This is a summary of a solicitation for steam trap replacements at two Department of Veterans Affairs facilities. The solicitation number is 36C24122B0010 and seeks to replace steam traps at the West Haven and Newington campuses. Bids are due by January 28, 2022. The work includes removing and replacing approximately 150 steam traps across the two locations. The contractor will be responsible for providing all labor, equipment, and materials. The base period of performance is 120 calendar days following award. The total contract value will depend on the number of traps replaced but is estimated between $250,000 to $500,000.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2020 Steam Trap Survey Report

Power & Process, Inc. 127 Industrial Drive

Southington, CT 06489

860-863-5454 www.powerprocessinc.com

VA Newington

555 Willard Ave.

Newington, CT 06111 http://www.powerprocessinc.com/

EXECUTIVE DATA SUMMARY

Traps Evaluated 477 Blowing thru Leaking Bypassed Plugged OK

Not

Tested

Out of

Service

Quantity Tested 320 16 20 0 52 232 115 42

Percentage able to be tested 67% 5.0% 6.3% 0.0% 16.3% 72.5%

Estimated Annual Gas

Savings (ccf):

26,104

Grashof

Calc

58,010 Napier Calc

MAP OF TRAPS EVALUATED TO DATE

SUMMARY OF FAILED TRAPS

Tag#: 10969

Bldg/Floor: Tunnel Between building 1&3 / Confined Space

Rm/Location: Boiler room/ Confined Space 1-6

App: Drip Leg Stm Press: 35

Cond: Returned Mfg: Steam Loc

Model: INL-Am Type: Orifice Size: 1/2"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/15/2020 Inspection Comments:

Inlet (F): 149

Outlet (F): 108

Test Result: Plugged

Recom: Replace

Tag#: 11001

Bldg/Floor: Building 1 / 2nd Floor

Rm/Location: Room 1S-278 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 222

Outlet (F): 212

Test Result: Leaking

Tag#: 11006

Rm/Location: Room 1S-274 / Right Office / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/8/20- No steam entering radiator, likely plugged trap/control head insert

Outlet (F): 0

Tag#: 11008

Rm/Location: Room 1S-274 / Left Office / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 228

Outlet (F): 213

Tag#: 11009

Rm/Location: Room 1S-274 / Left Office / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/8/20- Unable to get steam to radiator, likely plugged trap/control head insert

Outlet (F): 0

Tag#: 11017

Rm/Location: Room 1N-224 / Middle Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 75 5/8/20-Unable to get steam to radiator, likely plugged trap/control head insert (control head assembly appears new)

Outlet (F): 75

Tag#: 11025

Rm/Location: Room 1N-213 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/8/20- Needed to loosen control head to get steam to flow into radiator at setting “5”

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 220

Outlet (F): 213

Test Result: Blowing thru

Tag#: 11026

Rm/Location: Room 1N-214 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/8/20- trap plugged, replace

Outlet (F): 0

Tag#: 11028

Rm/Location: Room 1N-202 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Trane

Model: B1 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5-8-20 Control head is leaking steam and needs to be replaced. Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 87 5-8-20 Photo 2 shows steam inlet side of radiator. The trap is located on the left side. There is no condensate flow through the trap.

Suspect trap and or return line is plugged.

Outlet (F): 87

Tag#: 11031

Rm/Location: Room 1N-215 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 1971 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 90

Outlet (F): 87

Tag#: 11032

Rm/Location: Room 1N-217 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/8/20- unable to get steam to control head. Either trap plugged or broken insert. Insert appears newly replaced.

Outlet (F): 0

Tag#: 11033

Rm/Location: Room 1N-221 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 76 5/11/20- No steam entering radiator, control head appears to have been replaced, likely trap issue

Outlet (F): 76

Tag#: 11036

Rm/Location: Room 1C-246 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: No. 2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 0 5/11/20- unable to get steam to control valve, relatively new head.

Could be plugged trap or insert.

Outlet (F): 0

Tag#: 11037

Rm/Location: Room 1C-246 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 223

Outlet (F): 212

Tag#: 11038

Rm/Location: Room 1C-245 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 225

Outlet (F): 212

Tag#: 11039

Rm/Location: Room 1C-245 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 74

Outlet (F): 74

Tag#: 11041

Rm/Location: Room 1C-244 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 79 5/11/20- Steam up to control valve, none entering radiator, likely plugged trap/control head insert (control head broken off)

Outlet (F): 79

Tag#: 11042

Rm/Location: Room 1C-243 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 224

Outlet (F): 212

Tag#: 11044

Rm/Location: Room 1C-243 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg: 5/11/20- broken control head, continuously letting in steam.

Needs to be replaced.

Size:

Config:

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 237 5/11/20- blowing Thru, replace.

Control head also broken. Outlet (F): 214

Tag#: 11057

Bldg/Floor: Building 1 / 1st Floor

Rm/Location: Room 1N-102D / Back Wall Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: CSC Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 0 5/11/20- unable to get steam past control head. Either plugged control valve insert or trap.

Outlet (F): 0

Tag#: 11059

Rm/Location: Room 1N-102C / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: CSC Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 77 5/11/20- Unable to get steam to radiator, likely plugged trap/control head insert

Outlet (F): 77

Tag#: 11060

Rm/Location: Room 1N-102C / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 2N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 0 5/11/20- plugged trap, replace

Outlet (F): 0

Tag#: 11065

Rm/Location: Room 1N-109A / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: CSC Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 0 5/11/20- trap plugged, needs replaced. Outlet (F): 0

Tag#: 11084

Bldg/Floor: Building 1 / Confined Space 1-3

Rm/Location: Room 1N-110 / Confined Space 1-3 drip leg

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL-AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: Yes

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/14/2020 Inspection Comments:

Inlet (F): 103

Outlet (F): 103

Tag#: 11085

Bldg/Floor: Building 1 / Confined Space 1-4

Rm/Location: Room 1N-110 / Confined Space 1-4 low pressure steam supply drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL AM Type: Orifice Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Both Piping And Trap Jacket

Date Tested: 5/14/2020 Inspection Comments:

Inlet (F): 100

Outlet (F): 98

Tag#: 11087

Rm/Location: Room 1N-110 / Confined Space 1-3

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL-AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: Yes

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Angled

Insulation Needed:

Piping Insulation

Date Tested: 5/14/2020 Inspection Comments:

Inlet (F): 88 5-14-20 Trap is plugged. See photo

2. Outlet (F): 88

Tag#: 11102

Bldg/Floor: Building 12 / Main Floor

Rm/Location: SP203B / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Other

Model: 2N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5-4-20 Control Head is broken off. Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 123 5/4/20- Trap Model Marsh. 5-4-20 Control Head is broken off. Outlet (F): 121

Tag#: 11103

Rm/Location: Room SP203A / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Barnes & Jones

Model: 1971 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Angled

Insulation Needed:

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 91

Outlet (F): 90

Tag#: 11104

Rm/Location: SP203A / Right Side Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Other

Model: M2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: 5/4/20- Control head broken off valve. Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 125 5-4-20 Trap brand CSC.

Outlet (F): 117

Tag#: 11109

Rm/Location: Room SP203I / Back Office / Left Side Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/4/20- Control head is missing

Size: 3/4"

Inlet (F): 228 5/4/20-Also Control head is missing Outlet (F): 215

Tag#: 11111

Rm/Location: Room SP203I / Back Area Storage / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Unknown

Model: Unknown Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg: 5/4/20- control head is broken off Size:

Config:

Inlet (F): 231 5/4/20- Also control head is broken off Outlet (F): 218

Tag#: 11115

Bldg/Floor: Building 12 / Basement

Rm/Location: 27 / Right corner

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL-AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 102

Outlet (F): 100

Tag#: 11123

Bldg/Floor: Building 3 / Ground Level

Rm/Location: Boiler Room 3-128 / High pressure steam supply header drip leg

App: Drip Leg Stm Press: 90

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 328 5/4/20- Outlet isolation throttled for minimal flow Outlet (F): 245

Tag#: 11129

Rm/Location: Boiler Room 3-128 / High pressure steam supply drip leg upstream of water heater PRV

App: Drip Leg Stm Press: 90

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Inlet (F): 204 5/4/20- Unable to move inlet isolation, packing leaking. Inlet isolation likely closed due to bad trap, as well as 1” bypass gate valve leaking by. Suggest replacement of trap, inlet isolation, and bypass

Outlet (F): 150

Tag#: 11130

Rm/Location: Boiler Room 3-128 / drip leg next to heat exchanger

App: Drip Leg Stm Press: 50

Cond: Returned Mfg: Steam Loc

Model: INL-BO Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No

CHV: Yes

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 0

Outlet (F): 0

Tag#: 11132

Rm/Location: Boiler Room 3-128 / Low press drip leg at PRV station

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Steam Loc

Model: INL AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 0

Outlet (F): 0

Tag#: 11133

Rm/Location: Boiler Room 3-128 / End of Steam Supply For High Pressure Drip Leg / Above Ace HW Heater

App: Drip Leg Stm Press: 90

Cond: Returned Mfg: Steam Loc

Model: INL-AM Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 180 5/4/20- Trap plugged, needs to be replaced. Outlet (F): 150

Tag#: 11137

Bldg/Floor: Building 3 / Mezzanine Level

Rm/Location: Boiler Room 3-128 / Above the front of Boiler #2

App: Heating Coil Stm Press: 90

Cond: Returned Mfg: Spirax Sarco

Model: FT125 Type: Float & Thermostatic Size: 1"

Op Hrs: 3763

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Both Piping And Trap Jacket

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 330 5-4-20 Opened inlet steam valve to test trap. Returned valve to closed position after testing.

Outlet (F): 220

Tag#: 11142

Rm/Location: Boiler Room 3-128J / unit heater

App: Unit Heater Stm Press: 50

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Both Piping And Trap Jacket

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 289

Outlet (F): 225

Tag#: 11143

Rm/Location: Boiler Room 3 SP101A / Condensate discharge for fin and tube radiator in generator room

App: Radiator Stm Press: 50

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Inlet (F): 280

Outlet (F): 228

Tag#: 11153

Bldg/Floor: Building 2E / Lower level

Rm/Location: Room B133 / Steam supply drip leg for WH-2

App: Drip Leg Stm Press: 50

Cond: Returned Mfg: Spirax Sarco

Model: UTD52L Type: Thermodynamic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No

CHV: No

ISO: Both Inlet & Outlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Angled

Insulation Needed:

Piping Insulation

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 283

Outlet (F): 216

Tag#: 11181

Bldg/Floor: Building 2C / 2nd Floor

Rm/Location: Dental Clinic / Room 2107 / Left Side Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Dunham Bush

Model: No.1A Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2"

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 68 5/5/20- No steam up to control head (all radiators should be active per facility), insert/trap door plugged

Outlet (F): 68

Tag#: 11182

Rm/Location: Dental Clinic / Room 2107 / Right Side Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Dunham Bush

Model: No1A Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 217

Outlet (F): 212

Tag#: 11185

Rm/Location: Dental Clinic / Room 2109 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Barnes & Jones

Model: 1950 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 224

Outlet (F): 213

Tag#: 11188

Rm/Location: Dental Clinic / Room 2110 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Barnes & Jones

Model: 950 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 216

Outlet (F): 213

Tag#: 11200

Bldg/Floor: Building 3 / Third Floor

Rm/Location: Rm. 3-305D / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Marsh

Model: N1 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 235

Outlet (F): 215

Tag#: 11216

Rm/Location: Rm. 301D / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Marsh

Model: 2N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 234

Outlet (F): 214

Tag#: 11217

Rm/Location: Rm. 301C / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Unknown

Model: M2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Inlet (F): 0 5/5/20- Unable to get steam past control valve. Either plugged insert or trap.

Outlet (F): 0

Tag#: 11227

Bldg/Floor: Building 3 / Basement

Rm/Location: Rm. 3-123 / Unit heater

App: Unit Heater Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL-AM Type: Orifice Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 131

Outlet (F): 130

Tag#: 11228

Rm/Location: Rm. 3-123A / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: INL-EZ Type: Orifice Size: 1"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5-5-20 There is no control valve.

Unit is straight piped. Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 245

Outlet (F): 234

Tag#: 11245

Rm/Location: Rm. 3-207 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 2N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 80

Outlet (F): 80

Tag#: 11246

Rm/Location: Rm. 3-207 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 1971 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5-5-20 control valve is leaking by and needs replacement. Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/5/2020 Inspection Comments:

Inlet (F): 245

Outlet (F): 213

Tag#: 11255

Bldg/Floor: Building 3 / 1st Floor

Rm/Location: Chapel Rm 3-127 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/6/2020 Inspection Comments:

Inlet (F): 86 5-6-20 Steam is getting through the control valve but not to the trap.

