The document contains Salient Characteristics for a commercial cantilever hip roof style shade structure replacement project. The specifications detail precise requirements for structural steel components, including cold-formed structural quality steel tubing and pipes conforming to ASTM A-500, Grade B and ASTM-A36 standards. Key structural elements include 6" x 6" x 1/3" columns, 4" x 6" x 3/16" beams, 2-7/8" upper structure hoops, and a 3" center hip ridge pipe, with connections using 10" gussets, 5/8" bolts, nuts, lock washers, and flat washers. The structure must be powder coated or industrially coated for corrosion resistance, comply with UL 1332 requirements, and have all field connections bolted rather than welded. The accompanying technical drawing provides a detailed cross-section of the column footing, showing a 5'-0" tall embedded column with reinforced concrete, WWF 6x6 W2.1xW2.1 reinforcement, and a 4"x8"x16" prefabricated concrete block base with 3" clear cover on all sides.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
This cantilever hip roof style shade structure shall be a commercial product for the purpose of replacing existing deteriorated shade structure. The new structure needs to have the following characteristics:
• Structural steel shall be cold-formed structural quality steel, welded or seamless, complying with ASTM A-500, Grade B & ASTM-A36.
• Columns 6” x 6” x 1/3” A500 Gr B Tubing
• Beams 4” x 6” x 3/16” A500 Gr B Tubing
• Upper Structure Hoops 2-7/8” Sch 40 Round Pipe
• Center Hip Ridge 3” Sch 40 Pipe
• Columns & Beams Horizontal Flange to Flange 10” x 30” x ½” plate
• Connections w/ 10” Gusset (8) 5/8” Bolts, Nuts, Lock Washers & (16) Flat Washers
(top & bottom)
• All plate to be ½” for Connections and End Caps
• Columns shall be embedded per detail in reinforced concrete
• All steel shall be powder coated or industrial coated steel, providing excellent chemical, corrosion, and abrasion resistance complying with requirements of UL 1332, Organic Coating for Steel Enclosures for Outdoor Use Electrical Equipment – Component.
• All field connections shall be bolted in accordance with American Society for Testing and Materials (ASTM) Structural Specifications for Bolted Connections. No welding shall be done in the field.