STATEMENT OF WORK
B&F 24Z3A2R REPAIR CHILLER
OPTION A – CHILLER #2
FEDERAL CORRECTIONAL INSTITUION
ALICEVILLE, ALABAMA
OPTION A:
The Contractor shall provide all parts, materials and services to properly repair an oil leak that has been identified on a York 500-ton centrifugal chiller that was installed in 2011.
The chiller is identified as Chiller #2. The chiller is currently in service while monitoring the leak. The Contractor is solely responsible for providing any and all components for the repair associated with refrigerant that will be recovered and charged during the repair of the chiller. The Contractor will be required to perform a leak check and vacuum of the system to determine all leaks are identified and repaired. Any lubricant or filters may be changed during this leak repair associated with the repair location. The Contractor is required to perform a start up of the chiller, and verify all operating and safety controls are in working order once all repairs have been completed. Upon completion the chiller will be placed back into operational service.
All work provisions and conditions listed in the original SOW apply to this Option for
Chiller #2. The repair service shall be completed by qualified HVAC personnel using only genuine York factory parts. Seismic zone requirements, environmental compliance, life safety, NFPA, OSHA, federal, state, local codes and regulations will be considered during all phases of this project. All work shall be completed, equipment tested and adjusted per manufacturers recommendations and accepted by the Contracting Officer’s
Representative (COR) and Contracting Officer (CO).
A. SPECIFICATIONS
Manufacturer: York
Model: YKFQFQQ7-CRGS
Serial Number: SCWM518540
Refrigerant: R134A