Recommend checking operation of the control valve after replacing trap.

Outlet (F): 86

Tag#: 11258

Rm/Location: Hallway Outside Room 106 / Above Ceiling / Mushroom Unit Heater

App: Unit Heater Stm Press: 10

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: Yes

CHV: No

ISO: Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

None

Date Tested: 5/6/2020 Inspection Comments:

Inlet (F): 230 5/6/20- Blowing Thru, replace

Outlet (F): 213

Tag#: 11259

Rm/Location: Rm. 106 / Unit Heater

App: Unit Heater Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL-AZ Type: Orifice Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/6/2020 Inspection Comments:

Inlet (F): 0

Outlet (F): 0

Tag#: 11273

Bldg/Floor: Building 42 / 1st Floor

Rm/Location: Outside Chapel Hallway / Drip Leg in Ceiling / Fourth Tile from Hallway Door

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL-AM Type: Orifice Size: 1/2"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO:

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Date Tested: 5/6/2020 Inspection Comments:

Inlet (F): 0 5/6/20- Trap plugged, replace

Outlet (F): 0

Tag#: 11276

Rm/Location: Hallway, across from Room 3-126 / Steam supply drip leg inside small access panel

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 43868 Type: Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Straight

Inlet (F): 244

Outlet (F): 218

Tag#: 11277

Rm/Location: Rm 42-100 / Radiator left wall

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: Unknown Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: TRV Specific Comments:

TRV Mfg: 5/6/20- control head is missing

Size:

Inlet (F): 105 5/6/20- Inlet to radiator was shut open to test ,shut after testing Outlet (F): 105

Tag#: 11278

Rm/Location: Rm 42-100

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Steam Loc

Model: INL-AL Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO:

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Inlet (F): 92

Outlet (F): 207

Tag#: 11283

Rm/Location: Rm. 42-100 / Unit heater in hallway above ceiling

App: Unit Heater Stm Press: 15

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Both Inlet & Outlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4" Config: Angled

Insulation Needed:

Piping Insulation

Date Tested: 5/6/2020 Inspection Comments:

Inlet (F): 243

Outlet (F): 222

Tag#: 11292

Rm/Location: Hallway Outside 42-201 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: System Unit No 2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: TRV Specific Comments:

TRV Mfg: 5/6/20- Control head broken off

Size:

Inlet (F): 247

Outlet (F): 215

Tag#: 11293

Rm/Location: Hallway between Building 42 & 32 / Unit heater above ceiling

App: Unit Heater Stm Press: 15

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/6/2020 Inspection Comments:

Inlet (F): 245

Outlet (F): 219

Tag#: 11313

Bldg/Floor: Building 6A / Basement

Rm/Location: Basement / Steam supply drip leg entering building

App: Drip Leg Stm Press: 40

Cond: Returned Mfg: Plenty

Model: TS250 Type: Thermostatic Size: 1/2"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

Piping Insulation

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 266

Outlet (F): 221

Tag#: 11327

Bldg/Floor: Building 6B / 1st Floor

Rm/Location: Room 2 / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Hoffman

Model: No17C Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: Yes

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5/7/20- Control head missing

Size: 1/2"

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 222

Outlet (F): 213

Tag#: 11328

Bldg/Floor: Building 6B / 1st Floor

Rm/Location: Room 1 / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Marsh

Model: System Unit 02 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 64 5/7/20- No steam entering radiator, plugged trap/control insert

Outlet (F): 64

Tag#: 11335

Bldg/Floor: Building 7A / 1st Floor

Rm/Location: Dinning Room / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: O2H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0

Outlet (F): 0

Tag#: 11336

Rm/Location: Entrance / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: O2H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Other 5/7/20- Control head is broken

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0 5/7/20- The trap can be plugged or the control valve insert is seized close

Outlet (F): 0

Tag#: 11340

Bldg/Floor: Building 7A / 2nd Floor

Rm/Location: Center Room From Stairwell / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/7/20- Control head is broken off Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 225

Outlet (F): 212

Tag#: 11341

Rm/Location: Room to Right of Stairwell / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: O2H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/7/20- unable to get steam through control valve. Broken off. Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0 5/7/20- Unable to get steam through control valve, trap appears plugged. Control valve also broken.

