This solicitation is for design-bid-build services for the Whole Center Repair project at the Naval Operating Service Center in Bronx, New York. The project scope includes renovating administrative spaces, classrooms, medical spaces, fitness rooms, drill halls, storage rooms, toilet rooms, and vehicle maintenance facilities. The work encompasses civil, structural, architectural, mechanical, plumbing, electrical, force protection, and fire protection improvements. The estimated construction value is between $10-25 million. The NAICS code is 236220 and small business size standard is $39.5 million. All correspondence regarding this solicitation shall be directed to the point of contact listed.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
eProjects Work Order No.: 1145580 WIS/MAXIMO Work Order No.: 4974515
WHOLE CENTER REPAIR
At
NAVY OPERATIONAL SUPPORT CENTER (NOSC)
NEW YORK CITY, NEW YORK
SPECIFICATIONS
VOLUME 2 of 2
PREPARED BY:
Oak Point Associates 231 Main Street
Biddeford, Maine 04005
Construction Contract No. N40085-17-R-5029 A/E Contract No. N40085-16-D-3006, Task Order 004
REQUEST FOR PROPOSAL PREPARED BY:
Architectural: Scott Donovan, R.A. Mechanical: Christine Lyle, P.E.
Civil: Jacques L. Gagnon, Jr., P.E. Electrical: Ketan Shah, P.E.
Structural: David N. Martin, P.E. Fire Protection: Laura E. Clebak, P.E.
Geotechnical: N/A Safety: N/A
Submitted By: Date: March 10, 2017
REQUEST FOR PROPOSAL APPROVED BY:
Specifications:
For Commander, NAVFAC:
Date:
WHOLE CENTER REPAIR, NOSC NEW YORK CITY, BRONX, NEW YORK 1145580
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 15 LIST OF DRAWINGS
00 41 00 BID SCHEDULES
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00.00 22 WORK RESTRICTIONS (PWD ME)
01 20 00.00 20 PRICE AND PAYMENT PROCEDURES (PWD ME)
01 30 00 ADMINISTRATIVE REQUIREMENTS (PWD ME)
01 32 16.00 22 CONSTRUCTION PROGRESS SCHEDULES (PWD ME)
01 33 00 SUBMITTAL PROCEDURES
01 35 26.00 22 GOVERNMENTAL SAFETY REQUIREMENTS (PWD ME)
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 20 QUALITY CONTROL (PWD ME)
01 50 00.00 22 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS (PWD ME)
01 57 19.00 20 TEMPORARY ENVIRONMENTAL CONTROLS (AOR)
01 58 00 PROJECT IDENTIFICATION
01 74 19.00 22 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT (PWD ME)
01 75 00 STARTING AND ADJUSTING
01 78 00.00 22 CLOSEOUT SUBMITTALS (PWD ME)
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 24.00 20 FACILITY ELECTRONIC OPERATION AND MAINTENANCE SUPPORT
INFORMATION (eOMSI)
01 91 13 GENERAL COMMISSIONING REQUIREMENTS (PWD ME)
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION AND DECONSTRUCTION
02 82 16.00 20 ENGINEERING CONTROL OF ASBESTOS CONTAINING MATERIALS (PWD
ME AOR)
02 83 13.00 20 LEAD IN CONSTRUCTION (PWD ME AOR)
02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs
AND MERCURY
02 84 33 REMOVAL AND DISPOSAL OF POLYCHLORINATED BIPHENYLS (PCBs)
DIVISION 03 - CONCRETE
03 01 32 CONCRETE REHABILITATION FOR CIVIL WORKS
03 30 00 CAST-IN-PLACE CONCRETE
03 42 13.00 10 PLANT-PRECAST CONCRETE PRODUCTS FOR BELOW GRADE
CONSTRUCTION
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 52 00 METAL RAILINGS
05 72 00 DECORATIVE METAL SPECIALTIES
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
PROJECT TABLE OF CONTENTS Page 1
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 41 16.00 10 LAMINATE CLAD ARCHITECTURAL CASEWORK
06 61 16 SOLID POLYMER (SOLID SURFACING) AND QUARTZ AGGLOMERATE
FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 13 53 ELASTOMERIC SHEET WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 23 00 SPRAYED POLYURETHANE FOAM (SPF) INSULATION
07 24 00 EXTERIOR INSULATION AND FINISH SYSTEMS (PATCHING AND
REPAIR)
07 52 00 MODIFIED BITUMINOUS MEMBRANE ROOFING (REPAIR, PATCHING
AND ROOFTOP EQUIPMENT CURBS)
07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 55 00 SECURITY WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 87 23.13 SAFETY FILMS
08 91 00 METAL WALL AND DOOR LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 65 66 RESILIENT ATHLETIC FLOORING
09 68 00 CARPETING
09 83 13 ACOUSTICAL WALL TREATMENT
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 11 00 VISUAL DISPLAY UNITS
10 14 00.20 INTERIOR SIGNAGE
10 14 01 EXTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
10 51 13 METAL LOCKERS
DIVISION 11 - EQUIPMENT
11 66 53 GYMNASIUM DIVIDER CURTAIN
PROJECT TABLE OF CONTENTS Page 2
DIVISION 12 - FURNISHINGS
12 66 00 TELESCOPIC CHAIR PLATFORM
DIVISION 14 - CONVEYING EQUIPMENT
14 24 10 VERTICAL WHEELCHAIR LIFTS
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 30 00 FIRE PUMPS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS
23 05 48.00 40 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND
EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00.00 10 COMMISSIONING OF HVAC SYSTEMS
23 09 23.13 20 BACnet DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC
23 11 25 FACILITY GAS PIPING
23 21 13.00 20 LOW TEMPERATURE WATER (LTW) HEATING SYSTEM
23 52 46.00 20 LOW PRESSURE WATER HEATING BOILERS (OVER 800,000 BTU/HR
OUTPUT)
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED WATER PIPING SYSTEMS
23 82 00.00 20 TERMINAL HEATING UNITS
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 31 00 SOLAR PHOTOVOLTAIC (PV) COMPONENTS [OPTION 1]
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 16 PUBLIC ADDRESS SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 23 00.00 22 EXCAVATION AND FILL (PWD ME)
31 32 11 SOIL SURFACE EROSION CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
PROJECT TABLE OF CONTENTS Page 3
32 05 33 LANDSCAPE ESTABLISHMENT
32 12 10 BITUMINOUS TACK COATS
32 12 17 HOT MIX BITUMINOUS PAVEMENT
32 16 13 CONCRETE SIDEWALKS
32 17 23.00 20 PAVEMENT MARKINGS
32 31 13.53 HIGH-SECURITY CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
DIVISION 33 - UTILITIES
33 11 00 WATER DISTRIBUTION
33 30 00 SANITARY SEWERS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
SECTION 08 11 13
STEEL DOORS AND FRAMES
02/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2012; Errata 2011) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A653/A653M (2011) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A879/A879M (2012) Standard Specification for Steel Sheet, zinc Coated by the Electrolytic Process for Applications Requiring Designation of the Coating Mass on Each Surface
ASTM A924/A924M (2013) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM C578 (2012b) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C591 (2012a) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C612 (2010) Mineral Fiber Block and Board Thermal Insulation
ASTM D2863 (2012) Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
ASTM E1300 (2012a; E 2012) Determining Load Resistance of Glass in Buildings
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
SECTION 08 11 13 Page 1
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.115 (2006) Hardware Preparation in Steel Doors and Steel Frames
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 252 (2012) Standard Methods of Fire Tests of Door Assemblies
NFPA 80 (2013) Standard for Fire Doors and Other Opening Protectives
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR 111 (2009) Recommended Selection and Usage Guide for Standard Steel Doors, Frames and Accessories
SDI/DOOR 113 (2001; R2006) Standard Practice for Determining the Steady State Thermal Transmittance of Steel Door and Frame Assemblies
SDI/DOOR A250.11 (2001) Recommended Erection Instructions for Steel Frames
SDI/DOOR A250.6 (2003; R2009) Recommended Practice for Hardware Reinforcing on Standard Steel Doors and Frames
SDI/DOOR A250.8 (2003; R2008) Recommended Specifications for Standard Steel Doors and Frames
UNDERWRITERS LABORATORIES (UL)
UL 10C (2009) Standard for Positive Pressure Fire Tests of Door Assemblies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section
01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Doors; G
Frames; G
Borrowed Lites; G
Accessories
Weatherstripping
Show elevations, construction details, metal gages, hardware
SECTION 08 11 13 Page 2 provisions, method of glazing, and installation details.
Schedule of doors; G
Schedule of frames; G
Submit door and frame locations.
SD-03 Product Data
Doors; G
Frames; G
Accessories
Weatherstripping
Submit manufacturer's descriptive literature for doors, frames, and accessories. Include data and details on door construction, panel (internal) reinforcement, insulation, and door edge construction.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors, frames, and accessories undamaged and with protective wrappings or packaging. Strap knock-down frames in bundles. Provide temporary steel spreaders securely fastened to the bottom of each welded frame. Store doors and frames on platforms under cover in clean, dry, ventilated, and accessible locations, with 1/4 inch airspace between doors. Remove damp or wet packaging immediately and wipe affected surfaces dry. Replace damaged materials with new.
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
SDI/DOOR A250.8 , except as specified otherwise. Prepare doors to receive door hardware as specified in Section 08 71 00. Undercut where indicated. Exterior doors shall have top edge closed flush and sealed to prevent water intrusion. Doors shall be 1-3/4 inch thick, unless otherwise indicated Provide exterior glazing in accordance with ASTM F2248 and ASTM E1300.
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Maximum Duty Doors
SDI/DOOR A250.8 , Level 4, physical performance Level A, Model 1 with core construction as required by the manufacturer for interior doors and for indicated exterior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are required, the space between the stiffeners shall be filled with mineral board insulation. Provide Level 4 where indicated.
SECTION 08 11 13 Page 3
2.2 ACCESSORIES
2.2.1 Louvers
2.2.1.1 Interior Louvers
SDI/DOOR 111 , Louvers shall be stationary sightproof type where scheduled. Detachable moldings on room or non security side of door; on security side of door, moldings to be integral part of louver. Form louvers from extruded aluminum.
2.2.2 Astragals
For pairs of exterior steel doors which will not have aluminum astragals or removable mullions, as specified in Section 08 71 00 DOOR HARDWARE provide overlapping steel astragals with the doors.
2.2.3 Moldings
Provide moldings around glass of interior and exterior doors and louvers of interior doors. Provide nonremovable moldings on outside of exterior doors and on corridor side of interior doors. Other moldings may be stationary or removable. Secure inside moldings to stationary moldings, or provide snap-on moldings. Muntins shall interlock at intersections and shall be fitted and welded to stationary moldings.
2.2.4 Shelves for Dutch Doors
SDI/Door III. Fabricate doors of steel not lighter than 16 gauge, 1 inch wide. Brackets shall be stock type fabricated of the same metal used to fabricate shelves.
2.3 INSULATION CORES
Insulated cores shall be of type specified, and provide an apparent U-factor of 0.48 in accordance with SDI/DOOR 113 and shall conform to:
a. Rigid Cellular Polyisocyanurate Foam: ASTM C591, Type I or II, foamed-in-place or in board form, with oxygen index of not less than 22 percent when tested in accordance with ASTM D2863; or
b. Rigid Polystyrene Foam Board: ASTM C578, Type I or II; or
c. Mineral board: ASTM C612, Type I.
