500 kW and 350 kW Standby Emergency Diesel Generator Rental
Solicitation number
N42158-27-RFI-C431B
Issued by

About this file

This is a Statement of Work (SOW) for the rental of emergency diesel generators at Norfolk Naval Shipyard. The Government requires two trailer-mounted Emergency Diesel Generators (EDGs) with capacities of 500 kW and 350 kW to provide standby emergency electrical power during unplanned power outages. The anticipated contract type is firm-fixed price, and this sources sought notice is issued for market-research purposes only in accordance with FAR 15.201. Responses are intended to assess industry capability, availability, market conditions, acquisition strategy, and potential for small-business participation. The Government will not reimburse respondents for any information, documentation, capability statements, or costs incurred in responding to this notice, and responses will be used solely for evaluation purposes prior to a potential future procurement.

The SOW document serves as a draft enclosure defining the anticipated scope of work and performance requirements for the generator rental services. Respondents are required to complete a Capabilities Statement as part of their response to this sources sought notice. This pre-solicitation notice does not constitute a commitment by the Government to award a contract and is distinct from a formal solicitation, RFP, RFQ, or request for offer.

View the file

Other files

File Type Posted
EDG Technical Capabilities.docx DOCX document
Emergency Diesel Generator Rental Contractor Technical Certification_.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work Emergency Diesel Generator Rental

1.0 Scope

· 1.1 Objective: Norfolk Naval Shipyard (NNSY) requires the rental of two (2) trailer-mounted Emergency Diesel Generators (EDGs) to provide standby emergency electrical power during unplanned power outages.

· 1.2 Background: The EDGs will serve as standby equipment to maintain operations for project trailers and a living barge during utility outages.

2.0 Applicable Documents

The Contractor shall comply with the latest revisions of the following documents:

· 2.1 Federal Regulations:

· 29 CFR 1915.89 – Control of Hazardous Energy (Lockout/Tags-Plus)

· Occupational Safety and Health Administration (OSHA) standards

· 2.2 Department of the Navy & Shipyard-Specific Requirements:

· Norfolk Naval Shipyard OSHE Program Manual, NAVSHIPYDNORINST P5090.2

· NAVSEA Occupational Safety, Health, and Environment Corporate Manual (OSHECM), Chapter 250 (Hazardous Energy Control)

· NAVSEA 04 Ser 04/281 – Implementation Plan for Portable Electronic Devices (PEDs)

· NAVSEAINST 2200.1A – Portable Electronic Devices Policy

· SECPROMAN Vol 1 5510.36 Rev E – Security Program Manual

3.0 Requirements

· 3.1 Equipment Specifications:

· 3.1.1 500 kW Standby Power Diesel Generator (Quantity: 1)

· Output & Capacity: 480 Volts, 3-Phase, 3-wire grounded, with a minimum Standby Rating of 500 kW.

· Auxiliary Systems: Equipped with an auxiliary block heater and battery charging circuit. Auxiliary power connections must utilize standard commercial configurations (e.g., standard NEMA plugs).

· Safety Devices: Equipped with an output circuit breaker with overcurrent protection.

· Physical Limitations: Footprint shall not exceed 20' L x 8' W. Total unit weight shall not exceed 45,000 lbs.

· Fuel System: Onboard or external fuel tank capable of a minimum twenty-four (24) hour run time at full continuous load prior to refueling. External fuel tank, if utilized, shall not exceed 1,240 gallons in volume, 10' L x 8' W in footprint, and 15,000 lbs fully fueled weight (or dual tanks not exceeding 5'-5 3/8" x 7'-8 5/8" and 6,200 lbs each). Fuel tank lifting points must have current weight capacity certifications. The fuel system must allow safe refueling while the generator is operating.

· Enclosure: Self-contained, outdoor, rain-tight, sound-attenuated enclosure with a self-contained cooling system.

