S02 VA West Haven - 2020 COMPLETE SURVEY REPORT - Copy.pdf
PDF 19 MB Posted
- Attached to
- J044--Steam Trap Replacements, West Haven and Newington Federal contract opportunity
- Solicitation number
- 36C24122B0010
About this file
This solicitation is for steam trap replacements at two Department of Veterans Affairs medical centers in Connecticut. The IFB seeks replacement of failed steam traps at the West Haven and Newington campuses. Bids are due by June 15, 2022 and the contract is to be awarded by July 15, 2022. Pricing is to be provided on a firm fixed price basis for supply and installation of new steam traps. The solicitation is set aside for verified service-disabled veteran-owned small businesses. The Veterans Health Administration Veterans Integrated Service Network 1 is the contracting agency.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24122B0010 0003.docx | DOCX document | |
| 36C24122B0010 0002_1.docx | DOCX document | |
| S02 Attachment Instructions to Offerors for Steam Trap Replacements West Haven and Newington.docx | DOCX document | |
| S06 Attachment Site Visit Sign In Sheet.pdf | ||
| S06 Attachment HazMat Report Newington.pdf | ||
| S06 Attachment HazMat Report West Haven.pdf | ||
| 36C24122B0010 0001.docx | DOCX document | |
| S02 Wage Determination West Haven CT20220001 060322.pdf | ||
| S02 VA Newington - 2020 COMPLETE SURVEY REPORT - Copy.pdf | ||
| S02 Final SOW Steam Trap Replacements 5-27-2022.pdf | ||
| S02 VHA Supplemental Contract Requirements for Combatting COVID-19.pdf | ||
| 36C24122B0010_1.docx | DOCX document | |
| S02 Wage Determination Newington CT20220021 06032022.pdf | ||
| S02 PRE-AWARD CONTRACTOR EVALUATION FORM.pdf | ||
| S02 Specifications Steam Trap Replacements.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2020 Steam Trap Survey Report (Mar-May Season)
Power & Process, Inc. 127 Industrial Drive
Southington, CT 06489
860-863-5454 www.powerprocessinc.com
West Haven VA Hospital
950 Campbell Ave.
West Haven, CT 06516 http://www.powerprocessinc.com/
EXECUTIVE DATA SUMMARY
Traps Evaluated 1127 Blowin g thru Leaking Bypassed Plugged OK
Not
Tested
Not in
Service
Quantity Tested 702 23 34 4 73 568 370 55
Percentage able to be tested 62% 3.3% 4.8% 0.6% 10.4% 80.9%
Estimated Annual Gas Savings
(ccf):
162,020 Grashof Calc
233,984 Napier Calc
MAP OF TRAPS EVALUATED TO DATE
SUMMARY OF FAILED TRAPS
Tag#: 9748
Bldg/Floor: Building 1 / 10th Floor
Rm/Location: West Mechanical Room / Condensate discharge for Cemline steam generator
App: Other Stm Press: 8
Cond: Not Returned Mfg: Spirax Sarco
Model: GL51 9NQ Type: Pump Trap Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Trap Jacket
Date Tested: 3/16/2020 Inspection Comments:
Inlet (F): 236 3/16/20‐ Vacuum breaker on heat exchanger bundle leaking as well Outlet (F): 214 Test Result: Blowing thru
Recom: Replace
Tag#: 9761
Rm/Location: West Mechanical Room / Condensate discharge for unit heater by room entrance
App: Unit Heater Stm Press: 17
Cond: Returned Mfg: Velan
Model: TS20 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/16/2020 Inspection Comments:
Inlet (F): 238
Outlet (F): 213
Tag#: 9764
Rm/Location: Center Mechanical Room / High pressure steam supply drip leg to PRV
App: Drip Leg Stm Press: 110
Cond: Not Returned Mfg: Gestra
Model: MK45‐2 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/16/2020 Inspection Comments:
Inlet (F): 334
Outlet (F): 214 Test Result: Leaking
Tag#: 9767
Rm/Location: Center Mechanical Room / steam header drip leg by windows
