This document is a set of electrical drawings and specifications for a site lighting replacement project at the Fargo VA Health Care System in Fargo, North Dakota. The project involves removing existing pole-mounted and wall-mounted lighting fixtures and replacing them with new energy-efficient LED fixtures. Key details include:

The project includes replacing lighting for parking lots, walkways, building exteriors, and site fixtures such as bollards and in-grade stair lighting. The work is divided into a base bid and two bid alternates - Alternate 1 removes lighting in the parking ramp area, and Alternate 2 removes lighting in the mental health parking area and on Building 52. The project requires coordination with an ongoing Building 1 expansion project. The solicitation number is 36C26324B0006, and the project number is 437-23-135. The federal agency is the Department of Veterans Affairs Veterans Health Administration. No additional details on pricing, award dates, or set asides are provided in the drawings.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER PAGE

G-000

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

REPLACE SITE LIGHTING

PROJECT NO. 437-23-135

FARGO VA HEALTH CARE SYSTEM

DEPARTMENT OF VETERAN'S AFFAIRS

2101 ELM STREET

FARGO, NORTH DAKOTA 58102

VA U.S DEPARTMENT OF VETERAN'S AFFAIRS

VETERAN'S HEALTH ADMINISTRATION

SHEET INDEX

SHEET # SHEET TITLE

G-000 COVER PAGE

E-000 ELECTRICAL LEGENDS AND ABBREVIATIONS

E-001 ELECTRICAL DETAILS

E-002 ELECTRICAL SCHEDULES

E-100 LIGHTING DEMOLITION - FULL SITE PLAN

E-101 LIGHTING DEMOLITION ENLARGED SITE PLAN AREA A

E-102 LIGHTING DEMOLITION ENLARGED SITE PLAN AREA B

E-103 LIGHTING DEMOLITION ENLARGED SITE PLAN AREA C

E-104 LIGHTING DEMOLITION ENLARGED SITE PLAN AREA D

E-105 LIGHTING DEMOLITION ENLARGED SITE PLAN AREA E

E-110 NEW LIGHTING - FULL SITE PLAN

E-111 NEW LIGHTING ENLARGED SITE PLAN AREA A

E-112 NEW LIGHTING ENLARGED SITE PLAN AREA B

E-113 NEW LIGHTING ENLARGED SITE PLAN AREA C

E-114 NEW LIGHTING ENLARGED SITE PLAN AREA D

E-115 NEW LIGHTING ENLARGED SITE PLAN AREA E

ELECTRICAL ABBREVIATIONS

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADO AUTOMATIC DOOR OPENER

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

AMP AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAS BUILDING AUTOMATION SYSTEM

BFF BELOW FINISH FLOOR

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DAS DISTRIBUTED ANTENNA SYSTEM

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL

PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MVA MEGAVOLT-AMPERE

MW MEGAWATT MICROWAVE

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OF OWNER FURNISHED

OF/CI OWNER FURNISHED/CONTRACTOR

INSTALLED

OF/OI OWNER FURNISHED/OWNER INSTALLED

OL OVERLOAD

OS OCCUPANCY SENSOR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SPDT SINGLE POLE, DOUBLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

VS VACANCY SENSOR

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

SWITCH, MULTIPOSITION

SWITCH, NORMALLY CLOSED FLOAT

SWITCH, NORMALLY CLOSED FOOT OPERATED

SWITCH, NORMALLY CLOSED LIMIT

SWITCH, NORMALLY CLOSED TIME DELAY

SWITCH, NORMALLY OPEN FLOAT

SWITCH, NORMALLY OPEN LIMIT

SWITCH, NORMALLY OPEN TEMPERATURE ACTIVATED

SWITCH, NORMALLY OPEN TIME DELAY

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

HIGH-VOLTAGE OIL CIRCUIT BREAKER

HIGH-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

O.C.B.

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

PRESSURE SWITCH-CLOSE ON INCREASE

PRESSURE SWITCH-OPEN ON INCREASE

FUSIBLE LINK

TIME CLOCK

GENERATOR, POWERG

BATTERY

CAPACITOR

LIGHTNING ARRESTOR

R

RECTIFIER, CATHODIC PROTECTION SANITARY

INSTANTANEOUS OVERCURRENT RELAY

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

POTHEAD

STRESS CONE

M METER

A AMMETER

V VOLTMETER

W WATTMETER

WH WATT-HOUR METER

J

PB

R

AC-TIME OVERCURRENT RELAYR

AC-DIRECTIONAL OVERCURRENT RELAYR

LOCKING OUT RELAYR

TC

SYMBOL

SWITCH, NORMALLY CLOSED

TEMPERATURE ACTIVATED

DESCRIPTION

ELECTRICAL LEGEND

(DETAILS)

DUCT, CELL FLOOR HEADER

T T DUCT, TROLLEY

DUCT, UNDERFLOOR JUNCTION BOX

RC RIGID CONDUIT LINE = RC

SUBSTATION

DISTRIBUTION PANEL

LIGHTING PANEL

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

C RECEPTACLE, CLOCK HANGER

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, GFCI DUPLEX

RECEPTACLE, QUADRAPLEX

DB DIRECT BURIAL CABLE = DB

P POWER DUCT = P

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

J

PB

SYMBOL DESCRIPTION

ELECTRICAL LEGEND

(FLOORPLAN)

C C LADDER CABLE TRAY

BRANCH CIRCUIT HOMERUN. LINES INDICATE

NUMBER OF CIRCUITS, NEUTRAL, AND SWITCH LEG

CONDUCTORS. ONE SEPARATE GREEN GROUNDING

CONDUCTOR SHALL BE PROVIDED FOR EACH

HOMERUN; NOT SHOWN

W W WIREWAY

T P

LVS

HVS

S

B B BUSWAY

LP

DP#__

A

B

C

D

RECEPTACLE, SPECIAL PURPOSE 208V,

20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

RECEPTACLE, SPECIAL PURPOSE 120V,

30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

RECEPTACLE, SPECIAL PURPOSE 208V,

30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

RECEPTACLE, SPECIAL PURPOSE 120V,

20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

VENTILATOR OR FAN COIL UNIT OUTLET

SWITCH, SPST

VARIABLE FREQUENCY DRIVE

TIME CLOCK

R

RECTIFIER, CATHODIC PROTECTION SANITARY

INSTANTANEOUS OVERCURRENT RELAY

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

R

AC-TIME OVERCURRENT RELAYR

AC-DIRECTIONAL OVERCURRENT RELAYR

LOCKING OUT RELAYR

TC

SYMBOL DESCRIPTION

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]

CENTERS OR AS DESIGNATED ON DRAWINGS), MTD

3'-6" [1067mm] AFF OR AS INDICATED.

VFD

CONDUIT TERMINATED W/COUPLING

(FLUSH W/FINISHED FLOOR) FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED 6" [152mm] AFF IN STANDARD

BOX FOR EXTENSION TO EQUIPMENT AS DIRECTED.

SWITCH, DPST2

SWITCH, FUSEDF

SWITCH, KEY OPERATEDK

SWITCH, LOCKL

SWITCH, LOW VOLTAGE MASTERLM

SWITCH, MANUAL MOTOR STARTINGM

SWITCH, MOMENTARY CONTACTMC

MP

SWITCH, WITH PILOT LIGHTP

SWITCH, PUSH BUTTONPB

SWITCH, REMOTE CONTROLRC

SWITCH, WEATHER PROOFWP

SWITCH, EXPLOSION PROOFX

SWITCH, THREE WAY3

SWITCH, THREE WAY DIMMER3D

SWITCH, THREE WAY OCCUPANCY SENSOR3OS

SWITCH, FOUR WAY4

SWITCH, DIMMERD

SWITCH, DOOR JAMBDOOR

SWITCH, FOUR WAY OCCUPANCY SENSOR4OS

SWITCH, OCCUPANCY SENSOROS

SWITCH, PHOTOCELLPH

SWITCH, OCCUPANCY SENSOR DIMMEROSD

SWITCH, MOTOR SNAP WITH

PILOT LIGHT (THERMAL TYPE)

E

RECEPTACLE, SPECIAL PURPOSE 208V,

60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV

FIBEROPTICS LINE = FO

COMMUNICATIONS FLOOR RECEPTACLE

PAGING SPEAKER, CEILING MOUNTED

PAGING SPEAKER, WALL MOUNTED

CATV

CCTV

FO

COMMUNICATIONS WALL RECEPTACLE

COMMUNICATIONS LINE = COMCOM

INTERCOM LINE = II

NURSE CALL LINE = NCNC

NURSE'S CALL MASTER STATION

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

D = DUTY STATION. MTD 5' AFF

E = MTD 6' AFF FOR SHOWER LOCATION

MTD 4'-6" AFF FOR TUB LOCATION

MTD 3' AFF FOR TOILET LOCATION

P = PSYCHIATRIC CORRIDOR STATION WITH KEY

SWITCH

S = AUDIO VISUAL STAFF STATION MTD 5' AFF

U = UTILITY CALL STATION, MTD 5' AFF

NURSE CALL STATION.

D = CORRIDOR DOME LIGHT MTD 6" ABOVE DOOR

I = AUXILIARY INTERSECTIONAL DOME LIGHT

TELECOMMUNICATIONS TERMINAL CABINET

TELECOMMUNICATIONS BACKBOARD (WALL MTD)

TELECOMMUNICATIONS MANHOLE

COMMUNICATIONS CEILING RECEPTACLE

TELEVISION FLOOR RECEPTACLE

C = CAMERA (CCTV SYSTEM)

M =MONITOR (CATV SYSTEM).

AV= AUDIO VISUAL (CONFERENCE ROOM

CONNECTION RECEPTACLES)

AUDIO VISUAL LINE = AVAV

RECEPTACLE, SWITCHED DUPLEXS

F

G

H

RECEPTACLE, SPECIAL PURPOSE 208V,

30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

RECEPTACLE, SPECIAL PURPOSE 208V,

50A, 3 PHASE, 3 POLE, 4W, NEMA 15-50R.

RECEPTACLE, SPECIAL PURPOSE 208V,

60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN

FLEXIBLE CORD (CENTER LINE OF OUTLET: 6'-6"

[1981mm] AFF. MINIMUM).

TELEVISION WALL RECEPTACLE

C = CAMERA (CCTV SYSTEM)

M =MONITOR (CATV SYSTEM).

AV= AUDIO VISUAL (CONFERENCE ROOM

CONNECTION RECEPTACLES)

TELEVISION CEILING RECEPTACLE

C = CAMERA (CCTV SYSTEM)

M =MONITOR (CATV SYSTEM).

AV= AUDIO VISUAL (CONFERENCE ROOM

CONNECTION RECEPTACLES)

SYMBOL DESCRIPTION

J

RECEPTACLE, SPECIAL PURPOSE 208V,

20A, 3 PHASE, 3 POLE, 4W, NEMA 15-20R.

EH ELECTRIC POWER HINGE

DC DOOR CONTACT

MID MOTION INTRUSION DETECTOR

SSTV SECURITY SURVEILLANCE TELEVISION

C CAMERA

C 360 CAMERA

CARD ACCESS READER; LETTER INDICATES AS

FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION P-PEDESTAL R-RACK S-SURFACE

W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE M-MAG STRIP

F-ELEVATOR FLOOR CALL P-PROXIMITY

H-ELEVATOR HALL CALL S-SMART CARD

T-TOKEN

DURESS/PANIC ALARM PUSH BUTTON

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

ELECTRONIC LOCK; LETTER INDICATES AS

FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION P-PEDESTAL R-RACK S-SURFACE

W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET

M-MAGNETIC S-STRIKE

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION P-PEDESTAL R-RACK S-SURFACE

W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

ITEMS SHOWN IN GRAY ARE EXISTING TO REMAIN

DEMOLITION PLANS: SOLID DARK ITEMS ARE TO BE

REMOVED OR MODIFIED.

NEW PLANS: SOLID DARK ITEMS ARE TO BE

ADDED OR MODIFIED.

DASHED ITEMS ARE INSTALLED BELOW REFERENCED

PLAN

NCS

NCT

M

M

M

S

S

TTB

N D

N D

M

T

M

T

M

T

DH

POINT OF CONNECTION SYMBOL

BASIC ELECTRICAL REQUIREMENTS

FURNISH ALL LABOR AND MATERIALS AND PERFORM ALL

OPERATIONS NECESSARY FOR THE INSTALLATION OF COMPLETE

AND OPERATING ELECTRICAL SYSTEMS SUBJECT TO THE

CONDITIONS OF THE CONTRACT. PROVIDE SATISFACTORY

OPERATION OF ALL EQUIPMENT AND CONTROLS TO THE

ARCHITECT/ENGINEER UPON REQUEST.

ALL MATERIALS SHALL BE NEW. SUBSTITUTIONS SHALL BE

APPROVED BY OWNER AND/OR ENGINEER.

VISIT THE PREMISES BEFORE SUBMITTING BID AS NO CHANGE

ORDERS WILL BE ALLOWED FOR LACK OF KNOWLEDGE OF EXISTING

CONDITIONS.

COORDINATE AND ORDER THE PROGRESS OF WORK TO CONFORM

TO THE PROJECT SCHEDULE AND THE PROGRESS OF THE WORK OF

THE OTHER TRADES.

ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND BECAUSE OF THE

SMALL SCALE, IT IS NOT POSSIBLE TO INDICATE EVERY REQUIRED

OFFSET, FITTING, ETC. VERIFY ALL SPACE REQUIREMENTS,

COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS

IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES TO THE

OWNER.

PERFORM WORK IN ACCORDANCE WITH GOOD COMMERCIAL

PRACTICE. THE GOOD APPEARANCE OF THE FINISHED WORK SHALL

BE OF EQUAL IMPORTANCE WITH ITS ELECTRICAL EFFICIENCY AND

INTENT. THE OWNER MAY REJECT WORK IF WORKMANSHIP AND

APPEARANCE ARE NOT SATISFACTORY.

INSTALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH THE

MANUFACTURERS' RECOMMENDATIONS UNLESS SPECIFICALLY

INDICATED OTHERWISE, OR WHERE LOCAL CODES OR

REGULATIONS TAKE PRECEDENCE.

COMPLY WITH STATE AND LOCAL CODE REQUIREMENTS AND

ORDINANCES. COMPLY WITH REQUIREMENTS OF THE UTILITY

COMPANIES. IN THE CASE OF DIFFERENCES BETWEEN THESE

REQUIREMENTS AND ORDINANCES, THE MOST STRINGENT SHALL

GOVERN. CALL FOR INSPECTIONS REQUIRED BY LOCAL BUILDING

INSPECTION AUTHORITY.

PLANS AND SPECIFICATIONS GO HAND IN HAND. WHAT IS REQUIRED

IN ONE IS REQUIRED IN BOTH. WHERE CONFLICTS BETWEEN

SPECIFICATIONS AND PLANS EXIST, THE MOST STRINGENT

REQUIREMENTS SHALL APPLY.

BACKGROUND FLOOR PLANS USED FOR ELECTRICAL DRAWINGS

MAY SHOW DIFFERENT THAN THE FINAL ARCHITECTURAL LAYOUT.

REFER TO ARCHITECTURAL DRAWINGS FOR ACTUAL DIMENSIONS

AND LAYOUT PLACEMENTS FOR SPACE CONDITIONS.

ELECTRICAL DETAILS MAY OR MAY NOT BE DIRECTLY REFERENCED.

ALL DETAILS SHOWN ARE TO BE USED FOR BASIS OF INSTALLATION

IN ALL CASES, IN COORDINATED EFFORT WITH MANUFACTURERS

INSTALLATION RECOMMENDATIONS.

ELECTRICAL SHEETS ARE NOT INTENDED TO SPECIFICALLY BE

TRADE SPECIFIC TO ELECTRICAL INSTALLATION WORK. ALL

MECHANICAL AND ELECTRICAL TRADES ARE RESPONSIBLE FOR

FAMILIARIZING THEMSELVES AND INCLUDING A COMPLETE PACKAGE

WITHIN THEIR OFFER FOR A COMPLETE SYSTEM.

AT COMPLETION OF WORK, DELIVER COMPLETED PROJECT RECORD

DOCUMENTS MARKED WITH FIELD CHANGES TO OWNER.

PROVIDE A WRITTEN WARRANTY TO THE OWNER COVERING THE

ENTIRE ELECTRICAL WORK TO BE FREE FROM DEFECTIVE

MATERIALS, EQUIPMENT AND WORKMANSHIP FOR A PERIOD OF 1

YEAR AFTER DATE OF ACCEPTANCE.

CLEAN EXPOSED SURFACES OF LIGHT FIXTURES, SWITCHGEAR,

AND OTHER EXPOSED ITEMS OF GREASE, DIRT OR OTHER FOREIGN

MATERIAL. REMOVE RUBBISH AND DEBRIS RESULTING FROM THE

OPERATIONS AND LEAVE EQUIPMENT SPACES CLEAN AND READY

FOR USE.

MAINTAIN ALL CEILING, FLOOR AND WALL FIRE AND SMOKE

PROTECTION RATINGS. SEAL ALL CONDUIT AND ENCLOSURE

PENETRATIONS TO COMPLY WITH UL ASSEMBLY AND BUILDING

CODE REQUIREMENTS. ALL SEALANTS AND CONSTRUCTIONS SHALL

BE APPROVED BY OWNER PRIOR TO APPLICATION. ALL OPENINGS

SHALL BE SEALED DAILY.

CONTRACT DRAWINGS FOR ELECTRICAL WORK ARE IN PART

DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND

INDICATE GENERAL ARRANGEMENT OF EQUIPMENT, CONDUITS, AND

APPROXIMATE SIZES AND LOCATIONS OF EQUIPMENT AND OUTLETS.

MECHANICAL/ELECTRICAL TRADES SHALL FOLLOW THESE

DRAWINGS IN LAYING OUT THEIR WORK, CONSULT GENERAL

CONSTRUCTION DRAWINGS TO FAMILIARIZE THEMSELVES WITH ALL

CONDITIONS AFFECTING THEIR WORK, AND SHALL VERIFY SPACES

IN WHICH THEIR WORK WILL BE INSTALLED. COORDINATE WORK

WITH OTHER TRADES AND AS PROJECT CONDITIONS REASONABLY

REQUIRE WITHOUT EXTRA COSTS TO OWNER.

ELECTRICAL SPECIFIC:

RACEWAYS SHALL BE LEFT WITH 30% FREE SPACE FOR FUTURE

NEEDS.

SHARING OF NEUTRALS BETWEEN PHASES SHALL NOT BE

ALLOWED.

SEPARATE GROUNDING CONDUCTORS SHALL BE PROVIDED IN ALL

RACEWAYS.

CONDUCTORS SHALL BE COPPER. COLOR CODING SHALL BE NEC

APPROVED AND AT MINIMUM SHALL BE AS FOLLOWS:

120/208 VOLT-BLACK, RED, BLUE FOR PHASE CONDUCTORS, WHITE

FOR NEUTRAL CONDUCTORS. 277/480 VOLT-BROWN, ORANGE,

YELLOW FOR PHASE CONDUCTORS, GRAY FOR NEUTRAL

CONDUCTORS. GROUNDING CONDUCTORS SHALL BE GREEN.

ELECTRICAL SYSTEMS SHALL COMPLY WITH 2023 NATIONAL

ELECTRICAL CODE AND BE INSTALLED BY LICENSED CONTRACTORS.

LIGHTING SHALL COMPLY WITH THE 2021 IECC.

UTILITIES:

LOCATION OF UNDERGROUND UTILITIES ARE APPROXIMATE. IT IS

THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE EXACT

LOCATIONS IN THE FIELD (NOT ALL UTILITIES ARE SHOWN).

REGULATORY AND CODE REQUIREMENTS:

ALL WORK IS SUBJECT TO APPROVAL BY THE VA COR/CS AND

ENGINEER. ALL CORRECTIONS SHALL BE MADE WITHOUT EXTRA

COSTS TO OWNER.

E-000

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

ELECTRICAL LEGENDS AND

ABBREVIATIONS

34"

2' MIN

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

1" EMPTY CONDUIT

WITH CAP (WHERE

SHOWN ON PLANS)

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

LIGHT POLE PER LIGHT

FIXTURE SCHEDULE

3"x5" REINFORCED HAND HOLE

WITH TAMPER RESISTANT

SCREWS. PROVIDE IN-LINE

SCREW-TYPE FUSE HOLDER(S)

WITH FUSE(S).

POLE GROUNDING STUD

2-PIECE BOLT COVER PLATE.

FINISHED GRADE

PVC CONDUIT

ADAPTER COUPLING

PVC CONDUIT

RIGID STEEL CONDUIT

UNDISTURBED SOIL

OR SELECT BACKFILL

COMPACTED

6'

18"

NO. 6 BARS

NO. 4 @ 12" SPACING

3/4" NMC FOR GROUND WIRE

PLAN

CONDUIT CONFIGURATION

CONDUIT SIZE

MAY VARY

SEE PLAN FOR

11.5" DIA. BOLT

(ANCHOR ROD) CIRCLE

18" DIA. CONCRETE

LIGHT FOUNDATION

EXISTING GROUND ROD

EXISTING CONCRETE BASES

INSTALLED PER IBC 2021

ACI318-19 LAP

NEW LIGHTING POLES TO BE ORDERED

WITH 11.5" BOLT PATTERN DIAMETER

TO MATCH EXISTING BASES

34"

2' MIN

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

1" EMPTY CONDUIT

WITH CAP (WHERE

SHOWN ON PLANS)

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

LIGHT POLE PER LIGHT

FIXTURE SCHEDULE

3"x5" REINFORCED HAND HOLE

WITH TAMPER RESISTANT

SCREWS. PROVIDE IN-LINE

SCREW-TYPE FUSE HOLDER(S)

WITH FUSE(S).

POLE GROUNDING STUD

2-PIECE BOLT COVER PLATE.

FINISHED GRADE

PVC CONDUIT

ADAPTER COUPLING

PVC CONDUIT

RIGID STEEL CONDUIT

UNDISTURBED SOIL

OR SELECT BACKFILL

COMPACTED

6'

24"

NO. 6 BARS

NO. 4 @ 12" SPACING

3/4" NMC FOR GROUND WIRE

PLAN

CONDUIT CONFIGURATION

CONDUIT SIZE

MAY VARY

SEE PLAN FOR

11.5" DIA. BOLT

(ANCHOR ROD) CIRCLE

24" DIA. CONCRETE

LIGHT FOUNDATION

EXISTING GROUND ROD

EXISTING CONCRETE BASES

INSTALLED PER IBC 2021

ACI318-19 LAP

NEW LIGHTING POLES TO BE ORDERED

WITH 11.5" BOLT PATTERN DIAMETER

TO MATCH EXISTING BASES

30"

CONCRETE BASE &

REINFORCING STEEL,

SEE NOTE BELOW.

1" EMPTY CONDUIT

WITH CAP (WHERE

SHOWN ON PLANS)

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

LIGHT POLE PER LIGHT

FIXTURE SCHEDULE

3"x5" REINFORCED HAND HOLE

WITH TAMPER RESISTANT

SCREWS. PROVIDE IN-LINE

SCREW-TYPE FUSE HOLDER(S)

WITH FUSE(S).

POLE GROUNDING STUD

2-PIECE BOLT COVER PLATE.

FINISHED GRADE

PVC CONDUIT

ADAPTER COUPLING

PVC CONDUIT

RIGID STEEL CONDUIT

UNDISTURBED SOIL

OR SELECT BACKFILL

COMPACTED

6'

36"

NEW LIGHTING POLES TO BE

ORDERED WITH 11.5" BOLT DIAMETER

TO MATCH EXISTING BASES

NO. 6 BARS

NO. 4 @ 12" SPACING

3/4" NMC FOR GROUND WIRE

PLAN

CONDUIT CONFIGURATION

CONDUIT SIZE

MAY VARY

SEE PLAN FOR

11.5" DIA. BOLT

(ANCHOR ROD) CIRCLE

36" DIA. CONCRETE

LIGHT FOUNDATION

2' MIN

EXISTING GROUND ROD

BOLT PROJECTION

MINIMUM - 3.25"

MAXIMUM - 3.75

POLE BASE ANCHOR BOLT

PROJECTION LENGTH. (TYP.)

ANCHOR BOLTS PER POLE

MANUFACTURER'S REQUIREMENTS

WITH LEVELING NUTS ABOVE &

BELOW BASE PLATE

2-PIECE BOLT COVER PLATE.

LIGHT POLE

LIGHT POLE BASE PLATE

LIGHT POLE BASE

LIGHT POLE ANCHOR BOLT

EXISTING CONCRETE BASES

INSTALLED PER IBC 2021

ACI318-19 LAP

MIN. RADIUS ANCHOR ROD

PLACEMENT

THREADS

HEX NUTS PER ROD

2 GALVANIZED FLAT

6"

90^

90^

90^

90^

2 GALVANIZED HEAVY

WASHERS PER ROD

1" DIA.

36"

CONTRACTOR MUST INVENTORY AND MEASURE EVERY BOLT

PATTERN ON EVERY BASE PRIOR TO ORDERING MOUNTING

EQUIPMENT.

GENERAL ELECTRICAL NOTE

ELECTRICAL DETAILS

E-001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

EXISTING POLE BASE P1 DETAIL

SCALE: NTS

E-001

EXISTING POLE BASE P2 DETAIL

SCALE: NTS

E-001

EXISTING POLE BASE P3 DETAIL

SCALE: NTS

E-001

TYPICAL ANCHOR ROD (4 PER FOUNDATION)

SCALE: NTS

E-001

A. ON BOARD PHOTO CONTROL.

B. 0-10 V DIMMING..

E. EMERGENCY BACKUP BATTERY ON FIXTURES WITH ADDITIONAL E TAG.

NOTES

LAMPFIXTURE

EXISTING AND NEW LIGHTING FIXTURE SCHEDULE

SYMBOL HYPERLINK

1. EXISTING FIXTURE TO BE REMOVED AND REPLACED UNLESS OTHERWISE NOTED.

2. LUMINAIRES ARE DIRECTIONAL. INSTALL PROJECTION AREA IN DIRECTION OF ARROW ON PLANS.

3. INSTALL LUMINAIRE ON AV POLES & LIGHTING SWEEP ARM SMALL BRACKET AVPL-SWA-S-WALL MOUNT-DARK BRONZE

LETTER

DESIG.

EXISTING MULTIPLE GLOBE STYLE

POLE MOUNT

LOCATIONMANUFACTURER CATALOG NO. TYPEDESCRIPTION

LUMINAIRE NOTES:

HEIGHT

CONTROL NOTES:

P1 - EXISTING POLE MOUNT EXTERIOR -- -*- - --

TYPE NO. WATTS LUMENS

P2 - EXISTING POLE MOUNT WITH SOLAR EXTERIOR -- -*- - --

P3 - EXISTING POLE MOUNT EXTERIOR -- -*- - --

P4 - EXISTING DIKE LIGHTING EXTERIOR -- -*- - --

M1 - EXISTING SEMI CIRCULAR WALL PACK EXTERIOR -- -*- - --

M2 - EXISTING WALL PACK EXTERIOR -- -*- - --

M3 - EXISTING SLIM SURFACE WALL PACK EXTERIOR -- -*- - --

M4 - EXTERIOR -- -*- - --

M5 - EXISTING BUILDING MOUNT LUMINAIRE EXTERIOR -- -*- - --

M6 - EXTERIOR -- -*- - --

M7 - EXISTING SLENDER WALL PACK EXTERIOR -- -*- - --

M8 - EXTERIOR -- -*- - --

M9 - EXISTING WALL PACK EXTERIOR -- -*- - --

M10 - EXISTING WALL PACK EXTERIOR -- -*- - --

M11 - EXISTING SCONCE EXTERIOR -- -*- - --

B1 - EXISTING BULB STYLE BOLLARD EXTERIOR -- -*- - --

B2 - EXISTING BOLLARD EXTERIOR -- -*- - --

P5 - EXTERIOR -- -*- - --

P6 - EXISTING GLOBE STYLE POLE MOUNT EXTERIOR -- -*- - --

EXISTING SLIM SURFACE WALL PACK

EXISTING SLIM SURFACE WALL PACK

EXISTING SLIM SURFACE WALL PACK

NP2 EXTERIOR -

NP1 VICTORIAN POST TOP LANTERN EXTERIOR -

NB1 EXTERIOR -

LEXINGTON DECORATIVE POST TOP LUMINAIRE

INVUE MSA MESA AREA LUMINAIRE

AV POLES & LIGHTING

AV POLES & LIGHTING

COOPER LIGHTING

AVPL-VPTL-TYPEV-106W-4000K-120-277V-CSA-_-DARK BRONZE

AVPL-FAB8-36-26-4000K-120-277V-DR-DARK BRONZE-_

LXT-PA1-100-740-U-SL3-CL-BZ-HSS

20'POLE TOP

36"BOLLARD

POLE TOP 20'

-LED 106 16,698

-LED 8410

-LED 26 3515

SPEC

SPEC

SPEC

NM1 EXTERIOR -SLENDER WALL PACKMULE LIGHTING MERU-LED-ACEM-DB-IH-PIR *WALL PACK -LED 32 1600 SPEC

NM2 EXTERIOR -NO CUT-OFF WALL PACKELITE LIGHTING OWP-NC-101-LED-8000L-_-MVOLT-40K-_-BZ-_ *WALL PACK -LED 60 8097 SPEC

NP3 VICTORIAN COLUMN MOUNT LANTERN EXTERIOR -AV POLES & LIGHTING 6'COLUMN -LED 106 16,698 SPEC3 SPEC,AVPL-VPTL-TYPEV-106W-4000K-120-277V-CSA + AVPL-SWA-S-1-WALL

MOUNT-DARK BRONZE

NS1 EXTERIOR -IN-GRADE STAIR LUMINAIREHYDREL MP9420C-A-LED-P2-40K-MVOLT-MFL-FLC-34B-_-_-BZ *IN GRADE -LED 20 2154 SPEC

B2 - EXISTING IN-GRADE STAIR LUMINAIRE EXTERIOR -- -*- - -- 1

C1 - EXISTING CANOPY LUMINAIRE EXTERIOR -- -*- - -- 1

NC1 EXTERIOR -SURFACE MOUNT DOWNLIGHTELITE LIGHTING OVR-203-LED-6000L-_-MVOLT-40K-BZ-_-_ *SURFACE -LED 40 6000 SPEC

ELECTRICAL SCHEDULES

E-002

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

INSTALL CIRCUIT ON SPARE BREAKER FOR

NEW WALL MOUNT LIGHTING AROUND

BUILDING 50

N

RE

D

RI

VE

R

OF

TH

E

NO

RT

H

30W 30E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

8 3

01_PB_10N3

01_PB_EB10S1

09_PB_90W1

00_PB_RO

PARKING

00_PB_TQ

00_PB_STREET

P1 P1 P1 P1

P1 P1 P1 P1

P1

P1

P2 P2

P2

P2

P2 P2

P3

P3 P3 P3

P3

P3 P3

P3 P3

P3 P3

P3

P3

P2

P2

P2

P2

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1P1P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1 P1