· Connection Interface: Equipped with mechanical terminal lugs or standard connections compatible with standard 500MCM power cables (supporting up to 4 conductors per phase).

· Certification: The unit must be clean, well-maintained, and have undergone a load-bank test within two (2) weeks prior to delivery. Certified test data must be provided upon delivery. Winding insulation resistance shall meet commercial standards (minimum 5MΩ above ground with neutral disconnected).

· Operating Instructions: Legible, weatherproof operating instructions (start, stop, parallel synchronization, and breaker operation) must be permanently posted near the control panel.

· 3.1.2 350 kW Standby Power Diesel Generator (Quantity: 1)

· Output & Capacity: 480 Volts, 3-Phase, 3-wire grounded, with a minimum Standby Rating of 350 kW.

· Auxiliary Systems: Equipped with an auxiliary block heater and battery charging circuit. Auxiliary power connections must utilize standard commercial configurations (e.g., standard NEMA plugs).

· Safety Devices: Equipped with an output circuit breaker with overcurrent protection.

· Physical Limitations: Footprint shall not exceed 20' L x 8' W. Total unit weight shall not exceed 45,000 lbs.

· Fuel System, Enclosure, Connection Interface, Certification, and Instructions: Must meet the identical performance, size, safety, and certification requirements outlined in Section 3.1.1.

· 3.2 Contractor Responsibilities:

· 3.2.1 Maintenance & Repair: Provide all routine, preventative, and emergency maintenance (including parts and wear-and-tear replacement) at no additional charge during the rental term. All associated travel and labor costs shall be borne by the Contractor.

· 3.2.2 Service Response: Provide 24/7/365 repair coverage. The Contractor shall dispatch a qualified service technician to arrive on-site within four (4) hours of notification by NNSY. If repairs cannot be completed on-site, the Contractor must replace the unit within eight (8) hours of initial notification, at no additional cost.

· 3.2.3 Emergency Contacts: Legible, weatherproof emergency contact information for 24/7 service must be permanently affixed to each generator unit.

· 3.2.4 Badging & Security: Ensure all service technicians and drivers are U.S. citizens and comply with NNSY security requirements, including obtaining DBIDS cards, NAVSEA green badges, and adhering to Controlled Industrial Area (CIA) access policies.

· 3.2.5 Protective Coverings: Provide adequate weather and saltwater-corrosion protection coverings for all rental equipment.

· 3.2.6 Documentation: Provide comprehensive technical manuals, fuel consumption curves, allowable operating hours at various ratings, and technical parameters upon delivery.

· 3.2.7 On-Site Support: Provide a technical representative to assist NNSY personnel during initial cable installation, perform voltage and phase rotation checks, and participate in initial Hazardous Energy Control (HEC) lock coordination.

· 3.3 NNSY Responsibilities:

· 3.3.1 Facility Access: NNSY will provide access to the equipment during normal working hours (weekdays, 7:30 A.M. to 4:00 P.M.). Service coordinated outside these hours must be pre-approved in accordance with the contract rate schedule.

· 3.3.2 Government Negligence: NNSY shall only be responsible for maintenance or repairs necessitated by direct Government negligence.

· 3.4 Shipping, Delivery, and Demobilization:

· 3.4.1 Delivery Location: Norfolk Naval Shipyard, Bldg 298, Portsmouth, VA 23709

· 3.4.2 Period of Performance (PoP): Early November 2026- early November 2027 with one six month option period

· 3.4.3 Pickup and Demobilization: The Contractor shall pick up and remove all rental units on the morning after the expiration of the PoP. If expiration occurs on a weekend or recognized Federal holiday, removal will take place on the first subsequent business day at no additional charge.

· 3.4.4 Early Return/Prorating: NNSY reserves the right to return any or all units prior to expiration with forty-eight (48) hours' written notice. Rental costs for early returns shall be prorated based on the actual calendar days in use.

4.0 Contact Information

· 4.1 Technical POC:

· 4.2 Invoice Certifier: