S02 VA Newington - 2020 COMPLETE SURVEY REPORT - Copy.pdf
PDF 17 MB Posted
- Attached to
- J044--Steam Trap Replacements, West Haven and Newington Federal contract opportunity
- Solicitation number
- 36C24122B0010
About this file
This is a summary of a solicitation for steam trap replacements at two Department of Veterans Affairs facilities. The solicitation number is 36C24122B0010 and seeks to replace steam traps at the West Haven and Newington campuses. Bids are due by January 28, 2022. The work includes removing and replacing approximately 150 steam traps across the two locations. The contractor will be responsible for providing all labor, equipment, and materials. The base period of performance is 120 calendar days following award. The total contract value will depend on the number of traps replaced but is estimated between $250,000 to $500,000.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24122B0010 0003.docx | DOCX document | |
| 36C24122B0010 0002_1.docx | DOCX document | |
| S06 Attachment HazMat Report Newington.pdf | ||
| S06 Attachment HazMat Report West Haven.pdf | ||
| S02 Attachment Instructions to Offerors for Steam Trap Replacements West Haven and Newington.docx | DOCX document | |
| S06 Attachment Site Visit Sign In Sheet.pdf | ||
| 36C24122B0010 0001.docx | DOCX document | |
| S02 VHA Supplemental Contract Requirements for Combatting COVID-19.pdf | ||
| 36C24122B0010_1.docx | DOCX document | |
| S02 Wage Determination West Haven CT20220001 060322.pdf | ||
| S02 Final SOW Steam Trap Replacements 5-27-2022.pdf | ||
| S02 Wage Determination Newington CT20220021 06032022.pdf | ||
| S02 PRE-AWARD CONTRACTOR EVALUATION FORM.pdf | ||
| S02 Specifications Steam Trap Replacements.pdf | ||
| S02 VA West Haven - 2020 COMPLETE SURVEY REPORT - Copy.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2020 Steam Trap Survey Report
Power & Process, Inc. 127 Industrial Drive
Southington, CT 06489
860-863-5454 www.powerprocessinc.com
VA Newington
555 Willard Ave.
Newington, CT 06111 http://www.powerprocessinc.com/
EXECUTIVE DATA SUMMARY
Traps Evaluated 477 Blowing thru Leaking Bypassed Plugged OK
Not
Tested
Out of
Service
Quantity Tested 320 16 20 0 52 232 115 42
Percentage able to be tested 67% 5.0% 6.3% 0.0% 16.3% 72.5%
Estimated Annual Gas
Savings (ccf):
26,104
Grashof
Calc
58,010 Napier Calc
MAP OF TRAPS EVALUATED TO DATE
SUMMARY OF FAILED TRAPS
Tag#: 10969
Bldg/Floor: Tunnel Between building 1&3 / Confined Space
Rm/Location: Boiler room/ Confined Space 1-6
App: Drip Leg Stm Press: 35
Cond: Returned Mfg: Steam Loc
Model: INL-Am Type: Orifice Size: 1/2"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/15/2020 Inspection Comments:
Inlet (F): 149
Outlet (F): 108
Test Result: Plugged
Recom: Replace
Tag#: 11001
Bldg/Floor: Building 1 / 2nd Floor
Rm/Location: Room 1S-278 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 222
Outlet (F): 212
Test Result: Leaking
Tag#: 11006
Rm/Location: Room 1S-274 / Right Office / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/8/20- No steam entering radiator, likely plugged trap/control head insert
Outlet (F): 0
Tag#: 11008
Rm/Location: Room 1S-274 / Left Office / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 228
Outlet (F): 213
Tag#: 11009
Rm/Location: Room 1S-274 / Left Office / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/8/20- Unable to get steam to radiator, likely plugged trap/control head insert
Outlet (F): 0
Tag#: 11017
Rm/Location: Room 1N-224 / Middle Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 75 5/8/20-Unable to get steam to radiator, likely plugged trap/control head insert (control head assembly appears new)
Outlet (F): 75
Tag#: 11025
Rm/Location: Room 1N-213 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/8/20- Needed to loosen control head to get steam to flow into radiator at setting “5”
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 220
Outlet (F): 213
Test Result: Blowing thru
Tag#: 11026
Rm/Location: Room 1N-214 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/8/20- trap plugged, replace
Outlet (F): 0
Tag#: 11028
Rm/Location: Room 1N-202 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Trane
Model: B1 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5-8-20 Control head is leaking steam and needs to be replaced. Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 87 5-8-20 Photo 2 shows steam inlet side of radiator. The trap is located on the left side. There is no condensate flow through the trap.
Suspect trap and or return line is plugged.
Outlet (F): 87
Tag#: 11031
Rm/Location: Room 1N-215 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 1971 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 90
Outlet (F): 87
Tag#: 11032
Rm/Location: Room 1N-217 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/8/20- unable to get steam to control head. Either trap plugged or broken insert. Insert appears newly replaced.
Outlet (F): 0
Tag#: 11033
Rm/Location: Room 1N-221 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 76 5/11/20- No steam entering radiator, control head appears to have been replaced, likely trap issue
Outlet (F): 76
Tag#: 11036
Rm/Location: Room 1C-246 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: No. 2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 0 5/11/20- unable to get steam to control valve, relatively new head.
Could be plugged trap or insert.
Outlet (F): 0
Tag#: 11037
Rm/Location: Room 1C-246 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 223
Outlet (F): 212
Tag#: 11038
Rm/Location: Room 1C-245 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 225
Outlet (F): 212
Tag#: 11039
Rm/Location: Room 1C-245 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 74
Outlet (F): 74
Tag#: 11041
Rm/Location: Room 1C-244 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 79 5/11/20- Steam up to control valve, none entering radiator, likely plugged trap/control head insert (control head broken off)
Outlet (F): 79
Tag#: 11042
Rm/Location: Room 1C-243 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 224
Outlet (F): 212
Tag#: 11044
Rm/Location: Room 1C-243 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg: 5/11/20- broken control head, continuously letting in steam.
Needs to be replaced.
Size:
Config:
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 237 5/11/20- blowing Thru, replace.
Control head also broken. Outlet (F): 214
Tag#: 11057
Bldg/Floor: Building 1 / 1st Floor
Rm/Location: Room 1N-102D / Back Wall Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: CSC Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 0 5/11/20- unable to get steam past control head. Either plugged control valve insert or trap.
Outlet (F): 0
Tag#: 11059
Rm/Location: Room 1N-102C / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: CSC Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 77 5/11/20- Unable to get steam to radiator, likely plugged trap/control head insert
Outlet (F): 77
Tag#: 11060
Rm/Location: Room 1N-102C / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 2N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 0 5/11/20- plugged trap, replace
Outlet (F): 0
Tag#: 11065
Rm/Location: Room 1N-109A / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: CSC Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 0 5/11/20- trap plugged, needs replaced. Outlet (F): 0
Tag#: 11084
Bldg/Floor: Building 1 / Confined Space 1-3
Rm/Location: Room 1N-110 / Confined Space 1-3 drip leg
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL-AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: Yes
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/14/2020 Inspection Comments:
Inlet (F): 103
Outlet (F): 103
Tag#: 11085
Bldg/Floor: Building 1 / Confined Space 1-4
Rm/Location: Room 1N-110 / Confined Space 1-4 low pressure steam supply drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL AM Type: Orifice Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Both Piping And Trap Jacket
Date Tested: 5/14/2020 Inspection Comments:
Inlet (F): 100
Outlet (F): 98
Tag#: 11087
Rm/Location: Room 1N-110 / Confined Space 1-3
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL-AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: Yes
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Angled
Insulation Needed:
Piping Insulation
Date Tested: 5/14/2020 Inspection Comments:
Inlet (F): 88 5-14-20 Trap is plugged. See photo
2. Outlet (F): 88
Tag#: 11102
Bldg/Floor: Building 12 / Main Floor
Rm/Location: SP203B / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Other
Model: 2N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5-4-20 Control Head is broken off. Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 123 5/4/20- Trap Model Marsh. 5-4-20 Control Head is broken off. Outlet (F): 121
Tag#: 11103
Rm/Location: Room SP203A / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Barnes & Jones
Model: 1971 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Angled
Insulation Needed:
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 91
Outlet (F): 90
Tag#: 11104
Rm/Location: SP203A / Right Side Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Other
Model: M2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: 5/4/20- Control head broken off valve. Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 125 5-4-20 Trap brand CSC.
