This is a Statement of Work (SOW) for a Design-Build project to add a fire suppression system and interior office space to Building 450 at Grissom Air Reserve Base, Indiana. The contractor shall design and construct a new 512 square-foot (32' x 16'), heated, self-supporting interior office space with a 1-hour fire-resistance-rated envelope and an operational wet-pipe automatic fire suppression system protecting only the new office area within the existing 88' x 56' uninsulated wood-pole barn. The scope includes a complete architectural and multi-disciplinary engineering design package, procurement, site work, construction, and commissioning operations under the Design-Build delivery method.

The detailed scope encompasses: architectural design with a tested 1-hour fire-rated horizontal ceiling assembly and light-gauge steel framing walls; fire suppression system design per NFPA 13 (Light Hazard) including a dedicated heated mechanical/riser room, quick-response sprinkler heads, exterior fire department connection (FDC), yard hydrant, and post indicator valve (PIV); HVAC installation with freeze protection maintaining minimum 40°F; electrical upgrades including load calculations and potential transformer coordination with Peru Utilities; civil and underground water supply line installation from the municipal main approximately 250 feet north; and fire alarm and mass notification system integration with the existing Monaco master control panel. All work must comply with UFC standards, NFPA codes (13, 72, 101, 221), NEC, and GARB Base Standards. The contractor must submit design documentation at 35%, 65%, 95%, and 100% milestones; perform hydrostatic pressure testing and alarm commissioning; provide minimum 4 hours of operations and maintenance training; and deliver three complete sets of O&M manuals, warranty certificates, and As-Built drawings. The total Period of Performance is 180 calendar days from Notice to Proceed.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN-BUILD STATEMENT OF WORK (SOW)

PROJECT TITLE: Add Fire Suppression System & Interior Office, Building 450

BASE PROJECT NUMBER: CTGB13-2020

LOCATION: Grissom Air Reserve Base (GARB), Indiana CUSTOMER: 434th Mission Support Group Civil Engineers (434 MSG/CEC)

1.0 INTRODUCTION

The Design-Build (D-B) contractor shall design and construct a new, heated, self-supporting interior office space and an operational wet-pipe automatic fire suppression system protecting the new interior office area only within Building 450. Building 450 is an existing 88’ x 56’ uninsulated, wood-pole barn with metal siding and exposed wood roof trusses (20-foot rafter eave height).

The contractor shall provide a complete architectural and multi-disciplinary engineering design package in sufficient detail to satisfy all criteria within this Statement of Work (SOW) and execute all procurement, site work, construction, and commissioning operations.

2.0 PURPOSE

Under this contract, the 434th Mission Support Group Civil Engineers (434 MSG/CEC) will utilize the D-B delivery method to establish a code-compliant, fully protected Business Occupancy (Office) within Building 450 at Grissom Air Reserve Base, Indiana. This project creates a complete 1-hour fire-resistance-rated envelope separating the protected office space from the remaining unsuppressed Storage Occupancy (Warehouse).

3.0 GOVERNING CODES, STANDARDS, AND REFERENCES

All work performed under this contract shall comply with the latest editions of the following federal, Department of the Air Force, and local criteria:

Standard / Criteria
Title / Designation
Key Area of Application
UFC 3-600-01
Fire Protection Engineering for Facilities
Primary DoD criteria for suppression, alarm, and life safety.
UFC 4-021-01
Design and O&M: Mass Notification Systems
Combined fire alarm and Mass Notification System (MNS) integration.
UFC 3-520-01
Interior Electrical Systems
Interior power distribution, branch circuits, and panelboards.
UFC 3-501-01 / UFS 3-501-01
Electrical Engineering / Supplement
Electrical service, transformer capacity, and exterior coordination.
UFC 1-200-02
High Performance and Sustainable Building Requirements
Facility efficiency, commissioning standards, and thermal envelope.
DAFI 32-1020 / AFI 32-10141
Civil Engineering Facility Programs
USAF/DAF engineering design, programming, and construction rules.
GARB Base Standards (2020)
Base Facility Standards (Ch. A § A-13 & Ch. D)
Base-specific fire alarm radio tie-in, FDC coupling, and submittal milestones.
NFPA 13
Standard for the Installation of Sprinkler Systems
Sprinkler piping layout, water density, and obstruction rules.
NFPA 101
Life Safety Code
Occupancy classification, egress capacity, and mixed-occupancy barriers.
NFPA 221
Standard for Fire Walls and Fire Barrier Walls
1-Hour fire barrier walls and horizontal assembly construction.
NFPA 72
National Fire Alarm and Signaling Code
Initiating devices, alarm notification appliances, and panel wiring.
NFPA 70
National Electrical Code (NEC)
Power distribution, conduit routing, and electrical safety.

4.0 DETAILED SCOPE OF WORK

4.1 Architectural & Fire-Rated Enclosure ("Room-Within-a-Room")

· Footprint & Geometry: The contractor shall design and construct a freestanding, self-supporting 32' x 16' (512 sq. ft.) interior office enclosure. The finished interior ceiling height shall be between 10'-0" and 12'-0" above finished floor (AFF).

· Placement & Wall Alignment (Option A - Flush Alignment):

· The new office enclosure shall be constructed flush against the existing building perimeter structure (0-inch clearance) along one 32-foot wall line.

· Inaccessible narrow gaps between new framing and existing wood posts are prohibited; new framing must butt directly to existing wall lines with appropriate fire-stop/draft-stop sealing at all mating interfaces.

· Mixed-Occupancy Fire Separation (NFPA 101 / NFPA 221 / IBC Section 707 & 711):

· The office enclosure shall form a complete, continuous 1-hour fire-resistance-rated envelope (all perimeter walls AND a rated horizontal ceiling assembly) separating the Business Occupancy from the surrounding unsuppressed Storage Occupancy.

· Horizontal Ceiling Assembly: To eliminate the need for extending vertical walls 20 feet up to the rafters and prevent the creation of a combustible concealed attic/void space, the contractor shall construct a tested 1-hour fire-rated horizontal ceiling assembly (e.g., UL Design No. L500-series or equivalent ASTM E119 rated assembly).

· No Overhead Void Space: The rated ceiling assembly shall act as a solid, self-supporting roof cap over the office. Because no combustible enclosed void/attic is formed above the office ceiling, sprinklers are omitted above the ceiling per NFPA 13.

· Wall Assembly: Non-loadbearing/structural light-gauge steel framing with 5/8-inch Type X gypsum board installed in compliance with UL Design No. U419 (or equivalent 1-hour listed system).

· Structural Engineering Analysis: The D-B contractor shall provide signed/sealed calculations from a registered Professional Engineer (PE) confirming that the office framing and concrete floor slab safely carry all dead loads (ceiling assembly, HVAC unit, lighting, piping, and water-filled sprinkler systems) independently of the existing building’s 20-foot wood trusses.

· Master Fire Alarm Panel Relocation:

· The contractor shall professionally disconnect, extend existing conduit and wiring runs along the perimeter wall, and remount the existing building Monaco master fire alarm control panel inside the newly constructed office space.

· All wiring extensions must maintain circuit integrity and comply with NFPA 70 (NEC) and NFPA 72.

· Opening Protectives (NFPA 80 / NFPA 101):

· Personnel Doors: Minimum 45-minute (3/4-hour) fire-rated door assemblies equipped with listed positive-latching hardware, smoke gaskets, and automatic self-closing devices.

· HVAC Openings: All duct penetrations through the 1-hour envelope must be equipped with 1.5-hour rated combination fire/smoke dampers (UL 555/555S).

· Through-Penetrations: All electrical, plumbing, mechanical, and communications penetrations must be sealed with a tested UL-listed 1-hour firestop system (ASTM E814 / UL 1479).

4.2 Fire Suppression System (NFPA 13 / UFC 3-600-01 / GARB Base Standards)

· Protection Boundary: The contractor shall provide a complete wet-pipe automatic fire sprinkler system designed and installed in accordance with NFPA 13 (Light Hazard) protecting the interior of the new office space only. The main warehouse floor area (88' x 56') shall remain unsuppressed under this contract.

· Riser & Utility Room: Construct a dedicated, heated, 1-hour fire-rated mechanical/riser room within or immediately adjacent to the office footprint to house the sprinkler riser, backflow preventer, pressure gauges, water flow switch, and inspector’s test assembly. The room temperature shall be always maintained at a minimum of 40°F (4.4°C).

· Sprinkler Heads: Quick-response, concealed or flush pendant sprinklers (brass/white finish) located below the 1-hour ceiling assembly.

· Fire Department Connection (FDC): Install an exterior FDC in accordance with GARB Base Standard A-13.3 featuring a 2.5-inch female NST Siamese coupling with rigid metal caps and chains.

· Yard Hydrant & Post Indicator Valve (PIV): Install a new commercial-grade fire hydrant and associated Post Indicator Valve (PIV) on the southwest side of Building 450, designed for shared access with the adjacent family-camp campground.

· Exterior Hose Bib: Install an exterior freeze-proof (frost-free) commercial hose bib piped from the domestic supply to support equipment and vehicle washing in the parking lot area.

4.3 Mechanical & HVAC Systems

· HVAC Unit: Design and install a high-efficiency mini-split heat pump or dedicated packaged terminal air conditioner (PTAC/packaged unit) sized for the 512 sq. ft. office conditioned space.

· Freeze Protection: Ensure continuous thermostatic controls maintain interior space and riser enclosure above freezing thresholds (>40°F) under historical Grissom winter design conditions.

4.4 Electrical & Infrastructure Upgrades

· Load Calculation: The contractor shall perform a comprehensive electrical load calculation per NFPA 70 (NEC) and UFC 3-520-01.

· Transformer Coordination: Coordinate with Miami-Cass REMC / Peru Utilities at (765) 473-6668 to evaluate the existing 30kVA transformer. The contractor shall furnish and install any required panelboard, conduit, or transformer upgrades necessary to feed the new office, HVAC, and fire protection equipment.

· Lighting & Devices: Install energy-efficient LED recessed lighting and emergency battery backup lighting units per UFC 3-501-01 and NFPA 101.

4.5 Civil & Underground Water Supply

· Water Supply Tie-In: Excavate, route, bed, and backfill a new underground dedicated fire service water line. The primary tie-in point is the municipal water main located in the POL area (approximately 250 feet north of Building 450).

· Utility Coordination: The contractor shall coordinate all excavation, tapping, and water flow/pressure verification directly with Peru Utilities at (765) 473-6681.

· Backflow Prevention: Install an approved double-check backflow prevention assembly (DCBA) or reduced pressure zone (RPZ) device compliant with base water standards.

4.6 Fire Alarm & Mass Notification System (MNS) Integration

· Monaco Control Panel Integration (GARB A-13.1):

· All initiating devices (smoke detectors, manual pull stations, water flow switches, tamper switches, and duct detectors) and notification appliances (horn/strobes) must be fully compatible with and report to the Base central receiving system via an addressable Monaco radio transceiver.

· Mass Notification System (UFC 4-021-01 / GARB A-13.4): Install emergency communication strobes and speakers integrated with the base-wide MNS network for live voice and automated emergency announcements.

· Sole Source Supplier Coordination: Monaco Enterprises is the sole-source supplier for fire alarm transceivers at Grissom ARB. All technical programming, software configuration, and Command Post central station commissioning must be coordinated with:

· Company: Monaco Enterprises, Inc.

· Phone: (509) 926-6277

· Web: https://monaco-inc.com

5.0 SUBMITTAL & DESIGN STAGE REQUIREMENTS

The D-B contractor shall submit design documentation to 434 MSG/CEC and the Base Fire Marshal for review and approval per GARB Base Standards Chapter D at the following milestones:

Design Milestone
Required Deliverables & Documentation
35% Concept Submittal
Preliminary architectural floor plans, 1-hour envelope UL cut-sheets, water flow test data, and initial code compliance matrix.
65% Design Submittal
Structural analysis (slab and self-supporting ceiling), draft sprinkler hydraulic calculations, HVAC sizing schedules, and electrical load analyses.
95% Final Submittal
Sealed PE drawings, manufacturer cut-sheets for Monaco transceiver/FDC/PIV, final hydraulic calculation sheets, and draft testing plans.
100% Construction Issue
Approved stamped construction documents ready for building permit and Notice to Proceed with construction.

6.0 TESTING, TRAINING, AND CLOSEOUT

· Hydraulic & Hydrostatic Testing: Perform a 200 psi (or +50 psi above working pressure) 2-hour hydrostatic pressure test on all aboveground and underground fire piping per NFPA 13 and NFPA 24, witnessed by the Base Fire Inspector.

· Alarm Commissioning: Conduct complete functional acceptance testing of all Monaco alarm points, water flow switches, tamper alarms, and MNS audio audibility/intelligibility per NFPA 72 and UFC 4-021-01.

· Training: Provide a minimum of 4 hours of on-site operations and maintenance (O&M) training to 434 MSG/CEC civil engineering maintenance personnel and Base Fire Department staff.

· Closeout Deliverables: Furnish three (3) complete sets of: O&M manuals, warranty certificates (minimum 1-year general / manufacturer warranties), and CAD/PDF As-Built drawings.