App: Drip Leg Stm Press: 17
Cond: Returned Mfg: Steam Loc
Model: INL AX Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/16/2020 Inspection Comments:
Inlet (F): 109
Outlet (F): 86 Test Result: Plugged
Tag#: 9768
Rm/Location: Center Mechanical Room / Drip leg above pneumatic air compressor
App: Drip Leg Stm Press: 17
Cond: Returned Mfg: Steam Loc
Model: INL AX Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/16/2020 Inspection Comments:
Inlet (F): 126
Outlet (F): 92
Tag#: 10590
Bldg/Floor: Building 1 / 1st Floor
Rm/Location: 1‐101 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 4/30/2020 Inspection Comments:
Inlet (F): 76
Outlet (F): 76
Tag#: 10599
Bldg/Floor: Building 1 / 2nd Floor
Rm/Location: Room 2 110 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Barnes & Jones
Model: 4320 insert ‐ TRANE B1 Body
Type: Thermostatic Size: 1/2"
Op Hrs: 0
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 4/30/20‐ Control head broken off
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 4/30/2020 Inspection Comments:
Inlet (F): 75 4/30/20‐ No flow through trap, no steam entering radiator‐ CV:4/30/20‐ Control head broken off
Outlet (F): 75
Tag#: 10762
Rm/Location: Room 2 213B / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: BJ 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/1/20‐ Control head broken off
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/1/2020 Inspection Comments:
Inlet (F): 78 5/1/20‐ Control head broken off, steam is passing through control head but not entering radiator‐ CV:5/1/20‐ Control head broken off
Outlet (F): 78
Tag#: 9837
Rm/Location: Mechanical Room 2‐213B / Steam supply header drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/17/2020 Inspection Comments:
Inlet (F): 102
Outlet (F): 91
Tag#: 9816
Bldg/Floor: Building 1 / 4th Floor
Rm/Location: Mechanical Room 4‐254 / Medium pressure steam supply drip leg upstream of PRV
App: Drip Leg Stm Press: 50
Cond: Not Returned Mfg: Plenty
Model: 15 Type: Float & Thermostatic Size: 1"
Op Hrs: 0
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Trap Jacket
Date Tested: 3/17/2020 Inspection Comments:
Inlet (F): 277 3/17/20‐ Trap outlet currently isolated, opened to test. Audible blowby
Outlet (F): 238
Tag#: 9826
Rm/Location: Mechanical Room 4‐254 / Steam supply main drip leg behind
AHU‐3
App:
Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL AW Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/17/2020 Inspection Comments:
Inlet (F): 85
Outlet (F): 78
Tag#: 9829
Rm/Location: Mechanical Room 4‐260 / End of main low pressure steam supply above AHU‐7
App: Drip Leg Stm Press: 8
Cond: Returned Mfg: Steam Loc
Model: INL AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/17/2020 Inspection Comments:
Inlet (F): 103
Outlet (F): 91
Tag#: 10770
Bldg/Floor: Building 1 / 7th Floor
Rm/Location: Room 7‐186D / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5/9/20‐ Should be using a attached remote sensor not a local control valve
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/9/2020 Inspection Comments:
Inlet (F): 76 5/9/20‐ Should be using a attached remote sensor not a local control valve
Outlet (F): 76
Tag#: 10771
Rm/Location: Room 7 186E / Radiator
App: Radiator Stm Press: 10
Cond: Not Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5‐9‐20 Control valve head is broken and needs replacement.
See photo 2.
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/9/2020 Inspection Comments:
Inlet (F): 232 5‐9‐20 Control valve head is broken and needs replacement. See photo 2.