2.4 STANDARD STEEL FRAMES
SDI/DOOR A250.8 , Level 4, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners or knock-down field-assembled corners as indicated. Provide steel frames for doors, sidelights, mullions, and interior glazed panels, unless otherwise indicated.
2.4.1 Welded Frames (New Openings)
Continuously weld frame faces at corner joints. Mechanically interlock or continuously weld stops and rabbets. Grind welds smooth.
Weld frames in accordance with the recommended practice of the Structural
SECTION 08 11 13 Page 4
Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with the practice specified by the producer of the metal being welded.
2.4.2 Knock-Down Frames (Existing/Renovated Openings)
Design corners for simple field assembly by concealed tenons, splice plates, or interlocking joints that produce square, rigid corners and a tight fit and maintain the alignment of adjoining members. Provide locknuts for bolted connections.
2.4.3 Mullions and Transom Bars
Mullions and transom bars shall be closed or tubular construction and be a member with heads and jambs butt-welded thereto or knock-down for field assembly. Bottom of door mullions shall have adjustable floor anchors and spreader connections.
2.4.4 Stops and Beads
Form stops and beads from 20 gage steel. Provide for glazed and other openings in standard steel frames. Secure beads to frames with oval-head, countersunk Phillips self-tapping sheet metal screws or concealed clips and fasteners. Space fasteners approximately 12 to 16 inch on center.
Miter molded shapes at corners. Butt or miter square or rectangular beads at corners.
2.4.5 Anchors
Provide anchors to secure the frame to adjoining construction. Provide steel anchors, zinc-coated or painted with rust-inhibitive paint, not lighter than 18 gage.
2.4.5.1 Wall Anchors
Provide at least three anchors for each jamb. For frames which are more than 7.5 feet in height, provide one additional anchor for each jamb for each additional 2.5 feet or fraction thereof.
a. Masonry: Provide anchors of corrugated or perforated steel straps or 3/16 inch diameter steel wire, adjustable or T-shaped;
b. Stud partitions: Weld or otherwise securely fasten anchors to backs of frames. Design anchors to be fastened to closed steel studs with sheet metal screws, and to open steel studs by wiring or welding; and
c. Completed openings: Secure frames to previously placed concrete or masonry with expansion bolts in accordance with SDI/DOOR 111 .
2.4.5.2 Floor Anchors
Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each jamb member.
2.5 FIRE DOORS AND FRAMES
NFPA 80 and this specification. The requirements of NFPA 80 shall take precedence over details indicated or specified.
SECTION 08 11 13 Page 5
2.5.1 Labels
Fire doors and frames shall bear the label of Underwriters Laboratories (UL), Factory Mutual Engineering and Research (FM), or Warnock Hersey International (WHI) attesting to the rating required. Testing shall be in accordance with NFPA 252 or UL 10C . Labels shall be metal with raised letters, and shall bear the name or file number of the door and frame manufacturer. Labels shall be permanently affixed at the factory to frames and to the hinge edge of the door. Door labels shall not be painted.
2.5.2 Oversized Doors
For fire doors and frames which exceed the size for which testing and labeling are available, furnish certificates stating that the door and frames are identical in design, materials, and construction to a door which has been treated and meets the requirements for the class indicated.
2.5.3 Astragal on Fire Doors
On pairs of labeled fire doors, conform to NFPA 80 and UL requirements.
2.6 Borrowed Lites
Hollow metal full profile welded frames of steel sheet, minimum thickness
0.053 inch. Provide safety glazing. Refer to Section 08 81 00 GLAZING.
2.7 WEATHERSTRIPPING
As specified in Section 08 71 00 DOOR HARDWARE.
2.8 HARDWARE PREPARATION
Provide minimum hardware reinforcing gages as specified in SDI/DOOR A250.6 .
Drill and tap doors and frames to receive finish hardware. Prepare doors and frames for hardware in accordance with the applicable requirements of SDI/DOOR A250.8 and SDI/DOOR A250.6 . For additional requirements refer to ANSI/BHMA A156.115 . Drill and tap for surface-applied hardware at the project site. Build additional reinforcing for surface-applied hardware into the door at the factory. Locate hardware in accordance with the requirements of SDI/DOOR A250.8 , as applicable. Punch door frames to receive a minimum of two rubber or vinyl door silencers on lock side of single doors and one silencer for each leaf at heads of double doors. Set lock strikes out to provide clearance for silencers.
2.9 FINISHES
2.9.1 Factory-Primed Finish
All surfaces of doors and frames shall be thoroughly cleaned, chemically treated and factory primed with a rust inhibiting coating as specified in
SDI/DOOR A250.8 .
2.9.2 Hot-Dip Zinc-Coated and Factory-Primed Finish
Fabricate exterior doors and frames from hot dipped zinc coated steel, alloyed type, that complies with ASTM A924/A924M and ASTM A653/A653M . The coating weight shall meet or exceed the minimum requirements for coatings having 0.4 ounces per square foot, total both sides, i.e., A40. Repair
SECTION 08 11 13 Page 6 damaged zinc-coated surfaces by the application of zinc dust paint.
Thoroughly clean and chemically treat to insure maximum paint adhesion.
Factory prime as specified in SDI/DOOR A250.8 .
2.9.3 Electrolytic Zinc-Coated Anchors and Accessories
Provide electrolytically deposited zinc-coated steel in accordance with ASTM A879/A879M , Commercial Quality, Coating Class A. Phosphate treat and factory prime zinc-coated surfaces as specified in SDI/DOOR A250.8 .
2.10 FABRICATION AND WORKMANSHIP
Finished doors and frames shall be strong and rigid, neat in appearance, and free from defects, waves, scratches, cuts, dents, ridges, holes, warp, and buckle. Molded members shall be clean cut, straight, and true, with joints coped or mitered, well formed, and in true alignment. Dress exposed welded and soldered joints smooth. Design door frame sections for use with the wall construction indicated. Corner joints shall be well formed and in true alignment. Conceal fastenings where practicable. On wraparound frames for masonry partitions, provide a throat opening 1/8 inch larger than the actual masonry thickness. Design other frames in exposed masonry walls or partitions to allow sufficient space between the inside back of trim and masonry to receive caulking compound.
2.10.1 Grouted Frames
For frames to be installed in exterior walls and to be filled with mortar or grout, fill the stops with strips of rigid insulation to keep the grout out of the stops and to facilitate installation of stop-applied head and jamb seals.
2.11 PROVISIONS FOR GLAZING
Materials are specified in Section 08 81 00 GLAZING.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Frames
Set frames in accordance with SDI/DOOR A250.11 . Plumb, align, and brace securely until permanent anchors are set. Anchor bottoms of frames with expansion bolts or powder-actuated fasteners. Build in or secure wall anchors to adjoining construction. For frames in exterior walls, ensure that stops are filled with rigid insulation before grout is placed.
3.1.2 Doors
Hang doors in accordance with clearances specified in SDI/DOOR A250.8 .
After erection and glazing, clean and adjust hardware.
3.1.3 Fire Doors and Frames
Install fire doors and frames, including hardware, in accordance with
NFPA 80 .
SECTION 08 11 13 Page 7
3.2 PROTECTION
Protect doors and frames from damage. Repair damaged doors and frames prior to completion and acceptance of the project or replace with new, as directed. Wire brush rusted frames until rust is removed. Clean thoroughly. Apply an all-over coat of rust-inhibitive paint of the same type used for shop coat.
3.3 CLEANING
Upon completion, clean exposed surfaces of doors and frames thoroughly.
Remove mastic smears and other unsightly marks.
-- End of Section --
SECTION 08 11 13 Page 8
SECTION 08 14 00
WOOD DOORS
08/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ARCHITECTURAL WOODWORK INSTITUTE (AWI)
AWI AWS (2009) Architectural Woodwork Standards
ASTM INTERNATIONAL (ASTM)
ASTM E2226 (2012) Standard Practice for Application of Hose Stream
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 252 (2012) Standard Methods of Fire Tests of Door Assemblies
NFPA 80 (2013) Standard for Fire Doors and Other Opening Protectives
UNDERWRITERS LABORATORIES (UL)
UL 10B (2008; Reprint Apr 2009) Fire Tests of Door Assemblies
WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)
WDMA I.S. 1-A (2007) Architectural Wood Flush Doors
WDMA TM-7 (2008) Cycle Slam Test Method
WDMA TM-8 (2008) Hinge Loading Test Method
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. The following shall be submitted in accordance with Section
01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Doors; G
Submit drawings or catalog data showing each type of door unit;
descriptive data of head and jamb weatherstripping with installation instructions shall be included. Drawings and data
SECTION 08 14 00 Page 1 shall indicate door type and construction, sizes, thickness, methods of assembly and glazing.
SD-03 Product Data
Doors; G
Accessories
Water-resistant sealer
Sample warranty
Fire resistance rating; G
SD-06 Test Reports
Cycle-slam
Hinge loading resistance
Submit cycle-slam test report for doors tested in accordance with WDMA TM-7, and hinge loading resistance test report for doors tested in accordance with WDMA TM-8.
SD-07 Certificates
Certificates of Grade
SD-11 Closeout Submittals
Warranty
1.3 CERTIFICATIONS
1.3.1 Certified Wood Grades
Provide certificates of grade from the grading agency on fire doors.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver doors to the site in an undamaged condition and protect against damage and dampness. Stack doors flat under cover. Support on blocking, a minimum of 4 inch thick, located at each end and at the midpoint of the door. Store doors in a well-ventilated building so that they will not be exposed to excessive moisture, heat, dryness, direct sunlight, or extreme changes of temperature and humidity. Do not store in a building under construction until concrete, masonry work, and plaster are dry. Replace defective or damaged doors with new ones.
1.5 WARRANTY
Warrant doors free of defects as set forth in the door manufacturer's standard door warranty.
SECTION 08 14 00 Page 2
PART 2 PRODUCTS
2.1 DOORS
Provide doors of the types, sizes, and designs indicated free of urea-formaldehyde resins.
2.1.1 Flush Doors
Conform to WDMA I.S. 1-A for flush doors. Provide hollow core doors with lock blocks and 1 inch minimum thickness hinge stile. Hardwood stile edge bands of doors receives a natural finish, compatible with face veneer.
Provide mill option for stile edge of doors scheduled to be painted. No visible finger joints will be accepted in stile edge bands. When used, locate finger-joints under hardware.
2.1.1.1 Interior Flush Doors
Provide staved lumber core, Type II flush doors conforming to WDMA I.S. 1-A with faces of premium white birch. Hardwood veneers shall be plain sliced and book matched.
2.1.2 Fire Doors
Provide doors specified or indicated to have a fire resistance rating conforming to the requirements of UL 10B , ASTM E2226, or NFPA 252 for the class of door indicated. Affix a permanent metal label with raised or incised markings indicating testing agency's name and approved hourly fire rating to hinge edge of each door.
2.2 ACCESSORIES
2.2.1 Door Light Openings
Provide glazed openings with the manufacturer's standard wood moldings.
Lip type mouldings for flush doors.
2.2.2 Additional Hardware Reinforcement
Provide the minimum lock blocks to secure the specified hardware. The measurement of top, bottom, and intermediate rail blocks are a minimum 125 mm 5 inch by full core width. Comply with the manufacturer's labeling requirements for reinforcement blocking, but not mineral material similar to the core.
2.3 FABRICATION
2.3.1 Marking
Stamp each door with a brand, stamp, or other identifying mark indicating quality and construction of the door.
2.3.2 Quality and Construction
Identify the standard on which the construction of the door was based.
2.3.3 Adhesives and Bonds
WDMA I.S. 1-A . Use Type II bond for interior doors. Provide a
SECTION 08 14 00 Page 3 nonstaining adhesive on doors with a natural finish.
2.3.4 Prefitting
Provide factory prefinished and factory prefitted doors for the specified hardware, door frame and door-swing indicated. Machine and size doors at the factory by the door manufacturer in accordance with the standards under which the doors are produced and manufactured. The work includes sizing, beveling edges, mortising, and drilling for hardware and providing necessary beaded openings for glass and louvers. Provide the door manufacturer with the necessary hardware samples, and frame and hardware schedules to coordinate the work.
2.3.5 Finishes
2.3.5.1 Factory Finish
Provide doors finished at the factory by the door manufacturer as follows:
AWI AWS Section 1500, specification for System No. 4 Conversion varnish alkyd urea or System No. 5 Vinyl catalyzed. The coating is AWI AWS premium, medium rubbed sheen, closed grain effect. Use stain when required to produce the finish specified for color. Seal edges, cutouts, trim, and wood accessories, and apply two coats of finish compatible with the door face finish. Touch-up finishes that are scratched or marred, or where exposed fastener holes are filled, in accordance with the door manufacturer's instructions. Match color and sheen of factory finish using materials compatible for field application.
2.3.5.2 Color
Provide door finish colors as indicated.
2.3.6 Water-Resistant Sealer
Provide manufacturer's standard water-resistant sealer compatible with the specified finishes.
2.4 SOURCE QUALITY CONTROL
Meet or exceed the following minimum performance criteria of stiles of "B" and "C" label fire doors utilizing standard mortise leaf hinges:
a. Cycle-slam: 200,000 cycles with no loose hinge screws or other visible signs of failure when tested in accordance with the requirements of WDMA TM-7.
b. Hinge loading resistance: Averages of ten test samples not less than 700 pounds load when tested for direct screw withdrawal in accordance with WDMA TM-8 using a No. 12, 1-1/4 inch long, steel, fully threaded wood screw. Drill 5/32 inch pilot hole, use 1-1/2 inch opening around screw for bearing surface, and engage screw full, except for last 1/8 inch. Do not use a steel plate to reinforce screw area.
PART 3 EXECUTION
3.1 INSTALLATION
Before installation, seal top and bottom edges of doors with the approved water-resistant sealer. Seal cuts made on the job immediately after
SECTION 08 14 00 Page 4 cutting using approved water-resistant sealer. Fit, trim, and hang doors with a 1/16 inch minimum, 1/8 inch maximum clearance at sides and top, and a3/16 inch minimum, 1/4 inch maximum clearance over thresholds. Provide 3/8 inch minimum, 7/16 inch maximum clearance at bottom where no threshold occurs. Bevel edges of doors at the rate of 1/8 inch in 2 inch. Door warp shall not exceed1/4 inch when measured in accordance with
WDMA I.S. 1-A .
3.1.1 Fire Doors
Install fire doors in accordance with NFPA 80 . Do not paint over labels.
SECTION 08 14 00 Page 5
SECTION 08 55 00
SECURITY WINDOWS
02/15
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 611 (1998; R 2004) Voluntary Specification for Anodized Architectural Aluminum
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2010; Errata 2011) Structural Welding Code - Steel
AWS D1.2/D1.2M (2014) Structural Welding Code - Aluminum
AWS D1.3 (2008; Errata 2008) Structural Welding Code - Sheet Steel
AWS D1.6 (2014) Structral Welding Code - Stainless Steel
ASTM INTERNATIONAL (ASTM)
ASTM A240/A240M (2014) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A307 (2012) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A666 (2010) Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM B209 (2010) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2013) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B633 (2013) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C509 (2006; R 2011) Elastomeric Cellular
SECTION 08 55 00 Page 1
Preformed Gasket and Sealing Material
ASTM D1187 (1997; E 2011; R 2011) Asphalt-Base Emulsions for Use as Protective Coatings for Metal
ASTM D2000 (2012) Standard Classification System for Rubber Products in Automotive Applications
ASTM D2287 (2012) Nonrigid Vinyl Chloride Polymer and Copolymer Molding and Extrusion Compounds
ASTM F1233 (2008; R 2013) Security Glazing Materials and Systems
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM/NOMMA 500 (2006) Finishes Manual for Architectural Finish Products
UNDERWRITERS LABORATORIES (UL)
UL 752 (2005; Reprint Jul 2011) Standard for Bullet-Resisting Equipment
1.2 RELATED DOCUMENTS
Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Security Windows
Include plans, elevations, sections, and attachments to other work. Full-size section details of framing members, including internal armoring, reinforcement, and stiffeners. Location of weep holes. Glazing details. Details of deal tray.
Configuration Disclosure Drawing: For each type of forced-entry-resistant security window, complying with ASTM F1233.
SD-03 Product Data
For each type of product. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for window units.
SD-06 Test Reports
For each type of security window and accessory indicated as
SECTION 08 55 00 Page 2 ballistics or forced-entry resistant, for tests performed by a qualified testing agency.
Sample Warranty: For special warranty.
Examination reports documenting inspections of substrates, areas, and conditions.
Anchor inspection reports documenting inspections of built-in and cast-in anchors.
Field quality-control reports documenting inspections of installed products. Field quality-control certification signed by Contractor.
SD-07 Certificates
Installer Qualifications and Testing Agency
Welding Qualifications
1.4 COORDINATION
Coordinate installation of anchorages for security windows. Furnish setting drawings, templates, and directions for installing anchorages, including sleeves, concrete inserts, anchor bolts, and items with integral anchors, that are to be embedded in adjacent construction. Deliver such items to Project site in time for installation.
1.5 QUALITY ASSURANCE
1.5.1 Installer Qualifications
An authorized representative who is trained and approved by manufacturer for installation of units required for this Project.
1.5.2 Welding Qualifications
Qualify procedures and personnel according to the following:
1. AWS D1.1/D1.1M , "Structural Welding Code - Steel."
2. AWS D1.2/D1.2M , "Structural Welding Code - Aluminum."
3. AWS D1.3 , "Structural Welding Code - Sheet Steel."
4. AWS D1.6 , "Structural Welding Code - Stainless Steel."
1.6 DELIVERY, STORAGE, AND HANDLING
Pack security windows in wood crates for shipment. Crate glazing separate from frames unless factory glazed. Label security window packaging with drawing designation. Store crated security windows on raised blocks to prevent moisture damage.
1.7 FIELD CONDITIONS
Field Measurements: Verify actual dimensions of openings by field measurements before fabrication.
SECTION 08 55 00 Page 3
1.8 WARRANTY
Special Warranty: Manufacturer agrees to repair or replace security windows that fail in materials or workmanship within specified warranty period. Failures include, but are not limited to, the following:
a. Structural failures including deflections exceeding 1/4 inch.
b. Failure of welds.
c. Excessive air leakage.
d. Faulty operation of sliding window hardware.
e. Faulty operation of transaction drawers.
f. Deterioration of metals, metal finishes, and other materials beyond normal weathering and use.
Warranty Period: Minimum three years from date of Substantial Completion.
PART 2 PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
2.1.1 Attack Resistance
Provide units identical to those tested for compliance with requirements indicated, as as follows:
1. Ballistics Resistance: Listed and labeled as Level 3 when tested according to UL 752 .
2. Forced-Entry Resistance: Class II when tested according to ASTM F1233.
2.2 FIXED, TRANSACTION SECURITY WINDOWS
Provide fixed, framed transaction windows with operable sash or ventilator capable of allowing transfer of currency and documents.
2.2.1 Configuration
One fixed-glazed panel.
2.2.2 Framing
Fabricate perimeter framing, mullions, and glazing stops from aluminum as follows:
1. Profile: Manufacturer's standard, with minimum face dimension indicated. Minimum Face Dimension: 2 inches.
2. Depth: Manufacturer's standard.
3. Provide thermally improved construction for aluminum framing.
2.2.3 Head and Jamb Framing
Designed for gasket glazing.
2.2.4 Voice-Communication-Type Sill
Formed from stainless steel and designed to allow passage of speech at normal speaking volume without distortion.
1. Sill Depth: 12 inches.
2. Transaction Counter: Stainless steel, 12 inches deep by width of
SECTION 08 55 00 Page 4 security window, with integral deal tray centered in opening.
2.2.5 Glazing and Glazing Materials
Comply with requirements in Section 08 81 00 GLAZING.
2.2.6 Materials
1. Stainless-Steel Sheet, Strip, Plate, and Flat Bars: ASTM A666 or ASTM A240/A240M , austenitic stainless steel, Type 304.
2. Aluminum Extrusions: ASTM B221. Provide alloy and temper recommended by manufacturer for strength, corrosion resistance, and application of required finish, but not less than 22,000-psi ultimate tensile strength.
3. Aluminum Sheet and Plate: ASTM B209.
2.3 FABRICATION
2.3.1 General
Fabricate security windows to provide a complete system for assembly of components and anchorage of window units.
1. Provide units that are reglazable from the secure side without dismantling the nonsecure side of framing.
2. Prepare security windows for glazing unless preglazing at the factory is indicated.
Provide weep holes and internal water passages for exterior security windows to conduct infiltrating water to the exterior.
2.3.2 Framing
Miter or cope corners the full depth of framing; weld and dress smooth.
Fabricate framing with manufacturer's standard, internal opaque armoring in thicknesses required for security windows to comply with ballistics-resistance performance indicated.
2.3.3 Glazing Stops
Finish glazing stops to match security window framing.
1. Secure-Side (Exterior) Glazing Stops: Welded or integral to framing.
2. Nonsecure-Side (Interior) Glazing Stops: Removable, coordinated with glazing indicated.
2.3.4 Welding
Weld components to comply with referenced AWS standard. To greatest extent possible, weld before finishing and in concealed locations to minimize distortion or discoloratio of finish. Remove weld spatter and welding oxides from exposed surfaces by descaling or grinding.
2.3.5 Metal Protection
Separate dissimilar metals to protect against galvanic action by painting contact surfaces with primer or by applying sealant or tape recommended by manufacturer for this purpose.
SECTION 08 55 00 Page 5
2.3.6 Preglazed Fabrication
Preglaze window units at factory, where required for applications indicated.
2.3.7 Weatherstripping
Factory applied.
2.4 GENERAL FINISH REQUIREMENTS
Comply with NAAMM/NOMMA 500 for recommendations for applying and designating finishes. Protect mechanical finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping. Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
2.5 FINISHES
2.5.1 Aluminum Color Finishes
Anodic Finish: AAMA 611, AA-M12C22A42/44, Class I, 0.018 mm or thicker.
2.5.2 Stainless-Steel Finishes
Directional satin finish No. 4 with grain of directional finish awning with long dimension of each piece.
2.6 ACCESSORIES
2.6.1 Recessed, Nonricochet Deal Trays
Formed from stainless steel; fabricated with recessed bullet trap to ricochet bullets away from secure side, with exposed flanges for recessed installation into horizontal surface, and with sliding stainless-steel cover.
1. Clear Opening Size: 12 inches wide by 8 inches deep by 1-1/2 inches high.
2. Bullet Trap Location: Secure side.
3. Ballistics Resistance: Same as security window.
4. Listed and labeled as bullet resisting according to UL 752 .
2.6.2 Concealed Bolts
ASTM A307, Grade A unless otherwise indicated.
2.6.3 Embedded Plate Anchors
Fabricated from mild steel shapes and plates, minimum 3/16 inch thick;
with minimum 1/2-inch-diameter, headed studs welded to back of plate.
2.6.4 Welding Rods and Bare Electrodes
Select according to AWS specifications for metal alloy welded.
SECTION 08 55 00 Page 6
2.6.5 Compression-Type Glazing Strips and Weather Stripping
Unless otherwise indicated, provide compressible stripping for glazing and weather stripping, such as molded EPDM or neoprene gaskets complying with ASTM D2000, Designations 2BC415 to 3BC620; molded PVC gaskets complying with ASTM D2287; or molded, expanded EPDM or neoprene gaskets complying with ASTM C509, Grade 4.
2.6.6 Miscellaneous Glazing Materials
Provide material, size, and shape complying with requirements of glass manufacturers and with a proven record of compatibility with surfaces contacted in installation.
1. Cleaners, Primers, and Sealers: Type recommended by sealant or gasket manufacturer.
2. Setting Blocks: Elastomeric material with a Type A Shore durometer hardness of 85, plus or minus 5.
3. Spacers: Elastomeric blocks or continuous extrusions with a Type A Shore durometer hardness required by glass manufacturer to maintain glass lites in place for installation indicated.
4. Edge Blocks: Elastomeric material of hardness needed to limit glass lateral movement (side walking).
2.6.7 Anchors, Clips, and Window Accessories
Stainless steel; hot-dip, zinc-coated steel or iron, complying with ASTM B633; provide sufficient strength to withstand design pressures indicated.
2.6.8 Bituminous Paint
Cold-applied asphalt emulsion complying with ASTM D1187.
2.6.9 Sealants
For sealants required within fabricated security windows, provide type recommended by manufacturer for joint size and movement. Sealant shall remain permanently elastic, nonshrinking, and nonmigrating.
PART 3 EXECUTION
3.1 EXAMINATION
Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of security windows. Examine roughing-in for embedded and built-in anchors to verify actual locations of security window connections before security window installation. For the record, prepare written report, endorsed by Installer, listing conditions detrimental to performance of security windows. Inspect built-in and cast-in anchor installations, before installing security windows, to verify that anchor installations comply with requirements. Prepare inspection reports.
1. Remove and replace anchors where inspections indicate that they do not comply with specified requirements. Reinspect after repairs or replacements are made.
2. Perform additional inspections to determine compliance of replaced
SECTION 08 55 00 Page 7 or additional work. Prepare anchor inspection reports.
For glazing materials whose orientation is critical for performance, verify installation orientation. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
3.2.1 Coordination
Furnish layouts for anchors, clips, and other security window anchors.
3.3 INSTALLATION
3.3.1 Fastening to In-Place Construction
Provide anchorage devices and fasteners where necessary for securing security windows to in-place construction. Include threaded fasteners for inserts, security fasteners, and other connectors.
Install an attached or integral flange to secure side of security windows extending over rough-in opening gap so that gap has same forced-entry-resistance and ballistics-resistance performance as security window.
3.3.2 Glazed Framing
Provide gasket-glazed framing.
3.3.3 Removable Glazing Stops and Trim
Fasten components with security fasteners.
3.3.4 Fasteners
Install security windows using fasteners recommended by manufacturer with head style appropriate for installation requirements, strength, and finish of adjacent materials.
3.3.5 Sealants
Comply with requirements in Section 079200 "Joint Sealants" for installing sealants, fillers, and gaskets.
1. Set continuous sill members and flashing in a full sealant bed to provide weathertight construction unless otherwise indicated.
2. Seal frame perimeter with sealant to provide weathertight construction unless otherwise indicated.
3.3.6 Metal Protection
Where dissimilar metals will contact each other, protect against galvanic action by painting contact surfaces with primer or by applying sealant or tape recommended in writing by manufacturer for this purpose. Where aluminum will contact concrete or masonry, protect against corrosion by painting contact surfaces with bituminous paint.
SECTION 08 55 00 Page 8
3.4 FIELD QUALITY CONTROL
Inspect installed products to verify compliance with requirements. Prepare inspection reports and indicate compliance with and deviations from the Contract Documents. Perform additional inspections to determine compliance of replaced or additional work. Prepare inspection reports.
Prepare field quality-control certification that states installed products and their installation comply with requirements in the Contract Documents.
3.5 ADJUSTING
Remove and replace defective work, including security windows that are warped, bowed, or otherwise unacceptable.
3.6 CLEANING AND PROTECTION
Clean surfaces promptly after installation of security windows. Take care to avoid damaging the finish. Remove excess glazing and sealant compounds, dirt, and other substances.
1. Lubricate sliding security window hardware.
2. Lubricate transaction drawer hardware.
Clean glass of preglazed security windows promptly after installation.
Comply with requirements in Section 08 81 00 "GLAZING" for cleaning and maintenance. Provide temporary protection to ensure that security windows are without damage at time of Substantial Completion.
SECTION 08 55 00 Page 9
SECTION 08 71 00
DOOR HARDWARE
02/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM E283 (2004; R 2012) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.1 (2013) Butts and Hinges
ANSI/BHMA A156.12 (2013) Interconnected Locks & Latches
ANSI/BHMA A156.13 (2012) Mortise Locks & Latches Series 1000
ANSI/BHMA A156.15 (2015) Release Devices Closer Holder, Electromagnetic and Electromechanical
ANSI/BHMA A156.16 (2013) Auxiliary Hardware
ANSI/BHMA A156.18 (2012) Materials and Finishes
ANSI/BHMA A156.2 (2011) Bored and Preassembled Locks and Latches
ANSI/BHMA A156.21 (2014) Thresholds
ANSI/BHMA A156.22 (2012) Door Gasketing and Edge Seal Systems
ANSI/BHMA A156.26 (2012) Continuous Hinges
ANSI/BHMA A156.29 (2012) Exit Locks, Exit Alarms, Alarms for Exit Devices
ANSI/BHMA A156.3 (2014) Exit Devices
ANSI/BHMA A156.4 (2013) Door Controls - Closers
ANSI/BHMA A156.5 (2014) Cylinder and Input Devices for Locks
ANSI/BHMA A156.6 (2015) Architectural Door Trim
ANSI/BHMA A156.7 (2014) Template Hinge Dimensions
SECTION 08 71 00 Page 1
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2015; ERTA 2015) Life Safety Code
NFPA 252 (2012) Standard Methods of Fire Tests of Door Assemblies
NFPA 72 (2013) National Fire Alarm and Signaling Code
NFPA 80 (2016) Standard for Fire Doors and Other Opening Protectives
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR A250.8 (2003; R2008) Recommended Specifications for Standard Steel Doors and Frames
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL Bld Mat Dir (2012) Building Materials Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Manufacturer's Detail Drawings; G
Hardware Schedule; G
Keying System; G
SD-03 Product Data
Hardware Items; G
SD-08 Manufacturer's Instructions
Installation
SD-10 Operation and Maintenance Data
Hardware Schedule Items, Data Package 1; G
SD-11 Closeout Submittals
Key Bitting
SECTION 08 71 00 Page 2
1.3 SHOP DRAWINGS
Submit manufacturer's detail drawings indicating all hardware assembly components and interface with adjacent construction. Indicate power components and wiring coordination for electrified hardware.
1.4 PRODUCT DATA
Indicate fire-ratings at applicable components. Provide documentation of ABA/ADA accessibility compliance of applicable components, as required by 36 CFR 1191 Appendix D - Technical.
1.5 HARDWARE SCHEDULE
Prepare and submit hardware schedule in the following form:
Hardware Item
Quantity Size Reference Publi-cation Type No.
Finish Mfr Name and Catalog No.
Key Control Symbols
UL Mark (If fire-rated and listed)
BHMA
Finish Desig-nation
In addition, submit hardware schedule data package 1 in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.
1.6 KEY BITTING CHART REQUIREMENTS
1.6.1 Requirements
Submit key bitting charts to the Contracting Officer prior to completion of the work. Include:
a. Complete listing of all keys (e.g. AA1 and AA2).
b. Complete listing of all key cuts (AA1-123456, AA2-123458).
c. Tabulation showing which key fits which door.
d. Copy of floor plan showing doors and door numbers.
e. Listing of 20 percent more key cuts than are presently required in each master system.
1.7 QUALITY ASSURANCE
1.7.1 Hardware Manufacturers and Modifications
Provide, as far as feasible, locks, hinges, and closers of one lock, hinge, or closer manufacturer's make. Modify hardware as necessary to provide features indicated or specified.
1.7.2 Key Shop Drawings Coordination Meeting
Prior to the submission of the key shop drawing, the Contracting Officer, Contractor, Door Hardware Subcontractor, using Activity and Base Locksmith
SECTION 08 71 00 Page 3 must meet to discuss and coordinate key requirements for the facility.
1.8 DELIVERY, STORAGE, AND HANDLING
Deliver hardware in original individual containers, complete with necessary appurtenances including fasteners and instructions. Mark each individual container with item number as shown on hardware schedule.
Deliver permanent keys and removable cores to the Contracting Officer, either directly or by certified mail. Deliver construction master keys with the locks.
PART 2 PRODUCTS
2.1 TEMPLATE HARDWARE
Hardware applied to metal or to prefinished doors must be manufactured using a template. Provide templates to door and frame manufacturers in accordance with ANSI/BHMA A156.7 for template hinges. Coordinate hardware items to prevent interference with other hardware.
2.2 HARDWARE FOR FIRE DOORS AND EXIT DOORS
Provide all hardware necessary to meet the requirements of NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, NFPA 252 for fire tests of door assemblies, ABA/ADA accessibility requirements, and all other requirements indicated, even if such hardware is not specifically mentioned in paragraph HARDWARE SCHEDULE. Provide Underwriters Laboratories, Inc. labels for such hardware in accordance with UL Bld Mat Dir or equivalent labels in accordance with another testing laboratory approved in writing by the Contracting Officer.
2.3 HARDWARE ITEMS
Clearly and permanently mark with the manufacturer's name or trademark, hinges, locks, latches, exit devices, bolts and closers where the identifying mark is visible after the item is installed. For closers with covers, the name or trademark may be beneath the cover.
2.3.1 Hinges
Provide in accordance with ANSI/BHMA A156.1 . Provide hinges that are 4-1/2 by 4-1/2 inch unless otherwise indicated. Construct loose pin hinges for interior doors and reverse-bevel exterior doors so that pins are non-removable when door is closed. Other anti-friction bearing hinges may be provided in lieu of ball bearing hinges.
2.3.2…