Salient Characteristics - Amendment 2.pdf

PDF 101 KB Posted

Attached to
Shade Structure with Canopy - JBSA Randolph
Solicitation number
FA301625Q0232
Issued by

About this file

The document contains Salient Characteristics (Amendment 2) for a commercial cantilever hip roof style shade structure replacement. The specifications detail precise structural requirements, including cold-formed structural steel conforming to ASTM A-500 and ASTM-A36 standards, with specific dimensions for columns (6" x 6" x 1/3" A500 Gr B Tubing), beams (4" x 6" x 3/16" A500 Gr B Tubing), and upper structure components. The structure requires powder-coated or industrial-coated steel with excellent chemical, corrosion, and abrasion resistance, complying with UL 1332 standards.

Additional technical requirements include horizontal flange-to-flange connections with 10" x 30" x ½" plates, gusset connections using 5/8" bolts, nuts, lock washers, and flat washers, and columns to be embedded in reinforced concrete. All field connections must be bolted per ASTM structural specifications, with no field welding permitted. The aesthetic specification mandates a maroon canopy with a beige frame. The accompanying technical drawing provides a detailed cross-section of the column footing, showing a 5'-0" tall structure with a 1'-6" wide prefabricated concrete block base and specific reinforcement details.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

AMENDMENT 2

This cantilever hip roof style shade structure shall be a commercial product for the purpose of replacing existing deteriorated shade structure. The new structure needs to have the following characteristics:

• Structural steel shall be cold-formed structural quality steel, welded or seamless, complying with ASTM A-500, Grade B & ASTM-A36.

• Columns 6” x 6” x 1/3” A500 Gr B Tubing

• Beams 4” x 6” x 3/16” A500 Gr B Tubing

• Upper Structure Hoops 2-7/8” Sch 40 Round Pipe

• Center Hip Ridge 3” Sch 40 Pipe

• Columns & Beams Horizontal Flange to Flange 10” x 30” x ½” plate

• Connections w/ 10” Gusset (8) 5/8” Bolts, Nuts, Lock Washers & (16) Flat Washers

(top & bottom)

• All plate to be ½” for Connections and End Caps

• Columns shall be embedded per detail in reinforced concrete

• All steel shall be powder coated or industrial coated steel, providing excellent chemical, corrosion, and abrasion resistance complying with requirements of UL 1332, Organic Coating for Steel Enclosures for Outdoor Use Electrical Equipment – Component.

• All field connections shall be bolted in accordance with American Society for Testing and Materials (ASTM) Structural Specifications for Bolted Connections. No welding shall be done in the field.

• Color: The canopy should be maroon and the frame should be beige