This solicitation is for steam trap replacements at two Department of Veterans Affairs medical centers in Connecticut. The IFB seeks replacement of failed steam traps at the West Haven and Newington campuses. Bids are due by June 15, 2022 and the contract is to be awarded by July 15, 2022. Pricing is to be provided on a firm fixed price basis for supply and installation of new steam traps. The solicitation is set aside for verified service-disabled veteran-owned small businesses. The Veterans Health Administration Veterans Integrated Service Network 1 is the contracting agency.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2020 Steam Trap Survey Report (Mar-May Season)

Power & Process, Inc. 127 Industrial Drive

Southington, CT 06489

860-863-5454 www.powerprocessinc.com

West Haven VA Hospital

950 Campbell Ave.

West Haven, CT 06516 http://www.powerprocessinc.com/

EXECUTIVE DATA SUMMARY

Traps Evaluated 1127 Blowin g thru Leaking Bypassed Plugged OK

Not

Tested

Not in

Service

Quantity Tested 702 23 34 4 73 568 370 55

Percentage able to be tested 62% 3.3% 4.8% 0.6% 10.4% 80.9%

Estimated Annual Gas Savings

(ccf):

162,020 Grashof Calc

233,984 Napier Calc

MAP OF TRAPS EVALUATED TO DATE

SUMMARY OF FAILED TRAPS

Tag#: 9748

Bldg/Floor: Building 1 / 10th Floor

Rm/Location: West Mechanical Room / Condensate discharge for Cemline steam generator

App: Other Stm Press: 8

Cond: Not Returned Mfg: Spirax Sarco

Model: GL51 9NQ Type: Pump Trap Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Trap Jacket

Date Tested: 3/16/2020 Inspection Comments:

Inlet (F): 236 3/16/20‐ Vacuum breaker on heat exchanger bundle leaking as well Outlet (F): 214 Test Result: Blowing thru

Recom: Replace

Tag#: 9761

Rm/Location: West Mechanical Room / Condensate discharge for unit heater by room entrance

App: Unit Heater Stm Press: 17

Cond: Returned Mfg: Velan

Model: TS20 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/16/2020 Inspection Comments:

Inlet (F): 238

Outlet (F): 213

Tag#: 9764

Rm/Location: Center Mechanical Room / High pressure steam supply drip leg to PRV

App: Drip Leg Stm Press: 110

Cond: Not Returned Mfg: Gestra

Model: MK45‐2 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/16/2020 Inspection Comments:

Inlet (F): 334

Outlet (F): 214 Test Result: Leaking

Tag#: 9767

Rm/Location: Center Mechanical Room / steam header drip leg by windows

App: Drip Leg Stm Press: 17

Cond: Returned Mfg: Steam Loc

Model: INL AX Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/16/2020 Inspection Comments:

Inlet (F): 109

Outlet (F): 86 Test Result: Plugged

Tag#: 9768

Rm/Location: Center Mechanical Room / Drip leg above pneumatic air compressor

App: Drip Leg Stm Press: 17

Cond: Returned Mfg: Steam Loc

Model: INL AX Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/16/2020 Inspection Comments:

Inlet (F): 126

Outlet (F): 92

Tag#: 10590

Bldg/Floor: Building 1 / 1st Floor

Rm/Location: 1‐101 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 4/30/2020 Inspection Comments:

Inlet (F): 76

Outlet (F): 76

Tag#: 10599

Bldg/Floor: Building 1 / 2nd Floor

Rm/Location: Room 2 110 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Barnes & Jones

Model: 4320 insert ‐ TRANE B1 Body

Type: Thermostatic Size: 1/2"

Op Hrs: 0

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 4/30/20‐ Control head broken off

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 4/30/2020 Inspection Comments:

Inlet (F): 75 4/30/20‐ No flow through trap, no steam entering radiator‐ CV:4/30/20‐ Control head broken off

Outlet (F): 75

Tag#: 10762

Rm/Location: Room 2 213B / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: BJ 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/1/20‐ Control head broken off

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/1/2020 Inspection Comments:

Inlet (F): 78 5/1/20‐ Control head broken off, steam is passing through control head but not entering radiator‐ CV:5/1/20‐ Control head broken off

