Salient Characteristics.pdf

PDF 200 KB Posted

Attached to
79 RGS - Hangar Aircraft Frequency Converter
Solicitation number
FA487725QA539
Issued by

About this file

This document is a Salient Characteristics document for a Hard-wired Aircraft Power Panel, detailing specific technical requirements for a power panel to be delivered to the 79th RGS. The electrical requirements specify a three-phase input of 380-480V at 50/60 Hz with a full load input current of 93A, and an output of 115V L-N / 200V L-L at 400 Hz. Key features include a built-in maintenance diagnostic system, digital touch screen control panel, external USB communications port, internal step-up transformer, and input surge protection meeting IEEE C62.41 Category B standards.

The power panel comes with a one-year warranty and includes accessories such as a 60-foot AC output cable with an aircraft plug and safety interlock, and a floor or wall-mounted cable saddle or automatic reel. Additional requirements mandate installation and electrical connection services. The system is designed to be hard-wired into existing electrical infrastructure, with features like an AC output contactor with aircraft safety interlock, 5% maximum AC input current distortion, and an electronic operator and maintenance manual to support its operation and maintenance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

FOR

Hard-wired Aircraft Power Panel

1.0. SCOPE OF WORK:

All proposed products shall meet or exceed the following minimum specifications outlined in this Salient Characteristics. All items shall be delivered to the 79th RGS.

1.1. PRODUCT PERFORMANCE SPECIFICATION:

Item must meet the following minimum specifications:

SPECIFICATIONS

Headers Please adjust Headers to item requirement

Electrical Requirement:

Input: 380 to 480 V +10%/-15%, 3-phase, 50/60 Hz; full load input current 93 A (at 480 VAC)

Output: 115 V L-N / 200 V L-L, 3-phase, 4-wire, 400 Hz

Warranty: 1 Year

Features: Built-in maintenance diagnostic system

Digital touch screen control panel

External communications port access, front panel USB

208 to 480 V internal step up transformer

Input surge protection IAW IEEE C62.41, Category B

5% Max. AC input current distortion, IGBT active front end

AC output contactor “connect/disconnect” device with aircraft safety interlock

Electronic Operator and Maintenance Manual

Accessories: AC output cable, 60 feet, banded multiple conductors with aircraft plug and safety interlock

Floor or wall-mounted cable saddle or automatic reel

System is hard wired into existing electrical infrastructure

Additional Requirement:

Installation and electrical connection services provided

File details come from the government source that posted it. Updated .