This document is a procurement specification for a Trane air-cooled scroll packaged chiller (Model CGAM026A2) required by Patrick Space Force Base, Florida, 45 Civil Engineer Squadron Operations Flight. The specification details salient characteristics for one chiller unit to be delivered to 734 Delta Drive, Building B710, Patrick Space Force Base, Florida 32925 within 180 days after contract award.
The chiller specifications include an air-cooled scroll packaged design with R-454B refrigerant, factory-installed freeze protection, refrigerant isolation valves with discharge valve, and a factory-installed flow switch set at 60 cm/sec. Additional features include standard cooling with grooved pipe connections, 1.25-inch factory insulation rated for high humidity and low evaporator temperatures, lanced aluminum fins with BLYGOLD coating for corrosion resistance, across-the-line starter/direct online power configuration, high short circuit-rated circuit breaker in the control panel, BACnet MS/TP interface capability, elastomeric isolators, factory-installed water strainer, and architectural louvered panels. The unit includes a ten-year parts, labor, and refrigerant warranty, with Trane Service responsible for equipment startup to honor warranty coverage. The document was issued July 9, 2026, Revision 1.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PATRICK SPACE FORCE BASE, FL
45 CES / OPERATIONS FLIGHT
Date: 9 July 2026 Rev: 1
1 TRANE CHILLER
Air-Cooled Scroll Packaged Chiller/CGAM026A2
Salient Characteristics
Air-Cooled Scroll Packaged Chiller Startup Included - Trane Service must start equipment for warranty to be honored
Extra efficiency/performance Refrigerant Charge
R-454B
With factory installed freeze protection Refrigerant isolation valves
(discharge valve) Factory installed flow switch - set point 60 cm/sec
Standard Cooling
Grooved pipe connection
Factory insulation 1.25" - high humidity/low evaporator temperature Wide Ambient complete Coat lanced aluminum fins BLYGOLD coating for cabinet & casing Across the line starter/direct online
Single point connection main line unit power-ancillary items require other power
Circuit breaker-high fault rated control panel BACnet MS/TP
Interface
High A short circuit rating Elastomeric isolators
With water strainer factory installed Architectural louvered panels
Ten (10) year parts, labor & refrigerant warranty
Delivery Address: 734 Delta Drive, B710, Patrick SFB, FL 32925 Delivery Timeframe:
Delivery shall be completed within 180 days after award.