South Fork DSSP_Attachment.pdf

PDF 1 MB Posted

Attached to
Water Sampling, Testing, and Operation - Lincoln NF Federal contract opportunity
Solicitation number
127EAV22R0007
Issued by
Department of Agriculture Forest Service R3-Southwestern Region

View the file

Other files for this federal contract opportunity

Other files attached to Water Sampling, Testing, and Operation - Lincoln NF, newest first.
File Type Posted
WD 2015-5455.pdf PDF
Smokey Bear ADM Site - DSSP approved 4-6-2016 Attachment_Redacted.pdf PDF
FSM_7400_Attachment.pdf PDF
Mayhill_DSSP_Attachment.pdf PDF
Sacramento_DSSP_Attachment-Revised.pdf PDF
LNF_Water_Operator_Contract_Statment_of_Work - Final.pdf PDF
LNF_Water_Operator_Contract_Map.pdf PDF
LNF_Water_Operator_Contract_Bid_Schedule_Final.pdf PDF
Three_Rivers_DSSP_Attachment.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TITLE PAGE

DRINKING WATER DISTRIBUTION SYSTEM

SAMPLING PLAN (DSSP) FOR:

Southfork Campground

PWS #

Original Plan Prepared By:

Date Prepared : May 10 2020 Date Submitted to NMED DWB

Signature _James Rogge Reviewed by DWB SWIG Tech Services Coordinator Name Date Recommended for Approval

Signature ______________ _

Reviewed and Approved by DWB PWSS Group Compliance Officer Date Approved

Signature ______________ _

REVISION TRACKING

Original Plan Prepared By :

Date Prepared : May 10th 2020

1st Revision By 1st Revision Date Date Submitted to NM ED Date Approved by NMED

2nd Revision By 2nd Revision Date Date Submitted to NMED Date Approved by NMED

Section 1: System Description and Contact Information The US Forest Servic owns and operates one groundwater well. The water system seasonally serves up to 250 people in a given one week period and has 10 connections. Water from the well is pumped to a 20,000 gallon storage tank. Water from the tank gravity flows to our distribution system.

Our current sample schedule from Drinking Water Watch is provided in Appendix A.

Administrative Contact:

Certified Operator:

NMED-DWB Contact

WELL

l

RAW WATER

SAMPLING PORT

System Schematic

ENTRY POINT

/AMPl.:E PORT j

20,000 GALLON

STORAGE TANK

DISTRIBUTION

SYSTEM

Special samples will be taken at the 2 sites listed in the table below which identifies the location of the Special sample and the system feature (i.e., storage tank, distribution system) the sample is associated with along with the Special sample number. These sites were chosen based on the requirements established in the seasonal start-up guidance provided by the DWB. They are also designated on the distribution system map(s) in Appendix C. We further understand that Special samples are samples collected and paid for by the water system.

INLOW WATER SYSTEM SAMPLE TEST POINTS: NM 35902-30

IWS-001 Lower host site h drant S ecial Sam le See Ma

IWS-002 Tank Site S ecial Sam le See Ma

RT003 Survivor Restroom Routine Sample See Map H drant

RT004 Dalton H drant Routine Sam le See Ma

Groundwater Rule (GWR) Sampling One (1) Triggered Source Water sample is required to be collected from every active well if any of our routine monthly samples test positive for Total Coliform (TC) or E.Coli (EC). These Triggered Source Water Samples will be collected directly from our well prior to any treatment and are shown on the map(s) in Appendix C. Our sample points are labeled as "Raw Water11 as shown in the photograph below.

Raw Water - Water Faucet Next to Well Control Pit

Sampling Requirements New Mexico Regulations require that a certified sampler or certified operator collect the RTCR and GWR samples. Because of this requirement, our certified Sampler will be required to collect our bacteriological samples.

Once collected, our Sampler will submit the samples and their Chain-of Custody (CoC) forms to the following certified laboratory within 24 hours of the sample being collected:

Compliance Status

RTCR

Our water system triggers an assessment with the RTCR if:

• We get 2 TC+ samples in any one (1) month ;

• We fail to take all the required repeat samples;

• Any one (1) of these conditions will trigger a required Level 1 assessment/correction action

A Level 2 assessment/corrective action is triggered if we get:

• An EC Maximum Contaminant Level (MCL) violation; or

• An EC monitoring violation; or

• We trigger two (2) Level 1 assessments within a rolling 12 month period

GWR

We are in compliance with the GWR if our Triggered Source Water sample(s) are free of EC.

We will immediately notify our customers if any of our Triggered Source Water samples test positive for TC or EC. At that time, we can be required to conduct additional sampling, correct significant deficiencies, or disinfect our water to meet 4-log treatment requirements.

Section 3: Disinfectant Residual Monitoring Frequency We maintain a chlorinator and monitor chlorine residual.

Section 4: Lead and Copper Rule (LCR) Sampling Frequency We are not required to collect Lead and Copper samples.

Section 5: Disinfectants/Disinfection By-Products (D/DBP) Rule Sampl1ing

Frequency and Location

File details come from the government source that posted it. Updated .