SCO ID#23-26532-01A-ADD #2.pdf
PDF 432 KB Posted
- Attached to
- NC Department of Natural and Cultural Resources
- Solicitation number
- SCO-23-26532-01A
- Issued by
- Person County, North Carolina
About this file
This Revised Addendum Number 2 document is issued by Sud Associates, P.A. for the North Carolina Department of Natural and Cultural Resources, specifically for the Museum of the Albemarle Fire Alarm Replacement project (SCO # 23-26532-01A). The addendum provides critical clarifications for potential bidders, including specification details such as requiring 5 SLC loops (1 per floor and 1 for pump building), limiting addressable devices to no more than 20 between isolators, and identifying acceptable fire alarm system manufacturers including Honeywell Gamewell FCI and Potter. The document confirms that a graphic annunciator is not required and that contractors must provide duct detectors as indicated in the project drawings.
The pre-bid conference attendance list reveals multiple potential bidders from companies including Sud Associates, Lane Communications, J. Wayne Poole, and Cypress Electric, indicating competitive interest in the project. The addendum emphasizes that all contractors must incorporate these clarifications into their proposals and acknowledge receipt of the addenda on their bid proposal forms. The document is dated April 14, 2025, with a pre-bid conference held on April 3, 2025, suggesting an upcoming bid submission deadline and project timeline for the fire alarm system replacement at the Museum of the Albemarle.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SCO ID#23-26532-01A-ADD #3.pdf | ||
| SCO ID#23-26532-01A-ADD #1.pdf | ||
| SCO-23-26532-01A.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Satellite Office:
90 Southside Avenue, Suite 350
Asheville, NC 28801 O: (828) 255-4691
NORTH CAROLINA DEPARTMENT OF NATURAL AND CULTURAL RESOURCES
MUSEUM OF THE ALBEMARLE
FIRE ALARM REPLACEMENT
SCO # 23-26532-01A
REVISED ADDENDUM NUMBER 2 CLARIFICATIONS
April 14, 2025
These clarifications are from previous questions from other bidders.
1. 5 SLC loops are required, 1 per floor and 1 for pump building.
2. Each loop to have no more than 20 addressable devices between isolators. See Sheet 1/E205. This overrides the less stringent specification 283111,1.3, F.
3. Manufacturers allowed are indicated on the Drawings. Honeywell Gamewell FCI is an acceptable manufacturer.
4. In addition to the manufactures allowed by the drawings and specs, Potter is also acceptable as long as all project requirements are met.
5. Graphic annunciator is not required.
6. Provide duct detectors indicated in the drawings.
7. All contractors submitting proposals shall incorporate the items in this Addendum and all other addenda into their proposals and acknowledge receipt of the Addenda on their bid proposal forms. This Addendum shall be incorporated in the Drawings and Specifications which are a part of the Contract Documents and shall supersede anything contained therein with which it may conflict.