Outlet (F): 215
Tag#: 10794
Rm/Location: Room 7‐202 / Radiator Right
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/9/20‐ Control head is broken off Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/9/2020 Inspection Comments:
Inlet (F): 74 5/9/20‐ Control head is broken off
Outlet (F): 74
Tag#: 10801
Rm/Location: Room 7 154 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/9/2020 Inspection Comments:
Inlet (F): 225
Outlet (F): 214
Tag#: 10806
Rm/Location: Room 7‐149 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/9/20‐ Control head is broken
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/9/2020 Inspection Comments:
Inlet (F): 80 5/9/20‐ got steam pass the control valve but won’t fill the radiator‐ CV:5/9/20‐ Control head is broken
Outlet (F): 80
Tag#: 10814
Rm/Location: Room 7‐133 / Radiator
App: Radiator Stm Press: 10
Cond: Not Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/9/20‐ Control head not responding, full steam all the time
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/9/2020 Inspection Comments:
Inlet (F): 230 5/9/20‐ Control head not responding, full steam all the time Outlet (F): 212
Tag#: 10815
Rm/Location: Room 7‐132 / Radiator
App: Radiator Stm Press: 10
Cond: Not Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/12/20‐ Control head broken off
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 224 5/12/20‐ Control head broken off
Outlet (F): 213
Tag#: 10832
Rm/Location: Room 7‐112 / Right Side Radiator
App: Radiator Stm Press: 10
Cond: Not Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/12/20‐ Control head is missing
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 227 5/12/20‐ Manual isolation valve was shut open to test‐ CV:5/12/20‐ Control head is missing
Outlet (F): 212
Tag#: 10482
Bldg/Floor: Building 1 / Ground
Rm/Location: Port Of Call / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 4/22/20‐ Control head broken off
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 4/22/2020 Inspection Comments:
Inlet (F): 92 4/22/20‐ Even with control head broken off, steam confirmed to inlet of radiator‐ CV:4/22/20‐ Control head broken off
Outlet (F): 89
Tag#: 10499
Bldg/Floor: Building 1 / Ground
Rm/Location: G‐207 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 4/22/2020 Inspection Comments:
Inlet (F): 77
Outlet (F): 77
Tag#: 9848
Bldg/Floor: Building 1 / Ground Floor
Rm/Location: Mechanical Room G‐291 / Condensate discharge reheat coil
App: Heating Coil Stm Press: 10
Cond: Not Returned Mfg: Velan
Model: 15 Type: Float & Thermostatic Size: 1"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/17/2020 Inspection Comments:
Inlet (F): 238
Outlet (F): 212
Tag#: 9866
Bldg/Floor: Building 1 / Sub Ground
Rm/Location: Mechanical Room SG‐ 177 / Steam supply drip leg for Trane
AHU
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/18/2020 Inspection Comments:
Inlet (F): 97
Outlet (F): 82
Tag#: 9896
Rm/Location: Mechanical Room SG‐ 182 / Medium pressure steam supply manifold drip leg (right side)
App: Drip Leg Stm Press: 65
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/18/2020 Inspection Comments:
Inlet (F): 311 3/18/20‐ With trap isolated, audible blowby of bypass valve and should also be replaced. Inlet isolation valve stem also leaking
Outlet (F): 252
Tag#: 9897
Rm/Location: Mechanical Room SG‐ 182 / 65# steam manifold
App: Drip Leg Stm Press: 65
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/18/2020 Inspection Comments:
Inlet (F): 310
Outlet (F): 254
Tag#: 9898
Rm/Location: Mechanical Room SG‐ 182 / end of line drip leg far back wall
App: Drip Leg Stm Press: 30
Cond: Returned Mfg: Steam Loc
Model: INL AN Type: Orifice Size: 1/2"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/18/2020 Inspection Comments:
Inlet (F): 103
Outlet (F): 103
Tag#: 10356
Bldg/Floor: Building 1 / Sub‐ Ground
Rm/Location: Crawl space by elevator shaft / steam supply supply drip leg
App: Drip Leg Stm Press: 50
Cond: Not Returned Mfg: Gestra
Model: MK‐45‐2 Type: Thermostatic Size: 1/2"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 4/14/2020 Inspection Comments:
Inlet (F): 281 4/14/20‐ inlet threads to the trap are leaking. Requires bracing Outlet (F): 186
Error! Filename not specified.
