This solicitation is for steam trap replacements at two Department of Veterans Affairs facilities in West Haven and Newington, Connecticut. The solicitation number is 36C24122B0010 and seeks replacement of steam traps according to specifications in the attached Invitation for Bid. Bids are due by August 12, 2022. The work includes removing and replacing approximately 200 steam traps across the two locations. The contract will be a firm-fixed price award made to the responsible bidder submitting the lowest price. The Veterans Health Administration within the Department of Veterans Affairs is the contracting agency.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VOLUME II

ASBESTOS CONTAINING MATERIAL &

LEAD CONTAINING PAINT

SURVEY REPORT

BUILDING 5

VISN 1

West Haven VA Medical Center

950 Campbell Avenue West Haven, Connecticut

Project No. 2009023.006

September 16, 2011

5 Alfred Circle Bedford, MA 01730-2318

Telephone: (781) 275-6050 Toll Free: (800) 877-6050 Facsimile: (781) 275-5651 info@mabbett.com www.mabbett.com

© 2011, Mabbett & Associates, Inc.

West Haven VAMC - Building 5 September 2011 ©2011, Mabbett & Associates, Inc. Page i West Haven Building 5 Rpt Final 9-16-11.doc

ACKNOWLEDGMENT

This Asbestos Containing Materials (ACM) and Lead Containing Paint (LCP) Building Survey Report was prepared for the Veterans Affairs (VA) New England Healthcare System (VISN 1) in accordance with established scope of work as defined in Contract Number VA241-P-1653.

The information presented herein is based on the facts and information conveyed to or received by the Mabbett & Associates, Inc. (M&A) Team during the preparation of this report.

If any of the information provided to M&A that was used in preparing this report is incorrect, incomplete, or subject to change, M&A would wish to alter its opinion(s) accordingly. In addition, the professional opinions and information contained in this report are based solely on the requirements of the applicable regulations and technical data as known to M&A as of the date of this report and considered applicable to this report.

This individual building report within Volume II, which contains building specific lead and asbestos findings, is part of the Comprehensive VAMC Lead and Asbestos Survey Report consisting of the following Volumes:

Volume I - General

Chapter 1 - Introduction and Executive Summary Chapter 2 - Asbestos Operations & Maintenance (O&M) Plan Chapter 3 - Asbestos Containing Materials (ACM) Survey Tables Chapter 4 - Lead Containing Paint Survey Tables

Volume II – Individual Building Reports

Individual Building Reports Chapters including:

Cover page with building number Building narrative summary Floor plans Relevant asbestos findings for the building Relevant lead containing paint findings for the building Relevant photos

Volume III – Appendices and Supporting Data

Appendix A - Asbestos Laboratory Analysis Reports and Laboratory Certifications Appendix B - Inspector Field Data Sheets/Chains-of-Custody Appendix C - Personnel Certifications & Licenses Appendix D - XRF Performance Characteristics/Calibration Records Appendix E - Lead Laboratory Analysis Reports and Laboratory Certifications (If Applicable)

Volume IV – HUD Residential LBP Reports (If Applicable)

©2011, Mabbett & Associates, Inc. Page ii West Haven Building 5 Rpt Final 9-16-11.doc

This report was prepared by the following Mabbett & Associates, Inc. Team personnel:

ENVIROMED SERVICES, INC.

John Luby Project Manager EnviroMed Services, Inc.

Connecticut Asbestos Inspector 000281 Connecticut Management Planner 000281

This report has been reviewed and approved by:

MABBETT & ASSOCIATES, INC.

Robert K. McKinley, MPH, CIH, LIH Director of Industrial Hygiene Services

©2011, Mabbett & Associates, Inc. Page iii West Haven Building 5 Rpt Final 9-16-11.doc

TABLE OF CONTENTS

Description Page

1.0 INTRODUCTION & EXECUTIVE SUMMARY

2.0 BUILDING DESCRIPTION

3.0 ASBESTOS SURVEY

3.1 Sampling Methodology

3.2 Analytical Methodology

3.3 Summary of Asbestos Containing Materials (ACM) Findings

4.0 LEAD SCREENING SURVEY

4.1 Screening Survey Methodology

4.2 Summary of Lead Screening Survey Findings

5.0 LIMITATIONS

6.0 CLOSING REMARKS

6.1 Asbestos

6.2 Lead Containing Paint

Tables Table 1 – Specific Inaccessible Areas Table 2 – Summary of Positive ACM Samples Table 3 – Summary of Positive XRF Measurements Table 4 – Summary of ACM Building Results, including negative results.................. Appendix A Table 5 – Summary of XRF Measurements............................................................... Appendix B

Figures Figure 1 – Asbestos Survey Summary Plan – Building 5 – Basement Figure 2 – Asbestos Survey Summary Plan – Building 5 – First Floor Figure 3 – Asbestos Survey Summary Plan – Building 5 – Second Floor Figure 4 – Asbestos Survey Summary Plan – Building 5 – Third Floor Figure 5 – Lead Survey Summary Plan - Building 5 – Basement Figure 6 – Lead Survey Summary Plan - Building 5 – First Floor Figure 7 – Lead Survey Summary Plan - Building 5 – Second Floor Figure 8 – Lead Survey Summary Plan - Building 5 – Third Floor

Appendices Appendix A – Table 4, Summary of ACM Building Results, including negative results Appendix B – Table 5, Summary of XRF Measurements Appendix C – Representative Photographs of ACM Appendix D – Representative Photographs of Non-Intact Lead Containing Paint

©2011, Mabbett & Associates, Inc. Page 1 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

1.0 INTRODUCTION & EXECUTIVE SUMMARY

Mabbett and Associates, Inc. (M&A), with EnviroMed Services, Inc. (EnviroMed) as sub-contractor, performed surveys for suspect asbestos containing building materials (ACM) and screenings of suspect lead containing paint (LCP) surfaces utilizing an X-Ray Fluorescence (XRF) analyzer. Surveys were performed of selected buildings at the VA Medical Center (VAMC) located at 950 Campbell Avenue, West Haven, CT, under Contract VA241-P-1653. A complete list of buildings surveyed is in Volume I of this report. Site survey work was performed in July 2010 by appropriately credentialed personnel as required. Collected suspect ACM samples were submitted to a certified analytical laboratory for asbestos analysis by polarized light microscopy (PLM) using positive stop methodology and transmission electron microscopy (TEM) where indicated. When necessary, paint chip samples were collected and submitted to a certified analytical laboratory for lead content analysis using atomic absorption spectroscopy. The survey effort involved the collection or screening of the following samples, resulting in the following conclusions:

356 bulk samples for suspect ACM were collected in this building.

Based on laboratory analysis of suspect ACM, 51 of the collected samples contained asbestos greater than 1%.

719 XRF analyzer screening measurements of building surfaces were taken in this building.

Based on XRF screening measurements, 419 of the screening measurements revealed concentrations of lead in paint that exceeded 0.1 milligram per square centimeter (mg/cm2).

This building report consists of a summary of findings, floor plans that indicate positive sample locations, detailed analytical findings for the specific surveyed building materials, and photos of LCP greater than 1.0 mg/cm2 and in non-intact condition. Laboratory certificates of analysis and field data sheets for this building report are available in Volume III of the Comprehensive VAMC Lead and Asbestos Survey Report.

2.0 BUILDING DESCRIPTION

According to information provided by the VAMC Office of Facilities Management and observations made by the M&A team at the time of the survey, Building 5 was a four-story Business Office and Research Administration Building built in 1916, renovated in 1990, and occupied approximately 55,470 square feet.

3.0 ASBESTOS SURVEY

3.1 Sampling Methodology

A visual screening inspection was conducted to identify locations of suspect ACM throughout the building by state licensed asbestos inspectors. Only areas that were accessible during the field work phase were inspected. Every effort was made during the initial field survey work to access areas as necessary to complete the survey. However, areas that remained inaccessible to the survey team are indicated in Table 1 below.

©2011, Mabbett & Associates, Inc. Page 2 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Table 1 – Specific Inaccessible Areas West Haven VA Medical Center, Building 5

Building Floor Room

No.

Reason Area Was Inaccessible and Survey

Impacts, If Applicable

There were no inaccessible areas identified during this survey.

Other general areas that were inaccessible or where the survey was limited to visual observation only are identified below:

• Within walls • Within fire doors

• Enclosed pipe/duct chases • Inside mechanical equipment/ductwork

• Above fixed drywall or plaster ceilings without access panel

Due to these access restrictions, ACM surveys should be performed prior to any proposed renovations or maintenance involving inaccessible areas.

