This document includes plans and specifications for repairing a fire suppression sprinkler system pipe near Door 122 of Building 2001 at the Defense Logistics Agency Distribution Susquehanna facility in New Cumberland, Pennsylvania. The contractor shall remove and replace the existing concrete slab to access the damaged sprinkler pipe located between the interior floor slab and exterior dock wall. All work must be completed outside of normal business hours over a 60 calendar day performance period. A pre-solicitation notice seeks quotes under solicitation SP3300-24-Q-0040 for this project with a value between $25,000 to $100,000. The solicitation will be set aside 100% for small businesses with a NAICS code of 236220 and $45 million size standard. The pre-proposal site visit and RFQ due date will be specified in the solicitation to be posted on SAM.gov, with award to the lowest priced responsible small business.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT DESCRIPTION: SCOPE OF WORK

A. THE WORK SHOWN ON THESE DRAWINGS CONSISTS OF THE FOLLOWING ITEMS, BUT IS NOT

INTENDED TO BE LIMITED TO THESE ITEMS ALONE:

REPAIR FIRE SUPPRESSION SPRINKLER SYSTEM SUPPLY PIPE NEAR DOOR 122 (RECEIVING

AREA). REMOVE AND REPLACE THE EXISTING CONCRETE SLAB TO ACCESS SPRINKLER PIPE.

BASED ON SEEPAGE LOCATION, DAMAGED PIPE SECTION LIKELY LIES BETWEEN THE INTERIOR

FLOOR SLAB AND EXTERIOR DOCK WALL. DRAWING INVESTIGATION INDICATES THE 8" CAST

IRON PIPE SHOULD PASS UNDER THE DOCK WALL FOOTING.

FURNISH AND INSTALL TEMPORARY FRAMEWORK FOR DUST / FUME PROTECTION / SECURITY

WHILE WORKING INSIDE THE BUILDING.

ALL WORK SHALL BE COMPLETED OUTSIDE OF NORMAL WORKING HOURS.

THE ABOVE SUMMARY OF WORK IS FOR THE PURPOSE OF GENERAL INFORMATION AND IS NOT

INTENDED TO INCLUDE AND DESCRIBE EVERY FEATURE OR ITEM OR TO DEFINE THE SCOPE OF

WORK. IT IS EXPECTED THAT THE CONTRACTOR WILL VISIT THE SITE OF WORK AND

THOROUGHLY FAMILIARIZE HIMSELF WITH THE CONDITIONS EXISTING THERE. FAILURE ON THE PART OF THE CONTRACTOR TO ACQUAINT HIMSELF WITH THE CONDITIONS ATTENDING THE WORK

WILL NOT BE SUFFICIENT REASON FOR ANY INCREASE IN CONTRACT PRICE.

B. ALSO REFER TO THE DETAILED NOTES PROVIDED ON EACH OF THE DRAWING SHEETS IN THIS SET AND ALSO THE TECHNICAL SPECIFICATIONS FOR DETAILED INFORMATION ON THE PROJECT CONTRACT

AND MATERIAL REQUIREMENTS WHICH MUST BE SATISFIED IN ORDER TO COMPLETE THE WORK.

SPECIAL CLAUSES (SC): SUPPLEMENTAL REQUIREMENTS

SC-1 PROTECTION OF GOVERNMENT PERSONNEL SHALL INCLUDE THE FOLLOWING:

SC-2

SC-3

SC-4

A. THE CONTRACTOR SHALL ESTABLISH A SAFETY ZONE AT EXTERIOR LOCATIONS AS

DIRECTED BY THE COR. THE SPECIFIED LOCATIONS SHALL BE CLEARLY MARKED WITH

SIGNS, CAUTION TAPE, SAFETY FENCE, BARRICADES, ETC. AS REQUIRED. IN AREAS

CORDONED OFF ALONG THEIR PERIMETER USING YEULOW CAUTION TAPE, THE TAPE SHALL

BE MOUNTED AT STANDARD HANDRAIL HEIGHT. LOCATIONS INCLUDE BUT ARE NOT LIMITED

TO THE FOLLOWING; MATERIAL OFFLOADING AREA(S), STAGING AREA(S) AND ALL ACTIVE

CONSTRUCTION AREAS. PARTICULAR ATTENTION SHALL BE GIVEN TO THOSE AREAS

INVOLVING EXCAVATIONS AND OVERHEAD STRUCTURAL WORK.

8. PROTECTION FROM DUST GENERATED BY CONSTRUCTION. THE CONTRACTOR SHALL MAKE

EVERY EFFORT TO CONTAIN DUST AND DEBRIS.

C. DAILY INSPECTION OF THESE PROVISIONS TO ENSURE COMPLIANCE WITH REQUIREMENTS.

D. ADJACENT STREETS, FIRE LANES, PARKING AREAS, AND SIDEWALKS SHALL REMAIN OPEN

AT ALL TIMES UNLESS PART OF AN GOVERNMENT APPROVED TRAmc CONTROL PLAN

AND/OR GOVERNMENT APPROVED MATERIAL STORAGE AREA.

SEE SPECIFICATION SECTION 01 14 OD - WORK RESTRICTIONS FOR "WORK HOURS" AND

"WORK OUTSIDE REGULAR HOURS."

THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO AVOID DAMAGE TO THE

EXISTING ADJACENT FACILITIES, DAMAGED ITEMS SHALL BE REPAIRED OR REPLACED AS

APPROVED BY THE CONTRACTING OFFICER AT NO ADDITIONAL COST TO THE GOVERNMENT. THE

CONTRACTOR SHALL CAREFUULY COORDINATE THE WORK OF THIS CONTRACT WITH All OTHER

WORK BEING CONDUCTED BY OTHER CONTRACTORS OR GOVERNMENT FORCES.

ALL HOT WORK CONDUCTED ON SITE REQUIRES A HOT WORK PERMIT ISSUED BY THE FIRE

DEPARTMENT BEFORE WORK STARTS. HOT WORK PERMITS ARE ISSUED ON A DAILY BASIS AND

ARE ONLY VALID FOR THEIR DATE OF ISSUE. THERE ARE NO LONG-TIERM HOT WORK PERMITS.

CUI

REPAIR SPRINKLER PIPE NEAR DOOR

DEFENSE DISTRIBUTION CENTER,

NEW CUMBERLAND, PA

GENERAL NOTES

1 22, BLDG 2001

SUSQUEHANNA

17070

1. ALL CONSTRUCTION PRACTICES SHALL BE IN ACCORDANCE WITH ALL CURRENT NATIONAL FIRE PROTECTION

ASSOCIATION (NFPA) REGULATIONS AND NATIONAL ELECTRICAL CODE (NEC) CODES.

2. THE CONTRACTOR SHALL BE REQUIRED TO VERIFY ALL CONDITIONS AND DIMENSIONS OF THE JOB SITE BEFORE PROCEEDING WITH THE WORK AND SHAUL MAKE MINOR ADJUSTMENTS AS REQUIRED ON THE JOB. SUCH

ADJUSTMENTS ARE TO BE APPROVED BY THE GOVERNMENT.

3. LOCATION OF EXISTING UTILITIES WERE TAKEN FROM AVAILABLE RECORDS AND ARE APPROXIMATE ONLY. IN ACCORDANCE WITH THE REQUIREMENTS OF THE UNDERGROUND UTILITY LINE PROTECTION ACT (P.L. B52, NO. 2B7) AS AMENDED BY THE ACT (P.L. 1567, NO. 199) OF NOVEMBER 30, 2004, THE CONTRACTOR MUST CONTACT THE PA ONE CALL SYSTIEM AT (BOO) 242-1776 AT LEAST THREE (3) BUT NO MORE THAN TEN (10) WORKING DAYS IN ADVANCE OF BEGINNING EXCAVATION OR DEMOLITION WORK. THE CONTRACTOR MUST ALSO COMPLY WITH INSTALLATION SOP 26 - UNDERGROUND UTILITY LOCATING WHICH WILL BE PROVIDED AT THE PRE-CONSTRUCTION

MEETING.

VISITOR CENTER f--�

BUILDING 2021

OLD DEPOT ROAD

ENTRANCE AND

ACP 3

NORMANDY DRIVE

ENTRANCE AND

ACP 4

TRUCK GATE

INDEX 4. EXTREME CARE SHALL BE EXERCISED WHEN EXCAVATING UTILITY LINES AND HAND EXCAVATION ONLY WILL BE PERMITTED IN THE VICINITY OF EXISTING PIPES AND/OR CONDUITS. ANY DAMAGE TO UTILITIES SHOWN ON THE DRAWINGS, MARKED IN THE FIELD, OR DESIGNATED BY U/G WARNING TAPE SHALL BE REPAIRED IMMEDIATELY BY

CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.

SHEET DRAWING NO.

5. AT POINTS OF CONNECTION, CONTRACTOR SHALL EXPOSE EXISTING UTILITY TO VERIFY LOCATION, GEOMETRY, AND MATERIAL REQUIREMENTS PRIOR TO ORDERING MATIERIALS OR STARTING CONSTRUCTION OF ANY UTILITY CONNECTING

THERETO.

G-001

C-101

LOCATION PLAN, INDEX

EXISTING FLOOR PLAN,

PLAN

LOCATION OF WORK

= ,-:•<!:!-�,. t-- ' � ... '·-

OF

OF

DRAWINGS

LOCATION PLAN

1 "=2,000'

DESCRIPTION

DRAWINGS AND GENERAL NOTES

DEMOLITION PLAN , LEGEND, NOTES AND LOCATION KEY

6. THE CONTRACTOR SHALL SUSTAIN IN THEIR PLACES AND PROTECT FROM INJURY ALL PIPE CONDUITS, TRACKS, 3 C-501 DETAILS, SECTION PLAN AND NOTES UTILITY POLES, GUIDE RAILS, GUARD POSTS, WALLS, FOUNDATIONS, BUILDINGS, AND OTHER STRUCTURES OR PROPERTY IN THE VICINITY OF HIS WORK, WHETHER ABOVE OR BELOW GROUND, OR THAT MAY APPEAR IN THE SITE.

PIPES AND UNDERGROUND CONDUIT EXPOSED AS A RESULT OF THE CONTRACTOR'S OPERATIONS SHALL BE

ADEQUATELY SUPPORTIED ALONG THEIR ENTIRE EXPOSED LENGTHS.

7. ALL EXCAVATION SHALL BE KEPT TO A MINIMUM UTILIZING TRENCH BOXES AND/OR SHORING AS REQUIRED.

BACKFILL SHALL BE PLACED AND COMPACTED AS WORK PROGRESSES TO LIMIT THE DISTURBED FOOTPRINT TO THE BEST MEANS ACHIEVABLE. EXISTING CRUSHED CONCRETE SHALL BE REMOVED AND REPLACED TO ENSURE SOIL

SURFACE STABILITY.

8. THE CONTRACTOR SHALL MAINTAIN THE WORK SITIE AT ALL TIMES IN A MANNER THAT MINIMIZES THE DEPOSITION OF ANY CONSTRUCTION MATERIALS OR DEBRIS ONTO ADJACENT PAVED ROADWAYS AND/OR WALKWAYS. THE WORK SITIE SHALL BE MONITORED AND CLEANED/SWEPT ON A CONTINUAL BASIS AS REQUIRED. CLEANUP ACTIVITIES SHALL NOT

BE LEFT TO BE PERFORMED AT THE END OF EACH WORK DAY.

SAFEJY AND HEALTH REQUIREMENTS:

1. ALL CONSTRUCTION PRACTICES SHALL BE IN ACCORDANCE WITH CURRENT OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA) REGULATIONS, 29 CODE OF FEDERAL REGULATIONS (CFR) 1910/1926 AND EM 3B5-1-1

(CURRENT VERSION).

2. CONTRACTOR SHAUL SUBMIT CONFINED SPACE PROGRAM WITH SAFETY PLAN FOR GOVERNMENT APPROVAL PRIOR

TO START OF ANY CONSTRUCTION.

3. ALL RECYCLED MATERIALS FROM PROJECT SHALL BE HAULED TO BLDG 7B9.

D --ss--

EXISTING FEATURES

SIGN

FIRE HYDRANT

WATER VALVE/CURB BOX

GAS VALVE

MONITORING WELL

SANITARY SEWER MANHOLE

COMMUNICATIONS MANHOLE

STORM SEWER MANHOLE

LIGHT POLE

UTILITY PO LE

ABBREVIATIONS

A.T.

B.S.

BLDG

Cl

CJ

CONG

COR

DEMO

DIA

ELEC

EXIST/EX

FY

INV

O.C.

PA

PROP/PR

THK

TS

= ALL THREAD

= BOTH SIDES

= BUILDING

= CAST IRON

= CONTROL JOINT

= CONCRETE

= CONTRACTING omCER'S REPRESENTATIVE

= DEMOLISH/DEMOLITION

= DIAMETER

= ELECTRIC

= EXISTING

= FISCAL YEAR

= INVERT

= ON CENTER

= PENNSYLVANIA

= PROPOSED

= THICKNESS

WORK AREA - -s- -

STORM SEWER INLET

STORM SEWER MAIN

SANITARY SEWER

STEAM LINE

TYP

= TUBE STEEL

= TYPICAL

CUI

--STM-

- -SCR-

--G--

- - W -- --E--

--c- -

- -UE- -

-u;c-

----r- s ---,,L--

----r- w ---,,"-

------;," H PS ---;r'-

CONDENSATIE RETURN LINE

GAS MAIN/LATERAL

WATER MAIN

OVERHEAD ELIECTRIC

OVERHEAD COMMUNICATIONS

UNDERGROUND ELECTRIC

UNDERGROUND COMMUNICATIONS

ABANDONED SANITARY SEWER LINE

ABANDONED WATER LINE

ABANDONED STEAM LINE

CHAIN LINK FENCE

0� TREES

APPROVED BY

l CONSTRUCTION REPRESENTATIVE l SECURITY l ENVIRONMENTAL lsAFETY AND HEALTH

FIRE PROTECTION COMMUNICATIONS

INDUSTRl,t\.L HYGIENIST USER l FACILITY MAl,�TEN4NCE (i,EO)

SHAUN T. MEGONNELL CHIEF, ENGINEERl1'IG DIVISION

NO.

WWF = WELDED WIRE FABRIC

CONTROLLED BY:

CONTROLLED BY:

CUI CATEGORY:

LDC:

POC

DLA

DM-FSI

CTI

FEDCON

PM LEE MOORE, lee.moore@dla.mil

REVISIONS

DEFENSE LOGISTICS AGENCY

DATE

DLA INSTALLATION MANAGEMENT AT SUSQUEHANNA

INSTALLATION MANAGEMENT DIVISION

NEW CUMBERLAND, PA 17070-5002

REPAIR SPRINKLER PIPE NEAR DR 122, BLDG 2001

LOCATION PLAN, INDEX OF DRAWINGS AND GENERAL NOTES

DESIGNED BY CHECKED BY:

PROJECT NO.

OAP 4239

CIVIL

DRAWING NO.

DRfa.WN BY: G-001

LRM

ARCHITECTURAL

SHEET

MECHANICAL 1

SCfa,LE: OF

ELECTRICAL

DATE

NOTED ENERGY NOVEMBER 2023