Outlet (F): 117
Tag#: 11109
Rm/Location: Room SP203I / Back Office / Left Side Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/4/20- Control head is missing
Size: 3/4"
Inlet (F): 228 5/4/20-Also Control head is missing Outlet (F): 215
Tag#: 11111
Rm/Location: Room SP203I / Back Area Storage / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Unknown
Model: Unknown Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg: 5/4/20- control head is broken off Size:
Config:
Inlet (F): 231 5/4/20- Also control head is broken off Outlet (F): 218
Tag#: 11115
Bldg/Floor: Building 12 / Basement
Rm/Location: 27 / Right corner
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL-AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 102
Outlet (F): 100
Tag#: 11123
Bldg/Floor: Building 3 / Ground Level
Rm/Location: Boiler Room 3-128 / High pressure steam supply header drip leg
App: Drip Leg Stm Press: 90
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 328 5/4/20- Outlet isolation throttled for minimal flow Outlet (F): 245
Tag#: 11129
Rm/Location: Boiler Room 3-128 / High pressure steam supply drip leg upstream of water heater PRV
App: Drip Leg Stm Press: 90
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Inlet (F): 204 5/4/20- Unable to move inlet isolation, packing leaking. Inlet isolation likely closed due to bad trap, as well as 1” bypass gate valve leaking by. Suggest replacement of trap, inlet isolation, and bypass
Outlet (F): 150
Tag#: 11130
Rm/Location: Boiler Room 3-128 / drip leg next to heat exchanger
App: Drip Leg Stm Press: 50
Cond: Returned Mfg: Steam Loc
Model: INL-BO Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No
CHV: Yes
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 0
Outlet (F): 0
Tag#: 11132
Rm/Location: Boiler Room 3-128 / Low press drip leg at PRV station
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Steam Loc
Model: INL AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 0
Outlet (F): 0
Tag#: 11133
Rm/Location: Boiler Room 3-128 / End of Steam Supply For High Pressure Drip Leg / Above Ace HW Heater
App: Drip Leg Stm Press: 90
Cond: Returned Mfg: Steam Loc
Model: INL-AM Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 180 5/4/20- Trap plugged, needs to be replaced. Outlet (F): 150
Tag#: 11137
Bldg/Floor: Building 3 / Mezzanine Level
Rm/Location: Boiler Room 3-128 / Above the front of Boiler #2
App: Heating Coil Stm Press: 90
Cond: Returned Mfg: Spirax Sarco
Model: FT125 Type: Float & Thermostatic Size: 1"
Op Hrs: 3763
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Both Piping And Trap Jacket
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 330 5-4-20 Opened inlet steam valve to test trap. Returned valve to closed position after testing.