Bulk samples were collected of suspect ACM in accordance with US Environmental Protection Agency (EPA) Asbestos Hazard and Emergency Response Act (AHERA) and VISN 1 approved M&A VISN 1 Survey Program Standard Operating Procedure (SOP). Roofing materials were not sampled, unless otherwise indicated, in order to maintain applicable warranties. Bulk suspect ACM sampling was conducted according to the following sampling plan:

(a) Surfacing material:

(1) At least three bulk samples shall be collected from each homogeneous area that is 1,000 ft2 or less.

(2) At least five bulk samples shall be collected from each homogeneous area that is greater than 1,000 ft2 but less than or equal to 5,000 ft2.

(3) At least seven bulk samples shall be collected from each homogeneous area that is greater than 5,000 ft2.

(b) Thermal system insulation:

(1) At least three bulk samples shall be collected from each homogeneous area of thermal system insulation.

(2) At least one bulk sample shall be collected from each homogeneous area of patched area of thermal system insulation.

(3) Sufficient samples shall be collected from elbows and fittings to determine if it contains ACM.

(4) Bulk samples shall not be collected from any homogeneous area where the state licensed asbestos inspector determined that the thermal system insulation is fiberglass, foam glass, rubber, or other non-ACM.

©2011, Mabbett & Associates, Inc. Page 3 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

(c) Miscellaneous material:

(1) At least one bulk sample shall be collected from each homogeneous area that is less than 100 ft2.

(2) At least three bulk samples shall be collected from each homogeneous area that is greater than 100 ft2.

3.2 Analytical Methodology

The collected bulk samples were submitted under chain of custody procedures to EnviroMed Services, Inc. (EnviroMed) of Meriden, CT. EnviroMed is accredited by the American Industrial Hygiene Association (AIHA) and participates in the National Voluntary Laboratory Accreditation Program (NVLAP Lab Code 200858-0). Bulk samples were analyzed with polarized light microscopy (PLM) using EPA Method 600/R-93/116. When required, sample results that revealed trace concentrations (greater than 0% but less than or equal to 1%) of asbestos by PLM were analyzed using transmission electron microscopy (TEM) analysis. Duplicate bulk samples were submitted for PLM analysis to ProScience of Woburn, MA. ProScience is accredited by AIHA and participates in the NVLAP (Lab Code 200090-0). A summary table containing the duplicate bulk sample results is provided in Volume I, Table 5. Copies of the laboratory accreditations are included in Volume III of the Comprehensive VAMC Lead and Asbestos Survey Report.

Bulk sample results are summarized in Table 4 – Summary of ACM Building Results. The EPA, Occupational Safety and Health Administration (OSHA), and the State of Connecticut Department of Public Health (DPH) define any material that contains greater than one percent (>1%) asbestos as being an ACM. As such, the analytical laboratory identified bulk samples as positive for asbestos that met the regulatory criteria of >1% asbestos.

3.3 Summary of Asbestos Containing Materials (ACM) Findings

3.3.1 Data Tables, Laboratory Results, and Field Notes

Collected bulk samples confirmed by the analytical laboratory to contain >1% asbestos are listed in Table 2 - Summary of Positive ACM Samples. Samples analyzed by PLM containing trace levels of asbestos, defined as greater than 0% but less than 1%, are listed in Table 4 with the TEM analysis results. Volume III of the Comprehensive VAMC Lead and Asbestos Survey Report includes copies of the laboratory certificates of analysis (including duplicate samples) and Inspector Field Data Sheets.

©2011, Mabbett & Associates, Inc. Page 4 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Table 2 - Summary of Positive ACM Samples

Sample No.

Sample Location

ACM

Location(s)

Description of Material

Percent and Type of Asbestos

Condition Estimated Quantity

VISN 1

RISK

Hazard Category

1-4* 7A 7B 7C

B18 Records B18 9"X9" Black Vinyl Floor Tile w/white streaks

6% Chrysotile

Good

290 SF

8A 8B 8C

B18 Records B18

Mastic with 9"X9" Black Vinyl Floor Tile w/white streaks

5%

290 SF

12A 12B 12C

B8 B5 B9

Rooms B5, B5a, B5b, B5c, B6, B7, B8, B9, B14, B17, B24, B25, B25A, B26

Duct Insulation 8%

Damaged

2200 SF

13A 13B 13C

B18 B5 B9

Rooms B1, B2, B4, B5, B5a, B5b, B5c, B6, B7, B8, B9, B10, B14, B15, B18, B19, B21, B23, B24, B25, B25A, B26

Pipe Insulation - Mag

20%

1000 LF

14A 14B 14C

B18 B5 B9

Rooms B1, B2, B4, B5, B5a, B5b, B5c, B6, B7, B8, B9, B10, B14, B15, B18, B19, B21, B23, B24, B25, B25A, B26

Pipe Elbow w/Mag

100 LF

14% Amosite

15A

15B 15C

B21

B9

Rooms B1, B2, B4, B5, B5a, B5b, B5c, B6, B7, B8, B9, B10, B14, B15, B18, B19, B21, B23, B24, B25, B25A, B26

Pipe Elbow w/Air Cell

40%

50 LF

16A 16B 16C

Exterior Exterior

Window Frame Hard Caulk

4%

4200 LF

18A 18B

Exterior Exterior Door Frame Hard White Caulk

3%

60 LF

©2011, Mabbett & Associates, Inc. Page 5 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Table 2 - Summary of Positive ACM Samples

Sample No.

Sample Location

ACM

Location(s)

Description of Material

Percent and Type of Asbestos

Condition Estimated Quantity

VISN 1

RISK

Hazard Category

1-4*

21B 21C

B5 B9

B21 B5 B9

Pipe Insulation - Air Cell

30%

500 LF

56A 56B 56C

361 361 Yellow Linoleum w/Stone Pattern

2%

84 SF

57B 57C

361 361 Glue w/Yellow

Linoleum w/Stone Pattern

84 SF

58A 58B 58C

360A

Rooms 306, 360, 360A, 371

Green Linoleum Stone Pattern

728 SF

60A 60B 60C

Rooms 361, 362, 363, 363A, 364, 365, 366, 367, 368, 369, 370, Corridor 3-4, 3-5

Brown Linoleum, Stone Pattern

1300 SF

61A 61B 61C

Rooms 361, 362, 363, 363A, 364, 365, 366, 367, 368, 369, 370, Corridor 3-4, 3-5

Glue w/Brown Linoleum, Stone

Pattern

1300 SF

93A 93B 93C

Rooms 107, 109, 117, 118, 118A, 119, 120, 122, 123, 124, 140

9"X9" Green Vinyl Floor Tile

2280 SF

105A 105B 105C

139E 139E Black Mastic under Carpet

240 SF

106A 106B 106C

Rooms 219, 215, 234, 235, 237, 239, 241

Mastic w/12"x12" Vinyl Floor Tile Gray w/White

Specks

1232 SF

111A 111B 111C

Exterior Exterior Window Frame Caulk, Old Hard

White

4200 LF

Footnotes: SF - Square Feet LF - Linear Feet

* The VISN 1 hazard assessment scale 1 – 4 is a relative indicator of the risk and need for response/remediation. (1) Represents the highest priority (e.g. removal or encapsulation) where as a (4) represents the lowest priority (monitor as part of 6 month O&M program). The rating, assigned by an Asbestos Management Planner, takes into account: condition, friable

vs. non-friable, accessibility, occupancy (e.g. continuous, intermittent or occasional and patients/staff/visitors), potential for air erosion, potential for vibration damage, potential for disturbance / damage (e.g. exposed and in an accessible location), and potential for water damage.

©2011, Mabbett & Associates, Inc. Page 6 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

3.3.2 Photographs

Representative photographs of identified ACM are provided in Appendix C of this report.

3.3.3 CADD Drawings

The location of each collected bulk sample and its abridged sample ID is shown on the CADD drawings in the Figures Section of this report. The sample ID on the drawings has been abridged (by excluding the individual room number from the full sample ID) for aesthetic purposes. Each positive ACM sample location is colored red and marked with an asterisk (*), while positive stops are marked with two asterisks (**). Collected bulk samples that were not positive are identified solely by the abridged sample ID. Building areas containing ACM have been indicated with hatching to identify the location of the identified ACM.

4.0 LEAD SCREENING SURVEY

4.1 Screening Survey Methodology

The M&A Team completed a Lead Containing Paint Risk Analysis in accordance with the SOP and determined that a LCP screening survey was warranted in this building. The LCP screening survey was performed by trained lead inspectors/screeners meeting the qualifications outlined in the SOP. The screening survey measured lead concentrations in accessible building surfaces by using a Niton XLp 703A XRF (serial number 7712). The XRF instrument was calibrated at the frequency specified in the SOP.