P1

P1 P1

P1 P1

P1

P2

P2

P1

P3

P3

P3 P3 P3

P3

P3

P1

P3 P3 P3

P3

P3

P3

P3 P3P3 P3

P3

P3

P3 P3

P3

B1B1B1B1 B1

B1

B1 B1

B1 B1 B1

B1B2

B2B2

B2

B2 B2

B2

B2 B2

B2

B2

B2 B2

B2B2 B2

B2

B2

B2

B2

P3

P2

P1

P2

P3

P3

P3

P6

P6

P4

P4

P4

P4

P4

P4

P5 P5

M5 M5

M5

M5

M5

M5

M5

M5

M5

M5

M5

M5

M5 M5

M3

M2 M2 M2

M2 M2

M2

M3 M3 M3

M4 M4

M1 M1

M1

M1M1

M1M1

M1 M1

M1

M1

M1

M1M1M1

M1

M1

M1

M1

M1

M1

M1

M11

M11

M6M6

M8 M8 M8

M9 M9 M9 M9 M10

M10

M10

M10

M2

M2 M2 M2

M2

M2

M2

M2 M2

HH

H

H

H

H

P3

P3

H

P3

P3

M1

LUMINAIRE AND FIXTURE PREVIOUSLY

REMOVED. REMOVE EXISTING

LUMINAIRE CONCRETE BASE AND

PATCH ASPHALT AS REQUIRED.

P3

P3

M2

LUMINAIRES IN THIS AREA ARE

ALTERNATE NO. 1 BID ITEM.

LUMINAIRES IN THIS AREA WILL

BE PART OF A FUTURE

PROJECT.

S1 S1 S1 S1 C1

C1 C1 C1

EXISTING SUSPENDED

LUMINAIRE TO REMAIN

C1C1 C1

C1

LUMINAIRES IN THIS

AREA WILL BE BID

ALTERNATE #2

THIS PROJECT INCLUDES REPLACEMENT FOR POLES AND

POLE FIXTURES P1, P2, P3, B1 BOLLARDS, CANOPY C1,

STAIR S1 AND BUILDING MOUNT LUMINAIRES ONLY. THE

DIKE LIGHTING, P4, P5, P6 AND HEALING GARDEN B2

LIGHTING IS NOT INCLUDED IN THE PROJECT. EXISTING

POLE BASES TO REMAIN AND BE RE-USED. REFER TO

ENLARGED SITE PLANS FOR MORE INFORMATION

MAXIMUM OF 6 PARKING STALLS ALLOWED TO BE

BLOCKED AT ONE TIME DURING REMOVAL AND

INSTALLATION OF FIXTURES. COORDINATE WITH VA COR

FOR FINAL PHASING PLAN.

PHASING GENERAL NOTE

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #1: BASE BID EXCEPT DELETE WORK TO

INSTALL ALL LIGHTING IN PARKING RAMP AREA. POLES

AND POLE TOP LUMINAIRES INDICATED ON PLANS TO BE

REMOVED FROM PROJECT. ALL OTHER LUMINAIRES ON

PLANS TO REMAIN IN PROJECT, INCLUDING POLES AND

POLE TOP LUMINAIRES, BUILDING MOUNTED LUMINAIRES,

BOLLARDS, CANOPY LUMINAIRES AND STAIR LUMINAIRES

TO BE REPLACED.

BID ALTERNATE #1

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #2: BASE BID EXCEPT DELETE

SPECIFIED MENTAL HEALTH PARKING AREA POLE AND

POLE TOP MOUNTED LUMINAIRES, AND BUILDING 52

BUILDING MOUNTED WALL PACKS SHOWN ON PLANS. ALL

OTHER POLES AND POLE TOP LUMINAIRES, BUILDING

MOUNTED LUMINAIRES, BOLLARDS, CANOPY LUMINAIRES

AND STAIR LUMINAIRES TO BE REPLACED.

BID ALTERNATE #2

SITE PLAN - DEMOLITION PLAN LIGHTING

SCALE: 1/64" = 1'

E-100

E-100

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

LIGHTING DEMOLITION - FULL SITE

PLAN

D

RI

VE

R

OF

TH

E

NO

RT

H

30W 30E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

8 3

AREA

B

AREA

C

AREA

D

AREA

E

AREA

A

30W 30E

01_PB_10N309_PB_90W1

00_PB_TQ

P1 P1 P1

P1

P1

P1 P1 P1

P1

P1

P2 P2

P2

P2

P2

P2

P3

P3 P3 P3

P3

P3

P3 P3

P3

P3

P3

P2

B2

B2 B2

B2

B2

B2

B2

B2 B2

B2

B2

B2

B2

B2 B2

B2B2

B2

M3

M2

M2 M2

M1M1

M1M1

M1

M1

M1

M1

M1

M1M1M1

PANEL MOUNTED IN THE ENCLOSURE CONTAINS

THE BRANCH CIRCUITS SERVING NORTHWEST

PARKING LOT LIGHTING. NO INTENDED WORK IN

THE PANEL. SHOWN FOR REFERENCE ONLY.

PANEL CONTAINS THE BRANCH

CIRCUIT SERVING THE B2 BOLLARDS

IN THE HEALING GARDENS. NO

INTENDED WORK IN THE PANEL.

SHOWN FOR REFERENCE ONLY.

PANEL CONTAINS THE

BRANCH CIRCUIT FOR

EXTERIOR LIGHTING AT THE

VETERAN'S CAFE. NO

INTENDED WORK IN THE

PANEL. SHOWN FOR

REFERENCE ONLY.

1 1

1 1 1 1

1 1

1 1

5 5

J

J

J

J J

J

J

J

J

J

J

J J J

J

P3

P3

8 8

LUMINAIRES IN THIS

AREA WILL BE BID

ALTERNATE #2

THIS PROJECT INCLUDES REPLACEMENT FOR POLES AND

POLE LIGHTING P1, P2, P3, B1 BOLLARDS, CANOPY C1,

STAIR S1 AND BUILDING MOUNT LUMINAIRES ONLY. THE

DIKE LIGHTING, P4, P5, P6 AND HEALING GARDEN B2

LIGHTING IS NOT INCLUDED IN THE PROJECT. EXISTING

POLE BASES TO REMAIN AND BE RE-USED UNLESS

OTHERWISE NOTED. POLE, AND POLE TOP LUMINAIRE TO BE REMOVED FROM

EXISTING POLE BASE. POLE BASE TO REMAIN AND BE

REUSED FOR NEW POLE AND LUMINAIRE.

DEMOLITION KEYED ELECTRICAL NOTES

EXISTING BOLLARD TO BE REMOVED. PREPARE AREA

FOR NEW BOLLARD.

EXISTING LIGHT FIXTURE TO REMAIN.

REMOVE CONCRETE LIGHT BASE AND REPAIR DRIVEWAY.

EXISTING BUILDING MOUNT LIGHT TO BE REMOVED.

PREPARE AREA FOR NEW BUILDING MOUNT LIGHT.

LUMINAIRES ARE PART OF BID ALTERNATE #1

REMOVE EXISTING CONCRETE LIGHT POLE FOUNDATION

COMPLETLY, FILL WITH CLEAN FILL DIRT AND COMPACT

AT LEVELS TO MATCH ADJACENT SOILS. PATCH ASPHALT

TO MATCH ADJACENT THICKNESS AND PAINT ANY LINES

WITH APPROVED TRAFFIC PAINT TO COMPLETE THE

ADJACENT PATTERN.

EXISTING COLUMN MOUNTED ARM BRACKET, AND

LUMINAIRE TO BE REMOVED FROM BRICK COLUMN.