Outlet (F): 78

Tag#: 9837

Rm/Location: Mechanical Room 2‐213B / Steam supply header drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/17/2020 Inspection Comments:

Inlet (F): 102

Outlet (F): 91

Tag#: 9816

Bldg/Floor: Building 1 / 4th Floor

Rm/Location: Mechanical Room 4‐254 / Medium pressure steam supply drip leg upstream of PRV

App: Drip Leg Stm Press: 50

Cond: Not Returned Mfg: Plenty

Model: 15 Type: Float & Thermostatic Size: 1"

Op Hrs: 0

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Trap Jacket

Date Tested: 3/17/2020 Inspection Comments:

Inlet (F): 277 3/17/20‐ Trap outlet currently isolated, opened to test. Audible blowby

Outlet (F): 238

Tag#: 9826

Rm/Location: Mechanical Room 4‐254 / Steam supply main drip leg behind

AHU‐3

App:

Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL AW Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/17/2020 Inspection Comments:

Inlet (F): 85

Outlet (F): 78

Tag#: 9829

Rm/Location: Mechanical Room 4‐260 / End of main low pressure steam supply above AHU‐7

App: Drip Leg Stm Press: 8

Cond: Returned Mfg: Steam Loc

Model: INL AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/17/2020 Inspection Comments:

Inlet (F): 103

Outlet (F): 91

Tag#: 10770

Bldg/Floor: Building 1 / 7th Floor

Rm/Location: Room 7‐186D / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5/9/20‐ Should be using a attached remote sensor not a local control valve

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/9/2020 Inspection Comments:

Inlet (F): 76 5/9/20‐ Should be using a attached remote sensor not a local control valve

Outlet (F): 76

Tag#: 10771

Rm/Location: Room 7 186E / Radiator

App: Radiator Stm Press: 10

Cond: Not Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5‐9‐20 Control valve head is broken and needs replacement.

See photo 2.

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/9/2020 Inspection Comments:

Inlet (F): 232 5‐9‐20 Control valve head is broken and needs replacement. See photo 2.

Outlet (F): 215

Tag#: 10794

Rm/Location: Room 7‐202 / Radiator Right

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/9/20‐ Control head is broken off Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/9/2020 Inspection Comments:

Inlet (F): 74 5/9/20‐ Control head is broken off

Outlet (F): 74

Tag#: 10801

Rm/Location: Room 7 154 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/9/2020 Inspection Comments:

Inlet (F): 225

Outlet (F): 214

Tag#: 10806

Rm/Location: Room 7‐149 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/9/20‐ Control head is broken

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/9/2020 Inspection Comments:

Inlet (F): 80 5/9/20‐ got steam pass the control valve but won’t fill the radiator‐ CV:5/9/20‐ Control head is broken

Outlet (F): 80

Tag#: 10814

Rm/Location: Room 7‐133 / Radiator

App: Radiator Stm Press: 10

Cond: Not Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/9/20‐ Control head not responding, full steam all the time

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/9/2020 Inspection Comments:

Inlet (F): 230 5/9/20‐ Control head not responding, full steam all the time Outlet (F): 212

Tag#: 10815

Rm/Location: Room 7‐132 / Radiator

App: Radiator Stm Press: 10

Cond: Not Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/12/20‐ Control head broken off

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 224 5/12/20‐ Control head broken off

Outlet (F): 213

Tag#: 10832

Rm/Location: Room 7‐112 / Right Side Radiator

App: Radiator Stm Press: 10

Cond: Not Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/12/20‐ Control head is missing

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 227 5/12/20‐ Manual isolation valve was shut open to test‐ CV:5/12/20‐ Control head is missing

Outlet (F): 212

Tag#: 10482

Bldg/Floor: Building 1 / Ground

Rm/Location: Port Of Call / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 4/22/20‐ Control head broken off

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 4/22/2020 Inspection Comments:

Inlet (F): 92 4/22/20‐ Even with control head broken off, steam confirmed to inlet of radiator‐ CV:4/22/20‐ Control head broken off

Outlet (F): 89

Tag#: 10499

Bldg/Floor: Building 1 / Ground

Rm/Location: G‐207 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 4/22/2020 Inspection Comments:

Inlet (F): 77

Outlet (F): 77

Tag#: 9848

Bldg/Floor: Building 1 / Ground Floor

Rm/Location: Mechanical Room G‐291 / Condensate discharge reheat coil

App: Heating Coil Stm Press: 10

Cond: Not Returned Mfg: Velan

Model: 15 Type: Float & Thermostatic Size: 1"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/17/2020 Inspection Comments:

Inlet (F): 238

Outlet (F): 212

Tag#: 9866

Bldg/Floor: Building 1 / Sub Ground

Rm/Location: Mechanical Room SG‐ 177 / Steam supply drip leg for Trane

AHU

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/18/2020 Inspection Comments:

Inlet (F): 97

Outlet (F): 82

Tag#: 9896

Rm/Location: Mechanical Room SG‐ 182 / Medium pressure steam supply manifold drip leg (right side)

App: Drip Leg Stm Press: 65

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/18/2020 Inspection Comments:

Inlet (F): 311 3/18/20‐ With trap isolated, audible blowby of bypass valve and should also be replaced. Inlet isolation valve stem also leaking

Outlet (F): 252

Tag#: 9897

Rm/Location: Mechanical Room SG‐ 182 / 65# steam manifold

App: Drip Leg Stm Press: 65

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/18/2020 Inspection Comments:

Inlet (F): 310

Outlet (F): 254

Tag#: 9898

Rm/Location: Mechanical Room SG‐ 182 / end of line drip leg far back wall

App: Drip Leg Stm Press: 30

Cond: Returned Mfg: Steam Loc

Model: INL AN Type: Orifice Size: 1/2"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/18/2020 Inspection Comments:

Inlet (F): 103

Outlet (F): 103

Tag#: 10356

Bldg/Floor: Building 1 / Sub‐ Ground

Rm/Location: Crawl space by elevator shaft / steam supply supply drip leg

App: Drip Leg Stm Press: 50

Cond: Not Returned Mfg: Gestra

Model: MK‐45‐2 Type: Thermostatic Size: 1/2"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 4/14/2020 Inspection Comments:

Inlet (F): 281 4/14/20‐ inlet threads to the trap are leaking. Requires bracing Outlet (F): 186

Error! Filename not specified.

Tag#: 10375

Rm/Location: Crawl space 72 / low pressure drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Gestra

Model: MK‐45‐2 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 4/15/2020 Inspection Comments:

Inlet (F): 125 4/15/20‐ bypass is open and inlet and outlet of trap was close Outlet (F): 125

Tag#: 10376

Rm/Location: Crawl space 72 / low pressure drip leg

App: Drip Leg Stm Press: 10

Cond: Not Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 4/15/2020 Inspection Comments:

Inlet (F): 224

Outlet (F): 215

Tag#: 10384

Rm/Location: Crawl space entrance to SG 179 /

App: Drip Leg Stm Press: 10

Cond: Not Returned Mfg: Unknown

Model: Ft15 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 4/15/2020 Inspection Comments:

Inlet (F): 239 4/15/20‐ near trap is a major steam leak from a pipe 1 and 1/2 inch elbow

Outlet (F): 217

Tag#: 10388

Rm/Location: Crawl space 72 / medium pressure drip leg right side wall

App: Drip Leg Stm Press: 50

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 4/15/2020 Inspection Comments:

Inlet (F): 100 4/20/20‐ Abandoned condensate return line above trap should be plugged, currently leaking steam in tandem with the main condensate return line (not hooked into anything)

Outlet (F): 100

Tag#: 10473

Bldg/Floor: Building 1 / Sub‐Ground

Rm/Location: Tunnel between Crawl Space 61 and elevator crawl space / low pressure drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Gestra

Model: MK‐45‐2 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 4/21/2020 Inspection Comments:

Inlet (F): 202 Flir image 43

Outlet (F): 198

Tag#: 10157

Bldg/Floor: Building 1 / Sub‐Sub‐Ground Floor

Rm/Location: Mechanical Room SS‐6M / Steam supply drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/30/2020 Inspection Comments:

Inlet (F): 105

Outlet (F): 88

Tag#: 10742

Bldg/Floor: Building 11 / 1st Floor

Rm/Location: Room 109 / Radiator

App: Radiator Stm Press: 3

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/1/2020 Inspection Comments:

Inlet (F): 214

Outlet (F): 212

Tag#: 10745

Bldg/Floor: Building 11 / 1st Floor

Rm/Location: Room 110 / Radiator right side

App: Radiator Stm Press: 3

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Manual Valve TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/1/2020 Inspection Comments:

Inlet (F): 218

Outlet (F): 212

Tag#: 10753

Bldg/Floor: Building 11 / 2nd Floor

Rm/Location: Room 209 / Radiator left side

App: Radiator Stm Press: 3

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/1/2020 Inspection Comments:

Inlet (F): 78

Outlet (F): 78

Tag#: 10732

Bldg/Floor: Building 12 / 1st Floor

Rm/Location: Front office left side / Radiator

App: Radiator Stm Press: 3

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/1/2020 Inspection Comments:

Inlet (F): 217

Outlet (F): 212

Tag#: 10084

Bldg/Floor: Building 16 A / Main Floor

Rm/Location: Boiler Plant / Steam supply drip leg for boiler 3

App: Drip Leg Stm Press: 115

Cond: Returned Mfg: Steam Loc

Model: INL Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/25/2020 Inspection Comments:

Inlet (F): 145

Outlet (F): 119

Tag#: 10090

Rm/Location: Boiler Plant /steam header drip leg on boiler 1

App: Drip Leg Stm Press: 115

Cond: Returned Mfg: Spirax Sarco

Model: TD52 Type: Thermodynamic Size: 1/2"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/25/2020 Inspection Comments:

Inlet (F): 299 3/25/20‐ open to test after testing closed inlet back Outlet (F): 215

Tag#: 10092

Rm/Location: Boiler Plant / Steam supply drip leg to boiler 1

App: Drip Leg Stm Press: 115

Cond: Returned Mfg: Steam Loc

Model: INL AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/25/2020 Inspection Comments:

Inlet (F): 0

Outlet (F): 0

Tag#: 10098

Rm/Location: Boiler Plant / Drip leg above the front of Boiler #1

App: Drip Leg Stm Press: 115

Cond: Returned Mfg: Plenty

Model: TS250 Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/26/2020 Inspection Comments:

Inlet (F): 340 3‐26‐20 The slate is hung on the unistrut just over the railing on top of Boiler #1.

Outlet (F): 220

Tag#: 10008

Bldg/Floor: Building 2 / 4th Floor

Rm/Location: Mechanical Room 5‐110 / Header drip leg to AHU

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL‐AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/23/2020 Inspection Comments:

Inlet (F): 80 3‐23‐20 Recommend blowing down strainer before trap. Trap is plugged.

Outlet (F): 80

Tag#: 9989

Rm/Location: Mechanical Room 4‐132 / condensate discharge for reheat coil

App: Heating Coil Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model:

Type: Float & Thermostatic Size: 1"

Op Hrs: 3763

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Trap Jacket

Date Tested: 3/20/2020 Inspection Comments:

Inlet (F): 132

Outlet (F): 165

Tag#: 9990

Rm/Location: Mechanical Room 4‐132 / Steam supply header drip leg upstream of AHU‐5 control valves

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Hoffman

Model: FT015H Type: Float & Thermostatic Size: 3/4"

Op Hrs: 0

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Trap Jacket

Date Tested: 3/20/2020 Inspection Comments:

Inlet (F): 249 3/20/20‐ Trap found with outlet isolation closed, opened to test and re‐isolated

Outlet (F): 214

Tag#: 10917

Bldg/Floor: Building 2 / 5th Floor

Rm/Location: Room 5‐100 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/13/20‐ broken control head, replace Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 0 5/13/20‐ trap plugged, replace‐

CV:5/13/20‐ broken control head, replace

Outlet (F): 0

Tag#: 10918

Rm/Location: Room 5‐101 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Danfoss

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 258

Outlet (F): 213

Tag#: 10919

Rm/Location: Room 5‐102A / Bathroom / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 80

Outlet (F): 80

Tag#: 10924

Rm/Location: Room 5‐123 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/13/20‐ Control head is broken off Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 245 5/13/20‐ Control head is broken off

Outlet (F): 222

Tag#: 10929

Rm/Location: Room 5‐125D / Middle Right Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Pneumatic Valve TRV Specific Comments:

TRV Mfg: Honeywell

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 240

Outlet (F): 221

Tag#: 10930

Rm/Location: Room 5‐125D / Far Right Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Pneumatic Valve TRV Specific Comments:

TRV Mfg: Honeywell

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 247 5/13/20‐ Manual isolation valve was shut open to test, closed after testing

Outlet (F): 223

Tag#: 10931

Rm/Location: Hallway Outside Room 5‐125D / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 85

Outlet (F): 85

Tag#: 10934

Rm/Location: Left of Main Reception for Room 5‐125 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 85

Outlet (F): 85

Tag#: 10936

Rm/Location: Room 5‐125J / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 105

Outlet (F): 105

Tag#: 10937

Rm/Location: Room 5‐125K / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 255

Outlet (F): 215

Tag#: 10948

Rm/Location: Room 5‐156 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 78

Outlet (F): 78

Tag#: 10956

Rm/Location: Room 5‐170 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 78

Outlet (F): 78

Tag#: 10958

Rm/Location: Room 5‐172 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 81 5/13/20‐ Inlet isolation closed, opened to test, slight leak from stem

Outlet (F): 80

Tag#: 10960

Rm/Location: Room 5‐174 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 83

Outlet (F): 83

Tag#: 10963

Rm/Location: Room 5‐179 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 251

Outlet (F): 225

Tag#: 10964

Rm/Location: Room 5‐180 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 252

Outlet (F): 225

Tag#: 10965

Rm/Location: Room 5‐181 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/13/20‐ Control head is broken off Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 84 5/13/20‐ Control head is broken off

Outlet (F): 84

Tag#: 10177

Bldg/Floor: Building 2 / 6th Floor

Rm/Location: 6‐107 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Pneumatic Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 238

Outlet (F): 215

Tag#: 10193

Rm/Location: 6‐127 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Manual Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 77 3‐31‐20 Steam is passing through the control valve but trap is plugged and not allowing condensate out of the radiator. See photo 2.

Outlet (F): 77

Tag#: 10210

Rm/Location: 6‐141 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Istec 3/31/20‐ control head broken

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 77 3/31/20‐ control head broken

Outlet (F): 83

Tag#: 10218

Rm/Location: 6‐153/ Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 243

Outlet (F): 212

Tag#: 10232

Rm/Location: 6‐166 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 231

Outlet (F): 218

Tag#: 10233

Rm/Location: 6‐167 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Istec 3/31/20‐ Control head broken off

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 241 3/31/20‐ Control head broken off

Outlet (F): 212

Tag#: 10239

Rm/Location: 6‐173 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 3/31/2020 Inspection Comments:

Inlet (F): 76 3/31/20‐ Steam only up to the inlet of the radiator fins, no flow Outlet (F): 76

Tag#: 10252

Rm/Location: Hallway between 6‐183 and 6‐187A / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Pneumatic Valve TRV Specific Comments:

TRV Mfg: Other 4/1/20‐ Powers pneumatic head

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 4/1/2020 Inspection Comments:

Inlet (F): 85 4/1/20‐ Steam past pneumatic control valve, however unable to find thermostat associated with radiator.‐ CV:4/1/20‐ Powers pneumatic head

Outlet (F): 85

Tag#: 10256

Rm/Location: 6‐192 / 3rd Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 4/1/2020 Inspection Comments:

Inlet (F): 233

Outlet (F): 214

Tag#: 10271

Rm/Location: 6‐ / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 4/1/2020 Inspection Comments:

Inlet (F): 255

Outlet (F): 213

Tag#: 10274

Rm/Location: 6‐214 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 4/1/2020 Inspection Comments:

Inlet (F): 247

Outlet (F): 212

Tag#: 10280

Rm/Location: 6‐217 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 4/1/20‐ Control head broken off

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 4/1/2020 Inspection Comments:

Inlet (F): 240 4/1/20‐ Inlet isolation closed

(handle missing), opened to test‐ CV:4/1/20‐ Control head broken off

Outlet (F): 214

Tag#: 10916

Rm/Location: Room 6‐209 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/13/20‐ control head broken and insert leaking Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 0 5/13/20‐ trap plugged, needs to be replaced.‐ CV:5/13/20‐ control head broken and insert leaking