4.2 Summary of Lead Screening Survey Findings

4.2.1 Data Tables

As specified by VISN 1, a description of XRF-screened painted interior and exterior building components containing lead at concentrations greater than 0.1 mg/cm2, the VISN 1-specified threshold, have been included in Table 3 below:

Table 3 - Summary of Positive XRF Measurements Above VISN1-Specified Threshold of >0.1 mg/cm2

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2748 FIRST 124

PLASTER

WALL

SOUTH - C INTACT WHITE 0.15

2749 FIRST 124

WOOD DOOR

CASING

EAST - B

Not Intact-

POOR

WHITE 0.13

2752 FIRST 124 WOOD DOOR SOUTH - C INTACT WHITE 0.28

2753 FIRST 124

METAL

RADIATOR

WEST - D INTACT WHITE 0.16

2754 FIRST 124

METAL DOOR

CASING

SOUTH - C INTACT TAN 5.5

2755 FIRST

WEST

CORRIDOR

PLASTER

WALL

NORTH - A INTACT BEIGE 0.12

©2011, Mabbett & Associates, Inc. Page 7 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2756 FIRST

WEST

CORRIDOR

METAL

RADIATOR

SOUTH - C

Not Intact-

POOR

BEIGE 0.8

2757 FIRST

WEST

CORRIDOR

METAL

RADIATOR

WEST - D INTACT BROWN 6.1

2759 FIRST 123

PLASTER

WALL

NORTH - A

Not Intact-

POOR

WHITE 0.13

2762 FIRST 123

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

WHITE 5

2765 FIRST

CORRIDOR

METAL

FIREHOSE

CLOSET

WEST - D INTACT RED 1

2770 FIRST

CORRIDOR

WOOD DOOR

CASING

SOUTH - C INTACT BLUE 0.6

2775 FIRST 139

WOOD

WINDOW

CASING

SOUTH - C INTACT WHITE 4.7

2776 FIRST 139

WOOD

WINDOW

CASING

EAST - B

Not Intact-

POOR

WHITE 6.8

2779 FIRST 139

METAL

RADIATOR

EAST - B INTACT WHITE 0.17

2780 FIRST

CORRIDOR

METAL

RADIATOR

EAST - B INTACT WHITE 1.3

2781 FIRST 125c

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 2.5

2782 FIRST 125c

PLASTER

WALL

SOUTH - C INTACT WHITE 0.11

2788 FIRST c-125

METAL

ELECTRICAL

BOX MOUNT

EAST - B INTACT GRAY 0.19

2791 FIRST c-125

WOOD

WINDOW

CASING

SOUTH - C

Not Intact-

POOR

WHITE 2.6

2792 FIRST c-125

METAL

RADIATOR

SOUTH - C

Not Intact-

POOR

WHITE 0.4

2793 FIRST

EAST

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

NORTH - A INTACT RED 1.7

2794 FIRST

EAST

CORRIDOR

PLASTER

WALL

NORTH - A INTACT BEIGE 0.23

2796 FIRST

EAST

CORRIDOR

METAL

RADIATOR

SOUTH - C

Not Intact-

POOR

WHITE 2

2798 FIRST 131

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

WHITE 4.1

2802 FIRST 129a METAL PIPE NORTH - A INTACT BEIGE 3

2803 FIRST 129a METAL PIPE NORTH - A INTACT BEIGE 2.6

2804 FIRST 129a METAL PIPE NORTH - A INTACT BEIGE 2.8

2805 FIRST 129a METAL PIPE SOUTH - C INTACT BEIGE 3.6

©2011, Mabbett & Associates, Inc. Page 8 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2807 FIRST STAIR 1

METAL STAIR

BALUSTER

NORTH - A

Not Intact-

POOR

BEIGE 9.8

2808 FIRST STAIR 1

METAL STAIR

STRINGER

NORTH - A

Not Intact-

POOR

BEIGE 11.3

2809 FIRST STAIR 1

METAL STAIR

NEWEL POST

NORTH - A

Not Intact-

POOR

BEIGE 13.2

2810 FIRST STAIR 1

METAL

CEILING

WEST - D

Not Intact-

POOR

BEIGE 4.4

2811 FIRST STAIR 1

METAL STAIR

RISER

WEST - D

Not Intact-

POOR

BLACK 15.8

2812 FIRST STAIR 1

METAL STAIR

BASEBOARD

NORTH - A

Not Intact-

POOR

BLACK 21.8

2813 FIRST STAIR 1

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 0.3

2814 FIRST STAIR 1

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 0.26

2815 FIRST STAIR 1 METAL PIPE WEST - D INTACT WHITE 0.27

2819 FIRST 101

METAL STAIR

STRINGER

NORTH - A INTACT WHITE 5.6

2820 FIRST 101

METAL STAIR

RISER

NORTH - A

Not Intact-

POOR

BLACK 3.3

2821 FIRST 101

METAL STAIR

BASEBOARD

NORTH - A

Not Intact-

POOR

BLACK 5.5

2822 FIRST 101 METAL WALL NORTH - A

Not Intact-

POOR

WHITE 0.25

2824 FIRST 101

WOOD

WINDOW

CASING

NORTH - A INTACT WHITE 3.9

2829 FIRST 101 METAL DOOR NORTH - A INTACT GRAY 0.5

2831 FIRST

NORTH 1

CORRIDOR

METAL

FIREHOSE

CLOSET

WEST - D INTACT RED 0.6

2834 FIRST 103

PLASTER

ELECTRICAL

BOX MOUNT

EAST - B

Not Intact-

POOR

WHITE 0.14

2839 FIRST 117

PLASTER

WALL

NORTH - A INTACT WHITE 0.7

2840 FIRST 117

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

WHITE 0.4

2842 FIRST 118

WOOD

WINDOW

CASING

EAST - B INTACT WHITE 0.26

2843 FIRST 118

WOOD

WINDOW SASH

EAST - B INTACT WHITE 0.4

2848 FIRST 115

PLASTER

WALL

WEST - D INTACT WHITE 0.9

©2011, Mabbett & Associates, Inc. Page 9 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2849 FIRST

NORTH 2

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

EAST - B INTACT WHITE 0.4

2851 FIRST

NORTH 2

CORRIDOR

METAL

FIREHOSE

CLOSET

WEST - D INTACT RED 0.4

2852 FIRST

NORTH 2

CORRIDOR

METAL DOOR NORTH - A

Not Intact-

POOR

RED 0.8

2853 FIRST 113 METAL DOOR EAST - B INTACT RED 0.4

2857 FIRST

CORRIDOR

WOOD DOOR

CASING

SOUTH - C

Not Intact-

POOR

GRAY 1.8

2858 FIRST

CORRIDOR

WOOD DOOR

CASING

NORTH - A

Not Intact-

POOR

GRAY 1.6

2861 FIRST 112a

METAL

RADIATOR

NORTH - A INTACT WHITE 0.5

2863 FIRST 112a

WOOD SHELF

SUPPORT

SOUTH - C INTACT WHITE 2.3

2866 FIRST 112B METAL DUCT SOUTH - C INTACT WHITE 0.12

2870 FIRST 112B

METAL AC

UNIT

WEST - D INTACT WHITE 0.3

2872 FIRST 112B

WALLBOARD

WALL

SOUTH - C INTACT WHITE 0.22

2873 FIRST 112B METAL PIPE SOUTH - C INTACT WHITE 0.7

2876 FIRST STAIR 108

METAL STAIR

NEWEL POST

NORTH - A

Not Intact-

POOR

WHITE 11

2877 FIRST STAIR 108

METAL STAIR

HANDRAIL

NORTH - A

Not Intact-

POOR

WHITE 3.9

2878 FIRST STAIR 108

METAL STAIR

BASEBOARD

NORTH - A

Not Intact-

POOR

BLACK 12.8

2879 FIRST STAIR 108

METAL STAIR

RISER

EAST - B

Not Intact-

POOR

BLACK 9.3

2880 FIRST STAIR 108

METAL STAIR

STRINGER

EAST - B INTACT WHITE 7.7

2884 FIRST STAIR 108

PLASTER

CEILING

EAST - B

Not Intact-

POOR

WHITE 0.5

2885 FIRST STAIR 108

PLASTER

CEILING

EAST - B

Not Intact-

POOR

WHITE 6.6

2895 SECOND

EAST

CORRIDOR

PLASTER

WALL

NORTH - A INTACT WHITE 0.3

2901 SECOND

EAST

CORRIDOR

PLASTER

CEILING

NORTH - A INTACT WHITE 0.7

2902 SECOND

EAST

CORRIDOR

METAL

RADIATOR

NORTH - A

Not Intact-

POOR

WHITE 0.3

2904 SECOND

EAST

CORRIDOR

WOOD

WINDOW

CASING

SOUTH - C INTACT WHITE 0.4

2905 SECOND

EAST

CORRIDOR

WOOD

WINDOW SASH

SOUTH - C INTACT WHITE 0.4

2906 SECOND

EAST

CORRIDOR

WOOD DOOR WEST - D INTACT WHITE 0.19

©2011, Mabbett & Associates, Inc. Page 10 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2907 SECOND