PREPARE SURFACE FOR MOUNTING NEW MOUNTING

BRACKET.

LUMINAIRES ARE BID ALTERNATE #2. EXISTING

LUMINAIRES TO REMAIN AND BE REPLACED IN FUTURE

PROJECT.

REMOVE EXISTING IN STAIR LUMINAIRE. PREPARE AREA

TO INSTALL NEW LUMINAIRE IN EXISTING LOCATION.

REMOVE EXISTING CANOPY LUMINAIRES. PREPARE AREA

TO INSTALL NEW CANOPY LUMINAIRES IN EXISTING

LOCATIONS.

KEYED NOTES BELOW ARE FOR ALL SHEETS. IF KEYED

NOTE IS NOT SHOWN ON A SPECIFIC SHEET, THE KEYED

NOTE DOES NOT APPLY TO SHEET

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #1: BASE BID EXCEPT DELETE WORK TO

INSTALL ALL LIGHTING IN PARKING RAMP AREA. POLES

AND POLE TOP LUMINAIRES INDICATED ON PLANS TO BE

REMOVED FROM PROJECT. ALL OTHER LUMINAIRES ON

PLANS TO REMAIN IN PROJECT, INCLUDING POLES AND

POLE TOP LUMINAIRES, BUILDING MOUNTED LUMINAIRES,

BOLLARDS, CANOPY LUMINAIRES AND STAIR LUMINAIRES

TO BE REPLACED.

BID ALTERNATE #1

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #2: BASE BID EXCEPT DELETE

SPECIFIED MENTAL HEALTH PARKING AREA POLE AND

POLE TOP MOUNTED LUMINAIRES, AND BUILDING 52

BUILDING MOUNTED WALL PACKS SHOWN ON PLANS. ALL

OTHER POLES AND POLE TOP LUMINAIRES, BUILDING

MOUNTED LUMINAIRES, BOLLARDS, CANOPY LUMINAIRES

AND STAIR LUMINAIRES TO BE REPLACED.

BID ALTERNATE #2

SITE KEY PLAN

E-101

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

ENLARGED SITE PLAN - AREA A LIGHTING DEMOLITION

SCALE: 1/32" = 1'

E-101

LIGHTING DEMOLITION ENLARGED

SITE PLAN AREA A

AREA C

CONTINUES ON

SHEET E-103

AREA B

CONTINUES ON

SHEET E-102

D

RI

VE

R

OF

TH

E

NO

RT

H

30W 30E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

8 3

AREA

A

AREA

B

AREA

C

AREA

D

AREA

E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

01_PB_10N3

00_PB_STREET

P3

P3 P3 P2

P2

P1

P1

P1

P1

P1

P1

P1

P1

P1

P1

B1

B1

B1

B1

P1

P2

P4

P4

M5

M5

M5

M5

M5

M5

M5

M5

M5

M5

M5

M5

M5 M5

M2 M2

M2 M2

M2

M3 M3 M3

M4 M4

M1 M1

M1

M1

M8 M8 M8

M9 M9 M9 M9

M10

M6M6

PANEL CONTAINS THE

BRANCH CIRCUIT FOR

EXTERIOR LIGHTING AT THE

VETERAN'S CAFE. NO

INTENDED WORK IN THE

PANEL. SHOWN FOR

REFERENCE ONLY.

PANEL MOUNTED IN THE ENCLOSURE

CONTAINS THE BRANCH CIRCUITS

SERVING NORTHEAST PARKING LOT

LIGHTING. NO INTENDED WORK IN THE

PANEL. SHOWN FOR REFERENCE ONLY.

5 5

5 5

3 3

5 5

5 5

5 5

5 5 5

M1

J J

J

J

J

J

J J

J J

J

J J

JJ

J

J

J

J

J

J

J

J

J

J

J

J

J J

JJ

J J J

J J J J

J

THIS PROJECT INCLUDES REPLACEMENT FOR POLES AND

POLE LIGHTING P1, P2, P3, B1 BOLLARDS, CANOPY C1,

STAIR S1 AND BUILDING MOUNT LUMINAIRES ONLY. THE

DIKE LIGHTING, P4, P5, P6 AND HEALING GARDEN B2

LIGHTING IS NOT INCLUDED IN THE PROJECT. EXISTING

POLE BASES TO REMAIN AND BE RE-USED UNLESS

OTHERWISE NOTED. POLE, AND POLE TOP LUMINAIRE TO BE REMOVED FROM

EXISTING POLE BASE. POLE BASE TO REMAIN AND BE

REUSED FOR NEW POLE AND LUMINAIRE.

DEMOLITION KEYED ELECTRICAL NOTES

EXISTING BOLLARD TO BE REMOVED. PREPARE AREA

FOR NEW BOLLARD.

EXISTING LIGHT FIXTURE TO REMAIN.

REMOVE CONCRETE LIGHT BASE AND REPAIR DRIVEWAY.

EXISTING BUILDING MOUNT LIGHT TO BE REMOVED.

PREPARE AREA FOR NEW BUILDING MOUNT LIGHT.

LUMINAIRES ARE PART OF BID ALTERNATE #1

REMOVE EXISTING CONCRETE LIGHT POLE FOUNDATION

COMPLETLY, FILL WITH CLEAN FILL DIRT AND COMPACT

AT LEVELS TO MATCH ADJACENT SOILS. PATCH ASPHALT

TO MATCH ADJACENT THICKNESS AND PAINT ANY LINES

WITH APPROVED TRAFFIC PAINT TO COMPLETE THE

ADJACENT PATTERN.

EXISTING COLUMN MOUNTED ARM BRACKET, AND

LUMINAIRE TO BE REMOVED FROM BRICK COLUMN.

PREPARE SURFACE FOR MOUNTING NEW MOUNTING

BRACKET.

LUMINAIRES ARE BID ALTERNATE #2. EXISTING

LUMINAIRES TO REMAIN AND BE REPLACED IN FUTURE

PROJECT.

REMOVE EXISTING IN STAIR LUMINAIRE. PREPARE AREA

TO INSTALL NEW LUMINAIRE IN EXISTING LOCATION.

REMOVE EXISTING CANOPY LUMINAIRES. PREPARE AREA

TO INSTALL NEW CANOPY LUMINAIRES IN EXISTING

LOCATIONS.

KEYED NOTES BELOW ARE FOR ALL SHEETS. IF KEYED

NOTE IS NOT SHOWN ON A SPECIFIC SHEET, THE KEYED

NOTE DOES NOT APPLY TO SHEET

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #1: BASE BID EXCEPT DELETE WORK TO

INSTALL ALL LIGHTING IN PARKING RAMP AREA. POLES

AND POLE TOP LUMINAIRES INDICATED ON PLANS TO BE

REMOVED FROM PROJECT. ALL OTHER LUMINAIRES ON

PLANS TO REMAIN IN PROJECT, INCLUDING POLES AND

POLE TOP LUMINAIRES, BUILDING MOUNTED LUMINAIRES,

BOLLARDS, CANOPY LUMINAIRES AND STAIR LUMINAIRES

TO BE REPLACED.

BID ALTERNATE #1

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #2: BASE BID EXCEPT DELETE

SPECIFIED MENTAL HEALTH PARKING AREA POLE AND

POLE TOP MOUNTED LUMINAIRES, AND BUILDING 52

BUILDING MOUNTED WALL PACKS SHOWN ON PLANS. ALL

OTHER POLES AND POLE TOP LUMINAIRES, BUILDING

MOUNTED LUMINAIRES, BOLLARDS, CANOPY LUMINAIRES

AND STAIR LUMINAIRES TO BE REPLACED.

BID ALTERNATE #2

SITE KEY PLAN

E-102

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

SCALE: 1/32" = 1'

E-102

LIGHTING DEMOLITION ENLARGED

SITE PLAN AREA B

ENLARGED SITE PLAN - AREA B LIGHTING DEMOLITION

AREA D

CONTINUES ON

SHEET E-104

AREA A

SHEET E-101

D

RI

VE

R

OF

TH

E

NO

RT

H

30W 30E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

8 3

AREA

A

AREA

B

AREA

D

AREA

E

AREA

C

00_PB_RO

PARKING

P3

P3

P1

P1

P1

P1

P1

P1

P1

P1 P1

P1

P2

P1

P3

P3

P3 P3 P3

P3

P1

B1B1B1B1

B1

B1

B1 B1

B2

B2

B2B2

B2

B2

B2

P3

P2

P3

P3

P3

P6

P6

P5 P5

M11

M11

M2

M2

M2

SHOWN FOR REFERENCE ONLY.

PANEL MOUNTED IN THE ENCLOSURE

CONTAINS THE BRANCH CIRCUITS

SERVING THE SOUTH PARKING LOT

LIGHTING. NO INTENDED WORK IN THE

PANEL. SHOWN FOR REFERENCE ONLY.

1 1

1 2 2 2 2

2 2

1 1

1 1 1

J

J

J J

M2 5

S1

S1

S1

S1

C1

EXISTING SUSPENDED

LUMINAIRE TO REMAIN

C1

C1 C1

C1C1

C1C1 10 10

THIS PROJECT INCLUDES REPLACEMENT FOR POLES AND

POLE LIGHTING P1, P2, P3, B1 BOLLARDS, CANOPY C1,

STAIR S1 AND BUILDING MOUNT LUMINAIRES ONLY. THE

DIKE LIGHTING, P4, P5, P6 AND HEALING GARDEN B2

LIGHTING IS NOT INCLUDED IN THE PROJECT. EXISTING

POLE BASES TO REMAIN AND BE RE-USED UNLESS

OTHERWISE NOTED. POLE, AND POLE TOP LUMINAIRE TO BE REMOVED FROM

EXISTING POLE BASE. POLE BASE TO REMAIN AND BE

REUSED FOR NEW POLE AND LUMINAIRE.

DEMOLITION KEYED ELECTRICAL NOTES

EXISTING BOLLARD TO BE REMOVED. PREPARE AREA

FOR NEW BOLLARD.

EXISTING LIGHT FIXTURE TO REMAIN.

REMOVE CONCRETE LIGHT BASE AND REPAIR DRIVEWAY.

EXISTING BUILDING MOUNT LIGHT TO BE REMOVED.

PREPARE AREA FOR NEW BUILDING MOUNT LIGHT.

LUMINAIRES ARE PART OF BID ALTERNATE #1

REMOVE EXISTING CONCRETE LIGHT POLE FOUNDATION

COMPLETLY, FILL WITH CLEAN FILL DIRT AND COMPACT

AT LEVELS TO MATCH ADJACENT SOILS. PATCH ASPHALT

TO MATCH ADJACENT THICKNESS AND PAINT ANY LINES

WITH APPROVED TRAFFIC PAINT TO COMPLETE THE

ADJACENT PATTERN.

EXISTING COLUMN MOUNTED ARM BRACKET, AND

LUMINAIRE TO BE REMOVED FROM BRICK COLUMN.

PREPARE SURFACE FOR MOUNTING NEW MOUNTING

BRACKET.

LUMINAIRES ARE BID ALTERNATE #2. EXISTING

LUMINAIRES TO REMAIN AND BE REPLACED IN FUTURE

PROJECT.

REMOVE EXISTING IN STAIR LUMINAIRE. PREPARE AREA

TO INSTALL NEW LUMINAIRE IN EXISTING LOCATION.

REMOVE EXISTING CANOPY LUMINAIRES. PREPARE AREA

TO INSTALL NEW CANOPY LUMINAIRES IN EXISTING

LOCATIONS.

KEYED NOTES BELOW ARE FOR ALL SHEETS. IF KEYED

NOTE IS NOT SHOWN ON A SPECIFIC SHEET, THE KEYED

NOTE DOES NOT APPLY TO SHEET

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #1: BASE BID EXCEPT DELETE WORK TO

INSTALL ALL LIGHTING IN PARKING RAMP AREA. POLES

AND POLE TOP LUMINAIRES INDICATED ON PLANS TO BE

REMOVED FROM PROJECT. ALL OTHER LUMINAIRES ON

PLANS TO REMAIN IN PROJECT, INCLUDING POLES AND

POLE TOP LUMINAIRES, BUILDING MOUNTED LUMINAIRES,

BOLLARDS, CANOPY LUMINAIRES AND STAIR LUMINAIRES

TO BE REPLACED.

BID ALTERNATE #1

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #2: BASE BID EXCEPT DELETE

SPECIFIED MENTAL HEALTH PARKING AREA POLE AND

POLE TOP MOUNTED LUMINAIRES, AND BUILDING 52

BUILDING MOUNTED WALL PACKS SHOWN ON PLANS. ALL

OTHER POLES AND POLE TOP LUMINAIRES, BUILDING

MOUNTED LUMINAIRES, BOLLARDS, CANOPY LUMINAIRES

AND STAIR LUMINAIRES TO BE REPLACED.

BID ALTERNATE #2

SITE KEY PLAN

E-103

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

SCALE: 1/32" = 1'

E-103

LIGHTING DEMOLITION ENLARGED

SITE PLAN AREA C

ENLARGED SITE PLAN - AREA C LIGHTING DEMOLITION

AREA A

CONTINUES ON

SHEET E-101

AREA E

CONTINUES ON

SHEET E-105

AREA D

SHEET E-104

D

RI

VE

R

OF

TH

E

NO

RT

H

30W 30E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

8 3

1 AREA

D

AREA

A

AREA

B

AREA

C

AREA

E

RE

D

RI

VE

R

OF

TH

E

NO

RT

H

01_PB_EB10S1

P2

P1

P1

P1

P1

P3

P4

P4

P4

M1

M1

M1

M1

M1

M1

M9 M9 M9 M9

M10

M10

M10

M10

M2

M2

M2

M2

M2

M2

M2

M2

P3

P3

HH

H

H

H

H

H

PANEL CONTAINS THE

BRANCH CIRCUIT FOR

THE DIKE LIGHTING (P4).

NO INTENDED WORK IN

THE PANEL. SHOWN FOR

REFERENCE ONLY.

P3

P3

5 5 5

5 3

5 3

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J J J J

COORDINATE LIGHTING WITH

BUILDING 1 EXPANSION.

"BUILDING 1 EXPANSION" PROJECT

WILL BE ADDING NEW LIGHT BASES

WITH EXISTING LIGHTING IN THESE

LOCATIONS.

"REPLACE SITE LIGHTING" PROJECT

WILL REMOVE AND REPLACE EXISTING

POLES AND FIXTURES ONTO NEW

BASES INSTALLED FOR THE PRIMARY

CARE EXPANSION

THIS PROJECT INCLUDES REPLACEMENT FOR POLES AND

POLE LIGHTING P1, P2, P3, B1 BOLLARDS, CANOPY C1,

STAIR S1 AND BUILDING MOUNT LUMINAIRES ONLY. THE

DIKE LIGHTING, P4, P5, P6 AND HEALING GARDEN B2

LIGHTING IS NOT INCLUDED IN THE PROJECT. EXISTING

POLE BASES TO REMAIN AND BE RE-USED UNLESS

OTHERWISE NOTED. POLE, AND POLE TOP LUMINAIRE TO BE REMOVED FROM

EXISTING POLE BASE. POLE BASE TO REMAIN AND BE

REUSED FOR NEW POLE AND LUMINAIRE.

DEMOLITION KEYED ELECTRICAL NOTES

EXISTING BOLLARD TO BE REMOVED. PREPARE AREA

FOR NEW BOLLARD.

EXISTING LIGHT FIXTURE TO REMAIN.

REMOVE CONCRETE LIGHT BASE AND REPAIR DRIVEWAY.

EXISTING BUILDING MOUNT LIGHT TO BE REMOVED.

PREPARE AREA FOR NEW BUILDING MOUNT LIGHT.

LUMINAIRES ARE PART OF BID ALTERNATE #1

REMOVE EXISTING CONCRETE LIGHT POLE FOUNDATION

COMPLETLY, FILL WITH CLEAN FILL DIRT AND COMPACT

AT LEVELS TO MATCH ADJACENT SOILS. PATCH ASPHALT

TO MATCH ADJACENT THICKNESS AND PAINT ANY LINES

WITH APPROVED TRAFFIC PAINT TO COMPLETE THE

ADJACENT PATTERN.

EXISTING COLUMN MOUNTED ARM BRACKET, AND

LUMINAIRE TO BE REMOVED FROM BRICK COLUMN.

PREPARE SURFACE FOR MOUNTING NEW MOUNTING

BRACKET.

LUMINAIRES ARE BID ALTERNATE #2. EXISTING

LUMINAIRES TO REMAIN AND BE REPLACED IN FUTURE

PROJECT.

REMOVE EXISTING IN STAIR LUMINAIRE. PREPARE AREA

TO INSTALL NEW LUMINAIRE IN EXISTING LOCATION.

REMOVE EXISTING CANOPY LUMINAIRES. PREPARE AREA

TO INSTALL NEW CANOPY LUMINAIRES IN EXISTING

LOCATIONS.

KEYED NOTES BELOW ARE FOR ALL SHEETS. IF KEYED

NOTE IS NOT SHOWN ON A SPECIFIC SHEET, THE KEYED

NOTE DOES NOT APPLY TO SHEET

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #1: BASE BID EXCEPT DELETE WORK TO

INSTALL ALL LIGHTING IN PARKING RAMP AREA. POLES

AND POLE TOP LUMINAIRES INDICATED ON PLANS TO BE

REMOVED FROM PROJECT. ALL OTHER LUMINAIRES ON

PLANS TO REMAIN IN PROJECT, INCLUDING POLES AND

POLE TOP LUMINAIRES, BUILDING MOUNTED LUMINAIRES,

BOLLARDS, CANOPY LUMINAIRES AND STAIR LUMINAIRES

TO BE REPLACED.

BID ALTERNATE #1

BASE BID: MODIFY EXISTING LIGHTING LAYOUT AS

SHOWN IN PLANS. REMOVE EXISTING POLE AND POLE

TOP LUMINAIRES FROM EXISTING POLE BASE, INSTALL

NEW POLES AND POLE TOP LUMINAIRES. REMOVE

EXISTING BOLLARDS SHOWN IN PLANS, AND REPLACE

WITH NEW LED BOLLARDS. REMOVE EXISTING WALL

MOUNT LUMINAIRES SHOWN IN PLANS, AND REPLACE

WITH NEW LED WALL MOUNT LUMINAIRES. INSTALL NEW

WALL MOUNTED LUMINAIRES ON BUILDING 50 SHOWN ON

PLANS. INSTALL NEW CANOPY LUMINAIRES AND STAIR

LUMINAIRES SHOWN ON PLANS.

BID ALTERNATE #2: BASE BID EXCEPT DELETE

SPECIFIED MENTAL HEALTH PARKING AREA POLE AND

POLE TOP MOUNTED LUMINAIRES, AND BUILDING 52

BUILDING MOUNTED WALL PACKS SHOWN ON PLANS. ALL

OTHER POLES AND POLE TOP LUMINAIRES, BUILDING

MOUNTED LUMINAIRES, BOLLARDS, CANOPY LUMINAIRES

AND STAIR LUMINAIRES TO BE REPLACED.

BID ALTERNATE #2

SITE KEY PLAN

E-104

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTS

Office of

Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Replace Site Lighting

Fargo, ND

437-23-135

Project Director

02/23/2024 RD KRRevisions: Date:

Noel Nyborg

FOURFRONT DESIGN, INC.

517 7TH STREET

RAPID CITY, SOUTH DAKOTA 57701

PH: (605) 342-9470

FAX: (605) 342-2377

WWW.FOURFRONTDESIGN.COMFRONT

D E S I G N I N C.

FOUR

100% BID DOCUMENTS

SCALE: 1/32" = 1'

E-104

LIGHTING DEMOLITION ENLARGED

SITE PLAN AREA D

ENLARGED SITE PLAN - AREA D LIGHTING DEMOLITION

AREA B

CONTINUES ON

SHEET E-102

AREA C

SHEET E-103

D

RI

VE

R

OF

TH

E

NO

RT

H

30W 30E

12 13

CITY

LIFT

STATION

(STORM

SEWER)

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

8 3

AREA

E

AREA

A

AREA

B

AREA

C

AREA

D

BOTTOM O

F D

IKE SLO

PE

TOP O

F EARTHEN DIKE

TO

P

O F

EA

R

TH

EN

D

IK

E

BO

TT

O M

O F

D

IK

E

SL

O

PE

P1P1P1

P1

P1

P1

P1

P1

P1 P1

P1

P1

P1

P2

P2

P3 P3 P3

P3

P3

P3 P3

P3

P3

P3

P3 P3P3

P3

P3

P3

P3 P3

P3

P3

P3

P4

P4

1 1

1 8

1 1 1

LUMINAIRES IN THIS AREA ARE

ALTERNATE NO. 2 BID ITEM.

LUMINAIRES IN THIS AREA WILL

BE PART OF A FUTURE

PROJECT.

THIS PROJECT INCLUDES REPLACEMENT FOR POLES AND

POLE LIGHTING P1, P2, P3, B1 BOLLARDS, CANOPY C1,

STAIR S1 AND BUILDING MOUNT LUMINAIRES ONLY. THE

DIKE LIGHTING, P4, P5, P6 AND HEALING GARDEN B2

LIGHTING IS NOT INCLUDED IN THE PROJECT. EXISTING

POLE BASES TO REMAIN AND BE RE-USED UNLESS

OTHERWISE NOTED. POLE, AND POLE TOP LUMINAIRE TO BE REMOVED FROM

EXISTING POLE BASE. POLE BASE TO REMAIN AND BE

REUSED FOR NEW POLE AND LUMINAIRE.

DEMOLITION KEYED ELECTRICAL NOTES

EXISTING BOLLARD TO BE REMOVED. PREPARE AREA

FOR NEW BOLLARD.

EXISTING LIGHT FIXTURE TO REMAIN.

REMOVE CONCRETE LIGHT BASE AND REPAIR DRIVEWAY.

EXISTING BUILDING MOUNT LIGHT TO BE REMOVED.

PREPARE AREA FOR NEW BUILDING MOUNT LIGHT.

LUMINAIRES ARE PART OF BID ALTERNATE #1

REMOVE EXISTING CONCRETE LIGHT POLE FOUNDATION

COMPLETLY, FILL WITH CLEAN FILL DIRT AND COMPACT

AT LEVELS TO MATCH ADJACENT SOILS. PATCH ASPHALT

TO MATCH ADJACENT THICKNESS AND PAINT ANY LINES

WITH APPROVED TRAFFIC PAINT TO COMPLETE THE

ADJACENT PATTERN.

EXISTING COLUMN MOUNTED ARM BRACKET, AND

LUMINAIRE TO BE REMOVED FROM BRICK COLUMN.

PREPARE SURFACE FOR MOUNTING NEW MOUNTING

BRACKET.

LUMINAIRES ARE BID ALTERNATE #2. EXISTING

LUMINAIRES TO REMAIN AND BE REPLACED IN FUTURE

PROJECT.

REMOVE EXISTING IN STAIR LUMINAIRE. PREPARE AREA

TO INSTALL NEW LUMINAIRE IN EXISTING LOCATION.

REMOVE EXISTING CANOPY LUMINAIRES. PREPARE AREA

TO INSTALL NEW CANOPY LUMINAIRES IN EXISTING

LOCATIONS.

KEYED…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .