on a dedicated channel or equivalent system.
c) The gas detection system will compensate for ambient temperature (between -40°F to
150°F).
d) The gas detection system will compensate for ambient humidity (between 0% and 100%).
e) The gas detection system will include hermetically sealed optics and electronics.
8) The gas detection system will be designed to minimize the frequency of false or unwanted gas detection that will result in system disruption, but will properly initiate the following events automatically upon detection at any sensor:
a) Upon detection of 15% LEL (Lower Explosive Level) maximum, the system will display a
"gas warning" message on the control panel. The warning message will indicate the sensor location. A gas warning light will initiate on the handheld control unit.
b) Upon detection of 25% LEL maximum, the system will automatically shut down the gas supply to the trainer and display a "gas shutdown" message on the control unit and indicate the sensor location.
c) Upon failure of any detector, sensor, or draw sample pump, the system will automatically shut down the gas supply to the fire prop and display a "gas shutdown" message on the control unit and indicate the sensor location.
9) Upon any gas shutdown event, the ventilation exhaust system will automatically initiate on high and continue until the gas concentration level is reduced below the allowable limits.
10) The gas detection system will include constant self-checking diagnostics. Upon failure of any part of the gas detection system, the gas system throughout the training building will be shut down and secured.
11) The gas detection system may require periodic bump tests (“span check”) to d emonstrate proper operation of the sensors and system but will not require full calibration of the system more often than monthly.
12) Owner will manage and perform routine maintenance, bump testing, calibration, and sensor replacement of the gas detection system. KFT will train and certify Owner representatives for these tasks.
4.6.4. Exhaust Ventilation System
1) Each burn room will be equipped with an appropriately sized exhaust ventilation systems based on multiple fire training equipment factors including room size.
2) The exhaust ventilation systems will be designed and constructed to remove heat, combustion by-products, unburned gas, and smoke from each burn room.
3) The exhaust ventilation system will be designed and constructed to provide a complete air exchange within the burn room at least every 60 seconds.
4) The exhaust system consists of the following:
a) Variable speed exhaust fans rated for high temperatures.
b) Fan mounting provisions.
c)…