S02 Solicitation Attachment B Drawings.pdf
PDF 37 MB Posted
- Attached to
- Install Dedicated Fire Suppression Water Distribution System & Replace Potable Water Lines for North Campus Federal contract opportunity
- Solicitation number
- 36C26222B0007
About this file
This solicitation seeks proposals for a project to install a dedicated fire suppression water distribution system and replace potable water lines for the north campus at the VA Greater Los Angeles Healthcare System located in Los Angeles, California. Work will include general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The contractor will furnish all supervision, tools, labor, training, materials, equipment, and transportation to complete the project in accordance with the solicitation terms, specifications, drawings, and applicable local and VA building codes. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 is the issuing agency.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 0003 Solicitation 36C26222B0007.pdf | ||
| Amendment 0002 Attachment 1 RFI Log.pdf | ||
| Amendment 0002 Solicitation 36C26222B0007.pdf | ||
| Amendment 0001 Attachment 2 Traffic Control Plan.pdf | ||
| Amendment 0001 Attachment 3 Revised Plans.pdf | ||
| Amendment 0001 Solicitation 36C26222B0007.pdf | ||
| Amendment 0001 Attachment 1 RFI Log.pdf | ||
| S02 Solicitation Attachment E GLA Specific Requirements.pdf | ||
| S02 Solicitation 36C26222B0007.pdf | ||
| S02 Solicitation Attachment C Wage Determination.pdf | ||
| S02 Solicitation Attachment D Temporary Traffic Control Standards.pdf | ||
| S02 Solicitation Attachment A Specifications.pdf | ||
| S02 Solicitation Attachment E GLA Specific Requirements.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GRANT AVE
DE
W
EY
A
VE
GORHAM AVE
MACARTHUR AVE
EISENHOWER AVE
BRINGHAM AVE
MONTANA AV
CASHMERE ST
CHURCH LNBERWICK ST
CHENAULT STBELOIT AV
BARRINGTON PL
HEROES GOLF
COURSE
PATTON AVE
BONSALL AVE
BONSALL AVE
ARNOLD AVE
VANDERGRIFT AVE
NIMITZ AVETE
RRYHILL
PL
CHENAULT ST
PA
TT
ON
A
VE
CONSTITUTION AVE
PERSHING AVE
MACARTHUR
FIELD
MA
CA
RT
HU
R
AV
E
LOT 38
WILSHIRE BLVD
BONSALL AVE
S. SEPULVEDA BLVD.
PRIVATE ROAD
CONSTRUCTION PLANS FOR
WEST LOS ANGELES MEDICAL CENTER
VA GREATER LOS ANGELES HEALTH CARE SYSTEM
INSTALL DEDICATED FIRE SUPPRESSION WATER DISTRIBUTION SYSTEM
AND REPLACE POTABLE WATER LINES FOR GLA NORTH CAMPUS
VA PROJECT NO. 691-21-120
PACKAGE 1
JULY 2022
IMPORTANT NOTICE:
SECTION 4216/4217 OF THE GEVERNMENT
CODE REQUIRES A DIGALERT IDENTIFICAITON
NUMBER BE ISSUED BEFORE A "PERMIT TO
EXCAVATE" WILL BE VALID. FOR YOUR
DIGALERT I.D. NUMBER CALL UNDERGROUND
SERVICE ALERT TOLL FREE 1-800-227-2600 TWO
WORKING DAYS BEFORE YOU DIG.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\T B\
VA
SH
EE
T3
0X
D
AR
KE
R S
C R
EE
N
S (L
O N
G T
ER
M
).D W
G 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1
PROJECTSITE
LOCATION MAP
NOT TO SCALE
TITLE SHEET, LOCATION MAP, AND
VICINITY MAP
GI-101
VICINITY MAP
NOT TO SCALE
BONSALLPRV SITE
PERSHING/DEWEYPRV SITE
PROJECTPIPELINE(TYP)
PROJECT TANK SITE & LADWPCONNECTION SITE
UPPER PRESSURE ZONELADWP CONNECTION SITE
MOTORIZED ROLLING GATE.
PRIVATE VA ACCESS TO TANK SITE
(CODE IS REQUIRED).
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
\\P
PR
O D
.P
SO
M
AS
.C O
R P\
PA
N
ZU
R
AP
R
O
JE
C
TS
\O C
_P R
O
JE
C
TS
\V A-
W
LA
\G
LA
_P R
O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N \S
H
EE
TS
\6
-2
1-
(L
O N
G T
ER
M
N
PD
)\L
O N
G T
ER
M
P
AC
KA
G
E 1\
VA
W
LA
-G
I-1
.D W
G 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1GENERAL NOTES, ABBREVIATIONS,
STANDARD SYMBOLS,PROJECT TEAMS, AND
SHEET INDEX
GI-102
ASBESTOS CEMENT PIPE
ASPHALT CONCRETE
AGGREGATE BASE
BUTTERFLY VALVE
CAST IRON PIPE
CONCRETE CYLINDER PIPE
CATCH BASIN
CEMENT MORTAR LINING
CEMENT MORTAR COATING
CLEAN OUT (SEWER)
DUCTILE IRON PIPE
DUCTILE IRON
CEMENT MORTAR LINED & COATED
FIRE HYDRANT
FINISHED SURFACE
FINISHED FLOOR
GRADE BREAK
INTERSECTION
INSIDE DIAMETER
HOR (HORIZ)
ID
INV
INT
IRR
GV
GB
GALV
GA
IRRIGATION
INVERT
GATE VALVE
GALVANIZED
GAUGE
HORIZONTAL
CIP
EXIST (EX)
FH
FLG
FF
FS
E
EL, ELEV
FLANGE
EAST
EXISTING
ELEVATION
CML&C
(CL)LC
DI
DIA OR Ø
DTL
DIP
DWG
CMC
CML
CL
CO
CONT
CONC
DETAIL
DIAMETER
CENTERLINE
DRAWING
CLASS
CONTINUOUS
CONCRETE
ABAND
BFV
CCP
CB
CI
AB
AC
ACP
BEG
CAST IRON
BEGIN
ABANDONED
X
WJ
WM
THK
TC
TS
VERT
UG
W
WELDED JOINTS
WATER METER
BY
TRAFFIC SIGNAL
VERTICAL
UNDERGROUND
THICK
TOP OF CURB
WEST
SHT
SD
SCH
STD
STL
STA
SS
REQ'D
S
RWV
R/W
PP
RAD
R (RAD)
PVMT
PVC
RCP
OD
(P/L) PL
PCC
PE
RESILIENT WEDGE VALVE
STAINLESS STEEL OR SANITARY SEWER
SOUTH, SLOPE OR GRADIENT OF PIPELINE
SHEET
STORM DRAIN
SCHEDULE
STANDARD
STEEL
STATION
RIGHT-OF-WAY
REQUIRED
OUTSIDE DIAMETER
POLYVINYL CHLORIDE
POINT OF COMPUND CURVE
REINFORCED CONCRETE PIPE
POWER POLE
RADIAL
RADIUS
PAVEMENT
PROPERTY LINE
PLAIN END
N
MJ
MIN
MH
NTS
LAT
MECHANICAL JOINT
NORTH
NOT TO SCALE
MINIMUM
MANHOLE
LATERAL
SCCP STEEL CONCRETE CYLINDER PIPE
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
TOP TOP OF PAD
TOC TOP OF CONCRETE
AMERICANS WITH DISABILITIES ACT ADA
1. THE FOLLOWING GENERAL NOTES APPLY TO THE ENTIRE SET OF
DRAWINGS LISTED BY THE “SHEET INDEX”.
2. FOR GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS APPLICABLE
ONLY TO THE DRAWINGS OF ONE DISCIPLINE, REFER TO THE
DRAWINGS OF THAT DISCIPLINE – SEE “SHEET INDEX”.
3. THE COMPLETE SET OF DRAWINGS CONSIST OF ALL DRAWINGS
LISTED BY THE “SHEET INDEX”. THE WORK DESCRIBED IN ONE SHEET
MAY BE REFERENCED AND MAY BE AFFECTED BY WORK DESCRIBED
ON ANOTHER SHEET. THE WORK DESCRIBED IN ONE DISCIPLINE MAY
BE REFERENCED AND AFFECTED BY WORK OF ANOTHER DISCIPLINE.
PARTIAL SETS OF DRAWINGS ARE INCOMPLETE AND SHOULD NOT BE
REDISTRIBUTED OR UTILIZED BY THE THE CONTRACTOR.
4. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW AND
COORDINATE THE WORK OF ALL SUBCONTRACTORS, TRADES AND
SUPPLIERS WITH REQUIREMENTS OF THE CONTRACT DOCUMENTS
BEFORE COMMENCING CONSTRUCTION, AND TO ASSURE THAT ALL
PARTIES ARE AWARE OF ALL REQUIREMENTS, REGARDLESS OF
WHERE THE REQUIREMENTS OCCUR IN THE CONTRACT DOCUMENTS,
WHICH MIGHT AFFECT THE WORK OF THAT PARTY.
5. ALL PARTS OF THE WORK – INCLUDING MATERIALS, METHODS,
ASSEMBLIES, ETC – SHALL COMPLY WITH ALL APPLICABLE
GOVERNING RULES, CODES, REGULATIONS, ORDINANCES, AND LAWS
OF ALL FEDERAL, STATE DISTRICT, TERRITORIAL AND LOCAL
GOVERNMENT AUTHORITIES HAVING JURISDICTION OVER THE
DESIGN, CONSTRUCTION, AND OCCUPANCY OF THE PROJECT,
WHETHER LISTED BY THE CONTRACT DOCUMENTS OR NOT.
6. NO PART OF THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO
REQUIRE OR PERMIT WORK CONTRARY TO AN APPLICABLE
GOVERNING RULE, CODE, REGULATION, ORDINANCE, OR LAW.
7. IF A CONFLICT EXISTS BETWEEN THE CONTRACT DOCUMENTS AND A
REGULATORY REQUIREMENT, THE CONTRACTOR SHALL COMPLY
WITH THE ONE ESTABLISHING THE MORE STRINGENT OR RESTRICTIVE
REQUIREMENT:
7.1. THE DRAWINGS AND SPECIFICATIONS MAY SET FORTH MORE
DETAILED, MORE SPECIFIC, AND/OR MORE RESTRICTIVE
REQUIREMENTS THAN THOSE SET FORTH BY THE APPLICABLE
REGULATORY REQUIREMENTS, WHERE THE DRAWINGS AND
SPECIFICATIONS PROVIDE MORE DETAILED, MORE SPECIFIC,
AND/OR MORE RESTRICTIVE REQUIREMENTS, THE CONTRACTOR
SHALL COMPLY WITH THOSE REQUIREMENTS.
7.2. WHERE THE APPLICABLE REQUIREMENTS OF THE REFERENCED
RULES, CODES, REGULATIONS, ORDINANCES, OR LAWS ARE MORE
RESTRICTIVE THAN THAT SET FORTH BY THE DRAWINGS AND
SPECIFICATION, THE CONTRACTOR SHALL COMPLY WITH ALL SUCH
MORE RESTRICTIVE REQUIREMENTS. ALTHOUGH SUCH
REQUIREMENTS MAY NOT BE ILLUSTRATED BY THE DRAWINGS AND
SPECIFICATIONS.
8. APPLICABLE PORTIONS OF THE CODES, REGULATIONS, AND
STANDARDS LISTED HERE ARE INCORPORATED BY REFERENCE INTO
THE REQUIREMENTS OF THIS CONTRACT AND ESTABLISH MINIMUM
REQUIREMENTS WITH WHICH THE WORK MUST COMPLY.
9. PROPRIETARY PRODUCTS OR ASSEMBLIES UTILIZED AS “BASIS OF
DESIGN”.
9.1. ON OCCASION, THE DRAWINGS MAY REFER TO A SINGLE
PROPRIETARY PRODUCT OR ASSEMBLY WHILE THE SPECIFICATIONS
LIST TWO OR MORE ACCEPTABLE MANUFACTURERS AND/OR
PRODUCTS, WHEN THIS OCCURS, THE PRODUCT OR ASSEMBLY
ILLUSTRATED BY THE DRAWINGS IS THE “BASIS OF DESIGN”
PRODUCT OR ASSEMBLY.
9.2. THE DIMENSIONS, MOUNTING HEIGHTS, CLEARANCES, AND ACCESS
REQUIREMENTS OF SPECIFIED PRODUCTS AND ASSEMBLIES OTHER
THAN THE “BASIS OF DESIGN” MAY VARY FROM THAT SHOWN BY THE
DRAWINGS.
9.3. THE CONTRACTOR MAY UTILIZE ANY OTHER SPECIFIED PRODUCT
OR ASSEMBLY IN LIEU OF THE “BASIS OF DESIGN” PRODUCT OR
ASSEMBLY. HOWEVER, THE CONTRACTOR IS RESPONSIBLE (AT NO
ADDITIONAL EXPENSE TO THE OWNER) FOR ALL COORDINATION AND
REVISIONS TO DIMENSIONS AND/OR DETAILS NECESSARY TO
ACHIEVE THE SAME FUNCTIONAL AND AESTHETIC DESIGN INTENT AS
ILLUSTRATED BY THE “BASIS OF DESIGN” SHOWN BY THE CONTRACT
DOCUMENTS.
10. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS PRIOR TO THE START OF WORK AND SHALL NOTIFY THE
OWNER’S REPRESENTATIVE OF ANY DISCREPANCIES PRIOR TO
PROCEEDING WITH THE WORK.
11. THE CONTRACTOR IS HEREBY NOTIFIED THAT ESSENTIAL AND
PERTINENT INFORMATION REGARDING THE CONSTRUCTION AND
COMPLETION OF WORK FOR THIS PROJECT IS CONTAINED IN THE
CONTRACT DOCUMENTS AND SPECIFICATIONS. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO READ AND REVIEW THIS
INFORMATION TO HIS OWN SATISFACTION PRIOR TO PERFORMING
ANY WORK. ANY DEFICIENT, INCOMPLETE, OR INCORRECT WORK
SHALL BE REDONE TO MEET THE REQUIREMENTS AT THE
CONTRACTOR'S SOLE EXPENSE.
12. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE TO ENSURE THE
PROJECT IS CONSTRUCTED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS. IF THERE IS ANY QUESTION REGARDING THE
CONTRACT DOCUMENTS, THE CONTRACTOR SHALL REQUEST AN
INTERPRETATION BEFORE DOING ANY WORK.
13. THE CONTRACTOR SHALL HAVE A COPY OF THE CONTRACT
DOCUMENTS AND CONSTRUCTION PLANS ON THE JOB AT ALL TIMES.
14. THE VA INSPECTION REPRESENTATIVE, SHALL BE NOTIFIED AT LEAST
TWO (2) WORKING DAYS PRIOR TO BEGINNING CONSTRUCTION AND
OF ANY REQUIRED OBSERVATION. NO FACILITIES SHALL BE
BACKFILLED UNTIL INSPECTED BY THE VA. STANDARD WORKING
HOURS FOR VA INSPECTION/OPERATIONS PERSONNEL ARE 7:00 a.m.
TO 5:00 p.m. MONDAY THROUGH FRIDAY, EXCLUDING HOLIDAYS.
15. NEITHER THE OWNER NOR THE ENGINEER OF WORK WILL ENFORCE
SAFETY MEASURES OR REGULATIONS. THE CONTRACTOR SHALL
DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES, INCLUDING
SHORING, AND SHALL BE SOLELY RESPONSIBLE FOR CONFORMING
TO ALL LOCAL, STATE AND FEDERAL SAFETY AND HEALTH
STANDARDS, LAWS AND REGULATIONS.
16. THE WALL AND FACE OF ALL EXCAVATIONS FIVE (5) FEET OR
GREATER IN DEPTH SHALL BE EFFECTIVELY GUARDED BY A SHORING
SYSTEM: TRENCHES OR EXCAVATIONS LESS THAN FIVE (5) FEET IN
DEPTH SHALL ALSO BE GUARDED WHEN EXAMINATION INDICATES
THAT HAZARDOUS GROUND MOVEMENT MAY BE EXPECTED.
17. THE CONTRACTOR(S) SHALL OBTAIN A PERMIT TO PERFORM
EXCAVATION OR TRENCH WORK FROM CAL-OSHA. EXCAVATION
PERMIT BECOMES VALID ONCE ALL REQUIREMENTS PURSUANT TO
ASSEMBLY BILL 3019 ARE PERFORMED PRIOR TO CONSTRUCTION.
18. CONTRACTOR AGREES TO ASSUME SOLE AND COMPLETE
RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF
CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL
PERSONS AND PROPERTY. CONTRACTOR FURTHER AGREES THAT
THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE
LIMITED TO NORMAL WORKING HOURS.
19. PERFORM ALL WORK ON THE PROJECT IN ACCORDANCE WITH LOCAL,
STATE, AND FEDERAL STORMWATER POLLUTION PREVENTION LAWS,
AND ANY SPECIAL REQUIREMENTS OF THE CALIFORNIA REGIONAL
WATER QUALITY CONTROL BOARD, SANTA ANA REGION.
20. UTILITY MARK OUT: THE CONTRACTOR SHALL CALL UNDERGROUND
SERVICE ALERT (U.S.A.) AT 811 FOR MARK OUT OF EXISTING UTILITIES
A MINIMUM OF 48 HOURS PRIOR TO ANY WORK.
21. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY OR
STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A
SEARCH OF THE AVAILABLE RECORDS. THE CONTRACTOR SHALL
TAKE PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES
SHOWN ON THESE PLANS AND ANY OTHER LINES WHICH MAY NOT BE
OF RECORD NOR SHOWN ON THESE PLANS. THE CONTRACTOR
SHALL MAKE EXPLORATORY EXCAVATIONS TO LOCATE ALL EXISTING
UNDERGROUND FACILITIES IN AND AROUND THE AREAS OF
CONSTRUCTION. EXPLORATORY EXCAVATIONS SHALL BE
PERFORMED SUFFICIENTLY AHEAD OF CONSTRUCTION TO PERMIT
REVISIONS TO PLANS IF NECESSARY DUE TO ACTUAL LOCATION OF
EXISTING FACILITIES.
22. ELEVATIONS WHERE SHOWN ARE IN FEET ABOVE U.S.C. & G.S. MEAN
SEA LEVEL = O.C.S. DATUM.
23. ALL CONSTRUCTION DETAILED ON THESE PLANS SHALL BE
PERFORMED IN ACCORDANCE WITH THE STANDARD SPECIFICATIONS
FOR PUBLIC WORKS CONSTRUCTION, 2021 EDITION. EXCEPT AS
MODIFIED BY THE VA'S STANDARD DRAWINGS AND SPECIAL
PROVISIONS AND THIS CONTRACT'S SPECIAL PROVISIONS.
24. UTILITIES SHOWN ON THESE PLANS ARE CORRECT AND ACCURATE
TO THE EXTENT OF AVAILABLE RECORDS AND KNOWLEDGE. THE
CONTRACTOR, HOWEVER IS REQUIRED TO ASCERTAIN THE EXACT
LOCATION OF ALL UNDERGROUND FACILITIES PRIOR TO DOING ANT
WORK THAT MAY DAMAGE SUCH FACILITIES OR INTERFERE WITH
THEIR SERVICE.
25. ALL WORK SHOWN OR INDICATED ON THESE PLANS OR CALLED FOR
IN THE SPECIFICATIONS, BUT NOT INCLUDED AS PAY QUANTITY ITEMS,
SHALL BE CONSIDERED INCIDENTAL WORK, THE COST OF WHICH
SHALL BE CONSIDERED INCLUDED IN THE CONTRACTOR'S BID FOR
PAY QUANTITY ITEMS.
26. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE TO
EXISTING UTILITIES, PAVEMENTS, CURB, STRUCTURES, TREES, AND
LANDSCAPING AS A RESULT OF HIS OPERATIONS AND WILL BE
REQUIRED TO REPAIR OR REPLACE SAME TO THE SATISFACTION OF
AND AS DIRECTED BY THE CITY ENGINEER OR UTILITY COMPANY.
27. THE CONTRACTOR SHALL IMMEDIATELY HAUL AWAY AND DISPOSE OF,
OFF THE PROJECT SITE, ALL EXCESS EXCAVATED MATERIAL AND
CONSTRUCTION DEBRIS. ALL DISPOSALS SHALL BE AT THE
CONTRACTOR'S EXPENSE.
28. THE CONTRACTOR SHALL USE A VACUUM TO REMOVE SEDIMENT FOR
SAW-CUTTING OPERATIONS.
29. UNDERGROUND UTILITIES SHALL BE REQUIRED FOR THIS PROJECT.
30. EXISTING TOPOGRAPHY SHOWN HEREON WAS TAKEN FROM AN
AERIAL TOPOGRAPHIC SURVEY DATED SEPTEMBER 29, 2021 BY
PSOMAS. THE EXISTING UTILITY SURVEY SHOWN HEREON WAS TAKEN
FROM C BELOW SUBSURFACE IMAGING.
31. THE ENGINEER PREPARING THESE PLANS WILL NOT BE RESPONSIBLE
FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES TO OR USES OF
THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND
MUST BE APPROVED BY THE PREPARER OF THESE PLANS.
32. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER
GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
33. ALL FILL SOILS OR SOILS DISTURBED OR OVEREXCAVATED DURING
CONSTRUCTION SHALL BE COMPACTED NO LESS THAN 90% MAXIMUM
DENSITY AS DETERMINED BY A.S.T.M SOIL COMPACTION TEST D-1557.
34. ALL WATER LINES SHALL BE INSTALLED WITH 36" MINIMUM COVER
FROM TOP OF PIPE TO FINISHED GRADE, UNLESS OTHERWISE NOTED.
35. THRUST BLOCKS SHALL BE INSTALLED AT WATERLINE HORIZONTAL
AND VERTICAL BENDS, TEES, CAPPED ENDS AND REDUCERS
ACCORDING TO DETAILS PROVIDED ON THESE PLANS.
36. CONSTRUCTION STAKING FOR IMPROVEMENTS SHOWN ON THESE
PLANS SHALL BE PERFORMED BY A LICENSED LAND SURVEYOR.
CONSTRUCTION STAKING SURVEYOR SHALL BE RESPONSIBLE FOR
COORDINATION OF THESE PLANS WITH SOURCE DRAWINGS BY ANY
OTHER DISCIPLINE PRIOR TO START OF STAKING AND
CONSTRUCTION. ANY DISCREPANCIES THAT OCCUR SHALL BE
BROUGHT TO THE ATTENTION OF THE VA AND DESIGN ENGINEER SO
THAT A CLARIFICATION CAN BE ISSUED.
37. CONTRACTOR TO CONTACT UNDERGROUND SERVICE ALERT
(800-277-2600) PRIOR TO EXCAVATION.
38. CONTRACTOR TO BE AWARE OF OVERHEAD UTILITIES AT ALL TIMES,
SO AS TO NOT DISTURB THEM.
39. WATER SHALL BE PROVIDED ONSITE AND USED TO CONTROL DUST
DURING CONSTRUCTION OPERATIONS.
40. CONTRACTOR SHALL OBTAIN ANY NECESSARY PERMITS FROM THE
DEPARTMENT OF VETERANS AFFAIRS FOR ALL WORK WITHIN THE
ROAD WAY.
41. CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS, INCLUDING
NPDES, FROM THE APPROPRIATE JURISDICTIONAL AGENCIES FOR
DISCHARGE OF GROUNDWATER THAT MAY BE NECESSARY TO
ACCOMPLISH EXCAVATIONS SHOWN ON THESE PLANS.
42. NO SOILS REPORT HAS BEEN PREPARED EXPRESSLY FOR THIS
PROJECT. ALL WORK SHALL COMPLY WITH ALL APPLICABLE BUILDING
CODES AND OSHA REQUIREMENTS
VA U.S. DEPARTMENT OF VETERAN AFFAIRS
P.I.P. PROTECT-IN-PLACE
PRV PRESSURE REDUCING VALVE
CIVIL
PSOMAS
MATT HEIDEMAN, PROJECT MANAGER
MAIRA SALCEDO, PROJECT MANAGER
BOB TALAFUS, PRINCIPAL
JOE BOYLE, PRINCIPAL/DESIGN QUALITY CONTROL
BEN HALBACH, DESIGN PROJECT ENGINEER
KIM ALEXANDER, MODELING PROJECT ENGINEER
FIRE PROTECTION AND PLUMBING
COFFMAN ENGINEERING, INC.
AMAN SHAH, PRINCIPAL
ERICK CAMPOS, FIRE PROTECTION
GEORGE ABDELMALEK, PLUMBING
JOEY BALDUCCI, PLUMBING
SHEET NO. DRAWING NO. DRAWING TITLE
1 GI-101 TITLE SHEET, LOCATION MAP, AND VICINITY MAP
2 GI-102 GENERAL NOTES, ABBREVIATIONS, STANDARD SYMBOLS, PROJECT TEAMS, AND SHEET INDEX
3 GI-103 PROPOSED DOMESTIC WATER SYSTEM MAP
4 GI-104 PROPOSED DOMESTIC WATER SYSTEM MAP
5 GI-105 PROPOSED FIRE WATER SYSTEM MAP
6 GI-106 PROPOSED FIRE WATER SYSTEM MAP
7 GI-107 SHEET INDEX MAP DOMESTIC WATER SYSTEM
8 GI-108 SHEET INDEX MAP FIRE WATER SYSTEM
9 CD-101 ABANDONMENT AND REMOVAL
10 MD-101 TANK SITE MECHANICAL DEMOLITION LAYOUT
11 CI-101 TANK SITE CIVIL SITE PLAN AND CONNECTION TO LADWP
12 CI-102 TANK SITE PIPELINE PROFILES
13 CU-101 UPPER ZONE DOMESTIC WATER - PRIVATE RD STA. 101+15.00 TO STA. 108+62.47
14 CU-102 UPPER ZONE DOMESTIC WATER - PRIVATE RD STA. 108+62.47 TO STA. 115+05.43 AND STA. 400+00.00 TO STA. 401+05.00
15 CU-103 UPPER ZONE DOMESTIC WATER - BONSALL AVE STA. 120+00.00 TO STA. 125+45.11
16 CU-104 UPPER ZONE DW - BONSALL AVE STA. 130+00.00 TO STA. 133+90.00 AND ARNOLD AVE STA. 135+00.00 TO STA. 137+55.00
17 CU-105 UPPER ZONE DOMESTIC WATER - PATTON AVE STA. 140+00.00 TO STA. 143+03.36 AND BTWN. B206/207 STA. 145+00.00 TO STA. 147+46.89
18 CU-106 UPPER ZONE DOMESTIC WATER - NIMITZ AVE STA. 150+00.00 TO STA. 161+00.00
19 CU-107 UPPER ZONE DOMESTIC WATER - BTWN. B407 & B410 STA. 160+00.00 TO STA. 165+24.57
20 CU-108 UPPER ZONE DOMESTIC WATER - PERSHING AVE STA. 170+00.00 TO STA. 176+00.00
21 CU-109 UPPER ZONE DOMESTIC WATER - PERSHING AVE STA. 176+00.00 TO STA. 184+40.00
22 CU-110 LOWER ZONE DOMESTIC WATER - PRIVATE RD STA. 190+00.00 TO STA. 198+00.00
23 CU-111 LOWER ZONE DOMESTIC WATER - PRIVATE RD STA. 198+00.00 TO STA. 204+75.21
24 CU-112 LOWER ZONE DOMESTIC WATER - BONSALL AVE STA. 205+00.00 TO STA. 210+60.00
25 CU-113 UPPER ZONE DOMESTIC WATER - MACARTHUR AVE STA. 350+00.00 TO STA. 357+72.00
26 CU-114 UPPER ZONE DOMESTIC WATER - VANDERGRIFT AVE STA. 357+72.00 TO STA. 363+75.00
27 CU-115 UPPER ZONE DOMESTIC WATER - VANDERGRIFT AVE STA. 363+75.00 TO STA. 368+66.00
28 CU-116 UPPER ZONE FIRE WATER - PRIVATE RD STA. 221+50.00 TO STA. 228+98.83
29 CU-117 UPPER ZONE FIRE WATER - PRIVATE RD STA. 228+98.83 TO STA. 235+38.22 AND STA. 405+00.00 TO STA. 406+05.00
30 CU-118 UPPER ZONE FIRE WATER - BONSALL AVE STA. 240+00.00 TO STA. 245+54.58
31 CU-119 UPPER ZONE FIRE WATER - BONSALL AVE & PATTON AVE STA. 250+00.00 TO STA. 253+78.56 & STA. 325+00.00 TO STA. 329+40.00
32 CU-120 UPPER ZONE FIRE WATER - PATTON AVE STA. 260+00.00 TO STA. 263+05.14 AND BTWN. B206/207 STA. 265+00.00 TO STA. 267+49.66
33 CU-121 UPPER ZONE FIRE WATER - MACARTHUR AVE TO VANDERGRIFT AVE STA. 270+00.00 TO STA. 276+00.00
34 CU-122 UPPER ZONE FIRE WATER - VANDERGRIFT AVE STA. 276+00.00 TO STA. 285+31.28
35 CU-123 UPPER ZONE FIRE WATER - NIMITZ AVE STA. 290+00.00 TO STA. 299+30.00
36 CU-124 UPPER ZONE FIRE WATER - BTWN. B407 & 410 STA. 300+00.00 TO STA. 305+12.02
37 CU-125 UPPER ZONE FIRE WATER - PERSHING AVE STA. 310+00.00 TO STA. 316+00.00
38 CU-126 UPPER ZONE FIRE WATER - PERSHING AVE STA. 316+00.00 TO STA. 321+70.00
39 CU-201 CIVIL DETAILS
40 CU-202 CIVIL DETAILS
41 CU-203 CIVIL DETAILS
42 MP-101 TANK SITE MECHANICAL SITE PLAN AND SECTIONS
43 MP-102 TANK SITE MECHANICAL SITE PLAN AND SECTIONS
44 MP-103 TANK SITE MECHANICAL SITE PLAN AND SECTIONS
45 MP-104 MECHANICAL PRV SITE PLAN - BONSALL
46 MP-105 MECHANICAL PRV SITE PLAN - PERSHING AND DEWEY
47 MP-106 UPPER PRESSURE ZONE LADWP CONNECTION
CONTRACTOR
NPD ASSOCIATES INC.
JAMES REED, PRIME CONTRACTOR
COST ESTIMATING
HUNTER PACIFIC GROUP
DAVID COLERA, PROJECT ESTIMATOR
PRC POINT OF REVERSE CURVE
SHEET INDEXLA COUNTY FIRE DEPARTMENT NOTESGENERAL NOTES
ABBREVIATIONS
PROJECT TEAMS
DW DOMESTIC WATER
FDC FIRE DEPARTMENT CONNECTION
FINISHED GROUND FG
FW FIRE WATER
LADWP LA DEPARTMENT OF WATER AND POWER
MAX MAXIMUM
LF LINEAR FEET
1. THE DESIGN AND INSTALLATION OF THE PRIVATE UNDERGROUND FIRE LINE SHALL BE IN ACCORDANCE WITH THE 2010 NFPA 24 AND LACoFD REGULATIONS 7 AND 8.
2. THE INSTALLING CONTRACTOR MUST BE IN POSSESSION OF A CALIFORNIA STATE CONTRACTORS LICENSE AS FOLLOWS: C-16, 34, 36, OR GENERAL CONTRACTOR A. LICENSE MUST BE CURRENT AND IN GOOD STANDING WITH THE STATE AT THE TIME CONTRACT IS AWARDED.
3. EACH SPRINKLER RISER SHALL HAVE A READILY VISIBLE AND ACCESSIBLE ABOVE GROUND EXTERIOR INDICATION CONTROL VALVE.
4. ANY PIPING LOCATED UNDER THE BUILDING SHALL BE DUCTILE IRON. CONVERT TO DUCTILE IRON PIPING 5 FEET OUTSIDE THE BUILDING TO 6” MIN ABOVE FINISHED FLOOR.
5. IT IS THE RESPONSIBILITY OF THE OWNER TO MAINTAIN THE FIRE PROTECTION SYSTEM IN AN OPERABLE CONDITION AT ALL TIMES.
6. THE FIRE PROTECTION CONTRACTOR WILL PROVIDE THE OWNER WITH THE NECESSARY INSTRUCTION MANUALS FOR THE UPKEEP OF THE SYSTEM, AS WELL AS A COPY OF
NFPA 25.
7. THE SYSTEM SHALL ONLY EMPLOY THE USE OF APPROVED MATERIALS AND DEVICES.
8. FIRE PROTECTION PLANS SHALL BE APPROVED PRIOR TO THE INSTALLATION OF ANY PIPE. A SET OF APPROVED PLANS SHALL BE MAINTAINED AT ALL TIME AT THE JOB SITE.
9. AN APPOINTMENT SHALL BE MADE A MINIMUM OF TWO WORKING DAYS IN ADVANCE, WITH THE APPROPRIATE FIRE PREVENTION DIVISION REGIONAL OFFICE FOR ALL
INSPECTIONS AND TESTS.
10. ALL UNDERGROUND MAINS AND LEAD-IN CONNECTIONS SHALL BE FLUSHED, AS INDICATED IN NFPA PRIOR TO CONNECTING TO THE OVERHEAD PIPING. THE FLUSHING SHALL CONTINUE UNTIL THE WATER IS CLEAR. FLUSHING SHOULD BE PERFORMED AT THE TIME OF THE HYDROSTATIC TEST, AND SHALL BE WITNESSED BY A FIRE PREVENTION
DIVISION INSPECTOR.
11. SYSTEM PIPING SHALL BE HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS OR AT 50 PSI ABOVE THE MAXIMUM SYSTEM OPERATING PRESSURE, WHICHEVER IS GREATER.
12. ALL VALVES AND FIRE DEPARTMENT CONNECTIONS SHALL HAVE PERMANENT AFFIXED SIGNS, INDICATING THEIR FUNCTION.
13. ANY PORTION OF A WET FIRE PROTECTION SYSTEM EXPOSED TO FREEZING TEMPERATURES SHALL BE ADEQUATELY PROTECTED. (HEAT TAPE IS NOT AN ACCEPTABLE
METHOD OF PROTECTION).
14. WELDING SHALL BE PERFORMED PER NFPA 13 REQUIREMENTS.
15. ALL PRIVATE FIRE HYDRANTS SHALL FLOW A MINIMUM OF 1250 GPM AT 20 PSI FOR DURATION OF TWO HOURS. IF MORE THAN ONE ON-SITE FIRE HYDRANT IS REQUIRED, THE ON-SITE FLOW SHALL BE AT LEAST 2500 GPM AT 20 PSI, FLOWING THE MOST HYDRAULICALLY REMOTE HYDRANTS SIMULTANEOUSLY. ON-SITE SHALL MATCH THE PUBLIC
FLOW REQUIREMENTS.
16. ALL PRIVATE ON-SITE FIRE HYDRANTS SHALL BE INSTALLED A MINIMUM OF 25 FEET FROM A STRUCTURE OR PROTECTED BY A TWO-HOUR FIREWALL TO THE HIGHEST
PORTION OF THE BUILDING, ADJACENT TO THE HYDRANT.
17. EACH PRIVATE FIRE SYSTEM SHALL HAVE A MAIN POST INDICATOR VALVE, OR OTHER APPROVED VALVE, ON THE SYSTEM SIDE OF THE DETECTOR CHECK VALVE.
18. ALL PRIVATE ON-SITE FIRE HYDRANTS SHALL BE EQUIPPED WITH A SHUT-OFF VALVE, WHICH IS LOCATED AT LEAST 10 FEET, AND NOT MORE THAN 25 FEET, FROM THE HYDRANT. THE LOCATION MAYBE BE LESS THAN 10 FEET WHEN THE WATER MAIN IS EXISTING, AND THE 10 FOOT MINIMUM DISTANCE CANNOT BE SATISFIED. THE SHUT OFF VALVE SHALL BE READILY ACCESSIBLE AT ALL TIME (LOCATING UNDER A PARKING STALL IS NOT ALLOWED).
19. ALL PRIVATE ON-SITE FIRE HYDRANTS SHALL BE INSTALLED TO THE FOLLOWING SPECIFICATIONS, PRIOR TO FLOW TEST AND ACCEPTANCE OF THE SYSTEM:
19.1. ALL FIRE HYDRANTS SHALL MEASURE 6"x4"x2-1/2", BRASS OR BRONZE, CONFORMING TO AMERICAN WATER WORKS ASSOCIATION STANDARD C503, OR APPROVED EQUAL, AND SHALL BE INSTALLED IN ACCORDANCE WITH THE COUNTY OF LOS ANGELES FIRE DEPARTMENT REGULATION 8.
19.2. INSTALLED SO THAT THE CENTERLINE OF THE LOWEST OUTLET IS BETWEEN 14 AND 24 INCHES ABOVE FINISHED GRADE.
19.3. INSTALLED SO THAT THE FRONT OF THE RISER IS BETWEEN 12 AND 24 INCHES BEHIND THE CURB FACE.
19.4. INSTALLED SO THAT THE OUTLETS ARE FACING THE CURB AT A 45-DEGREE ANGLE TO THE CURB LINE.
19.5. OF A TYPE OF CONSTRUCTION WHICH CONFORMS TO CURRENT AMERICAN WATER WORKS ASSOCIATION STANDARD 503.
19.6. PROVIDED WITH A 3 FOOT UNOBSTRUCTED CLEARANCE ON ALL SIDES.
19.7. INSTALLED SO THAT THE FIRE HYDRANT IS CENTERED ON A 3'x3'x1' THICK CONCRETE PAD.
19.8. PROPERLY TREATED PRIOR TO PAINT APPLICATION, AND PAINTED WITH TWO COATS OF PRIMER AND ONE COAT OF “FIRE ENGINE RED” PAINT.
FCA FLANGE COUPLING ADAPTER
PIV POST INDICATOR VALVE
[FUTURE]
[FUTURE]
VAN
EV
EV
EV
EV
PATTON AVE
MACARTHUR AVE
PRIVATE ROAD
BONSALL
AVE PATTON
AVE
PATTON AV
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-G I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1PROPOSED DOMESTIC WATER
SYSTEM MAP
GI-103
0 100 200
SCALE: 1" = 100'
08-PVC-DW-101
12-PVC-DW-201
08-PVC-DW-101 12-PVC-DW-201
08-DGV-109
12-DGV-209
08-PVC-DW-101
12-PVC-DW-201
-P
VC
-D
W-20
-P
VC
-D
W -10
08-PVC-DW-102
-PVC-DW-20
-PVC-DW-10
08-PVC-DW-104
08-PVC-DW-104
08-PVC-DW-103
06-DGV-112
08-DGV-120
04-DGV-122
LEGEND
IDENTIFICATION LABELS
PIPE
0 8 - P V C - D W - X X X
DIAMETER
MATERIAL
WATER SYSTEM
D - DOMESTIC
F - FIRE
PRESSURE ZONE
0 - DWP ZONE
1 - UPPER ZONE
2 - LOWER
SERIAL NUMBER
VALVE
0 8 - D G V - X X X
DIAMETER
VALVE TYPE
GV - GATE VALVE
HV - HYDRANT VALVE
PR - PRESSURE REDUCING VALVE
PRESSURE ZONE
1 - UPPER
2 - LOWER
SERIAL NUMBER
WATER SYSTEM
D - DOMESTIC
F - FIRE
VALVE COVER TOP MARK
DOMESTIC WATER
WATER
FIRE WATER
FIRE
PROPOSED PRESSURE REDUCING VALVE
PROPOSED WATER LINE
PROPOSED FIRE HYDRANT
EXISTING FIRE HYDRANT (TO BE PROTECTED IN PLACE)
PROPOSED GATE VALVE
MA
TC
H
LIN
E
SE
E
DW
G
GI
-1
GI-103
A
GI-103
B
CONNECTION TO
EX. PVC PIPE
FIRE HYDRANT
FH - 1 01
FIRE HYDRANT
SERIAL NUMBER
PRESSURE ZONE
1 - UPPER
2 - LOWER
04-DGV-110
CONNECTION
TO EX. PVC
08-DGV-121
CONNECTION TO
EX. PVC 04-DGV-111
04-DGV-113
08-DGV-115
08-DGV-114
08-DGV-116
04-DGV-117
SCALE: 1" = 5'B
UPPER ZONE DOMESTIC WATER
PRESSURE REDUCING AND
BACKFLOW PREVENTER ASSEMBLIES
SCALE: 1" = 5'A TANK SITE CONNECTION TO LADWP
12-DGV-001
08-DGV-003
08-DPR-103
08-DGV-104
08-DGV-107
08-DGV-108
06-DPR-101
06-DGV-102
08-DGV-105
06-DGV-002
08-DGV-106
OR
CALVETS
PARKING
LOT
408 306
CALVETS
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
GR
AN
T A
VE
DEW
EY AVE
MACARTHUR AVE
BONSALL AVE
VANDERGRIFT
NIM
ITZ
A
VE
AVE
PE
RS
HI
N
G
AV
E (F
U
TU
RE
AR
NO
LD
A
VE
PATTON
AVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-G I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1PROPOSED DOMESTIC WATER
SYSTEM MAP
GI-104
0 100 200
SCALE: 1" = 100'
08-PVC-DW-105
-P
VC
-D
W -1
-P
VC
-D
W -1
08-PVC-DW-108
08-PVC-DW-108
08-PVC-DW-107
-P
VC
-D
W-10
-P
VC
-D
W -1
-P
VC
-D
W -1
-PV
C-
DW
-10
08-PVC-DW-104
08-PVC-DW-106
-P
VC
-D
W-10
08-DGV-134
08-DGV-135
04-DGV-119
04-DGV-130
08-DGV-129
08-DGV-128
04-DGV-127
08-DGV-141
08-DGV-142
08-DGV-140
08-DGV-139
08-DGV-126
08-DGV-133
08-DGV-124
04-DGV-123
08-DGV-137
08-DGV-XXX
08-DGV-138
08-DGV-140
04-DGV-141
08-DGV-143
08-DGV-142
04-DGV-144
08-DGV-151
08-DGV-146
08-PVC-DW-110
08-DGV-151
LEGEND
PROPOSED PRESSURE REDUCING VALVE
PROPOSED WATER LINE
PROPOSED FIRE HYDRANT
EXISTING FIRE HYDRANT (TO BE PROTECTED IN PLACE)
PROPOSED GATE VALVE
IDENTIFICATION LABELS
PIPE
0 8 - P V C - D W - X X X
DIAMETER
MATERIAL
WATER SYSTEM
D - DOMESTIC
F - FIRE
PRESSURE ZONE
0 - DWP ZONE
1 - UPPER ZONE
2 - LOWER
SERIAL NUMBER
VALVE
0 8 - D G V - X X X
DIAMETER
VALVE TYPE
GV - GATE VALVE
HV - HYDRANT VALVE
PR - PRESSURE REDUCING VALVE
PRESSURE ZONE
1 - UPPER
2 - LOWER
SERIAL NUMBER
WATER SYSTEM
D - DOMESTIC
F - FIRE
VALVE COVER TOP MARK
DOMESTIC WATER
WATER
FIRE WATER
FIRE
04-DGV-148
MA
TC
H
LIN
E
SE
E
DW
G
GI
-1
04-DGV-118
08-PVC-DW-103
GI-104
A
CONNECT TO
EX. PVC PIPE
08-DGV-125
08-DGV-136
GI-104
B
04-DGV-145
08-DGV-147
GI-104
C
04-DGV-150
04-DGV-149
SCALE: 1" = 5'A PRV - BONSALL
SCALE: 1" = 5'B UPPER ZONE LADWP CONNECTION
SCALE: 1" = 5'C PRV - PERSHING/DEWEY
FIRE HYDRANT
FH - 1 01
FIRE HYDRANT
SERIAL NUMBER
PRESSURE ZONE