Tag#: 10375
Rm/Location: Crawl space 72 / low pressure drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Gestra
Model: MK‐45‐2 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 4/15/2020 Inspection Comments:
Inlet (F): 125 4/15/20‐ bypass is open and inlet and outlet of trap was close Outlet (F): 125
Tag#: 10376
Rm/Location: Crawl space 72 / low pressure drip leg
App: Drip Leg Stm Press: 10
Cond: Not Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 4/15/2020 Inspection Comments:
Inlet (F): 224
Outlet (F): 215
Tag#: 10384
Rm/Location: Crawl space entrance to SG 179 /
App: Drip Leg Stm Press: 10
Cond: Not Returned Mfg: Unknown
Model: Ft15 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 4/15/2020 Inspection Comments:
Inlet (F): 239 4/15/20‐ near trap is a major steam leak from a pipe 1 and 1/2 inch elbow
Outlet (F): 217
Tag#: 10388
Rm/Location: Crawl space 72 / medium pressure drip leg right side wall
App: Drip Leg Stm Press: 50
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 4/15/2020 Inspection Comments:
Inlet (F): 100 4/20/20‐ Abandoned condensate return line above trap should be plugged, currently leaking steam in tandem with the main condensate return line (not hooked into anything)
Outlet (F): 100
Tag#: 10473
Bldg/Floor: Building 1 / Sub‐Ground
Rm/Location: Tunnel between Crawl Space 61 and elevator crawl space / low pressure drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Gestra
Model: MK‐45‐2 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 4/21/2020 Inspection Comments:
Inlet (F): 202 Flir image 43
Outlet (F): 198
Tag#: 10157
Bldg/Floor: Building 1 / Sub‐Sub‐Ground Floor
Rm/Location: Mechanical Room SS‐6M / Steam supply drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/30/2020 Inspection Comments:
Inlet (F): 105
Outlet (F): 88
Tag#: 10742
Bldg/Floor: Building 11 / 1st Floor
Rm/Location: Room 109 / Radiator
App: Radiator Stm Press: 3
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/1/2020 Inspection Comments:
Inlet (F): 214
Outlet (F): 212
Tag#: 10745
Bldg/Floor: Building 11 / 1st Floor
Rm/Location: Room 110 / Radiator right side
App: Radiator Stm Press: 3
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Manual Valve TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/1/2020 Inspection Comments:
Inlet (F): 218
Outlet (F): 212
Tag#: 10753
Bldg/Floor: Building 11 / 2nd Floor
Rm/Location: Room 209 / Radiator left side
App: Radiator Stm Press: 3
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/1/2020 Inspection Comments:
Inlet (F): 78
Outlet (F): 78
Tag#: 10732
Bldg/Floor: Building 12 / 1st Floor
Rm/Location: Front office left side / Radiator
App: Radiator Stm Press: 3
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/1/2020 Inspection Comments:
Inlet (F): 217
Outlet (F): 212
Tag#: 10084
Bldg/Floor: Building 16 A / Main Floor
Rm/Location: Boiler Plant / Steam supply drip leg for boiler 3
App: Drip Leg Stm Press: 115
Cond: Returned Mfg: Steam Loc
Model: INL Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/25/2020 Inspection Comments:
Inlet (F): 145
Outlet (F): 119
Tag#: 10090
Rm/Location: Boiler Plant /steam header drip leg on boiler 1
App: Drip Leg Stm Press: 115
Cond: Returned Mfg: Spirax Sarco
Model: TD52 Type: Thermodynamic Size: 1/2"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/25/2020 Inspection Comments:
Inlet (F): 299 3/25/20‐ open to test after testing closed inlet back Outlet (F): 215
Tag#: 10092
Rm/Location: Boiler Plant / Steam supply drip leg to boiler 1
App: Drip Leg Stm Press: 115
Cond: Returned Mfg: Steam Loc
Model: INL AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/25/2020 Inspection Comments:
Inlet (F): 0
Outlet (F): 0
Tag#: 10098
Rm/Location: Boiler Plant / Drip leg above the front of Boiler #1
App: Drip Leg Stm Press: 115
Cond: Returned Mfg: Plenty
Model: TS250 Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/26/2020 Inspection Comments:
Inlet (F): 340 3‐26‐20 The slate is hung on the unistrut just over the railing on top of Boiler #1.
Outlet (F): 220
Tag#: 10008
Bldg/Floor: Building 2 / 4th Floor
Rm/Location: Mechanical Room 5‐110 / Header drip leg to AHU
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL‐AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/23/2020 Inspection Comments:
Inlet (F): 80 3‐23‐20 Recommend blowing down strainer before trap. Trap is plugged.
Outlet (F): 80
Tag#: 9989
Rm/Location: Mechanical Room 4‐132 / condensate discharge for reheat coil
App: Heating Coil Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model:
Type: Float & Thermostatic Size: 1"
Op Hrs: 3763
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Trap Jacket
Date Tested: 3/20/2020 Inspection Comments:
Inlet (F): 132
Outlet (F): 165
Tag#: 9990
Rm/Location: Mechanical Room 4‐132 / Steam supply header drip leg upstream of AHU‐5 control valves
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Hoffman
Model: FT015H Type: Float & Thermostatic Size: 3/4"
Op Hrs: 0
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Trap Jacket
Date Tested: 3/20/2020 Inspection Comments:
Inlet (F): 249 3/20/20‐ Trap found with outlet isolation closed, opened to test and re‐isolated
Outlet (F): 214
Tag#: 10917
Bldg/Floor: Building 2 / 5th Floor
Rm/Location: Room 5‐100 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/13/20‐ broken control head, replace Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 0 5/13/20‐ trap plugged, replace‐
CV:5/13/20‐ broken control head, replace
Outlet (F): 0
Tag#: 10918
Rm/Location: Room 5‐101 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Danfoss
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 258
Outlet (F): 213
Tag#: 10919
Rm/Location: Room 5‐102A / Bathroom / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 80
Outlet (F): 80
Tag#: 10924
Rm/Location: Room 5‐123 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/13/20‐ Control head is broken off Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 245 5/13/20‐ Control head is broken off
Outlet (F): 222
Tag#: 10929
Rm/Location: Room 5‐125D / Middle Right Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Pneumatic Valve TRV Specific Comments:
TRV Mfg: Honeywell
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 240
Outlet (F): 221
Tag#: 10930
Rm/Location: Room 5‐125D / Far Right Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Pneumatic Valve TRV Specific Comments:
TRV Mfg: Honeywell
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 247 5/13/20‐ Manual isolation valve was shut open to test, closed after testing
Outlet (F): 223
Tag#: 10931
Rm/Location: Hallway Outside Room 5‐125D / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 85
Outlet (F): 85
Tag#: 10934
Rm/Location: Left of Main Reception for Room 5‐125 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 85
Outlet (F): 85
Tag#: 10936
Rm/Location: Room 5‐125J / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 105
Outlet (F): 105
Tag#: 10937
Rm/Location: Room 5‐125K / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 255
Outlet (F): 215
Tag#: 10948
Rm/Location: Room 5‐156 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 78
Outlet (F): 78
Tag#: 10956
Rm/Location: Room 5‐170 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 78
Outlet (F): 78
Tag#: 10958
Rm/Location: Room 5‐172 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 81 5/13/20‐ Inlet isolation closed, opened to test, slight leak from stem
Outlet (F): 80
Tag#: 10960
Rm/Location: Room 5‐174 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 83
Outlet (F): 83
Tag#: 10963
Rm/Location: Room 5‐179 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 251
Outlet (F): 225
Tag#: 10964
Rm/Location: Room 5‐180 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 252
Outlet (F): 225
Tag#: 10965
Rm/Location: Room 5‐181 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/13/20‐ Control head is broken off Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 84 5/13/20‐ Control head is broken off
Outlet (F): 84
Tag#: 10177
Bldg/Floor: Building 2 / 6th Floor
Rm/Location: 6‐107 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Pneumatic Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 238
Outlet (F): 215
Tag#: 10193
Rm/Location: 6‐127 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Manual Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 77 3‐31‐20 Steam is passing through the control valve but trap is plugged and not allowing condensate out of the radiator. See photo 2.
Outlet (F): 77
Tag#: 10210
Rm/Location: 6‐141 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Istec 3/31/20‐ control head broken
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 77 3/31/20‐ control head broken
Outlet (F): 83
Tag#: 10218
Rm/Location: 6‐153/ Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 243
Outlet (F): 212
Tag#: 10232
Rm/Location: 6‐166 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 231
Outlet (F): 218
Tag#: 10233
Rm/Location: 6‐167 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Istec 3/31/20‐ Control head broken off
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 241 3/31/20‐ Control head broken off
Outlet (F): 212
Tag#: 10239
Rm/Location: 6‐173 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 3/31/2020 Inspection Comments:
Inlet (F): 76 3/31/20‐ Steam only up to the inlet of the radiator fins, no flow Outlet (F): 76
Tag#: 10252
Rm/Location: Hallway between 6‐183 and 6‐187A / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Pneumatic Valve TRV Specific Comments:
TRV Mfg: Other 4/1/20‐ Powers pneumatic head
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 4/1/2020 Inspection Comments:
Inlet (F): 85 4/1/20‐ Steam past pneumatic control valve, however unable to find thermostat associated with radiator.‐ CV:4/1/20‐ Powers pneumatic head
Outlet (F): 85
Tag#: 10256
Rm/Location: 6‐192 / 3rd Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 4/1/2020 Inspection Comments:
Inlet (F): 233
Outlet (F): 214
Tag#: 10271
Rm/Location: 6‐ / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 4/1/2020 Inspection Comments:
Inlet (F): 255
Outlet (F): 213
Tag#: 10274
Rm/Location: 6‐214 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 4/1/2020 Inspection Comments:
Inlet (F): 247
Outlet (F): 212
Tag#: 10280
Rm/Location: 6‐217 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 4/1/20‐ Control head broken off
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 4/1/2020 Inspection Comments:
Inlet (F): 240 4/1/20‐ Inlet isolation closed
(handle missing), opened to test‐ CV:4/1/20‐ Control head broken off
Outlet (F): 214
Tag#: 10916
Rm/Location: Room 6‐209 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/13/20‐ control head broken and insert leaking Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 0 5/13/20‐ trap plugged, needs to be replaced.‐ CV:5/13/20‐ control head broken and insert leaking
Outlet (F): 0
Tag#: 10853
Bldg/Floor: Building 2 / 7th Floor
Rm/Location: Room 7‐124 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss 5/12/20‐ Control head leaks by
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 237 5/12/20‐ Inlet isolation closed, opened to test‐ CV:5/12/20‐ Control head leaks by
Outlet (F): 214
Tag#: 10854
Rm/Location: Room 7‐126 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss 5/12/20‐ Control head is broken can not close Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 245 5/12/20‐ Control head is broken can not close Outlet (F): 212
Tag#: 10857
Rm/Location: Room 7‐134 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 100
Outlet (F): 100
Tag#: 10859
Rm/Location: Room 7‐136 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 85
Outlet (F): 85
Tag#: 10861
Rm/Location: Room 7‐137 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 83
Outlet (F): 83
Tag#: 10862
Rm/Location: Room 7‐140 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 98 5/12/20‐ Inlet isolation valve closed, opened to test Outlet (F): 92
Tag#: 10867
Rm/Location: Room 7‐149 / Side Bathroom / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 85
Outlet (F): 85
Tag#: 10872
Rm/Location: Room 7‐107 / Radiator at end of Hallway / Next to Room 7‐
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss 5/12/20‐ Control head is broken can’t control Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 249 5/12/20‐ Control head is broken can’t control Outlet (F): 216
Tag#: 10875
Rm/Location: Room 7‐107 / Radiator across from Room 7‐115
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss 5/12/20‐ Danfoss head broken
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 96 5/12/20‐ Inlet isolation closed, opened to test‐ CV:5/12/20‐ Danfoss head broken
Outlet (F): 85
Tag#: 10876
Rm/Location: Room 7‐107 / Radiator across hallway between Rooms 7‐113 and 7–115
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss 5/12/20‐ Control head is broken can’t control Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 232 5/12/20‐ Control head is broken can’t control Outlet (F): 213
Tag#: 10877
Rm/Location: Room 7‐107 / Radiator in hallway across from Room 7‐113
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 80 5/12/20‐ Control head is broken
Outlet (F): 80
Tag#: 10878
Rm/Location: Room 7‐107 / Radiator in hallway across from Room 7‐112
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Danfoss
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/12/2020 Inspection Comments:
Inlet (F): 75 5/12/20‐ Inlet isolation confirmed open Outlet (F): 75
Tag#: 10886
Rm/Location: Room 7‐ 100 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/13/20‐ control head broken, needs replaced. Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 76 5/13/20‐ control head broken, needs replaced. Outlet (F): 71
Tag#: 10891
Rm/Location: Women’s Clinic / Room 7‐165 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Electronic TRV Specific Comments:
TRV Mfg: Johnson Controls 5/13/20‐ Outlet of control valve leaking Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 85 5/13/20‐ Outlet of control valve leaking Outlet (F): 85
Tag#: 10895
Rm/Location: Women’s Clinic / Room 7‐172 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Electronic TRV Specific Comments:
TRV Mfg: Johnson Controls
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 74
Outlet (F): 74
Tag#: 10896
Rm/Location: Women’s Clinic / Room 7‐173 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Electronic TRV Specific Comments:
TRV Mfg: Johnson Controls
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 246
Outlet (F): 226
Tag#: 10901
Rm/Location: Men’s Bathroom / Room 7‐181 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/13/20‐ Control head is missing
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 84 5/13/20‐ Control head is missing
Outlet (F): 79
Tag#: 10909
Rm/Location: Room 7‐186 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 229 5/13/20‐ Isolation valve was shut, opened to test Outlet (F): 212
Tag#: 10911
Rm/Location: Room 7‐201 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 68
Outlet (F): 70
Tag#: 10915
Rm/Location: Room 7‐205I / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 4320 Insert Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5‐13‐20 Control valve head is broken and needs to be replaced. Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/13/2020 Inspection Comments:
Inlet (F): 75 5‐13‐20 Control valve head is broken and needs to be replaced. Outlet (F): 75
Tag#: 9934
Bldg/Floor: Building 2 / 8th Floor
Rm/Location: Mechanical Room Penthouse / SF‐1 steam supply drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL‐AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No CHV: Yes ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/19/2020 Inspection Comments:
Inlet (F): 84
Outlet (F): 84
Tag#: 9935
Rm/Location: Mechanical Room Penthouse / Drip leg above EV‐5 vent
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL‐AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/19/2020 Inspection Comments:
Inlet (F): 87
Outlet (F): 87
Tag#: 9942
Rm/Location: Mechanical Room Penthouse / Low pressure steam supply drip leg downstream of Spence PRV, by HX skid
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL AN Type: Float & Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/19/2020 Inspection Comments:
Inlet (F): 87
Outlet (F): 95
Tag#: 9909
Bldg/Floor: Building 2 / Ground
Rm/Location: Mechanical Room G ‐ 139 / Steam supply drip leg for Aerco heater H‐13‐497
App: Drip Leg Stm Press: 50
Cond: Returned Mfg: Steam Loc
Model: INL Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/18/2020 Inspection Comments:
Inlet (F): 262 3/19/20‐ trap inlet was shut open to test Outlet (F): 214
Tag#: 10156
Bldg/Floor: Building 2 / Ground Floor
Rm/Location: Crawl space #3
App: Drip Leg Stm Press: 110
Cond: Returned Mfg: Gestra
Model: MK45‐2 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 3/27/2020 Inspection Comments:
Inlet (F): 209
Outlet (F): 168
Tag#: 10051
Bldg/Floor: Building 21 / Main Floor
Rm/Location: Maintenance Shop / Radiator
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 122 Type: Thermostatic Size: 1/2"
Op Hrs: 4000
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Other TRV Specific Comments:
TRV Mfg: Other 3‐24‐20 Control valve is a 1/2” ball valve. Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 252 3‐24‐20 Control valve is a 1/2” ball valve. Outlet (F): 223
Tag#: 10052
Rm/Location: Men’s Bathroom / Wall mounted radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 122 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 244
Outlet (F): 212
Tag#: 10057
Rm/Location: Maintenance Shop / radiator in hallway
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 4320 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Manual Valve TRV Specific Comments:
TRV Mfg: Other
Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 100
Outlet (F): 100
Tag#: 10040
Bldg/Floor: Building 22 / Basement
Rm/Location: Basement Mechanical Room / Low pressure steam supply drip leg
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Trap Jacket
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 252
Outlet (F): 212
Tag#: 3682
Bldg/Floor: Building 22 / Basement
Rm/Location: Mechanical Room / High pressure steam supply main drip leg
App: Drip Leg Stm Press: 110
Cond: Returned Mfg: Spirax Sarco
Model: B‐1H Type: Inverted Bucket Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: Yes ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Trap Jacket
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 330
Outlet (F): 220
Tag#: 10118
Bldg/Floor: Building 22 / Main Floor
Rm/Location: Plow bay / Steam supply drip leg for unit heater
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/26/2020 Inspection Comments:
Inlet (F): 122
Outlet (F): 122
Tag#: 10121
Bldg/Floor: Building 22 / Main Floor
Rm/Location: Paint Shop / Steam supply header drip leg
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL AL Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes CHV: No ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 3/26/2020 Inspection Comments:
Inlet (F): 115
Outlet (F): 110
Tag#: 10073
Bldg/Floor: Building 24 / 1st Floor
Rm/Location: Laundry Room / Condensate discharge for wall mounted radiator
App: Radiator Stm Press: 8
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Other 3/25/20‐ Control head likely
Istec, broken off and full open Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 222 2/25/20‐ Trap leaking, as well as slight leak from trap union‐ CV:3/25/20‐ Control head likely Istec, broken off and full open
Outlet (F): 212
Tag#: 10074
Rm/Location: Laundry Room / Wall mounted radiator left side back wall
App: Radiator Stm Press: 8
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Manual Valve TRV Specific Comments:
TRV Mfg:
Size: 3/4" Config: Straight
Insulation Needed:
None
Date Tested: 3/24/2020 Inspection Comments:
Inlet (F): 223
Outlet (F): 212
Tag#: 10075
Rm/Location: Laundry Room / Condensate discharge for wall mounted radiator
App: Radiator Stm Press: 8
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No CHV: No ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Other 3/25/20‐ Control head missing, likely Istec Size: 3/4" Config: Angled
Insulation…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .