Salient Char. Doc Bldg 1368.pdf
PDF 89 KB Posted
- Attached to
- Replace Air Cooled Chiller B559, 759 & 1368
- Solicitation number
- FA252126QB098A
About this file
This is a federal contract solicitation for procurement of a single air-cooled scroll packaged chiller for Patrick Space Force Base, Florida, issued by the 45 Civil Engineer Squadron Operations Flight on 7 April 2026.
The required equipment is one Trane Air-Cooled Scroll Packaged Chiller, model CGAM020A2, with the following specifications: 20 nominal tons capacity, 208 volt 3-phase power, extra efficiency/performance rating, and R-454B refrigerant charge. The chiller must include factory-installed freeze protection, refrigerant isolation valves (discharge valve), flow switch set at 60 cm/sec, grooved pipe connections, 1.25-inch factory insulation for high humidity/low evaporator temperature operation, and wide ambient capability. Additional required features include complete coat lanced aluminum fins with BLYGOLD coating, across-the-line starter with direct online connection, high fault-rated circuit breaker control panel, BACnet MS/TP interface, elastomeric isolators, and factory-installed water strainer with architectural louvered panels. The equipment must include Trane Service startup with technician commissioning for warranty validation. A 10-year parts, labor, and refrigerant warranty is required. Delivery must be completed within 180 days after contract award to 734 Delta Drive, Building 710, Patrick Space Force Base, Florida 32925.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PATRICK SPACE FORCE BASE, FL
45 CES / OPERATIONS FLIGHT
Date: 07 April 2026
1 TRANE CHILLER
Air-Cooled Scroll Packaged Chiller/CGAM020A2
Salient Characteristics
Air-Cooled Scroll Packaged Chiller
Startup Included - Trane Service must start equipment for warranty to be honored 20 nominal tons 208 volt 3 phases Extra efficiency/performance Refrigerant Charge R-454B
With factory installed freeze protection Refrigerant isolation valves (discharge valve) Factory installed flow switch - set point 60 cm/sec Standard Cooling
Grooved pipe connection
Factory insulation 1.25" - high humidity/low evaporator temperature Wide Ambient
Complete Coat lanced aluminum fins BLYGOLD coating for cabinet & casings Across the line starter/direct online
Single point connection main line unit power-ancillary items require other power Circuit breaker-high fault rated control panel BACnet MS/TP Interface Elastomeric isolators
With water strainer factory installed Architectural louvered panels
Ten (10) year parts, labor & refrigerant warranty
Delivery Address: 734 Delta Drive, B710, Patrick SFB, FL 32925
Delivery Timeframe: Delivery shall be completed within 180 days after award.
File details come from the government source that posted it. Updated .