EAST

CORRIDOR

METAL DOOR

CASING

WEST - D INTACT WHITE 7.2

2908 SECOND

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

NORTH - A INTACT WHITE 0.29

2909 SECOND

CORRIDOR

PLASTER

WALL

SOUTH - C INTACT WHITE 0.21

2911 SECOND

CORRIDOR

METAL PIPE NORTH - A INTACT WHITE 0.6

2912 SECOND

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

NORTH - A INTACT WHITE 0.3

2914 SECOND

WEST

CORRIDOR

METAL

RADIATOR

SOUTH - C INTACT WHITE 0.4

2915 SECOND

WEST

CORRIDOR

METAL

BASEBOARD

SOUTH - C INTACT BLACK 8.1

2916 SECOND

WEST

CORRIDOR

METAL

BASEBOARD

SOUTH - C

Not Intact-

POOR

BLACK 6.1

2917 SECOND

CORRIDOR

METAL

BASEBOARD

SOUTH - C INTACT BLACK 0.5

2919 SECOND

WEST

CORRIDOR

PLASTER

CEILING

NORTH - A INTACT WHITE 0.6

2920 SECOND

WEST

CORRIDOR

WOOD

WINDOW

CASING

SOUTH - C INTACT WHITE 0.17

2921 SECOND

WEST

CORRIDOR

WOOD

WINDOW SASH

SOUTH - C INTACT WHITE 0.5

2922 SECOND

WEST

CORRIDOR

WOOD

WINDOW JAMB

SOUTH - C INTACT WHITE 0.12

2923 SECOND

WEST

CORRIDOR

WOOD DOOR EAST - B INTACT BLUE 0.18

2924 SECOND

WEST

CORRIDOR

METAL DOOR

CASING

EAST - B INTACT BLUE 6.6

2926 SECOND STAIR 1

METAL

RADIATOR

EAST - B INTACT WHITE 0.7

2928 SECOND STAIR 1 METAL PIPE EAST - B

Not Intact-

POOR

BLACK 1.3

2929 SECOND STAIR 1

METAL

BASEBOARD

EAST - B INTACT BLACK 8.9

2931 SECOND STAIR 1

METAL STAIR

NEWEL POST

WEST - D

Not Intact-

POOR

WHITE 8.7

2932 SECOND STAIR 1

METAL STAIR

BALUSTER

WEST - D

Not Intact-

POOR

WHITE 10

2933 SECOND STAIR 1

METAL STAIR

STRINGER

WEST - D

Not Intact-

POOR

WHITE 9.9

2934 SECOND STAIR 1

METAL STAIR

RISER

WEST - D

Not Intact-

POOR

BLACK 11.5

2935 SECOND STAIR 1

PLASTER

WALL

WEST - D

Not Intact-

POOR

WHITE 0.15

2936 SECOND STAIR 1

METAL STAIR

BASEBOARD

WEST - D

Not Intact-

POOR

BLACK 13.4

©2011, Mabbett & Associates, Inc. Page 11 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2939 SECOND STAIR 1

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 0.5

2940 SECOND STAIR 1

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 0.24

2945 SECOND STAIR 1

PLASTER

WALL

EAST - B INTACT WHITE 0.11

2947 SECOND STAIR 1

METAL STAIR

BASEBOARD

SOUTH - C INTACT BLACK 0.15

2949 SECOND STAIR 1

METAL DOOR

CASING

WEST - D

Not Intact-

POOR

BLUE 3.5

2950 SECOND STAIR 1

METAL STAIR

RISER

WEST - D

Not Intact-

POOR

BLACK 3.6

2951 SECOND

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

EAST - B INTACT RED 0.15

2952 SECOND

CORRIDOR

METAL

RADIATOR

EAST - B INTACT WHITE 0.15

2955 SECOND

CORRIDOR

METAL

BASEBOARD

WEST - D INTACT BLACK 0.22

2956 SECOND

CORRIDOR

PLASTER

WALL

WEST - D INTACT WHITE 0.18

2957 SECOND

CORRIDOR

PLASTER

CEILING

NORTH - A INTACT WHITE 1.2

2958 SECOND

CORRIDOR

WOOD DOOR EAST - B INTACT WHITE 0.3

2959 SECOND

CORRIDOR

METAL DOOR

CASING

EAST - B INTACT BLUE 7.5

2960 SECOND

BATHROOM

WALLBOARD

CEILING

EAST - B INTACT WHITE 0.11

2968 SECOND 246

METAL

RADIATOR

EAST - B INTACT WHITE 0.5

2969 SECOND 246 WOOD DOOR WEST - D INTACT WHITE 0.28

2970 SECOND 246

METAL DOOR

CASING

WEST - D

Not Intact-

POOR

BLUE 8.2

2975 SECOND

CORRIDOR

METAL

BASEBOARD

NORTH - A INTACT BLACK 0.24

2976 SECOND 210

PLASTER

WALL

NORTH - A INTACT WHITE 1.9

2979 SECOND 210 METAL PIPE NORTH - A INTACT WHITE 0.18

2980 SECOND 210

METAL FIRE

SPRINKLER

PIPE

EAST - B INTACT WHITE 1.3

2981 SECOND 210

PLASTER

CEILING

EAST - B INTACT WHITE 1.4

2982 SECOND 210 WOOD DOOR SOUTH - C INTACT WHITE 0.21

2983 SECOND 210

METAL DOOR

CASING

SOUTH - C

Not Intact-

BLUE 4.5

©2011, Mabbett & Associates, Inc. Page 12 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

2984 SECOND 210

METAL FIRE

SPRINKLER

PIPE

WEST - D INTACT WHITE 3

2986 SECOND 210

METAL

LOUVER

SOUTH - C INTACT WHITE 0.8

2987 SECOND

NORTH

CORRIDOR

WALLBOARD

WALL

EAST - B INTACT WHITE 0.24

2989 SECOND

NORTH

CORRIDOR

PLASTER

WALL

EAST - B INTACT WHITE 0.29

2990 SECOND

NORTH

CORRIDOR

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

TAN 0.21

2991 SECOND

NORTH

CORRIDOR

PLASTER

CEILING

SOUTH - C

Not Intact-

POOR

WHITE 0.26

2992 SECOND

NORTH

CORRIDOR

METAL

BASEBOARD

EAST - B

Not Intact-

POOR

BLACK 0.2

2996 SECOND

NORTH

CORRIDOR

METAL

ELECTRICAL

BOX MOUNT

WEST - D INTACT WHITE 0.15

3000 SECOND 212

PLASTER

CEILING

WEST - D

Not Intact-

POOR

YELLOW 0.16

3001 SECOND 212

PLASTER

WALL

WEST - D

Not Intact-

POOR

YELLOW 0.11

3002 SECOND 212

METAL FIRE

SPRINKLER

PIPE

WEST - D

Not Intact-

POOR

BEIGE 0.6

3004 SECOND 212

METAL FIRE

SPRINKLER

PIPE

EAST - B

Not Intact-

POOR

BEIGE 0.4

3005 SECOND 212 WOOD DOOR EAST - B

Not Intact-

POOR

YELLOW 0.16

3008 SECOND

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

NORTH - A

Not Intact-

POOR

RED 0.29

3009 SECOND

CORRIDOR

METAL

RADIATOR

NORTH - A

Not Intact-

POOR

WHITE 0.26

3012 SECOND

SOUTH

CORRIDOR

METAL

ELECTRICAL

BOX MOUNT

NORTH - A INTACT GRAY 0.2

3013 SECOND

CORRIDOR

METAL

ELECTRICAL

BOX MOUNT

NORTH - A INTACT GRAY 0.25

3014 SECOND

CORRIDOR

METAL

ELECTRICAL

BOX MOUNT

SOUTH - C INTACT GRAY 0.16

3021 SECOND 266

WOOD

WINDOW

CASING

SOUTH - C

Not Intact-

POOR

WHITE 3.6

3041 SECOND 278 WOOD DOOR SOUTH - C INTACT WHITE 0.4

3042 SECOND 278 WOOD DOOR WEST - D INTACT WHITE 0.24

3043 SECOND 278

METAL

RADIATOR

NORTH - A INTACT WHITE 0.4

©2011, Mabbett & Associates, Inc. Page 13 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

3045 SECOND 273

WOOD

THRESHOLD

NORTH - A

Not Intact-

POOR

BLACK 0.25

3047 SECOND 273

METAL

RADIATOR

SOUTH - C

Not Intact-

POOR

WHITE 0.5

3048 SECOND

CORRIDOR

METAL

FIREHOSE

CLOSET

WEST - D INTACT RED 0.12

3049 SECOND STAIR 235

METAL STAIR

BASEBOARD

NORTH - A

Not Intact-

POOR

BLACK 11.8

3050 SECOND STAIR 235

METAL STAIR

RISER

EAST - B

Not Intact-

POOR

BLACK 12.4

3051 SECOND STAIR 235

METAL STAIR

HANDRAIL

EAST - B

Not Intact-

POOR

WHITE 4.7

3052 SECOND STAIR 235

METAL STAIR

NEWEL POST

EAST - B

Not Intact-

POOR

WHITE 10.4

3053 SECOND STAIR 235

METAL STAIR

STRINGER

EAST - B

Not Intact-

POOR

WHITE 8.3

3054 SECOND STAIR 235

METAL

CEILING

EAST - B INTACT WHITE 9.7

3055 SECOND STAIR 235 METAL PIPE NORTH - A INTACT WHITE 0.23

3056 SECOND STAIR 235

METAL

RADIATOR

NORTH - A

Not Intact-

POOR

WHITE 0.24

3057 SECOND STAIR 235

METAL

BASEBOARD

WEST - D

Not Intact-

POOR

BLACK 7.2

3059 SECOND 234

METAL

CONDUIT

SOUTH - C INTACT WHITE 0.6

3061 SECOND 234

METAL CHAIR

RAIL

SOUTH - C INTACT WHITE 0.5

4 THIRD STAIR 1

METAL STAIR

BALUSTER

NORTH - A INTACT WHITE 6.9

5 THIRD STAIR 1

METAL STAIR

NEWEL POST

NORTH - A INTACT WHITE 9.5

6 THIRD STAIR 1

METAL STAIR

RISER

EAST - B INTACT BLACK 8.3

7 THIRD STAIR 1

METAL STAIR

BASEBOARD

SOUTH - C INTACT BLACK 5.1

8 THIRD STAIR 1

PLASTER

WALL

WEST - D

Not Intact-

POOR

WHITE 0.4

9 THIRD STAIR 1

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 0.18

16 THIRD STAIR 1 METAL DOOR EAST - B INTACT WHITE 10.9

17 THIRD STAIR 1

METAL DOOR

CASING

EAST - B INTACT GRAY 8.5

26 THIRD

CORRIDOR

PLASTER

WALL

EAST - B INTACT WHITE 0.16

29 THIRD

CORRIDOR

METAL

BASEBOARD

WEST - D INTACT BLACK 2

30 THIRD

CORRIDOR

METAL

EAST - B INTACT WHITE 0.3

©2011, Mabbett & Associates, Inc. Page 14 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

31 THIRD

CORRIDOR

METAL PIPE EAST - B INTACT WHITE 17.8

33 THIRD

CORRIDOR

METAL

FIREHOSE

CLOSET

WEST - D INTACT RED 0.2

34 THIRD

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

SOUTH - C INTACT RED 0.3

35 THIRD

CORRIDOR

PLASTER

WALL

EAST - B INTACT WHITE 0.15

36 THIRD

CORRIDOR

METAL

BASEBOARD

EAST - B INTACT BLACK 2.5

40 THIRD

CORRIDOR

METAL AIR

VENT -

CEILING

SOUTH - C INTACT WHITE 0.4

41 THIRD

CORRIDOR

METAL

RADIATOR

EAST - B INTACT WHITE 0.5

42 THIRD

CORRIDOR

METAL PIPE EAST - B INTACT BLACK 1.3

43 THIRD LOBBY

WOOD CHAIR

RAIL

NORTH - A INTACT WHITE 0.11

44 THIRD LOBBY

PLASTER

WALL

NORTH - A INTACT WHITE 0.6

45 THIRD LOBBY

WOOD CHAIR

RAIL

EAST - B INTACT WHITE 0.15

47 THIRD LOBBY

WOOD CHAIR

RAIL

SOUTH - C INTACT WHITE 0.13

48 THIRD LOBBY

WOOD CHAIR

RAIL

WEST - D INTACT WHITE 0.18

52 THIRD LOBBY

WOOD CROWN

MOLDING

EAST - B INTACT BEIGE 0.13

53 THIRD LOBBY

METAL

BASEBOARD

EAST - B

Not Intact-

POOR

BLACK 9.1

54 THIRD LOBBY

METAL

RADIATOR

NORTH - A INTACT WHITE 0.4

55 THIRD LOBBY METAL PIPE NORTH - A

Not Intact-

POOR

WHITE 5.1

58 THIRD LOBBY

WOOD CLOSET

SHELF

SUPPORT

EAST - B INTACT GREEN 0.24

59 THIRD LOBBY

METAL DOOR

CASING

SOUTH - C INTACT WHITE 10.4

60 THIRD

EAST

CORRIDOR

WOOD

WINDOW

CASING

EAST - B INTACT WHITE 0.17

64 THIRD

EAST

CORRIDOR

WALLBOARD

WALL

SOUTH - C INTACT WHITE 0.18

67 THIRD

EAST

CORRIDOR

WALLBOARD

CEILING

SOUTH - C

Not Intact-

POOR

WHITE 0.16

68 THIRD

EAST

CORRIDOR

METAL

NORTH - A INTACT WHITE 0.6

©2011, Mabbett & Associates, Inc. Page 15 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

69 THIRD

EAST

CORRIDOR

METAL PIPE NORTH - A INTACT WHITE 0.27

70 THIRD

EAST

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

SOUTH - C INTACT RED 0.6

71 THIRD

WEST

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

SOUTH - C INTACT RED 0.5

78 THIRD

WEST

CORRIDOR

WALLBOARD

CEILING

NORTH - A INTACT WHITE 0.7

79 THIRD

WEST

CORRIDOR

METAL

RADIATOR

NORTH - A INTACT WHITE 0.7

80 THIRD

WEST

CORRIDOR

METAL PIPE NORTH - A INTACT WHITE 4

81 THIRD

WEST

CORRIDOR

METAL

BASEBOARD

NORTH - A INTACT BLACK 7.4

82 THIRD

WEST

CORRIDOR

WOOD HATCH EAST - B

Not Intact-

POOR

WHITE 3.4

83 THIRD

WEST

CORRIDOR

WOOD HATCH

CASING

WEST - D INTACT WHITE 2.1

84 THIRD

CORRIDOR

PLASTER

WALL

SOUTH - C INTACT BEIGE 0.25

88 THIRD

CORRIDOR

METAL DOOR SOUTH - C INTACT BLUE 0.8

89 THIRD

CORRIDOR

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

BLUE 2.2

90 THIRD

CORRIDOR

PLASTER

WALL

EAST - B INTACT BEIGE 1.4

91 THIRD

CORRIDOR

WALLBOARD

WALL

WEST - D INTACT BEIGE 1.8

93 THIRD

CORRIDOR

PLASTER

CEILING

WEST - D INTACT BEIGE 1.6

94 THIRD

CORRIDOR

WOOD HATCH EAST - B INTACT WHITE 2.3

95 THIRD

CORRIDOR

METAL HATCH

CASING

EAST - B INTACT WHITE 3

96 THIRD

CORRIDOR

METAL

LADDER

EAST - B

Not Intact-

POOR

GRAY 5.7

97 THIRD

CORRIDOR

METAL AIR

VENT -

CEILING

EAST - B INTACT WHITE 2.7

102 THIRD

CORRIDOR

PLASTER

WALL

SOUTH - C INTACT WHITE 2

103 THIRD

CORRIDOR

WALLBOARD

CEILING

SOUTH - C INTACT WHITE 1.6

104 THIRD

CORRIDOR

PLASTER

WALL

NORTH - A INTACT WHITE 2.1

105 THIRD

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

NORTH - A

Not Intact-

RED 1.2

©2011, Mabbett & Associates, Inc. Page 16 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

106 THIRD

CORRIDOR

METAL

RADIATOR

NORTH - A INTACT WHITE 0.4

107 THIRD

CORRIDOR

METAL PIPE NORTH - A INTACT WHITE 0.21

110 THIRD

CORRIDOR

WOOD

WINDOW

CASING

EAST - B INTACT WHITE 0.16

111 THIRD

CORRIDOR

METAL

RADIATOR

NORTH - A INTACT WHITE 0.27

112 THIRD

CORRIDOR

METAL PIPE NORTH - A INTACT WHITE 0.25

113 THIRD

CORRIDOR

METAL FIRE

EXTINGUISHER

CASING

NORTH - A INTACT RED 0.9

114 THIRD

CORRIDOR

METAL

FIREHOSE

CLOSET

NORTH - A INTACT RED 0.17

117 THIRD 362

PLASTER

CEILING

EAST - B

Not Intact-

POOR

WHITE 1.8

121 THIRD 365

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

WHITE 0.4

122 THIRD 365

PLASTER

WALL

NORTH - A

Not Intact-

POOR

WHITE 1.5

123 THIRD 365

METAL

RADIATOR

NORTH - A

Not Intact-

POOR

WHITE 0.4

124 THIRD 365

METAL CHAIR

RAIL

NORTH - A INTACT WHITE 1.8

125 THIRD 365

WOOD CROWN

MOLDING

SOUTH - C INTACT WHITE 2.1

126 THIRD 365

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

WHITE 8

127 THIRD 360a

METAL DOOR

CASING

EAST - B

Not Intact-

POOR

BLUE 5.9

130 THIRD 360a

WOOD

WINDOW

CASING

WEST - D INTACT WHITE 0.23

131 THIRD 360a

PLASTER

WALL

WEST - D INTACT WHITE 4.1

133 THIRD 360a

PLASTER

COLUMN

SOUTH - C

Not Intact-

POOR

BEIGE 6.2

134 THIRD STAIR 2

METAL

LADDER

NORTH - A

Not Intact-

POOR

BLACK 3.7

139 THIRD STAIR 2

PLASTER

CEILING

WEST - D

Not Intact-

POOR

WHITE 0.11

140 THIRD STAIR 2 WOOD HATCH NORTH - A

Not Intact-

POOR

WHITE 3.9

142 THIRD STAIR 2

METAL HATCH

CASING

NORTH - A

Not Intact-

POOR

WHITE 1.4

143 THIRD STAIR 2

METAL STAIR

HANDRAIL

NORTH - A

Not Intact-

WHITE 7.5

©2011, Mabbett & Associates, Inc. Page 17 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

146 THIRD STAIR 2

METAL STAIR

NEWEL POST

NORTH - A

Not Intact-

POOR

WHITE 7.1

147 THIRD STAIR 2

METAL STAIR

NEWEL POST

SOUTH - C

Not Intact-

POOR

BLACK 9.3

148 THIRD STAIR 2

METAL STAIR

RISER

SOUTH - C

Not Intact-

POOR

BLACK 8.7

149 THIRD STAIR 2

METAL STAIR

STRINGER

EAST - B INTACT WHITE 4.6

150 THIRD STAIR 2

METAL STAIR

STRINGER

WEST - D INTACT WHITE 7.8

152 THIRD STAIR 2 METAL DOOR WEST - D

Not Intact-

POOR

WHITE 0.4

153 THIRD STAIR 2

METAL DOOR

CASING

WEST - D

Not Intact-

POOR

BLUE 7.7

156 THIRD STAIR 2

WOOD

WINDOW

CASING

EAST - B INTACT WHITE 0.21

157 THIRD 360

METAL

COLUMN

SOUTH - C

Not Intact-

POOR

BEIGE 4.6

160 THIRD 359 METAL PIPE EAST - B INTACT WHITE 3.8

161 THIRD 359

METAL

RADIATOR

EAST - B INTACT WHITE 0.5

164 THIRD 306 METAL PIPE NORTH - A INTACT WHITE 0.29

175 THIRD 346 WOOD DOOR WEST - D INTACT WHITE 0.22

177 THIRD 346

WALLBOARD

CEILING

EAST - B INTACT WHITE 0.5

178 THIRD 302

PLASTER

CEILING

WEST - D INTACT WHITE 0.4

179 THIRD 302

WOOD CROWN

MOLDING

NORTH - A INTACT WHITE 0.19

180 THIRD 302

METAL CHAIR

RAIL

NORTH - A INTACT WHITE 0.23

181 THIRD 302 WOOD DOOR EAST - B INTACT WHITE 0.4

182 THIRD 302

WOOD CLOSET

DOOR

SOUTH - C INTACT WHITE 0.21

183 THIRD 302

WOOD CLOSET

SHELF

SUPPORT

SOUTH - C INTACT WHITE 0.22

184 THIRD 347 WOOD DOOR WEST - D INTACT WHITE 0.3

185 THIRD 347

PLASTER

CEILING

SOUTH - C

Not Intact-

POOR

WHITE 0.6

186 THIRD 347

WALLBOARD

CEILING

SOUTH - C

Not Intact-

POOR

WHITE 0.18

187 THIRD 347

METAL CHAIR

RAIL

SOUTH - C

Not Intact-

POOR

WHITE 0.3

188 THIRD 347 WOOD DOOR NORTH - A INTACT WHITE 0.24

189 THIRD 303

METAL CHAIR

RAIL

SOUTH - C INTACT WHITE 0.6

©2011, Mabbett & Associates, Inc. Page 18 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

190 THIRD 303

WOOD HATCH

CASING

SOUTH - C INTACT WHITE 0.4

193 THIRD 303 WOOD DOOR EAST - B INTACT WHITE 0.24

194 THIRD 303

WOOD CLOSET

DOOR

NORTH - A INTACT WHITE 0.11

195 THIRD 303

WOOD CLOSET

SHELF

SUPPORT

NORTH - A INTACT WHITE 0.19

197 THIRD 345 WOOD DOOR WEST - D INTACT WHITE 0.29

199 THIRD 345 WOOD HATCH WEST - D INTACT WHITE 5.6

200 THIRD 345

WOOD HATCH

CASING

WEST - D INTACT WHITE 1.3

205 THIRD ATTIC

METAL

RAILING

NORTH - A

Not Intact-

POOR

GRAY 9.2

206 THIRD ATTIC

METAL

RAILING

NORTH - A

Not Intact-

POOR

GRAY 6.3

207 THIRD ATTIC METAL I-BEAM NORTH - A

Not Intact-

POOR

RED 7.7

208 THIRD ATTIC METAL I-BEAM NORTH - A

Not Intact-

POOR

RED 10.9

209 THIRD ATTIC METAL I-BEAM NORTH - A

Not Intact-

POOR

RED 8.4

210 THIRD ATTIC METAL I-BEAM SOUTH - C

Not Intact-

POOR

RED 8.3

211 THIRD ATTIC METAL I-BEAM SOUTH - C

Not Intact-

POOR

RED 8.4

212 THIRD ATTIC METAL I-BEAM SOUTH - C

Not Intact-

POOR

RED 6.8

224 THIRD ATTIC

METAL

FIREHOSE

CLOSET

NORTH - A

Not Intact-

POOR

YELLOW 0.23

231 THIRD ATTIC

METAL

ELECTRICAL

BOX MOUNT

WEST - D INTACT GRAY 0.29

235 THIRD ATTIC METAL MOTOR WEST - D INTACT TAN 0.19

237 BASEMENT B-32

METAL DOOR

CASING

EAST - B

Not Intact-

POOR

GRAY 9.7

243 BASEMENT B-32 METAL POLE NORTH - A INTACT RED 0.9

244 BASEMENT B-32 METAL POLE NORTH - A INTACT RED 0.2

245 BASEMENT B-32 METAL POLE SOUTH - C INTACT RED 0.6

246 BASEMENT B-32 METAL BEAM SOUTH - C INTACT RED 0.9

247 BASEMENT B-32 METAL BEAM WEST - D INTACT RED 0.5

248 BASEMENT B-32 METAL BEAM WEST - D INTACT RED 0.24

252 BASEMENT B-18 METAL POLE WEST - D

Not Intact-

POOR

WHITE 0.15

253 BASEMENT B-18 METAL BEAM WEST - D

Not Intact-

WHITE 0.14

©2011, Mabbett & Associates, Inc. Page 19 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

257 BASEMENT B-18 WOOD DOOR SOUTH - C

Not Intact-

POOR

GREEN 4

258 BASEMENT B-18

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

GREEN 2.2

259 BASEMENT B-18 METAL PIPE SOUTH - C

Not Intact-

POOR

WHITE 0.3

265 BASEMENT B-18

METAL

RAILING

SOUTH - C

Not Intact-

POOR

BLACK 0.9

271 BASEMENT B-18

WOOD

WINDOW SASH

NORTH - A

Not Intact-

POOR

GREEN 8.6

273 BASEMENT B-18

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

GREEN 1.3

275 BASEMENT B-15

WOOD

FIREHOSE

CLOSET

NORTH - A

Not Intact-

POOR

RED 0.21

281 BASEMENT B-15

METAL

ELECTRICAL

BOX MOUNT

NORTH - A

Not Intact-

POOR

GRAY 0.17

283 BASEMENT B-15

METAL

CONDUIT

SOUTH - C

Not Intact-

POOR

WHITE 0.5

284 BASEMENT B-15 METAL DOOR NORTH - A INTACT GRAY 0.17

287 BASEMENT B-31 METAL POLE SOUTH - C INTACT RED 0.5

288 BASEMENT B-31 METAL POLE SOUTH - C INTACT RED 0.6

289 BASEMENT B-31 METAL POLE SOUTH - C INTACT RED 0.6

292 BASEMENT B-31 METAL BEAM SOUTH - C INTACT RED 0.6

293 BASEMENT B-31 METAL BEAM SOUTH - C INTACT RED 0.8

294 BASEMENT B-31 METAL BEAM SOUTH - C INTACT RED 0.6

296 BASEMENT B-31

METAL DOOR

CASING

WEST - D

Not Intact-

POOR

GRAY 4.6

297 BASEMENT B-31

WOOD

WINDOW SASH

NORTH - A

Not Intact-

POOR

GRAY 5.9

298 BASEMENT B-31

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

GRAY 6.8

306 BASEMENT B-31

PLASTER

WALL

NORTH - A

Not Intact-

POOR

GRAY 0.14

310 BASEMENT B-14

WOOD

WINDOW SASH

NORTH - A

Not Intact-

POOR

WHITE 5.9

311 BASEMENT B-14

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

WHITE 7.5

313 BASEMENT B-14

PLASTER

CEILING

NORTH - A

Not Intact-

POOR

WHITE 0.7

315 BASEMENT B-14

METAL

CONDUIT

NORTH - A

Not Intact-

POOR

WHITE 0.7

323 BASEMENT B-14 METAL PIPE SOUTH - C

Not Intact-

WHITE 0.9

©2011, Mabbett & Associates, Inc. Page 20 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

325 BASEMENT B-14 METAL POLE SOUTH - C

Not Intact-

POOR

WHITE 0.21

326 BASEMENT B-14 METAL POLE SOUTH - C

Not Intact-

POOR

WHITE 0.25

329 BASEMENT

MEN’S

TOILET 1

WOOD DOOR SOUTH - C

Not Intact-

POOR

GRAY 0.23

330 BASEMENT

MEN’S

TOILET 1

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

GRAY 0.6

331 BASEMENT B-13

METAL FIRE

EXTINGUISHER

CASING

WEST - D INTACT RED 0.4

332 BASEMENT B-13 METAL I-BEAM SOUTH - C

Not Intact-

POOR

WHITE 0.12

333 BASEMENT B-13 METAL DOOR WEST - D

Not Intact-

POOR

BLACK 2.1

334 BASEMENT B-13

METAL DOOR

CASING

WEST - D

Not Intact-

POOR

BLACK 1.4

335 BASEMENT B-13

METAL DOOR

CASING

WEST - D INTACT BEIGE 12.8

336 BASEMENT B-13 METAL DOOR WEST - D

Not Intact-

POOR

BLACK 2.1

338 BASEMENT B-31

METAL DOOR

CASING

WEST - D

Not Intact-

POOR

TAN 3.2

342 BASEMENT B-31

WOOD

WINDOW SASH

EAST - B

Not Intact-

POOR

TAN 0.21

343 BASEMENT B-31

WOOD

WINDOW

CASING

EAST - B

Not Intact-

POOR

TAN 4.7

344 BASEMENT B-31

PLASTER

WALL

WEST - D

Not Intact-

POOR

TAN 0.22

358 BASEMENT B-10

METAL FIRE

SPRINKLER

PIPE

NORTH - A INTACT RED 0.3

362 BASEMENT

FEMALE

TOILET B-22

METAL BUS

BOX

EAST - B INTACT GRAY 1.7

363 BASEMENT B-23

CONCRETE

COLUMN

NORTH - A INTACT WHITE 0.16

364 BASEMENT B-23 WOOD DOOR EAST - B INTACT WHITE 0.5

366 BASEMENT B-23

WOOD

WINDOW

CASING

EAST - B INTACT WHITE 8.1

367 BASEMENT B-23

METAL STAIR

NEWEL POST

EAST - B INTACT GRAY 4.1

368 BASEMENT B-23

METAL STAIR

RISER

WEST - D INTACT GRAY 3.5

369 BASEMENT B-23

METAL STAIR

STRINGER

SOUTH - C INTACT GRAY 4.1

370 BASEMENT B-23 METAL I-BEAM SOUTH - C INTACT WHITE 8.3

372 BASEMENT B-23

CONCRETE

WALL

NORTH - A

Not Intact-

WHITE 0.3

©2011, Mabbett & Associates, Inc. Page 21 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

373 BASEMENT B-9

METAL

RADIATOR

WEST - D INTACT BROWN 0.4

374 BASEMENT B-9

METAL DOOR

CASING

EAST - B

Not Intact-

POOR

GRAY 7.8

376 BASEMENT

CORRDIDOR

B-4

METAL FIRE

EXTINGUISHER

CASING

WEST - D INTACT RED 0.3

378 BASEMENT

CORRDIDOR

B-4

WOOD

FIREHOSE

CLOSET

WEST - D INTACT RED 0.25

382 BASEMENT

CORRDIDOR

B-4

BRICK WALL SOUTH - C

Not Intact-

POOR

WHITE 0.2

384 BASEMENT B-6 WOOD DOOR SOUTH - C

Not Intact-

POOR

GRAY 0.5

385 BASEMENT B-6

METAL DOOR

CASING

SOUTH - C

Not Intact-

POOR

GRAY 1.9

386 BASEMENT

CORRDIDOR

B-4

WOOD

FIREHOSE

CLOSET

WEST - D INTACT RED 0.11

387 BASEMENT

CORRDIDOR

B-4

METAL FIRE

EXTINGUISHER

CASING

EAST - B INTACT RED 0.3

390 BASEMENT B-6

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 0.3

391 BASEMENT B-6

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 0.25

392 BASEMENT B-7

WOOD

WINDOW SASH

NORTH - A

Not Intact-

POOR

BLUE 10

393 BASEMENT B-7

WOOD

WINDOW SASH

NORTH - A

Not Intact-

POOR

BLUE 14

395 BASEMENT B-7

METAL

COLUMN

WEST - D

Not Intact-

POOR

GREEN 0.4

396 BASEMENT B-6

CONCRETE

WALL

EAST - B

Not Intact-

POOR

WHITE 2.7

397 BASEMENT STAIR B-1

METAL STAIR

NEWEL POST

SOUTH - C

Not Intact-

POOR

WHITE 2.9

398 BASEMENT STAIR B-1

METAL

RAILING

SOUTH - C

Not Intact-

POOR

WHITE 10.8

399 BASEMENT STAIR B-1

METAL STAIR

RISER

SOUTH - C

Not Intact-

POOR

BLACK 0.3

400 BASEMENT STAIR B-1

METAL STAIR

STRINGER

SOUTH - C INTACT WHITE 11.8

401 BASEMENT STAIR B-1

CONCRETE

WALL

NORTH - A

Not Intact-

POOR

WHITE 6.1

403 BASEMENT STAIR B-1

METAL

RADIATOR

WEST - D INTACT WHITE 0.17

405 FIRST EXTERIOR

WOOD DOOR

CASING

SOUTH - C INTACT GRAY 17.3

406 FIRST EXTERIOR

WOOD

AWNING

SOUTH - C

Not Intact-

WHITE 8.2

©2011, Mabbett & Associates, Inc. Page 22 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

413 FIRST EXTERIOR

METAL DOWN

SPOUT

SOUTH - C

Not Intact-

POOR

GRAY 0.12

414 FIRST EXTERIOR

METAL

RAILING

SOUTH - C INTACT BLACK 11.2

418 FIRST EXTERIOR

WOOD DOOR

CASING

SOUTH - C

Not Intact-

POOR

WHITE 8.5

419 FIRST EXTERIOR

METAL

RAILING

SOUTH - C

Not Intact-

POOR

BLACK 6.1

421 FIRST EXTERIOR

WOOD

WINDOW

CASING

SOUTH - C

Not Intact-

POOR

WHITE 0.5

424 FIRST EXTERIOR

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 8.7

430 FIRST EXTERIOR

WOOD DOOR

CASING

EAST - B INTACT WHITE 15.9

434 FIRST EXTERIOR

CONCRETE

WALK STRIPE

EAST - B

Not Intact-

POOR

YELLOW 0.5

435 FIRST EXTERIOR

METAL LAMP

POST

EAST - B INTACT BLACK 14.4

436 FIRST EXTERIOR

METAL LAMP

POST

EAST - B INTACT BLACK 16.7

452 FIRST EXTERIOR

WOOD

WINDOW

CASING

SOUTH - C

Not Intact-

POOR

WHITE 12.4

453 FIRST EXTERIOR

METAL AC

UNIT

EAST - B

Not Intact-

POOR

TAN 0.11

458 FIRST EXTERIOR

METAL DOWN

SPOUT

EAST - B

Not Intact-

POOR

GRAY 0.22

460 FIRST EXTERIOR

METAL

WINDOW

CASING

NORTH - A INTACT WHITE 0.22

461 FIRST EXTERIOR

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

WHITE 18.6

463 FIRST EXTERIOR

METAL DOWN

SPOUT

NORTH - A

Not Intact-

POOR

BLACK 8

464 FIRST EXTERIOR

METAL DOWN

SPOUT

WEST - D

Not Intact-

POOR

BLACK 5.3

467 FIRST EXTERIOR

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 22.8

468 FIRST EXTERIOR

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 23.2

469 FIRST EXTERIOR

WOOD

WINDOW WELL

WEST - D

Not Intact-

POOR

WHITE 1.5

470 FIRST EXTERIOR

WOOD

WINDOW JAMB

WEST - D

Not Intact-

WHITE 17.6

©2011, Mabbett & Associates, Inc. Page 23 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

471 FIRST EXTERIOR

METAL

WINDOW

SECURITY

GATE

WEST - D

Not Intact-

POOR

WHITE 3

472 FIRST EXTERIOR

METAL

WINDOW

SECURITY

GATE

WEST - D

Not Intact-

POOR

WHITE 2.9

473 FIRST EXTERIOR

METAL

WINDOW

SECURITY

GATE

WEST - D

Not Intact-

POOR

WHITE 9.6

474 FIRST EXTERIOR

METAL

WINDOW

SECURITY

GATE

WEST - D

Not Intact-

POOR

WHITE 3.1

475 FIRST EXTERIOR

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 22.9

476 FIRST EXTERIOR

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 19.8

477 FIRST EXTERIOR

WOOD

WINDOW SASH

WEST - D

Not Intact-

POOR

WHITE 20.2

478 FIRST EXTERIOR

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 25.4

479 FIRST EXTERIOR

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 25.7

480 FIRST EXTERIOR

WOOD

WINDOW

CASING

WEST - D

Not Intact-

POOR

WHITE 23.7

481 FIRST EXTERIOR

WOOD

WINDOW WELL

WEST - D

Not Intact-

POOR

WHITE 0.8

482 FIRST EXTERIOR

WOOD

WINDOW WELL

WEST - D

Not Intact-

POOR

WHITE 17.3

483 FIRST EXTERIOR

WOOD

WINDOW WELL

WEST - D

Not Intact-

POOR

WHITE 3.3

484 FIRST EXTERIOR

WOOD

WINDOW WELL

WEST - D

Not Intact-

POOR

WHITE 0.8

485 FIRST EXTERIOR

WOOD

WINDOW JAMB

WEST - D

Not Intact-

POOR

WHITE 18

486 FIRST EXTERIOR

WOOD

WINDOW JAMB

WEST - D

Not Intact-

POOR

WHITE 17

487 FIRST EXTERIOR

WOOD

WINDOW JAMB

WEST - D

Not Intact-

POOR

WHITE 17.5

490 FIRST EXTERIOR

METAL FIRE

HYDRANT

WEST - D

Not Intact-

POOR

RED 18.8

493 FIRST EXTERIOR

CONCRETE

CURB

NORTH - A

Not Intact-

YELLOW 1.6

©2011, Mabbett & Associates, Inc. Page 24 of 26 West Haven Building 5 Rpt Final 9-16-11.doc

Reading No.

Floor Location Substrate and Component

Side Condition Color Results

(mg/cm2)

498 FIRST EXTERIOR

WOOD

WINDOW

CASING

NORTH - A

Not Intact-

POOR

WHITE 18.8

499 FIRST EXTERIOR

WOOD

WINDOW SASH

NORTH - A

Not Intact-

POOR

WHITE 24.2

503 BASEMENT EXTERIOR

METAL DOOR

CASING

NORTH - A INTACT GRAY 6.4

504 BASEMENT EXTERIOR

METAL DOOR

LINTEL

NORTH - A

Not Intact-

POOR

WHITE 7.2

509 BASEMENT EXTERIOR METAL DOOR EAST - B

Not Intact-

POOR

GREEN 3.5

510 BASEMENT EXTERIOR

METAL DOOR

CASING

EAST - B

Not Intact-

POOR

GREEN 0.25

511 FIRST EXTERIOR

WOOD

WINDOW SASH

EAST - B

Not Intact-

POOR

WHITE 24.6

512 FIRST EXTERIOR

WOOD

WINDOW SASH

EAST - B

Not Intact-

POOR

WHITE 1.7

513 FIRST EXTERIOR METAL GRATE EAST - B

Not Intact-

POOR

BLACK 4.2

514 FIRST EXTERIOR

METAL DOWN

SPOUT

EAST - B

Not Intact-

POOR

BLACK 1.7

517 FIRST EXTERIOR

WOOD DOOR

CASING

EAST - B

Not Intact-

POOR

GRAY 2

521 BASEMENT EXTERIOR

METAL

WINDOW

SECURITY

GATE

EAST - B

Not Intact-

POOR

WHITE 0.26

526 FIRST EXTERIOR

METAL FIRE

HYDRANT

EAST - B

Not Intact-

POOR

RED 15.8

528 FIRST EXTERIOR

METAL LAMP

POST

EAST - B

Not Intact-

GRAY 0.3

In addition, all other XRF measurements collected during the screening survey of interior and exterior building components are included in Table 5 – Summary of XRF Measurements.

Table 5 includes a description of each screened surface and resulting XRF-measured lead concentration.

4.2.2 Photographs

Representative photographs of building materials greater than or equal to 1.0 mg/cm2 and in non-intact condition (e.g. fair, peeling, cracking) are provided in Appendix D of this report.

4.2.3 CADD Drawings

Based on the results of the lead screening survey, a table of LCP components identified with >0.1 mg/cm2 was developed. This table is presented on the CADD drawings for use by the VAMC for exposure assessments and preliminary renovation planning. Based on the results

©2011, Mabbett & Associates, Inc. Page 25 of 26 West Haven Building 5 Rpt Final 9-16-11.doc of the survey, these components identified in the CADD table and on the plan should be assumed to be LCP unless otherwise determined.

5.0 LIMITATIONS

This inspection report is the result of a diligent search of the building for ACM and LCP. Only accessible areas were included in this survey. Although a comprehensive inspection was performed, the M&A Team does not claim to have identified all of the ACM and LCP that could be present in the facility (for example, materials potentially located within aforementioned inaccessible areas in Section 3.1). M&A’s survey was performed with limitations inherent to visual inspections. M&A has conducted this assessment with reasonable care and has performed this project within generally accepted industry standards. There can be no assurances, and M&A makes no assurances, that the information, research, and technology used to prepare this report may not change in the future, thus affecting the results reported herein.

6.0 CLOSING REMARKS

Prior to initiating plans for maintenance, renovation or demolition activities, the VAMC should review the asbestos and lead survey results to determine whether any of the materials identified as ACM or LCP will be disturbed by proposed work activities.

6.1 Asbestos

The purpose of the ACM survey was to identify ACM in the building within the limitations of the survey for worker protection purposes and future renovation or demolition planning purposes.

In regard to asbestos, any suspect material encountered during renovation/demolition that is not identified in this report as being non-ACM should be assumed to be ACM unless laboratory analytical data for bulk samples prove otherwise. Suspect ACM that may be present within the walls, above inaccessible hard ceilings, or in other inaccessible locations, and that accordingly was not inspected, should be assumed to contain asbestos if discovered until otherwise verified, as previously described. If ACM must be disturbed, the ACM must be removed by a licensed asbestos abatement contractor and be performed in accordance with applicable regulations. If proposed work activities will not disturb intact ACM, continuous monitoring of ACM should be conducted throughout work activities to ensure the ACM remains in an intact condition. Additionally, prior to commencing work activities, personnel involved with the work activities should be made aware of the location of ACM within the building in which they will be working. Additional information regarding asbestos management and the Operations & Maintenance (O&M) program is outlined in the VAMC campus-wide Asbestos O&M Management Plan available in Volume I of the Comprehensive VAMC Lead and Asbestos Survey Report.

6.2 Lead Containing Paint

The purpose of the LCP screening survey was to identify patterns of LCP. For the purpose of this LCP screening survey, representative interior and exterior building components were

©2011, Mabbett & Associates, Inc. Page 26 of 26 West Haven Building 5 Rpt Final 9-16-11.doc tested. The regulations addressing LCP in non-residential building are focused on protecting workers involved with paint-disturbing activities and related waste-disposal activities.

Worker protection is regulated by OSHA regulations as well as applicable state regulations.

These regulations involve air monitoring of workers to determine exposure levels when disturbing paint…