SOW Attachment 09 - X-Matrix Summary - Site Assessment.xlsx

XLSX spreadsheet 23 KB Posted

Attached to
C1BG--660-21-707 EHRM Design Package SLC (VA-22-00028648)
Solicitation number
36C77623R0032
Issued by

About this file

This document contains details for an Architect-Engineering (A-E) services solicitation for the Veterans Health Administration (VHA). The solicitation seeks design services for network infrastructure upgrades at the George E. Wahlen VA Medical Center in Salt Lake City, Utah, including construction of a replacement data center. Responses are due by November 15, 2022 in the form of Standard Form 330 statements of qualifications. The project has a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses and is estimated at $8.7 million. Selection will be based on specialized experience designing similar healthcare IT systems projects, past performance, capacity to complete the work on schedule, and knowledge of local site conditions. The secondary criterion is geographic proximity to the medical center.

View the file

Other files

File Type Posted
SOW Attachment 11- Appendix B Contract Clause.pdf PDF
Attachment 20 AE Design SOW - EHRM Infrastructure Upgrades -Tier 2.pdf PDF
SOW Attachment 03-1 HEFP SEP Design Alert 1-8.pdf PDF
SOW Attachment 19 - Construction Cost Estimate Template.xlsx XLSX spreadsheet
36C77623R0032.docx DOCX document
SOW Attachment 17 - Electrical Design Manual.pdf PDF
Attachment 21 - Wage Determination SL County.gov.pdf PDF
SOW Attachment 12 - Appendix C Contract Clause.pdf PDF
SOW Attachment 02 - VA OEHRM Site Infrastructure Requirements 2.0.pdf PDF
Attachment 22 - Past Performance Questionnaire.docx DOCX document
SOW Attachment 07 - Seasonal Influenza with Vaccines.pdf PDF
SOW Attachment 16 - Infrastructure Standard for Telecommunication Spaces.pdf PDF
SOW Attachment 13 - 01 32 16.01 EHRM Arch and Eng CPM Schedule Spec.pdf PDF
SOW Attachment 05 - 01 32 16.01 EHRM A-E CPM Schedules - NOA.docx DOCX document
SOW Attachment 08 - VHA Directive 1061.pdf PDF
SOW Attachment 01 - VHA Required Div 01 Spec Sections.docx DOCX document
SOW Attachment 15 - Salt Lake City MCR Design.pdf PDF
SOW Attachment 10 - VHA COVID-19 Supplemental Contract Requirements 12-14-21.pdf PDF
SOW Attachment 14 - Salt Lake City Campus Map.pdf PDF
SOW Attachment 04 - Sensitive Infrastructure Data Classification Memo.pdf PDF
SOW Attachment 18 - Physical Security and Resiliency Design Manual.pdf PDF
SOW Attachment 06 - PG 18-15 A-E Submission Reqs Vol C - EHRM.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

X Matrix Summary

LocationNameBuildingRoomCablingPatch PanelsFiberPowerBondingUPSDedicated CoolingTempHumidityRacks SensorsSpace
660VA Salt Lake City11-GA16X*X*XXXXXXXXX-Relocate
660VA Salt Lake City11-GB05XXXXXXXXXXX-RelocatePharmacy - Relocate
660VA Salt Lake City11-GB08X*X*XXXXXXXXX-Relocate
660VA Salt Lake City11-GB02N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/Ademark
660VA Salt Lake City1GD03AAN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/APBX room
660VA Salt Lake City11-GC10BX*X*XXXXXXXXX-RelocateExpand into paint shop.
660VA Salt Lake City11-GD03CN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
660VA Salt Lake City11-1A19AX*X*XXXXXXXXX-Relocateelectrical closet and stairwell adjacent. Stacked.
660VA Salt Lake City11-1B05X*X*XXXXXXXXX-RelocatePharmacy - stacked on 1-GB05
660VA Salt Lake City11-1B29XXXXXXXXXXX-RelocateExpand into 1B31 - Adjacent office
660VA Salt Lake City11-1C12X*X*XXXXXXXXX-Relocate
660VA Salt Lake City11-1D18XXXXXXXXXXX-RelocateSurrounded by elec, stairwell
660VA Salt Lake City11-1D71X*X*XXXXXXXXX-RelocateExpand into 1-1D75A
660VA Salt Lake City11-1EACXXXXXXXXXXX-ExpandTake over all 1EAB
660VA Salt Lake City11-1F02NONOXXXXXXXXNOLandlocked, but could be addressed by 660-337
660VA Salt Lake City11-1F33GNONOXXXXXXXXNO
660VA Salt Lake City11-1H17XXXXXXXXXXX-Relocatewill be served by D zone stack
660VA Salt Lake City11-2A15CX*X*XXXXXXXXX-RelocateStacked - landlocked.
660VA Salt Lake City11-2B09X*X*XXXXXXXXX-RelocateStacked - landlocked.
660VA Salt Lake City11-2C20BX*X*XXXXXXXXX-RelocateExpand into 2C29A??
660VA Salt Lake City11-2D07X*X*XXXXXXXXX-RelocateLong, skinny, landlocked. Stacked
660VA Salt Lake City11-2EACNONOXXXXXXXXX-ExpandTake over all 2EAB
660VA Salt Lake City11-2f55NONOXXXXXXXXNOThis is a newly constructed space and has a large IT closet.
660VA Salt Lake City11-3A15AX*X*XXXXXXXXX-RelocateStacked - landlocked.
660VA Salt Lake City11-3B09X*X*XXXXXXXXX-RelocateStacked - landlocked.
660VA Salt Lake City11-3C20BX*X*XXXXXXXXX-RelocateExpand into 3C22
660VA Salt Lake City11-3D07X*X*XXXXXXXXX-RelocateLong, skinny, landlocked. Stacked
660VA Salt Lake City11-4A15DX*X*XXXXXXXXX-RelocateLandlocked. Stacked
660VA Salt Lake City11-4B13X*X*XXXXXXXXX-RelocateLandlocked. Stacked
660VA Salt Lake City11-4C22BX*X*XXXXXXXXX-RelocateExpand into 4C24?
660VA Salt Lake City11-4D05X*X*XXXXXXXXX-RelocateLong, skinny, landlocked. Stacked
660VA Salt Lake City11-5B13BXXXXXXXXXXX-RelocateLandlocked. Stacked
660VA Salt Lake City21A36-2NONOXXXXXXXXNOLandlocked. StackedResearch
660VA Salt Lake City21B09-2NONOXXXXXXXXNOCould expand into 1B05Research
660VA Salt Lake City21C31-2NONOXXXXXXXXNOLandlocked.Research
660VA Salt Lake City21D09-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City21D35-2NONOXXXXXXXXNOLandlocked.Research
660VA Salt Lake City22A24-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City22B07-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City22C33-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City22D13-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City22D29-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City2GA28-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City2GB03-2NONOXXXXXXXXX-ExpandLandlockedResearch
660VA Salt Lake City2GC21-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City2GD05-2NONOXXXXXXXXNOLandlockedResearch
660VA Salt Lake City33-GA02N/AN/AXN/AXN/AN/AN/AN/AN/ANOtelephone switch room
660VA Salt Lake City33-GA08CNONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-GB01ANONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-GC14BNONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-1A13CNONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-1B01ANONOXXXXXXXXX-RelocateCan expand into 1A02
660VA Salt Lake City33-1C18ANONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-1D01NONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-2A13CNONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City33-2B01ANONOXXXXXXXXX-Relocate2A02
660VA Salt Lake City33-2C16BNONOXXXXXXXXX-RelocateLandlocked
660VA Salt Lake City41A30ANONOXXXXXXXXNO
660VA Salt Lake City41B14NONOXXXXXXXXNO
660VA Salt Lake City41C40ANONOXXXXXXXXNO
660VA Salt Lake City55-1A14NONOXXXXXXXXX-ExpandCould expand into adjacent HAC 1A12
660VA Salt Lake City6B103-6X*X*XXXXXXXXX-Relocate??? Build a new one
660VA Salt Lake City71A38-7XXXXXXXXXXX-ExpandExpand into adjacent locker room
660VA Salt Lake City71B05-7N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AExpand Linen Distro project will be funded this FY
660VA Salt Lake City71C10-7XXXXXXXXXXX-ExpandCould expand into corrdior?
660VA Salt Lake City88-2A08X*X*XXXXXXXXX-RelocateRelocate
660VA Salt Lake City99-1A21X*X*XXXXXXXXX-RelocateRelocate
660VA Salt Lake City1414-BA05X*X*XXXXXXXXX-RelocateLandlocked.
660VA Salt Lake City1414-BC07X*X*XXXXXXXXX-Relocate
660VA Salt Lake City1414-GB34X*X*XXXXXXXXX-Relocate
660VA Salt Lake City1414-GB51AX*X*XXXXXXXXX-RelocateCan expand
660VA Salt Lake City1414-GB64X*X*XXXXXXXXX-RelocateLandlocked
660VA Salt Lake City1414-1B01X*X*XXXXXXXXX-Relocate
660VA Salt Lake City1414-1B25X*X*XXXXXXXXX-RelocateLandlocked
660VA Salt Lake City1414-2B02X*X*XXXXXXXXX-RelocateLandlocked
660VA Salt Lake City1414-2B43X*X*XXXXXXXXX-RelocateLandlocked
660VA Salt Lake City1414-3B02X*X*XXXXXXXXX-RelocateLandlocked
660VA Salt Lake City1414-3B14X*X*XXXXXXXXX-RelocateNot sure….
660VA Salt Lake City1616-1A46NONOXXXXXXXXNO
660VA Salt Lake City1616-2A48NONOXXXXXXXXNO
660VA Salt Lake City1616-GA50NONOXXXXXXXXNO
660VA Salt Lake City3232-110N/AN/AN/AN/AN/AN/AN/AN/AN/AN/ANOFisher House
660VA Salt Lake City381A08-38XXXXXXXXXXNO
660VA Salt Lake City4747-1A97DNONOXXXXXXXXNOTemporary trailer
660VA Salt Lake City590590-1A00F1N/AN/AXN/AN/AN/AN/AN/AN/AN/ANOEUL
660VA Salt Lake City590590-245N/AN/AXN/AN/AN/AN/AN/AN/AN/ANOEUL
660VA Salt Lake City590590-GA05N/AN/AXN/AN/AN/AN/AN/AN/AN/ANOEUL
660VA Salt Lake City5501st flrN/AN/AXN/AN/AN/AN/AN/AN/AN/ANOEUL
660VA Salt Lake City5502nd flrN/AN/AXN/AN/AN/AN/AN/AN/AN/ANOEUL
660VA Salt Lake City5503rd flrN/AN/AXN/AN/AN/AN/AN/AN/AN/ANOEUL
660VA Salt Lake CityT1T1-1A25NONOXXXXXXXXNOTemprary trailer
660VA Salt Lake CityT2T2-1A02N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AMoth balled
4242868080808080808048-Relocate; 6-Expand;
660VA Salt Lake CityEUL590590-1A00F1X-site needs to verifyX-site needs to verifyN/A (within 660-21-700)X-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyNOEUL
660VA Salt Lake CityEUL590590-245X-site needs to verifyX-site needs to verifyN/A (within 660-21-700)X-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyNOEUL
660VA Salt Lake CityEUL590590-GA05X-site needs to verifyX-site needs to verifyN/A (within 660-21-700)X-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyNOEUL
660VA Salt Lake CityEUL5501st flrX-site needs to verifyX-site needs to verifyN/A (within 660-21-700)X-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyNOEUL
660VA Salt Lake CityEUL5502nd flrX-site needs to verifyX-site needs to verifyN/A (within 660-21-700)X-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyNOEUL
660VA Salt Lake CityEUL5503rd flrX-site needs to verifyX-site needs to verifyN/A (within 660-21-700)X-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyX-site needs to verifyNOEUL

660 VA Salt Lake City Vet Center Pocatello 1A00-POC Per Infrastructure requirements 1.8, Vet Centers do not need infrastructure updates

660VA Salt Lake CityClinicRoosevelt1A01-RSVLTN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/Acontract clinic
660VA Salt Lake CityCBOCPrice1A02A-PRICEN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/Anot in scope - replacing/expanding in FY21
660VA Salt Lake CityCBOCElko1A06A-ELKON/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/Anot in scope - replacing/expanding in FY21
660VA Salt Lake CityCBOCPocatello1A11-POC2NONONONONONONONONOXNO
660VA Salt Lake CityCBOCIdaho Falls1A14-IFNONONONONONONONONOXNO
660VA Salt Lake CityVet CenterSalt Lake1A22-FIRECLAYPer Infrastructure requirements 1.8, Vet Centers do not need infrastructure updates
660VA Salt Lake CityCBOCOgden1A41-OGDENNONONONONONONONONOXNO
660VA Salt Lake CityCBOCSt George1A41-STGN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/Anot in scope - replacing/expanding in FY21
660VA Salt Lake CityCBOCWest Valley1A69AA-WSLVN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/Ano longer exists
660VA Salt Lake CityVet CenterSt George Vet1-C102N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A
660VA Salt Lake CityCBOCSouth JordanNONONONONONONONONOXNOnew clinic
660VA Salt Lake CityMental HealthOgden WeberN/AN/AN/AN/AN/ANON/AN/AN/AN/AN/Ano longer exists
660VA Salt Lake CityVet CenterOgden Vet1A06-OGDENPer Infrastructure requirements 1.8, Vet Centers do not need infrastructure updates
660VA Salt Lake CityGenomics2A07-RPNONONOXXNOXXXXNOsite needs to review
660VA Salt Lake CityCBOCOREM3A05-OREMNONONONONONONONONOXNONew clinic
660VA Salt Lake CityVet CenterPROVOCLINIC-PROVOPer Infrastructure requirements 1.8, Vet Centers do not need infrastructure updates
Data CenterBuildingRoomSpaceHVACCable DistroWANUPS
660VA Salt Lake CityNOXNONONOTier 1
660VA Salt Lake CityXXXXXTier 2
Notes:
General Notes
X~included in scope of NRM project
NO~not included in scope
X*~included in scope only because space will be addressed; if space remains as is, component is adequate as is
TR NOTES
Bldg 1~Bldg 1's TRs will relocate into new A, B, C & D stacks within the facility
Bldg 14~bldg was costed for three stacks. Facility believes two stacks may be enough.
Fiber~Site needs a secondary diverse path to TRs
~Diverse path not required at CBOCs
Power~Both Normal and Emergency power should be added where available
DC Notes
Space~1000SF
~8" raised floor
~space exists for 4 additional cabinets
~Tier 2 project to open up space in the room as a bigger data center
cabinets~20 cabinets
HVAC~Two 10T units, about 35kW of cooling available
~critical load of 22kW therefore 10kW is avaible for JSA and FDS, but close
JSASpace exists; Power is at risk due to no redundancy; Cooling is not ready-needs another CRAC.
FDSSpace exists; Power is at risk due to no redundancy; Cooling is not ready-needs another CRAC.