Outlet (F): 0

Tag#: 11342

Bldg/Floor: Building 7A / 3rd Floor

Rm/Location: Common Room / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Marsh

Model: No. 2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg: 5/7/20- Attached remote sensor broken Size:

Config:

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0 5/7/20- Able to get steam to control valve, but not into radiator.

Control valve snapped, trap could be plugged too

Outlet (F): 0

Tag#: 11345

Bldg/Floor: Building 8 / Basement

Rm/Location: Art Studio and Supply Room Crawlspace / Steam supply drip leg

App: Radiator Stm Press: 5

Cond: Returned Mfg: Trane

Model: 55AL Type: Float & Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

Both Piping And Trap Jacket

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 222 5/7/20-Trap casting has hole on the underside Outlet (F): 200

Tag#: 11349

Bldg/Floor: Building 8 / 1st Floor

Rm/Location: Room 1 / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: 02H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0 5/7/20- Plugged trap, replace.

Outlet (F): 0

Tag#: 11350

Rm/Location: Living Room / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: O2H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0 5/7/20- Able to get steam to control valve, but not into radiator.

New control valve, most likely plugged trap.

Outlet (F): 0

Tag#: 11352

Bldg/Floor: Building 8 / 2nd Floor

Rm/Location: Room 3-8 (1) / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: 02H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 62 5/7/20- Steam up to control head, nothing entering radiator, plugged trap/control head insert

Outlet (F): 62

Tag#: 11353

Rm/Location: Room 2 / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: O2H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 68

Outlet (F): 68

Tag#: 11355

Rm/Location: Room 4 / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: 02H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/7/20- Control head broken, replace Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 231 5/7/20- Trap blowing thru, replace

Outlet (F): 213

Tag#: 11356

Rm/Location: Room 2-8 (4) / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: 02H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 67 5/7/20- No steam getting to control valve, plugged trap/control head insert

Outlet (F): 67

Tag#: 11358

Bldg/Floor: Building 8 / 3rd Floor

Rm/Location: BathRoom / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: 02H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Istec 5/7/20- control valve head broken Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 0 5/7/20- unable to get steam past control valve. Could be either plugged trap or control valve insert.

Outlet (F): 0

Tag#: 11365

Bldg/Floor: Building 7B / 1st Floor

Rm/Location: Dining Room / Radiator

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: 02H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/7/20- Control head broken off

Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 225

Outlet (F): 213

Tag#: 11367

Bldg/Floor: Building 7B / 1st Floor

Rm/Location: Living Room / Radiator right side

App: Radiator Stm Press: 5

Cond: Returned Mfg: Warren Webster

Model: O2H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/7/20- Control head is broken

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/7/2020 Inspection Comments:

Inlet (F): 219

Outlet (F): 215

Tag#: 11388

Rm/Location: Room 1S- 261A / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 227

Outlet (F): 213

Tag#: 11394

Rm/Location: Room 1S-275 / Side Office / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: TRV Specific Comments:

TRV Mfg: 5/8/20- Needed to loosen head to allow steam into radiator, possibly faulty

Size:

Config:

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 79

Outlet (F): 73

Tag#: 11397

Rm/Location: Room 1S-279 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: TRV Specific Comments:

TRV Mfg: Attached Remote Sensor Straight

Size: Oventrop Config: 1/2"

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 227 5-8-20 Also Insert needs to be replaced. Gets stuck in the closed position.

Outlet (F): 213

RECOMMENDED REPAIRS

Tag#: 11002

Rm/Location: Staff Bathroom / Room 1S-272 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5-8-20 Unable to get steam to radiator. Inlet shut off valve is stuck. Unable to tell if valve is stuck open or closed. Recommend replacing valve and control head.

