Specifications .pdf
PDF 428 KB Posted
- Attached to
- SIX (6) ELECTRIC WALK IN REFRIGERATED BOX
- Solicitation number
- N4215826Q0010
About this file
This document contains technical specifications and electrical schematics for a temporary power distribution system designed to provide 480V, 15 KVA single-phase transformer service to a temporary structure.
The system utilizes a CAM-LOK receptacle and cover detail with a male receptacle rated for 600 volts up to 400 amps continuous service. The receptacle features a ¾" stud connection, #6-250 MCM cable capacity, TPE body construction, brass contacts, and is UL listed and CSA certified with NEMA 3R environmental rating. A snapback enclosure assembly with NEMA 3R rated environmental seal, stainless steel hardware, and high-impact resistant thermoplastic covers completes the primary connector assembly. The electrical schematic illustrates the complete temporary power feed configuration from X99 CAMLOCKS at 480V, 100A circuit, including a 40-amp circuit breaker enclosure (NEMA 3R), 15 KVA transformer with 480/240V primary and 120/240V secondary ratings, and a 100-amp main distribution panel for the temporary structure. The suggested exterior material list specifies components including a Wiegmann 12" x 12" x 6" galvanized NEMA 3R junction box, two CAM-LOK panel-mount receptacles (black and red male), Square D circuit breakers rated for 480/600V at 15-100 amps with FAL-type molded case construction, and an Acme Electric 15 KVA general-purpose single-phase wall-mount transformer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment N4215826Q00100001.pdf | ||
| QUESTIONS ANSWERS INDUSTRY.pdf | ||
| Solicitation - N4215826Q0010.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
gg
SUGGESTED EXTERIOR MATERIAL LIST
PC # ITEM/DESCRIPTION
WIEGMANN ENCLOSURE, 12” X 12” X 6”, NEMA 3R
JUNCTION BOX, GALVANIZED, 16 GAUGE, WITH NO
KNOCKOUTS. GRAINGER ITEM # 6JYT1.
2A
CAMLOK, PANEL MOUNT BLACK MALE RECEPTACLE.
CROUSE HINDS P/N: E1016-1600.
2C
CAMLOK, PANEL MOUNT RED MALE RECEPTACLE.
CROUSE HINDS P/N: E1016-1602.
SQUARE D CIRCUIT BREAKER ENCLOSURE. VOLTAGE
RATING 480/600V, CURRENT RATING 15-100 AMPS, FOR
FAL TYPE BREAKERS. NEMA 3R RATED. GRAINGER
ITEM # 1H906.
SQUARE D FAL TYPE CIRCUIT BREAKER, 600 VOLT, 40
AMP. 2-POLE MOLDED CASE. GRAINGER ITEM #
5B825.
ACME ELECTRIC TRANSFORMER, 480/240V PRIMARY,
240/120V SECONDARY. 15KVA, GENERAL PURPOSE,
SINGLE PHASE. WALL MOUNT ENCLOSURE, NEMA 3R
RATED. 16.94” X 11.59” X 14.12”. GRAINGER ITEM #
4WUC3.
File details come from the government source that posted it. Updated .