S05 07 40 00 - Roofing and Siding Panels.pdf

PDF 97 KB Posted

Attached to
Amendment 0001 to Solicitation 36C25523R0084_1
Solicitation number
36C25523R0084_A0001
Issued by

About this file

This document package includes a construction specification section for roofing and siding panels and details for a federal construction contract opportunity. The specification section outlines technical requirements for uninsulated metal wall panels for a Department of Veterans Affairs medical center project, including performance standards, submittal requirements, manufacturer qualifications, warranty terms, and installation instructions. The related federal contract opportunity notice is an amendment to a solicitation seeking offers for construction of a primary care and women's health building at the Marion VA Medical Center as part of project number 657-503. The specification section provides product and installation standards that would apply to offers submitted in response to this solicitation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veteran Affairs VA Project No. 657-503

Marion VA Medical Center Construct Primary Care & Women’s Health

Marion, IL. Construction Documents: 06/30/21

07 40 00 - Roofing and Siding Panels - 1

SECTION 07 40 00

ROOFING AND SIDING PANELS

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies uninsulated metal wall panels as shown on contract documents.

1.2 RELATED WORK

A. Section 07 92 00, JOINT SEALANTS: Sealant.

B. Section 09 06 00, SCHEDULE FOR FINISHES: Color and texture of finish.

1.3 QUALITY ASSURANCE

A. Manufacturer’s Qualifications: Provide metal wall panels products of a manufacturer regularly engaged for not less than five (5) years in the fabrication of metal panels of the type and design indicated.

B. Installer: A firm with three (3) years of successful experience with installation of roofing and siding panels of type and scope equivalent to Work of this Section. Submit installer qualifications.

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Samples: Metal panel, 152 mm (6 inch) square, showing finish, each color and texture.

C. Shop Drawings: Wall panels, showing details of construction and installation. Collateral steel framing thickness and kind of material, closures, flashing, fastenings and related components and accessories.

Show interfaces and relationships to work at other trades and continuity with adjacent thermal, weather, air and vapor barriers.

D. Manufacturer's Literature and Data: Wall panels

E. Manufacturer’s Certificates: Indicating manufacturer’s qualifications specified.

F. Installer qualifications.

G. Manufacturer warranty.

1.5 QUALITY ASSURANCE

A. Approval by Contracting Officer Representative (COR) is required of products of proposed manufacturer.

B. Certify manufacturer has five (5) years continuous documented experience in fabrication of metal roofing and siding panels.

07 40 00 - Roofing and Siding Panels - 2

C. Source: For each material type required for work of this section, provide primary materials, which are products of one manufacturer.

Provide secondary or accessory materials, which are acceptable to manufacturers of primary materials.

D. Installer: A firm with a minimum of three (3) years’ experience in type of work required by this section and which is acceptable to manufacturers of primary materials.

1.6 WARRANTY

A. Construction Warranty: Comply with FAR clause 52.246-21 “Warranty of

Construction”.

B. Manufacturer Warranty: Manufacturer shall warranty their metal wall panels for a minimum of ten (10) years from the date of installation and final acceptance by the Government. Submit manufacturer warranty.

C. Warranty on Panel Finishes: Manufacturer’s shall warrant their wall panel finish and provide standard agreement to repair finish or replace metal panels that show evidence of deterioration of factory-applied finishes within specified warranty period.

1. Exposed Panel Finish: Deterioration includes, but is not limited to, the following:

a. Color fading more than 5 Hunter units when tested according to

ASTM D2244.

b. Chalking in excess of a No. 8 rating when testing according to

ASTM D4214.

c. Cracking, checking, peeling, or failure of paint to adhere to bare metal.

2. Finish Warranty Period: 10 years from date of installation and final acceptance by the COR.

1.7 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extend referenced. The publications are referenced in the text by the basic designation only.

B. American Architecture Manufacturers Association (AAMA):

611-14 ................. Anodized Architectural Aluminum

621-02 ................. Voluntary Specifications for High Performance

Organic Coatings on Coil Coated Architectural

Hot Dipped Galvanized (HDG) and Zinc-Aluminum

Coated Steel Substrates

07 40 00 - Roofing and Siding Panels - 3

2605-13 ................ Voluntary Specification, Performance

Requirements and Test Procedures for Superior

Performing Organic Coatings on Aluminum

Extrusions and Panels

C. American Iron and Steel Institute (AISI):

SG03-02 ................ Cold-Formed Steel Design Manual

D. ASTM International (ASTM):

A463/A463M-15 .......... Steel Sheet, Cold-Rolled, Aluminum-Coated, by the Hot-Dip Process

A653/A653M-20 .......... Steel Sheet, Zinc-Coated (Galvanized), or Zinc-

Iron Alloy-Coated (Galvannealed) by the Hot-Dip

Process.

A924/A924M-19 .......... Steel Sheet, Metallic Coated by the Hot-Dip

Process

A1008/A1008M-18 ........ Steel, Sheet, Cold-Rolled, Carbon, Structural, High Strength Low Alloy

B209-14 ................ Aluminum and Aluminum Alloy Sheet and Plate

B209M-14 ............... Aluminum and Aluminum Alloy Sheet and Plate

(Metric)

C553-19 ................ Mineral Fiber Blanket Thermal Insulation for

Commercial and Industrial Applications

C591-20. ............... Unfaced Preformed Rigid Cellular

Polyisocyanurate Thermal Insulation

C612-14(2019) .......... Mineral Fiber Block and Board Thermal

Insulation

C1396/C1396M-17 ........ Gypsum Board

D2244-16 ............... Calculation of Color Tolerances and Color

Differences from Instrumentally Measured Color

Coordinates

D4214-07(2015) ......... Test Methods for Evaluating the Degree of

Chalking of Exterior Paint Films

E119-20 ................ Fire Test of Building Construction and

Materials

E283-19 ................ Test Method for Determining Rate of Air Leakage

Through Exterior Windows, Curtain Walls, and

Doors Under Specified Pressure Differences

Across the Specimen

07 40 00 - Roofing and Siding Panels - 4

E331-00(2016) .......... Test Method for Water Penetration of Exterior

Windows, Skylight, Doors, and Curtain Walls by

Uniform Static Air Pressure Difference

E1592-05(2017) ......... Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by

Uniform Static Air Pressure Method

E1646-95(2018) ......... Test Method for Water Penetration of Exterior

Metal Roof Panel Systems by Uniform Static Air

Pressure Difference

E1680-16 ............... Test Method for Rate of Air Leakage Through

Exterior Metal Roof Panel Systems

E1980-11(2019) ......... Calculating Solar Reflectance Index of

Horizontal and Low-Sloped Opaque Surfaces

E2140-01(2017) ......... Test Method for Water Penetration of Metal Roof

Panel Systems by Static Water Pressure Head

E. Cool Roof Rating Council (CRRC):

Standard-14

F. FM Global:

4471-10 ................ Class 1 Panel Roofs

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS FOR WALL PANELS

A. Structural Performance: Provide metal panel systems capable of withstanding the effects of the following loads, based on testing according to ASTM E1592.

1. Wind Loads: As indicated.

2. Deflection Limits: For wind loads, no greater than 1/180 of the span.

3. Minimum Panel rib depth: 1.5”

4. Panel width: 36 inches.

2.2 ALUMINUM PLATE AND SHEET

A. ASTM B209M (B209).

2.3 FASTENERS

A. Fasteners for Aluminum Panels to be aluminum or stainless steel.

B. Fasteners of size, type and holding strength as recommended by panel manufacturer.

07 40 00 - Roofing and Siding Panels - 5

2.4 FABRICATION

A. General:

1. Furnish panels in one continuous length for full height, with no horizontal joints, except at cut-outs or openings as required for the passage of pipes, conduits, vents and the like.

2. Construct panels by pressing members together to form a structural unit with closed ends.

3. Overall thickness of panels is shown of the contract documents.

4. Provide collateral steel framing, panel reinforcements for support of mechanical and electrical work as shown on the contract documents, and related components and accessories.

a. Sub-girts: 1.0 mm (0.0396 inches) thick galvanized steel hat channels deigned to receive panel fasteners or clips.

b. Accessories, fastenings, and flashings to be the same material and finish as the panels. Thickness and installation of accessories and flashing to be as recommended by the panel manufacturer.

2.5 FINISH

A. For wall panels, provide finishes as follows for face sheets. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers’ written instructions.

B. Provide aluminum alloy for color coating as required to produce specified color. Provide color as specified in Section 09 06 00, SCHEDULE FOR FINISHES. Color for sheet aluminum to not deviate more than the colors of extrusion samples.

1. Exposed Anodized Finish:

a. Clear Anodic Finish: AAMA 611, AA-M12C22A41, Class I, 0.018 mm

(0.7 mil) (min.)

PART 3 - EXECUTION

3.1 INSTALLATION

A. General: Install panels in accordance with the manufacturer's approved erection instructions and diagrams, except as specified otherwise.

B. Install panels in full and firm contact with supports and with each other at side and end laps.

C. Where panels are cut in the field, or where factory applied coverings or coatings are abraded or damaged in handling or installation, make

07 40 00 - Roofing and Siding Panels - 6 finish repairs with material of the same type and color as the weather coating, before being installed.

D. Seal cut ends and edges, including those at openings through the sheets.

E. Correct defects or errors in the materials in a manner approved by the

COR.

F. Replace defective materials which cannot be corrected with nondefective material.

G. Provide molded closure strips where indicated and whenever sheets terminate with open ends after installation.

H. Wall Panels:

1. Apply panels with the configuration in a vertical position.

2. Provide panels in full heights from base to eave with no horizontal joints except at the junctions of door frames, window frames, louver panels, and similar locations.//

3. Seal side and end laps with joint sealing material.

4. Flash and seal walls at the base, at the top, around windows, door frames, framed louvers, and other similar openings. Install closure strips, flashings, and sealing material in an approved manner that will assure complete weather tightness.

I. Flashing:

1. Provide flashing and related closures and accessories in connection with the preformed metal panels as indicated and as necessary to provide a watertight installation.

2. Install details of installation, which are not indicated, in accordance with the panel manufacturer's printed instruction and details, or the approved shop drawings.

3. Allow for expansion and contraction of flashing.

J. Fasteners:

1. Space fasteners in accordance with the manufacturer's recommendations, and as necessary to withstand the design loads indicated.

2. Install fasteners in valleys or crowns as recommended by the manufacturer of the panel being used.

3. Install fasteners in straight lines within a tolerance of 13 mm

(1/2-inch) in the length of a bay.

07 40 00 - Roofing and Siding Panels - 7

4. Drive exposed penetrating type fasteners normal to the surface, and to a uniform depth to seat gasketed washers properly, and drive so as not to damage factory applied coating.

5. Exercise care in drilling pilot holes for fastenings to keep drills perpendicular and centered in valleys, or crowns, as applicable.

After drilling, remove metal filings and burrs from holes prior to installing fasteners and washers. Do not torque fasteners to exceed values recommended by the manufacturer.

6. Remove panels deformed or otherwise damaged by over-torqued fastenings, and provide new panels.

7. Remove metal shavings and filings from roofs on completion to prevent rusting and discoloration of the panels.

3.2 ISOLATION OF ALUMINUM

A. Isolate aluminum in contact with or fastened to dissimilar metals other than stainless steel, white bronze, or other metal compatible with aluminum by one of the following:

1. Painting the dissimilar metal with a prime coat of Zinc-Molybdate followed by two coats of aluminum paint.

2. Placing a non-abrasive tape or gasket between the aluminum and the dissimilar metal.

B. Paint aluminum in contact with, or built into mortar, concrete, plaster, or other masonry materials with a coat of alkali-resistant bituminous paint.

C. Paint aluminum in contact with wood or other absorptive materials that may become repeatedly wet, with two coats of bituminous paint, or two coats of aluminum paint. Seal joints with caulking material.

3.3 PROTECTION AND CLEANING

A. Protect panels and other components from damage during and after erection, and until project is accepted by the COR.

B. After completion of work, all exposed finished surfaces of panels are to be cleaned of soil, discoloration and disfiguration. Touch-up abraded surfaces of panels.

- - - E N D - - -

File details come from the government source that posted it. Updated .