S05 04-MixValve.pdf

PDF 627 KB Posted

Attached to
Amendment 0001 to Solicitation 36C25523R0084_1
Solicitation number
36C25523R0084_A0001
Issued by

About this file

This document provides technical specifications for a digital mixing center and recirculation control system. The Armstrong DMC40BS digital control unit offers precise hot water temperature regulation within 2 degrees Fahrenheit at points of use up to 25 feet downstream during periods of demand and idle time. It automatically shuts off hot water in the event of cold water or power supply failures. The control unit's programmable set point range is between 81 to 158 degrees Fahrenheit and includes a thermal disinfection mode. Connectivity options integrate the control unit with building automation systems using Modbus, BACnet, or LonWorks protocols. The unit is suitable for recirculation systems requiring a minimum circulation flow of 5 GPM. The related federal contract opportunity is a solicitation amendment to construct a primary care and women's health building for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

All dimensions and weights are approximate. Use certified print for exact dimensions. Design and materials are subject to change without notice.All dimensions and weights are approximate. Use certified print for exact dimensions. Design and materials are subject to change without notice.

Armstrong Hot Water Group, 221 Armstrong Blvd., Three Rivers, MI 49093 – USA Phone: 269-279-3602, Fax: 269-279-3130 armstronginternational.com

Armstrong Hot Water Group, 221 Armstrong Blvd., Three Rivers, MI 49093 – USA Phone: 269-279-3602, Fax: 269-279-3130 armstronginternational.com

Water Temperature Control - Recirculation Systems Digital The Brain® Model DMC40BS DMC40BS is a fully Digital Mixing Center (DMC), with BrainScan® - hot water monitoring control module, designed specifically to be the primary water temperature controller in a continuously pumped circulating hot water system.

Digital technology provides enhanced water temperature control accuracy which resists zero system demand “Temperature Creep” without the use of a manual throttling valve or a temperature activated pump shut-off device (aquastat).

Operational Specifications (DRV40)

• +/-2°F water temperature control at points of use 25’ downstream during demand

• +/-2°F water temperature control at the DRV during zero system demand “idling” periods

• 2°F minimum valve inlet to outlet temperature requirement

(system recirculation temperature loss)

• Automatic shutoff of hot water flow upon cold water inlet supply failure

• Automatic shutoff of hot water flow in the event of a power failure

• Programmable set point range of 81-158°F (27-70°C)

• Programmable thermal disinfection mode

• Programmable 1st level hi/lo temp alarm display

• Programmable temperature error level for safety shutdown

Technical Specifications (DRV40)

• 100-240 V AC

• Polymer Electronics Enclosure

• Stainless Steel Valve Construction

• Complete Assembly Lead Free Compliant

• Maximum inlet HW supply temperature 185°F (85°C)

• Minimum Circulation Flow – 5 GPM/19 LPM

• Minimum System Draw Off - 0

• ASSE 1017, CSA B125 and CE Certified

• Operational water pressure of 10-150 psig

• Display in °C or °F

• Shipping weight 334 lbs (151.5 kg)

Connectivity (DRV40) SPCO Relay Outputs – Relay which is energized during operation.

LCD Display – Provides information on set point, delivered temperature, error codes and alert conditions.

RS485 Serial Port – Connects the DRV to either BrainScan or Modbus.

BrainScan® – BAS interface for Modbus, Bacnet™ or LonWorks™ plus operates as a web server.

Modbus – DRV can be configured to communicate directly with Building Automation Systems (BAS) using Modbus protocols.

For a submittal drawing, refer to D40806.

Recirculation Systems - Digital (gpm)

Model Pressure Drop (psi)

Minimum System Draw-Off Maximum Flow @7.5 ft/sec. CV5 10 15 20

DMC40BS 48 70 85 98 0 41 22

39.0

45.0

59.0

DRV40

SERVICE BY-PASS

(NORMALLY

CLOSED)

PRESSURE GAUGE

THERMOMETER

BALL VALVE

STRAINER

SPRING

CHECK VALVE

CHECK VALVE

BRAINSCAN

2.5

4.5

13.2

14.4

7.8

4.8

RETURN

TO HEATER

1 SWEAT

HOT WATER

INLET

1-1/2 SWEAT

MIXED WATER

OUTLET

1-1/2 SWEAT

COLD WATER

INLET

1-1/2 SWEAT

RECIRC

RETURN

1 SWEAT

11.9

45.1

NOTE:

ALL VALVES AND FITTINGS IN THIS ASSEMBLY CONTAIN LESS THAN 0.25% LEAD BY WEIGHTED AVERAGE

D40806

SHEET 1 OF 2

DMC40BS

04/11/2012Jon Singer

REV DWG.

NAME DATE

DRAWN MATERIAL

TOLERANCES UNLESS

OTHERWISE SPECIFIED

A

ARMSTRONG INTERNATIONAL

FRACTIONAL 1/64

ANGULAR: 2

IN. MM

DECIMAL .XXXX .0005 -----

.XXX .005 .010

.XX .015 .10

.X ---------- .3

Copyright C 2010 ARMSTRONG INTERNATIONAL, INC.

CN32171RELEASED

DO NOT SCALE DRAWING

DIMENSIONING

ENGLISH [mm]

File details come from the government source that posted it. Updated .