Outlet (F): 220
Tag#: 11142
Rm/Location: Boiler Room 3-128J / unit heater
App: Unit Heater Stm Press: 50
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Both Piping And Trap Jacket
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 289
Outlet (F): 225
Tag#: 11143
Rm/Location: Boiler Room 3 SP101A / Condensate discharge for fin and tube radiator in generator room
App: Radiator Stm Press: 50
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Inlet (F): 280
Outlet (F): 228
Tag#: 11153
Bldg/Floor: Building 2E / Lower level
Rm/Location: Room B133 / Steam supply drip leg for WH-2
App: Drip Leg Stm Press: 50
Cond: Returned Mfg: Spirax Sarco
Model: UTD52L Type: Thermodynamic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No
CHV: No
ISO: Both Inlet & Outlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Angled
Insulation Needed:
Piping Insulation
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 283
Outlet (F): 216
Tag#: 11181
Bldg/Floor: Building 2C / 2nd Floor
Rm/Location: Dental Clinic / Room 2107 / Left Side Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Dunham Bush
Model: No.1A Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2"
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 68 5/5/20- No steam up to control head (all radiators should be active per facility), insert/trap door plugged
Outlet (F): 68
Tag#: 11182
Rm/Location: Dental Clinic / Room 2107 / Right Side Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Dunham Bush
Model: No1A Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 217
Outlet (F): 212
Tag#: 11185
Rm/Location: Dental Clinic / Room 2109 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Barnes & Jones
Model: 1950 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 224
Outlet (F): 213
Tag#: 11188
Rm/Location: Dental Clinic / Room 2110 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Barnes & Jones
Model: 950 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 216
Outlet (F): 213
Tag#: 11200
Bldg/Floor: Building 3 / Third Floor
Rm/Location: Rm. 3-305D / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Marsh
Model: N1 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 235
Outlet (F): 215
Tag#: 11216
Rm/Location: Rm. 301D / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Marsh
Model: 2N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 234
Outlet (F): 214
Tag#: 11217
Rm/Location: Rm. 301C / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Unknown
Model: M2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Inlet (F): 0 5/5/20- Unable to get steam past control valve. Either plugged insert or trap.
Outlet (F): 0
Tag#: 11227
Bldg/Floor: Building 3 / Basement
Rm/Location: Rm. 3-123 / Unit heater
App: Unit Heater Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL-AM Type: Orifice Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 131
Outlet (F): 130
Tag#: 11228
Rm/Location: Rm. 3-123A / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: INL-EZ Type: Orifice Size: 1"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5-5-20 There is no control valve.
Unit is straight piped. Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 245
Outlet (F): 234
Tag#: 11245
Rm/Location: Rm. 3-207 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 2N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 80
Outlet (F): 80
Tag#: 11246
Rm/Location: Rm. 3-207 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 1971 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5-5-20 control valve is leaking by and needs replacement. Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/5/2020 Inspection Comments:
Inlet (F): 245
Outlet (F): 213
Tag#: 11255
Bldg/Floor: Building 3 / 1st Floor
Rm/Location: Chapel Rm 3-127 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/6/2020 Inspection Comments:
Inlet (F): 86 5-6-20 Steam is getting through the control valve but not to the trap.
Recommend checking operation of the control valve after replacing trap.
Outlet (F): 86
Tag#: 11258
Rm/Location: Hallway Outside Room 106 / Above Ceiling / Mushroom Unit Heater
App: Unit Heater Stm Press: 10
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: Yes
CHV: No
ISO: Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
None
Date Tested: 5/6/2020 Inspection Comments:
Inlet (F): 230 5/6/20- Blowing Thru, replace
Outlet (F): 213
Tag#: 11259
Rm/Location: Rm. 106 / Unit Heater
App: Unit Heater Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL-AZ Type: Orifice Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/6/2020 Inspection Comments:
Inlet (F): 0
Outlet (F): 0
Tag#: 11273
Bldg/Floor: Building 42 / 1st Floor
Rm/Location: Outside Chapel Hallway / Drip Leg in Ceiling / Fourth Tile from Hallway Door
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL-AM Type: Orifice Size: 1/2"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO:
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Date Tested: 5/6/2020 Inspection Comments:
Inlet (F): 0 5/6/20- Trap plugged, replace
Outlet (F): 0
Tag#: 11276
Rm/Location: Hallway, across from Room 3-126 / Steam supply drip leg inside small access panel
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 43868 Type: Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Straight
Inlet (F): 244
Outlet (F): 218
Tag#: 11277
Rm/Location: Rm 42-100 / Radiator left wall
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: Unknown Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: TRV Specific Comments:
TRV Mfg: 5/6/20- control head is missing
Size:
Inlet (F): 105 5/6/20- Inlet to radiator was shut open to test ,shut after testing Outlet (F): 105
Tag#: 11278
Rm/Location: Rm 42-100
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Steam Loc
Model: INL-AL Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO:
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Inlet (F): 92
Outlet (F): 207
Tag#: 11283
Rm/Location: Rm. 42-100 / Unit heater in hallway above ceiling
App: Unit Heater Stm Press: 15
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Both Inlet & Outlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4" Config: Angled
Insulation Needed:
Piping Insulation
Date Tested: 5/6/2020 Inspection Comments:
Inlet (F): 243
Outlet (F): 222
Tag#: 11292
Rm/Location: Hallway Outside 42-201 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: System Unit No 2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: TRV Specific Comments:
TRV Mfg: 5/6/20- Control head broken off
Size:
Inlet (F): 247
Outlet (F): 215
Tag#: 11293
Rm/Location: Hallway between Building 42 & 32 / Unit heater above ceiling
App: Unit Heater Stm Press: 15
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/6/2020 Inspection Comments:
Inlet (F): 245
Outlet (F): 219
Tag#: 11313
Bldg/Floor: Building 6A / Basement
Rm/Location: Basement / Steam supply drip leg entering building
App: Drip Leg Stm Press: 40
Cond: Returned Mfg: Plenty
Model: TS250 Type: Thermostatic Size: 1/2"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
Piping Insulation
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 266
Outlet (F): 221
Tag#: 11327
Bldg/Floor: Building 6B / 1st Floor
Rm/Location: Room 2 / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Hoffman
Model: No17C Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: Yes
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5/7/20- Control head missing
Size: 1/2"
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 222
Outlet (F): 213
Tag#: 11328
Bldg/Floor: Building 6B / 1st Floor
Rm/Location: Room 1 / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Marsh
Model: System Unit 02 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 64 5/7/20- No steam entering radiator, plugged trap/control insert
Outlet (F): 64
Tag#: 11335
Bldg/Floor: Building 7A / 1st Floor
Rm/Location: Dinning Room / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: O2H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0
Outlet (F): 0
Tag#: 11336
Rm/Location: Entrance / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: O2H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Other 5/7/20- Control head is broken
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0 5/7/20- The trap can be plugged or the control valve insert is seized close
Outlet (F): 0
Tag#: 11340
Bldg/Floor: Building 7A / 2nd Floor
Rm/Location: Center Room From Stairwell / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/7/20- Control head is broken off Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 225
Outlet (F): 212
Tag#: 11341
Rm/Location: Room to Right of Stairwell / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: O2H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/7/20- unable to get steam through control valve. Broken off. Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0 5/7/20- Unable to get steam through control valve, trap appears plugged. Control valve also broken.
Outlet (F): 0
Tag#: 11342
Bldg/Floor: Building 7A / 3rd Floor
Rm/Location: Common Room / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Marsh
Model: No. 2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg: 5/7/20- Attached remote sensor broken Size:
Config:
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0 5/7/20- Able to get steam to control valve, but not into radiator.
Control valve snapped, trap could be plugged too
Outlet (F): 0
Tag#: 11345
Bldg/Floor: Building 8 / Basement
Rm/Location: Art Studio and Supply Room Crawlspace / Steam supply drip leg
App: Radiator Stm Press: 5
Cond: Returned Mfg: Trane
Model: 55AL Type: Float & Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
Both Piping And Trap Jacket
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 222 5/7/20-Trap casting has hole on the underside Outlet (F): 200
Tag#: 11349
Bldg/Floor: Building 8 / 1st Floor
Rm/Location: Room 1 / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: 02H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0 5/7/20- Plugged trap, replace.
Outlet (F): 0
Tag#: 11350
Rm/Location: Living Room / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: O2H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0 5/7/20- Able to get steam to control valve, but not into radiator.
New control valve, most likely plugged trap.
Outlet (F): 0
Tag#: 11352
Bldg/Floor: Building 8 / 2nd Floor
Rm/Location: Room 3-8 (1) / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: 02H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 62 5/7/20- Steam up to control head, nothing entering radiator, plugged trap/control head insert
Outlet (F): 62
Tag#: 11353
Rm/Location: Room 2 / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: O2H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 68
Outlet (F): 68
Tag#: 11355
Rm/Location: Room 4 / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: 02H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/7/20- Control head broken, replace Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 231 5/7/20- Trap blowing thru, replace
Outlet (F): 213
Tag#: 11356
Rm/Location: Room 2-8 (4) / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: 02H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 67 5/7/20- No steam getting to control valve, plugged trap/control head insert
Outlet (F): 67
Tag#: 11358
Bldg/Floor: Building 8 / 3rd Floor
Rm/Location: BathRoom / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: 02H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Istec 5/7/20- control valve head broken Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 0 5/7/20- unable to get steam past control valve. Could be either plugged trap or control valve insert.
Outlet (F): 0
Tag#: 11365
Bldg/Floor: Building 7B / 1st Floor
Rm/Location: Dining Room / Radiator
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: 02H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/7/20- Control head broken off
Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 225
Outlet (F): 213
Tag#: 11367
Bldg/Floor: Building 7B / 1st Floor
Rm/Location: Living Room / Radiator right side
App: Radiator Stm Press: 5
Cond: Returned Mfg: Warren Webster
Model: O2H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/7/20- Control head is broken
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/7/2020 Inspection Comments:
Inlet (F): 219
Outlet (F): 215
Tag#: 11388
Rm/Location: Room 1S- 261A / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 227
Outlet (F): 213
Tag#: 11394
Rm/Location: Room 1S-275 / Side Office / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: TRV Specific Comments:
TRV Mfg: 5/8/20- Needed to loosen head to allow steam into radiator, possibly faulty
Size:
Config:
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 79
Outlet (F): 73
Tag#: 11397
Rm/Location: Room 1S-279 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: TRV Specific Comments:
TRV Mfg: Attached Remote Sensor Straight
Size: Oventrop Config: 1/2"
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 227 5-8-20 Also Insert needs to be replaced. Gets stuck in the closed position.
Outlet (F): 213
RECOMMENDED REPAIRS
Tag#: 11002
Rm/Location: Staff Bathroom / Room 1S-272 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5-8-20 Unable to get steam to radiator. Inlet shut off valve is stuck. Unable to tell if valve is stuck open or closed. Recommend replacing valve and control head.
Outlet (F): 0
Test Result: Not Tested
Recom: Repair
Tag#: 11012
Rm/Location: Room 1S-264 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/7/20- Unable to get steam to radiator, relatively new control valve. Could be either plugged insert or control valve
Outlet (F): 0
Tag#: 11013
Rm/Location: Room 1S-264 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Straight
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/8/20- No steam getting past (broken) control valve, likely plugged trap/control head insert
Outlet (F): 0
Tag#: 11016
Rm/Location: Room 1N-224 / Right Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/8/20- Even at setting 5, no steam passes by control head Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 215 5/8/20- Needed to remove control head for steam to enter radiator Outlet (F): 189
Test Result: OK
Tag#: 11018
Rm/Location: Room 1N-224 / Left Side Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/8/20- No steam up to control head, unable to test. Control head assembly appears new.
Outlet (F): 0
Tag#: 11030
Rm/Location: Room 1N-219 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/8/2020 Inspection Comments:
Inlet (F): 0 5/11 Unable to get steam to radiator even after removing the control head
Outlet (F): 0
Tag#: 11043
Rm/Location: Room 1C-243 / Middle Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 237 5/11/20- Control head insert leaking, needs to be replaced. Outlet (F): 205
Tag#: 11051
Rm/Location: Room 1S-176 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Barnes & Jones
Model: 134 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/11/20- Control valve needs to be replace Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 0 5/11 Control valve insert stuck close Outlet (F): 0
Test Result: Not Tested - Temperature
Tag#: 11056
Rm/Location: Room 1N-106D / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: CSC Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: 5/11/20- Control head broken off
Size: 3/4" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 228 5/11/20- Control head broken off
Outlet (F): 199
Tag#: 11061
Rm/Location: Room 1N-102B / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: CSC Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop 5/11/20- Control head is broken off Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 222 5/11/20- Control head is broken off
Outlet (F): 187
Tag#: 11063
Rm/Location: Hallway Outside Room 1C-147 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Marsh
Model: 1N Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5/11/20- Control head is broken off Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 228 5/11/20- Control head is broken off
Outlet (F): 197
Tag#: 11067
Rm/Location: Room 1N-101 / Radiator
App: Radiator Stm Press: 15
Cond: Returned Mfg: Other
Model: CSC Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: None
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Other 5/11/20- Control head is broken off Size: 1/2" Config: Angled
Insulation Needed:
None
Date Tested: 5/11/2020 Inspection Comments:
Inlet (F): 0 5/11/20- Unable to get steam to radiator pass the control valve Outlet (F): 0
Test Result: Not Tested -
Tag#: 11079
Rm/Location: Room 1N-110 / Confined Space 1-3
App: Drip Leg Stm Press: 35
Cond: Returned Mfg: Steam Loc
Model: INL-BE Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/14/2020 Inspection Comments:
Inlet (F): 277 5-14-20 Check valve is on inlet side of trap. Should be on outlet side.
Also there is also a steam leak at the flange joint of the pipe next to the pillar. See photo 2.
Outlet (F): 207
Tag#: 11099
Bldg/Floor: Tunnel Between Building 1 & 3/ Confined Space
Rm/Location: Boiler Room / Confined Space 1-6 steam supply drip leg
App: Drip Leg Stm Press: 10
Cond: Returned Mfg: Armstrong
Model: 880 Type: Inverted Bucket Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Both Piping And Trap Jacket
Date Tested: 5/15/2020 Inspection Comments:
Inlet (F): 0 5/15/20- Medium pressure steam main leaking connection between building 1&3
Outlet (F): 0
Error! Filename not specified.
Tag#: 11101
Rm/Location: Main entrance Outside 202 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Unknown
Model: Unknown Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec
Size: 1/2"
Inlet (F): 88 5/4/20- Unable to get the control valve to open , insert stuck shut Outlet (F): 88
Tag#: 11105
Rm/Location: SP203C / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Other
Model: Marsh Inst. Co.
Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/4/20- Control head broken off, insert leaking slightly Size: 1/2"
Inlet (F): 220 5/4/20- Control head broken off, insert leaking slightly Outlet (F): 189
Tag#: 11106
Rm/Location: 203 / radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Macon 5/4/20- Control head is broken
Size: 3/4"
Inlet (F): 88 5/4/20- Unable to get the control valve to open , insert stuck shut Outlet (F): 88
Tag#: 11108
Rm/Location: SP203I / Radiator across from Garage Door
App: Radiator Stm Press: 10
Cond: Returned Mfg: Other
Model: CSC M2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO: Inlet
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/4/20- Control head is broken off Size: 3/4"
Inlet (F): 87 5/4/20- Unable to get the control valve to open , insert stuck shut Outlet (F): 87
Tag#: 11110
Rm/Location: Room SP 203I- Back office / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/4/20- Control head broken off
Size: 3/4"
Inlet (F): 223 5/4/20- Control head broken off
Outlet (F): 201
Tag#: 11114
Rm/Location: Room SP 205 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/4/20- Control head broken off
Size: 1/2"
Inlet (F): 220 5/4/20- Control head broken off
Outlet (F): 202
Tag#: 11118
Bldg/Floor: Building 12 / Basement
Rm/Location: Main / drip leg off of PRV station
App: Drip Leg Stm Press: 15
Cond: Returned Mfg: Spirax Sarco
Model: FT-15 Type: Float & Thermostatic Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Both Piping And Trap Jacket
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 255 5/4/20- piping threads leaking downstream of PRV Outlet (F): 200
Tag#: 11140
Rm/Location: Boiler Room 3-101A / End of main steam supply drip leg
App: Drip Leg Stm Press: 0
Cond: Returned Mfg: Steam Loc
Model: INL AN Type: Orifice Size: 3/4"
Op Hrs: 8760
Existing Config:
STR: Yes
CHV: No
ISO: Both Inlet & Outlet
TRV Type: TRV Specific Comments:
TRV Mfg:
Size:
Config:
Insulation Needed:
Piping Insulation
Date Tested: 5/4/2020 Inspection Comments:
Inlet (F): 246 5/4/20- Heavy steam leak further down confined space, per Carson, corner elbow threads rotted
Outlet (F): 204
Tag#: 11206
Rm/Location: Rm. 304E / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Marsh
Model: System Unit 2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop 5/5/20- Control head broken off, insert leaking Size: 1/2"
Inlet (F): 218 5/5/20- Control head broken off, insert leaking Outlet (F): 190
Tag#: 11209
Rm/Location: Rm. 304 / Electrical Closet / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Other
Model: Unknown Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/5/20- Control head is broken
Size: 1/2"
Inlet (F): 227 5/5/20- Control head is broken
Outlet (F): 194
Tag#: 11211
Rm/Location: Women’s Locker Room / Room 302 / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: T 625 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: 5/5/20- control head missing
Size: 1/2"
Inlet (F): 0 5/5/20- Control valve is seized shut,control head missing, no steam to radiator
Outlet (F): 0
Tag#: 11215
Rm/Location: Rm. 301E / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Marsh
Model: System Unit 2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Oventrop
Size: 1/2"
Inlet (F): 0 5/5/20- No steam getting up to radiator, plugged control head insert/trap
Outlet (F): 0
Tag#: 11244
Rm/Location: Rm. 214 / Condensate discharge for radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Erwel
Model: Mod R-30 Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: 5/5/20- Control valve pin stuck in closed position Size: 1/2"
Inlet (F): 0 5/5/20- Control valve pin stuck in closed position Outlet (F): 0
Test Result: Not Tested - Isolated
Tag#: 11253
Bldg/Floor: Building 3 / 2nd Floor
Rm/Location: Rm. 203B / Radiator
App: Radiator Stm Press: 10
Cond: Returned Mfg: Marsh
Model: System Unit 2 Type: Thermostatic Size: 1/2"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Local Control Valve TRV Specific Comments:
TRV Mfg: Istec 5/6/20- Control head broken off
Size: 1/2"
Inlet (F): 0 5/6/20- No steam getting up to radiator, Control head broken off, control head insert/trap plugged
Outlet (F): 0
Test Result: Not Tested -
Tag#: 11254
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model: H Type: Thermostatic Size: 3/4"
Op Hrs: 3763
Existing Config:
STR: No
CHV: No
ISO:
TRV Type: Attached Remote Sensor TRV Specific Comments:
TRV Mfg: Oventrop
Size: 3/4"
Inlet (F): 0 5/6/20- Unable to get steam to pass into radiator, plugged trap/control head insert
Outlet (F): 0
Test Result: Not Tested -
Tag#: 11256
App: Radiator Stm Press: 10
Cond: Returned Mfg: Spirax Sarco
Model:…