Appendix C
DEFINITIONS OF JPTS TEST SERIES
I. TYPE A: Includes all specification quality confOlmance tests in accordance with MIL DTL-25524E plus any additional contractual requirements.
n. TYPE B & C: As shown in the table.below. Properties and test methods will be in accordance with MIL-DTL-25524E.
PROPERTIES
Appearance Color (visual) Densitv or API gravity Particulate malter' Distillation Copper strip con'osion Freezing point Existent gum Flash point Water reaction Fuel svstem icinJ!: inhibitor Water separation index Thermal stability Color (Savbolt) Acid number
.B·I
TEST
X
X
X
X
X
B·2
TEST
CTEST
X X X X X X X X X X X X X
X X X X X
TABLE II NOTES:
I CLEAN AND BRIGHT AND FREE OF UNDISSOLVED WATER. OBTAIN SAMPLE
IN A CLEAR ROUND ONE QUART GLASS BOTTLE, SWIRL THE BOTTLE
VIGOROUSLY SO A VORTEX IS FORMED. VISUALLY CHECK FOR SEDIMENT AT
THE POINT OF THE VORTEX. IF SEDIMENT IS VISIBLE, AN INVESTIGATION IS
NECESSARY IN ORDER TO DETERMINE THE SOURCE OF THE CONTAMINANT.
(A SPOT LARGER THAN 3 MM DIAMETER INDICATES CORRECTIVE ACTION
MAYBE REQUIRED TO PREVENT THE DELIVERY OF CONTAMINATED FUEL)
2 FOR PARTICULATE MATTER TESTING THE "DESTINATION" LIMITS OF MIL
DTL-25524E APPLY.