Outlet (F): 0

Tag#: 10853

Bldg/Floor: Building 2 / 7th Floor

Rm/Location: Room 7‐124 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss 5/12/20‐ Control head leaks by

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 237 5/12/20‐ Inlet isolation closed, opened to test‐ CV:5/12/20‐ Control head leaks by

Outlet (F): 214

Tag#: 10854

Rm/Location: Room 7‐126 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss 5/12/20‐ Control head is broken can not close Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 245 5/12/20‐ Control head is broken can not close Outlet (F): 212

Tag#: 10857

Rm/Location: Room 7‐134 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 100

Outlet (F): 100

Tag#: 10859

Rm/Location: Room 7‐136 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 85

Outlet (F): 85

Tag#: 10861

Rm/Location: Room 7‐137 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 83

Outlet (F): 83

Tag#: 10862

Rm/Location: Room 7‐140 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 98 5/12/20‐ Inlet isolation valve closed, opened to test Outlet (F): 92

Tag#: 10867

Rm/Location: Room 7‐149 / Side Bathroom / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 85

Outlet (F): 85

Tag#: 10872

Rm/Location: Room 7‐107 / Radiator at end of Hallway / Next to Room 7‐

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss 5/12/20‐ Control head is broken can’t control Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 249 5/12/20‐ Control head is broken can’t control Outlet (F): 216

Tag#: 10875

Rm/Location: Room 7‐107 / Radiator across from Room 7‐115

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss 5/12/20‐ Danfoss head broken

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 96 5/12/20‐ Inlet isolation closed, opened to test‐ CV:5/12/20‐ Danfoss head broken

Outlet (F): 85

Tag#: 10876

Rm/Location: Room 7‐107 / Radiator across hallway between Rooms 7‐113 and 7–115

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss 5/12/20‐ Control head is broken can’t control Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 232 5/12/20‐ Control head is broken can’t control Outlet (F): 213

Tag#: 10877

Rm/Location: Room 7‐107 / Radiator in hallway across from Room 7‐113

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 80 5/12/20‐ Control head is broken

Outlet (F): 80

Tag#: 10878

Rm/Location: Room 7‐107 / Radiator in hallway across from Room 7‐112

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Danfoss

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/12/2020 Inspection Comments:

Inlet (F): 75 5/12/20‐ Inlet isolation confirmed open Outlet (F): 75

Tag#: 10886

Rm/Location: Room 7‐ 100 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/13/20‐ control head broken, needs replaced. Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 76 5/13/20‐ control head broken, needs replaced. Outlet (F): 71

Tag#: 10891

Rm/Location: Women’s Clinic / Room 7‐165 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Electronic TRV Specific Comments:

TRV Mfg: Johnson Controls 5/13/20‐ Outlet of control valve leaking Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 85 5/13/20‐ Outlet of control valve leaking Outlet (F): 85

Tag#: 10895

Rm/Location: Women’s Clinic / Room 7‐172 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Electronic TRV Specific Comments:

TRV Mfg: Johnson Controls

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 74

Outlet (F): 74

Tag#: 10896

Rm/Location: Women’s Clinic / Room 7‐173 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Electronic TRV Specific Comments:

TRV Mfg: Johnson Controls

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 246

Outlet (F): 226

Tag#: 10901

Rm/Location: Men’s Bathroom / Room 7‐181 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/13/20‐ Control head is missing

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 84 5/13/20‐ Control head is missing

Outlet (F): 79

Tag#: 10909

Rm/Location: Room 7‐186 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 229 5/13/20‐ Isolation valve was shut, opened to test Outlet (F): 212

Tag#: 10911

Rm/Location: Room 7‐201 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 68

Outlet (F): 70

Tag#: 10915

Rm/Location: Room 7‐205I / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 4320 Insert Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5‐13‐20 Control valve head is broken and needs to be replaced. Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/13/2020 Inspection Comments:

Inlet (F): 75 5‐13‐20 Control valve head is broken and needs to be replaced. Outlet (F): 75

Tag#: 9934

Bldg/Floor: Building 2 / 8th Floor

Rm/Location: Mechanical Room Penthouse / SF‐1 steam supply drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL‐AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No CHV: Yes ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/19/2020 Inspection Comments:

Inlet (F): 84

Outlet (F): 84

Tag#: 9935

Rm/Location: Mechanical Room Penthouse / Drip leg above EV‐5 vent

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL‐AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/19/2020 Inspection Comments:

Inlet (F): 87

Outlet (F): 87

Tag#: 9942

Rm/Location: Mechanical Room Penthouse / Low pressure steam supply drip leg downstream of Spence PRV, by HX skid

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL AN Type: Float & Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/19/2020 Inspection Comments:

Inlet (F): 87

Outlet (F): 95

Tag#: 9909

Bldg/Floor: Building 2 / Ground

Rm/Location: Mechanical Room G ‐ 139 / Steam supply drip leg for Aerco heater H‐13‐497

App: Drip Leg Stm Press: 50

Cond: Returned Mfg: Steam Loc

Model: INL Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/18/2020 Inspection Comments:

Inlet (F): 262 3/19/20‐ trap inlet was shut open to test Outlet (F): 214

Tag#: 10156

Bldg/Floor: Building 2 / Ground Floor

Rm/Location: Crawl space #3

App: Drip Leg Stm Press: 110

Cond: Returned Mfg: Gestra

Model: MK45‐2 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 3/27/2020 Inspection Comments:

Inlet (F): 209

Outlet (F): 168

Tag#: 10051

Bldg/Floor: Building 21 / Main Floor

Rm/Location: Maintenance Shop / Radiator

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 122 Type: Thermostatic Size: 1/2"

Op Hrs: 4000

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Other TRV Specific Comments:

TRV Mfg: Other 3‐24‐20 Control valve is a 1/2” ball valve. Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 252 3‐24‐20 Control valve is a 1/2” ball valve. Outlet (F): 223

Tag#: 10052

Rm/Location: Men’s Bathroom / Wall mounted radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 122 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 244

Outlet (F): 212

Tag#: 10057

Rm/Location: Maintenance Shop / radiator in hallway

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 4320 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Manual Valve TRV Specific Comments:

TRV Mfg: Other

Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 100

Outlet (F): 100

Tag#: 10040

Bldg/Floor: Building 22 / Basement

Rm/Location: Basement Mechanical Room / Low pressure steam supply drip leg

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Trap Jacket

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 252

Outlet (F): 212

Tag#: 3682

Bldg/Floor: Building 22 / Basement

Rm/Location: Mechanical Room / High pressure steam supply main drip leg

App: Drip Leg Stm Press: 110

Cond: Returned Mfg: Spirax Sarco

Model: B‐1H Type: Inverted Bucket Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: Yes ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Trap Jacket

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 330

Outlet (F): 220

Tag#: 10118

Bldg/Floor: Building 22 / Main Floor

Rm/Location: Plow bay / Steam supply drip leg for unit heater

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/26/2020 Inspection Comments:

Inlet (F): 122

Outlet (F): 122

Tag#: 10121

Bldg/Floor: Building 22 / Main Floor

Rm/Location: Paint Shop / Steam supply header drip leg

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL AL Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes CHV: No ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 3/26/2020 Inspection Comments:

Inlet (F): 115

Outlet (F): 110

Tag#: 10073

Bldg/Floor: Building 24 / 1st Floor

Rm/Location: Laundry Room / Condensate discharge for wall mounted radiator

App: Radiator Stm Press: 8

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Other 3/25/20‐ Control head likely

Istec, broken off and full open Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 222 2/25/20‐ Trap leaking, as well as slight leak from trap union‐ CV:3/25/20‐ Control head likely Istec, broken off and full open

Outlet (F): 212

Tag#: 10074

Rm/Location: Laundry Room / Wall mounted radiator left side back wall

App: Radiator Stm Press: 8

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Manual Valve TRV Specific Comments:

TRV Mfg:

Size: 3/4" Config: Straight

Insulation Needed:

None

Date Tested: 3/24/2020 Inspection Comments:

Inlet (F): 223

Outlet (F): 212

Tag#: 10075

Rm/Location: Laundry Room / Condensate discharge for wall mounted radiator

App: Radiator Stm Press: 8

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No CHV: No ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Other 3/25/20‐ Control head missing, likely Istec Size: 3/4" Config: Angled

Insulation…