Outlet (F): 0

Test Result: Not Tested

Recom: Repair

Tag#: 11012

Rm/Location: Room 1S-264 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/7/20- Unable to get steam to radiator, relatively new control valve. Could be either plugged insert or control valve

Outlet (F): 0

Tag#: 11013

Rm/Location: Room 1S-264 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Straight

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/8/20- No steam getting past (broken) control valve, likely plugged trap/control head insert

Outlet (F): 0

Tag#: 11016

Rm/Location: Room 1N-224 / Right Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/8/20- Even at setting 5, no steam passes by control head Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 215 5/8/20- Needed to remove control head for steam to enter radiator Outlet (F): 189

Test Result: OK

Tag#: 11018

Rm/Location: Room 1N-224 / Left Side Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/8/20- No steam up to control head, unable to test. Control head assembly appears new.

Outlet (F): 0

Tag#: 11030

Rm/Location: Room 1N-219 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/8/2020 Inspection Comments:

Inlet (F): 0 5/11 Unable to get steam to radiator even after removing the control head

Outlet (F): 0

Tag#: 11043

Rm/Location: Room 1C-243 / Middle Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 237 5/11/20- Control head insert leaking, needs to be replaced. Outlet (F): 205

Tag#: 11051

Rm/Location: Room 1S-176 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Barnes & Jones

Model: 134 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/11/20- Control valve needs to be replace Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 0 5/11 Control valve insert stuck close Outlet (F): 0

Test Result: Not Tested - Temperature

Tag#: 11056

Rm/Location: Room 1N-106D / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: CSC Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: 5/11/20- Control head broken off

Size: 3/4" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 228 5/11/20- Control head broken off

Outlet (F): 199

Tag#: 11061

Rm/Location: Room 1N-102B / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: CSC Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop 5/11/20- Control head is broken off Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 222 5/11/20- Control head is broken off

Outlet (F): 187

Tag#: 11063

Rm/Location: Hallway Outside Room 1C-147 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Marsh

Model: 1N Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5/11/20- Control head is broken off Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 228 5/11/20- Control head is broken off

Outlet (F): 197

Tag#: 11067

Rm/Location: Room 1N-101 / Radiator

App: Radiator Stm Press: 15

Cond: Returned Mfg: Other

Model: CSC Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: None

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Other 5/11/20- Control head is broken off Size: 1/2" Config: Angled

Insulation Needed:

None

Date Tested: 5/11/2020 Inspection Comments:

Inlet (F): 0 5/11/20- Unable to get steam to radiator pass the control valve Outlet (F): 0

Test Result: Not Tested -

Tag#: 11079

Rm/Location: Room 1N-110 / Confined Space 1-3

App: Drip Leg Stm Press: 35

Cond: Returned Mfg: Steam Loc

Model: INL-BE Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/14/2020 Inspection Comments:

Inlet (F): 277 5-14-20 Check valve is on inlet side of trap. Should be on outlet side.

Also there is also a steam leak at the flange joint of the pipe next to the pillar. See photo 2.

Outlet (F): 207

Tag#: 11099

Bldg/Floor: Tunnel Between Building 1 & 3/ Confined Space

Rm/Location: Boiler Room / Confined Space 1-6 steam supply drip leg

App: Drip Leg Stm Press: 10

Cond: Returned Mfg: Armstrong

Model: 880 Type: Inverted Bucket Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Both Piping And Trap Jacket

Date Tested: 5/15/2020 Inspection Comments:

Inlet (F): 0 5/15/20- Medium pressure steam main leaking connection between building 1&3

Outlet (F): 0

Error! Filename not specified.

Tag#: 11101

Rm/Location: Main entrance Outside 202 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Unknown

Model: Unknown Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec

Size: 1/2"

Inlet (F): 88 5/4/20- Unable to get the control valve to open , insert stuck shut Outlet (F): 88

Tag#: 11105

Rm/Location: SP203C / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Other

Model: Marsh Inst. Co.

Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/4/20- Control head broken off, insert leaking slightly Size: 1/2"

Inlet (F): 220 5/4/20- Control head broken off, insert leaking slightly Outlet (F): 189

Tag#: 11106

Rm/Location: 203 / radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Macon 5/4/20- Control head is broken

Size: 3/4"

Inlet (F): 88 5/4/20- Unable to get the control valve to open , insert stuck shut Outlet (F): 88

Tag#: 11108

Rm/Location: SP203I / Radiator across from Garage Door

App: Radiator Stm Press: 10

Cond: Returned Mfg: Other

Model: CSC M2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO: Inlet

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/4/20- Control head is broken off Size: 3/4"

Inlet (F): 87 5/4/20- Unable to get the control valve to open , insert stuck shut Outlet (F): 87

Tag#: 11110

Rm/Location: Room SP 203I- Back office / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/4/20- Control head broken off

Size: 3/4"

Inlet (F): 223 5/4/20- Control head broken off

Outlet (F): 201

Tag#: 11114

Rm/Location: Room SP 205 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/4/20- Control head broken off

Size: 1/2"

Inlet (F): 220 5/4/20- Control head broken off

Outlet (F): 202

Tag#: 11118

Bldg/Floor: Building 12 / Basement

Rm/Location: Main / drip leg off of PRV station

App: Drip Leg Stm Press: 15

Cond: Returned Mfg: Spirax Sarco

Model: FT-15 Type: Float & Thermostatic Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Both Piping And Trap Jacket

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 255 5/4/20- piping threads leaking downstream of PRV Outlet (F): 200

Tag#: 11140

Rm/Location: Boiler Room 3-101A / End of main steam supply drip leg

App: Drip Leg Stm Press: 0

Cond: Returned Mfg: Steam Loc

Model: INL AN Type: Orifice Size: 3/4"

Op Hrs: 8760

Existing Config:

STR: Yes

CHV: No

ISO: Both Inlet & Outlet

TRV Type: TRV Specific Comments:

TRV Mfg:

Size:

Config:

Insulation Needed:

Piping Insulation

Date Tested: 5/4/2020 Inspection Comments:

Inlet (F): 246 5/4/20- Heavy steam leak further down confined space, per Carson, corner elbow threads rotted

Outlet (F): 204

Tag#: 11206

Rm/Location: Rm. 304E / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Marsh

Model: System Unit 2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop 5/5/20- Control head broken off, insert leaking Size: 1/2"

Inlet (F): 218 5/5/20- Control head broken off, insert leaking Outlet (F): 190

Tag#: 11209

Rm/Location: Rm. 304 / Electrical Closet / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Other

Model: Unknown Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/5/20- Control head is broken

Size: 1/2"

Inlet (F): 227 5/5/20- Control head is broken

Outlet (F): 194

Tag#: 11211

Rm/Location: Women’s Locker Room / Room 302 / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: T 625 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: 5/5/20- control head missing

Size: 1/2"

Inlet (F): 0 5/5/20- Control valve is seized shut,control head missing, no steam to radiator

Outlet (F): 0

Tag#: 11215

Rm/Location: Rm. 301E / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Marsh

Model: System Unit 2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Oventrop

Size: 1/2"

Inlet (F): 0 5/5/20- No steam getting up to radiator, plugged control head insert/trap

Outlet (F): 0

Tag#: 11244

Rm/Location: Rm. 214 / Condensate discharge for radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Erwel

Model: Mod R-30 Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: 5/5/20- Control valve pin stuck in closed position Size: 1/2"

Inlet (F): 0 5/5/20- Control valve pin stuck in closed position Outlet (F): 0

Test Result: Not Tested - Isolated

Tag#: 11253

Bldg/Floor: Building 3 / 2nd Floor

Rm/Location: Rm. 203B / Radiator

App: Radiator Stm Press: 10

Cond: Returned Mfg: Marsh

Model: System Unit 2 Type: Thermostatic Size: 1/2"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Local Control Valve TRV Specific Comments:

TRV Mfg: Istec 5/6/20- Control head broken off

Size: 1/2"

Inlet (F): 0 5/6/20- No steam getting up to radiator, Control head broken off, control head insert/trap plugged

Outlet (F): 0

Test Result: Not Tested -

Tag#: 11254

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model: H Type: Thermostatic Size: 3/4"

Op Hrs: 3763

Existing Config:

STR: No

CHV: No

ISO:

TRV Type: Attached Remote Sensor TRV Specific Comments:

TRV Mfg: Oventrop

Size: 3/4"

Inlet (F): 0 5/6/20- Unable to get steam to pass into radiator, plugged trap/control head insert

Outlet (F): 0

Test Result: Not Tested -

Tag#: 11256

App: Radiator Stm Press: 10

Cond: Returned Mfg: Spirax Sarco

Model:…