Statement of Need.pdf

PDF 90 KB Posted

Attached to
20TON Split A/C Unit-CANCELED REQUIREMENT
Solicitation number
FA301626Q0046
Issued by

About this file

This Statement of Need outlines the requirement for a 20-ton split air conditioning system, with the contractor responsible for furnishing all supervision, labor, transportation, materials, tools, incidentals, equipment, and quality assurance to procure the specified equipment.

The scope includes three main components: an outdoor condenser unit with a nominal capacity of 20 tons (240,000 BTU/h), 208/230V three-phase 60HZ power requirements, R-454B refrigerant, dual 2-stage scroll compressors, three fans, efficiency ratings up to 11.2 EER and 14.8 IEER, dimensions of approximately 44-3/4" H x 83-7/8" W x 38-3/8" D, and a weight of 926 pounds with a minimum circuit ampacity of 91A and maximum fuse/breaker of 110A. The indoor air handler unit matches the 20-ton capacity with a standard 5HP motor operating at 1725 RPM, 18-inch blower diameter and width, 16.5 square-foot coil face area, 4-row deep coil with 15 fins per inch, a 20 x 25 x 1 filter size, and 230V three-phase 60HZ electrical specifications. Additionally, a commercial heat element kit designed for the 20-ton air handler unit is required with 208/230V three-phase 60HZ power specifications. All components must be compatible and function as an integrated split AC system.

View the file

Other files

File Type Posted
Name Plate AHU B41.jpg JPG image
Heating Element for AHU B41.jpg JPG image
20TON ktr questions.docx DOCX document
IMG_0227.jpeg JPEG file
IMG_0225.jpeg JPEG file
Pic4.jpg JPG image
IMG_0226.jpeg JPEG file
SOO-B41 PURCHASE AC SPLIT SYSTEM.pdf PDF
Solicitation - FA301626Q0046.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF NEED

Equipment Only: 20 TON Split AC System

PROJECT SCOPE: CE shall furnish all supervision; labor, transportation materials, tools, incidentals, equipment, and quality assurance to purchase 20TON Split AC Unit.

SCOPE OF MATERIAL. Purchasing 20TON Split AC Unit.

Material that will be purchased is as follows:

Outdoor Unit (Condenser):

Nominal Capacity: 20 TON (240,000 BTU/h) Voltage: 208/230V – 3 Phase – 60HZ Refrigerant TYPE: R-454B Compressors: 2-Stage (Dual) Scroll Compressors Fans: 3 Efficiency: Up to 11.2 EER / 14.8 IEER Dimensions: ~44-3/4” H x 83-7/8” W x 38- 3/8” D Weight: 926lbs Minimum Circuit Ampacity (MCA): 91A Maximum Fuse/Breaker: 110 A

Inside Unit (Air Handler):

Nominal Capacity: 20 TON (240,000 BTU/h) Motor Horsepower: Standard (1725 RPM) 5HP Blower Diameter: 18 in.

Blower Width: 18 in Blower Shaft Size: 1 in Motor Sheave Size: VP56 1- 1/8” in Belt Type and Size: B51 Coil Face Area 16.5 FT^2 Coil Tube Diameter: 3/8” in Coil Rows Deep: 4 in Fins Per Inch: 15 Refrigerant Control – Thermal Expansion Valve: BBIZE – 12.5 – GA Refrigerant Control – Thermal Expansion Valves No. 2 Filter Size: 20 x 25 x 1 Gauge Top: 18 in

Gauge Side: 16 in Gauge Bottom: 18 in Gauge – Door Covers: 20 in Voltage: 230V Frequency: 60HZ Number of Phases: 3

Commercial Heat Element Kit

For Air Handler Unit: 20 TON Voltage: 208/230V – 3 Phase – 60HZ