1 - UPPER
2 - LOWER
OR
08-DGV-131
08-DPR-201
08-DGV-202
06-DGV-132
06-DPR-203
06-DGV-204
08-DGV-144
08-DGV-143
08-DGV-146
08-DGV-145
08-DGV-206
08-DPR-205
08-DGV-152
06-DGV-153
08-DGV-208
08-DPR-207
[FUTURE]
[FUTURE]
VAN
EV
EV
EV
EV
PATTON AVE
MACARTHUR AVE
PRIVATE ROAD
PATTON
AVE
PATTON AV
BONSALL
AVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-G I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1PROPOSED FIRE WATER
SYSTEM MAP
GI-105
0 100 200
SCALE: 1" = 100'
12-PVC-FW-101
12-PVC-FW-101
10-PVC-FW-102
12-PVC-FW-105
-PV
C-FW
-10
12-PVC-FW-104
12-PVC-FW-106
12-FGV-109
-P
VC
-F
W -10
06-FHV-115
10-FGV-114
FH-101
FH-107
FH-106
12-PVC-FW-105
12-PVC-FW-103
06-FHV-121
12-FGV-120
06-FHV-118
FH-103
FH-102
06-FHV-116
08-FGV-130
XX-FHV-XXX
FH-XXX
06-FHV-131
FH-109
FH-108
06-FHV-129
XX-FGV-XXX
XX-FGV-XXX
MA
TC
H
LIN
E
SE
E
DW
G
GI
-1
LEGEND
IDENTIFICATION LABELS
PIPE
0 8 - P V C - D W - X X X
DIAMETER
MATERIAL
WATER SYSTEM
D - DOMESTIC
F - FIRE
PRESSURE ZONE
0 - DWP ZONE
1 - UPPER ZONE
2 - LOWER
SERIAL NUMBER
VALVE
0 8 - D G V - X X X
DIAMETER
VALVE TYPE
GV - GATE VALVE
HV - HYDRANT VALVE
PR - PRESSURE REDUCING VALVE
PRESSURE ZONE
1 - UPPER
2 - LOWER
SERIAL NUMBER
WATER SYSTEM
D - DOMESTIC
F - FIRE
VALVE COVER TOP MARK
DOMESTIC WATER
WATER
FIRE WATER
FIRE
PROPOSED PRESSURE REDUCING VALVE
PROPOSED WATER LINE
PROPOSED FIRE HYDRANT
EXISTING FIRE HYDRANT (TO BE PROTECTED IN PLACE)
PROPOSED GATE VALVE
FIRE HYDRANT
FH - 1 01
FIRE HYDRANT
SERIAL NUMBER
PRESSURE ZONE
1 - UPPER
2 - LOWER
OR
SCALE: 1" = 5'A
UPPER ZONE FIRE WATER PRESSURE
REDUCING AND BACKFLOW
PREVENTER ASSEMBLIES
GI-105
A
12-FGV-001
12-FGV-101
12-FGV-102
08-FGV-002
08-FPR-103
08-FGV-104 08-FGV-107
08-FGV-108 12-FGV-106
12-FGV-105
CONNECTION TO
EX. PVC PIPE CONNECTION TO
EX. PVC PIPE
06-FHV-112
06-FHV-11106-FHV-113
10-FGV-110
06-FHV-128
06-FHV-127
FH-104
12-FGV-126
04-FGV-119
06-FGV-117
CONNECT
TO EX. PVC
CONNECT
TO EX. PVC
04-FGV-132
10-FGV-207
LOT
408 306
CALVETS
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
GR
AN
T A
VE
DEW
EY AVE
MACARTHUR AVE
BONSALL AVE
VA
ND
ER
GR
IFT
AV
E
PE
RS
HI
N
G
AV
E (F
U
TU
RE
)NIM
ITZ
A
VE
AR
NO
LD
A
VE
PATTON
AVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-G I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1PROPOSED FIRE WATER
SYSTEM MAP
GI-106
-P
VC
-F
W -1
-P
VC
-F
W -1
12-PVC-FW-110
12-PVC-FW-110
-PV
C-
FW
-10
12-PVC-FW-109
12-PVC-FW-106
-PV
C-
FW
-10
-P
VC
-F
W -1
12-PVC-FW-108
12-PVC-FW-107
FH-117
06-FHV-167
12-FGV-168
06-FGV-170
FH-118
06-FGV-171
06-FHV-175
FH-121
12-FGV-173
12-FGV-172
06-FGV-179
12-FGV-179
FH-119
06-FHV-134
FH-110
12-FGV-135
12-FGV-149
12-FGV-136
FH-111
06-FHV-137
12-FGV-152
04-FGV-138
12-FGV-150
12-FGV-151
12-FGV-141
06-FHV-139
FH-112
06-FGV-154
06-FHV-153
FH-113
06-FHV-155
FH-114
12-FGV-160
12-FGV-156
12-FGV-157
06-FGV-158
06-FHV-161
FH-116
06-FHV-159
FH-115
06-FGV-143
FH-120
06-FHV-210
06-FHV-209
FH-105
06-FHV-122
0 100 200
SCALE: 1" = 100'
MA
TC
H
LIN
E
SE
E
DW
G
GI
-1
LEGEND
PROPOSED PRESSURE REDUCING VALVE
PROPOSED WATER LINE
PROPOSED FIRE HYDRANT
EXISTING FIRE HYDRANT (TO BE PROTECTED IN PLACE)
PROPOSED GATE VALVE
IDENTIFICATION LABELS
PIPE
0 8 - P V C - D W - X X X
DIAMETER
MATERIAL
WATER SYSTEM
D - DOMESTIC
F - FIRE
PRESSURE ZONE
0 - DWP ZONE
1 - UPPER ZONE
2 - LOWER
SERIAL NUMBER
VALVE
0 8 - D G V - X X X
DIAMETER
VALVE TYPE
GV - GATE VALVE
HV - HYDRANT VALVE
PR - PRESSURE REDUCING VALVE
PRESSURE ZONE
1 - UPPER
2 - LOWER
SERIAL NUMBER
WATER SYSTEM
D - DOMESTIC
F - FIRE
VALVE COVER TOP MARK
DOMESTIC WATER
WATER
FIRE WATER
FIRE
FIRE HYDRANT
FH - 1 01
FIRE HYDRANT
SERIAL NUMBER
PRESSURE ZONE
1 - UPPER
2 - LOWER
OR
SCALE: 1" = 5'A PRV - BONSALL
SCALE: 1" = 5'B UPPER ZONE LADWP CONNECTION
SCALE: 1" = 5'C PRV - PERSHING/DEWEY
10-FGV-147
10-FPR-203
10-FGV-204
08-FGV-148
08-FPR-201 08-FGV-202
10-FGV-164
10-FGV-163
08-FGV-166
08-FGV-165
08-FGV-208
08-PR-207
08-FGV-182
10-FGV-183
10-FGV-206
10-FPR-205
GI-106
A
GI-106
B
GI-106
C
08-FGV-145
06-FHV-123
12-PVC-FW-104
06-FGV-124
06-FGV-125
06-FHV-146
06-FGV-144
06-FHV-142
12-FGV-140
04-FGV-133
06-FGV-181
06-FGV-180
12-FGV-182
12-FGV-178
06-FHV-177
12-PVC-FW-112
06-FGV-176
12-FGV-162
06-FGV-169
LOT
[FUTURE]
408 306
CALVETS
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
VAN
EV
EV
EV
EV
CU-101CU-110
CU-102CU-111
CU-103
CU-10
CU-113
CU-112 CU-105
CU-105
CU
-1
CU-107
C U
-1
C U
-1
GR
AN
T A
VE
DEW
EY AVE
MACARTHUR AVE
PATTON AVE
BONSALL AVE
AR
NO
LD
A
VE
VA
ND
ER
GR
IF
T
NI
M
IT
Z A
VE
PATTON AVE
MACARTHUR AVE
LOT 38
AV
E
PRIVATE ROAD
PE
RS
HI
N
G
AV
E (F
U
TU
RE
BRINGHAM AVE
CU-102
CU-11
CU
-1
CU-104
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-G I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1SHEET INDEX MAP
DOMESTIC WATER SYSTEM
GI-107
LEGEND
0 100 200
SCALE: 1" = 100'
PROPOSED NEW BUILDING AND BUILDING NUMBER
EXISTING BUILDING AND BUILDING NUMBER
PROPOSED FIRE WATER LINE
DOMESTIC WATER DRAWING VIEW LIMIT
PROPOSED CURB (BY OTHERS)
PROPOSED DOMESTIC WATER LINE
CU-101 DOMESTIC WATER DRAWING SHEET NUMBER
VA RECORDED PROPERTY LINE
EUL PARCEL LINES (DIGITIZED FROM PDF OF NORTH CAMPUS PARCEL
MAP PROVIDED BY KPFF)
EUL PARCEL LINES (PER JRN SURVEY DATA)
LOT
[FUTURE]
408 306
CALVETS
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
VAN
EV
EV
EV
EV
CU-116
CU-117
CU-118
CU-121
CU
-1
CU-120
CU-120
CU
-1
CU-124
C U
-1
C U
-1
GR
AN
T A
VE
MACARTHUR AVE
BRINGHAM AVE
PATTON AVE
BONSALL AVE
AR
NO
LD
A
VE
NI
M
IT
Z A
VE
PATTON AVE
PE
RS
HI
NG
A
VE
MACARTHUR AVE
LOT 38
(F
UT
UR
E)
VA
NDE
RG
RI
FT
AV
E
PRIVATE ROAD
CU-119
CU-119
CU-117
DEW
EY AVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-G I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1SHEET INDEX MAP
FIRE WATER SYSTEM
GI-108
0 100 200
SCALE: 1" = 100'
LEGEND
PROPOSED NEW BUILDING AND BUILDING NUMBER
EXISTING BUILDING AND BUILDING NUMBER
PROPOSED DOMESTIC WATER LINE
FIRE WATER DRAWING VIEW LIMIT
PROPOSED CURB (BY OTHERS)
PROPOSED FIRE WATER LINE
CU-101 FIRE WATER DRAWING SHEET NUMBER
EUL PARCEL LINES (PER JRN SURVEY DATA)
VA RECORDED PROPERTY LINE
EUL PARCEL LINES (DIGITIZED FROM PDF OF NORTH CAMPUS PARCEL
MAP PROVIDED BY KPFF)
LOT
[FUTURE]
408 306
CALVETS
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
[FUTURE]
BLD
G. A
, B & C
BLD
G. G
BLD
G. J
BLD
G. H
BLD
G. K
BLD
G. I
BLD
G. F
BLD
G. E
BLD
G. D
BLD
G. L
BLD
G. M
VAN
EV
EV
EV
EV
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-C D
-1
.D W
G 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1ABANDONMENT AND REMOVAL
CD-101
BONSALL AVE
0 100 200
SCALE: 1" = 100'
LEGEND
PROPOSED NEW BUILDING
EXISTING BUILDING
EXISTING IRRIGATION (PLAN VIEW)
EXISTING UTILITY TO BE REMOVED AND DISPOSED OF (VA #691-21-120)
EXISTING WATER (PLAN VIEW)
EXISTING UTILITY TO BE ABANDONED IN PLACE AND PLUGGED (VA #691-21-120)
BONSALL AVE
N
IM
IT
Z
AV
E
VA
ND
ER
GR
IF
T
AV
E
AR
NO
LD
A
VE
BRINGHAM AVE
PATTON AVE
PE
RS
HI
NG
A
VE
(F
UT
.)MACARTHUR AVE
PROPOSED EUL PARCEL LINE
EXISTING UTILITY TO BE REMOVED AND DISPOSED OF OR ABANDONED IN PLACE BY OTHERS
1. CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT LEAST TWO DAYS PRIOR TO STARTING EXCAVATION WORK.
2. UNLESS OTHERWISE NOTED, ALL EXISTING UNDERGROUND UTILITIES AND ASSOCIATED STRUCTURES SHALL BE PROTECTED-IN-PLACE.
3. CONTRACTOR TO FIELD VERIFY EXISTING UTILITY DEPTHS AND TO NOTIFY THE VA REPRESENTATIVE IF ANY UTILITIES CONFLICT WITH PROPOSED IMPROVEMENTS.
4. SHOULD ANY EXITING UTILITIES NOT SHOWN HEREON BE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE VA REPRESENTATIVE PRIOR TO DEMOLITION OR CONSTRUCTION.
5. CONTRACTOR SHALL COORDINATE WITH THE VA AND VERIFY THE NUMBER OF TREES AND ROOTS TO BE REMOVED AND DISPOSED OF PRIOR TO START OF CONSTRUCTION.
6. UNLESS OTHERWISE NOTED, REMOVAL INCLUDES ALL COMPONENTS OF ITEM, STRUCTURE, BASE, FOUNDATION, UTILITIES, VALVES AND APPURTENANCES, AND CONSTRUCTION OF CONCRETE PLUGS, ETC.
7. UNLESS NOTED OTHERWISE NOTED. ABANDONMENT INCLUDED ABANDONMENT IN PLACE, REMOVAL OF INTERFERING PORTIONS, AND CONSTRUCTION OF CONCRETE PLUGS
8. THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES AND SHALL NOTIFY VA'S REPRESENTATIVE WITH ANY DISCREPANCIES.
9. LIMITS OF TRANSITE PIPE IS UNKNOWN. CONTRACTOR SHALL DISPOSE OF AND ABANDON ALL TRANSITE PIPE PER VA, STATE, AND LOCAL REQUIREMENTS.
10. CONTRACTOR SHALL PROTECT EXISTING IRRIGATION SERVICES, APPURTENANCES, AND SPRINKLERS. IF DAMAGED, CONTRACTOR SHALL REPLACE THEM TO THE SATISFACTION OF THE VA AT THE CONTRACTOR'S EXPENSE
GENERAL NOTES
DEMOLITION NOTES
ABANDON VALVE. CLOSE VALVE AND REMOVE AND DISPOSE OF VALVE CAN LID, AND FILL WITH CONCRETE. RESURFACE IN KIND.3
PRV. REMOVE AND DISPOSE OF ABOVE GROUND INFRASTRUCTURE AND SALVAGE PRV AND GATE VALVES. CAP PIPELINE MINIMUM 5' BELOW SURFACE.1
FIRE HYDRANT. ABANDON EXISTING FIRE HYDRANT LATERAL IN PLACE. REMOVE AND DISPOSE OF FIRE HYDRANT, ABOVE GROUND RISER, VALVE BOX AND COVER CAP MINIMUM 5' BELOW SURFACE.2
SCHEDULE IS UNKNOWN
ACP NOTES:
SNAP CUT EXISTING AC PIPE AND REMOVE INTERFERING PORTIONS OF PIPE AS
NECESSARY TO PROVIDE ROOM FOR NEW CONNECTING PIPE, FITTINGS AND VALVE. DO
NOT UNDER ANY CIRCUMSTANCES ALLOW ASBESTOS PARTICLES TO BECOME AIRBORNE.
DISPOSE OF AC PIPE IN ACCORDANCE WITH LOCAL, STATE, AND FEDERAL REGULATIONS.
INSTALL NEW PIPE AS SHOWN IN CONNECTION DETAILS SHOWN IN PLANS, USE LONG
BARREL TYPE FLEX COUPLINGS WITH TYPE 316 STAINLESS STEEL HARDWARE WITH
FLUOROPOLYMER (TRIPAC 2000) OR EQUAL COATING PER SPECIFICATIONS AND DI CL 250
PIPE SPOOLS CUT TO FIT AS REQUIRED. ALL MATERIAL SHALL BE APPROVED BY THE
OWNER'S INSPECTOR PRIOR TO INSTALLATION.
B-3
B-4
B-6
B-7
B-8
B-9
B-10
B-14
B-15
B-13
B-12
PIV
B-11
(EX FH CONNECTED TO
MAJESTYC)
B-20
B-19
B-18
3 B-17
B-16
PRIVATE CALVETS WATER
B334
B329
EX. TRANSITE PIPE, SEE
NOTE 8
EX. TRANSITE PIPE, SEE
NOTE 8
(ASSUMED) EX.
ABND WATR
EX. FDC TO
BE REMOVED
SCALE: 1" = 10'A PIT B
SCALE: 1" = 10'B PIT C
PROPOSED SIDEWALK AND CURB
EXISTING IRRIGATION (DETAILVIEW)
EXISTING WATER (DETAIL VIEW)
EX. NORMALLY
CLOSED VALVE 3
REMOVE VALVE. REMOVE AND DISPOSE OF VALVE AND VALVE CAN LID. RESURFACE IN KIND4
4 4
EX. 12" PVC
(PROTECT IN PLACE)
(ASSUMED) EX.
HP IRRIGATION
EX. 12" PVC
(PROTECT IN PLACE)
EX. 12" PVC
(PROTECT IN PLACE)
2 3
3 3
EX. 12" PVC
(PROTECT IN PLACE) EX. 12" PVC
(PROTECT IN PLACE)
EX. B300 IRR.
BACKFLOW
(PROTECT IN
PLACE)
EX. NORMALLY
CLOSED GV
(ASSUMED) EX.
DW/FW TO B210
(ASSUMED) EX. IRR
SERVICE TO B300
(PROTECT IN PLACE)
4EX. NORMALLY
CLOSED GV
CONNECTION
TO EX. 12" PVC
EX. NORMALLY
CLOSED GV
EX. NORMALLY
CLOSED GV
EX. IRR. LINE
EX. B300 FIRE
BACKFLOW
(PROTECT IN
PLACE)
EX. B300 DOMESTIC
WATER BACKFLOW
(PROTECT IN PLACE)
(ASSUMED)
EX. SERVICE
TO BE B300
EX. ABND. 10" WTR
EX. ABND 12"
WTR
EX. 12" PVC WTR,
LOWER FW
(ASSUMED) B300
SERVICE TO B300
CD-101
A
CD-101
B
3 3
D-4
D-3
D-2
EX. TRANSITE,
SEE NOTE 8
B-2
B-5
D-74
4 D-1
D-6
LEGEND
EX. ASPHALT
ACCESS ROAD
TANK SITE MECHANICAL
DEMOLITION LAYOUT
MD-101
EXISTING ITEMS TO BE DEMOLISHED
AND DISPOSED OF
GENERAL NOTES
1. UNLESS OTHERWISE NOTED, ALL EXISTING UNDERGROUND UTILITIES AND ASSOCIATED STRUCTURES SHALL BE
PROTECTED IN PLACE.
2. CONTRACTOR TO FIELD VERIFY EXISTING UTILITY DEPTHS AND TO NOTIFY THE VA REPRESENTATIVE IF ANY UTILITIES
CONFLICT WITH PROPOSED IMPROVEMENTS.
3. SHOULD ANY EXISTING UTILITIES NOT SHOWN HEREON BE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE VA
REPRESENTATIVE PRIOR TO DEMOLITION OR CONSTRUCTION.
4. CONTRACTOR SHALL COORDINATE WITH THE VA AND VERIFY THE NUMBER OF TREES AND ROOTS TO BE REMOVED AND
DISPOSED OF PRIOR TO START OF CONSTRUCTION.
5. UNLESS OTHERWISE NOTED, REMOVAL INCLUDES ALL COMPONENTS OF ITEM, STRUCTURE, BASE, FOUNDATION, UTILITIES, CONSTRUCTION OF CONCRETE PLUGS, ETC.
6. THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES AND SHALL NOTIFY VA'S REPRESENTATIVE
WITH ANY DISCREPANCIES.
7. CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT LEAST TWO DAYS PRIOR TO STARTING EXCAVATION
WORK.
8. 12" PIPING, VALVES, AND FITTINGS SHALL BE REMOVED AND DISPOSED OF AFTER ALL WORK IN LADWP VAULTS IS COMPLETED. THIS SECTION OF PIPE MAY BE USED AS A BYPASS WHILE WORK IN THE VAULT IS BEING COMPLETED.
CONTRACTOR SHALL COORDINATE WITH LADWP AS NECESSARY AND PROVIDE A CONSTRUCTION PHASING PLAN FOR THE VA'S REVIEW AND APPROVAL A MINIMUM OF 3 WEEKS BEFORE SCHEDULED LADWP WORK AND EACH WATER
SHUT-DOWN.
DEMOLITION NOTES
REMOVE PUMP SKID, PIPE AND FITTINGS, AND ELECTRICAL PANEL1
REMOVE BLIND FLANGE2
2 3
REMOVE PLUG3
REMOVE 12" DI WATER MAIN4
EX. EDGE OF PAVEMENT
PROTECT-IN-PLACE
0 10 20
SCALE: 1" = 10'
500,000 GAL. WATER
RESERVOIR
300,000 GAL. WATER
RESERVOIR
REMOVE EX. VALVE, FITTINGS, THRUST BLOCK, AND INTERFERING
PORTIONS OF PIPE
EX. FENCE
PROTECT-IN-PLACE
EX. TREE
PROTECT-IN-PLACE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-M D
1.
D W
G 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1
VAN
EV
EV
EV
EV
BONSALL AVE
DEWEY AVE
W
ILS
HI
RE
B
LV
D
CO
NS
TI
TU
TI
ON
A
VE
NI
MITZ
AV
E
GRA
NT
AV
E
PATTON AVE
RELOCATE VALVE AND VALVE CAN6
RELOCATE FLANGE COUPLING ADAPTER7
EX. PIPING, METERS, VALVES, AND FITTINGS (TO BE REMOVED BY OTHERS/LADWP)8
EX. 12" LADWP METER VAULT (4020755) (VA PIT-1)
TO BE CONVERTED TO A FIRE SERVICE BY
LADWP WITH TWO 6" METERS
EX. LADWP CONCRETE VAULT
PROTECT-IN-PLACE
4 SEE NOTE 8
EX. IRRIGATION CONTROLLERS
PROTECT-IN-PLACE
EX. ELECTRICAL RISER
PROTECT-IN-PLACE
ABANDONED PIT-9
ABANDONED PIT-4
ABANDONED
PIT-2
REMOVE INTERFERING PORTIONS OF EXISTING CHAINLINK FENCE9
EX. CHAINLINK FENCE
EX. CHAINLINK FENCE
EX. 20' WIDE CHAINLINK
DOUBLE-LEAF GATE
4 5
221+50
0+
221+00
101+15
+7
0+
101+00
+7
TANK SITE CIVIL SITE PLAN AND
CONNECTION TO LADWP
CI-101
ELECTRICAL
PULLBOX
ELECTRICAL
PANEL
12" EX. RESERVOIR
OUTLET
PIT-5
ABAND. 12" WATER
(TO V.A. CENTER)
EX. 12" LADWP METER VAULT (4020755) (VA
PIT-1) TO BE CONVERTED TO A FIRE SERVICE
BY LADWP WITH TWO 6" METERS
EXISTING 12" LADWP SERVICE (4020755)
TO LADWP 36" TRANSMISSION MAIN
12" GATE VALVE EX. IRRIGATION
CONTROLLERS
PROTECT-IN-PLACE
EX. 12" C900 WATER MAIN
(MAJESTYC), TO V.A. CENTER
EX. 4" SCH. 80 PVC WATER LINE (IRRIGATION
TO GOLF COURSE)
(POTHOLED)
EX. 6" H.P. LINE (IRRIGATION)
(NOT FOUND)
12" AC WATER TO BE
ABANDONED (TO V.A.
CAMPUS)
EX. ASPHALT
ACCESS ROAD
EX. DOUBLE LEAF
ACCESS HATCH
10" TANK FILL LINE (TO BE
REMOVED FROM SERVICE)
PIT-6
ABANDONED PIT-9
EX. 4" SCH. 40 PVC WATER MAIN TO
GOLF COURSE
(POTHOLED)
PIT-3
ABANDONED PIT-4
8" EX. TANK FILL
LINE
FUTURE LADWP METER VAULT (TO BE
DESIGNED AND CONSTRUCTED BY
LADWP, WITH TWO 4" METERS)
REMOVE PLUG AND
CONNECT TO EX. 12" PIPE
POINT OF CONNECTION MAY VARY,
CONTRACTOR TO COORDINATE
WITH LADWP AS NEEDED
EX. 12" STORM DRAIN
PROTECT-IN-PLACE
500,000 GAL. WATER
RESERVOIR
ABANDONED PIT-2
300,000 GAL. WATER
RESERVOIR
PROPOSED 12" PVC
FIRE WATER
PROPOSED 8" PVC
DOMESTIC WATER
0 10 20
SCALE: 1" = 10'
FUTURE 12" LADWP SERVICE (TO BE
DESIGNED AND CONSTRUCTED BY
LADWP)
EX. ASPHALT
CONSTRUCTION NOTES
4 INSTALL 12" DI 22.5° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
5 INSTALL 12" DI 11.25° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
10 INSTALL 8" DI 90° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
8 INSTALL 8" C900 (DR 18) PVC WATER MAIN PER
2 INSTALL 12" C900 (DR 18) PVC WATER MAIN PER
15 12" FLEXIBLE TRANSITION COUPLING
11 INSTALL 8" DI 22.5° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
SEE DWG CU-101 FOR CONTINUATION
BEGIN CONSTRUCTION
CONNECT TO EX. 12" PIPE
PROFILE A
N: 1846820.57 E: 6420731.00
BEGIN CONSTRUCTION
PROFILE B
N: 1846826.72 E: 6420736.08
SEE DWG CU-116 FOR CONTINUATION
12 INSTALL 8" DI 11.25° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
2 15
STA. 220+64.884 5
STA. 100+03.85 11 12
7 INSTALL 12"x8" DI REDUCER WITH THRUST BLOCK PER LACWD STANDARD W-21
14 OPEN VALVE FOLLOWING CONSTRUCTION AND VA'S ACCEPTNACE
13 NORMALLY CLOSED VALVE FOLLOWING CONSTRUCTION AND VA'S ACCEPTANCE
STA. 99+79.00 7
2-FLGxMJ
STA. 100+30.67 10MJ x MJ
STA. 100+80.92
MJ x MJ
BEGIN CONSTRUCTION
CONNECT TO EX. 12" PIPE
SEE DWG CU-110 FOR CONTINUATION
N: 1846763.43 E: 6420756.53
2 15
3 INSTALL 12" DI 90° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
2-FLGxMJ
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-C I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1
VAN
EV
EV
EV
EV
STA. 220+29.00
STA. 101+15.00
STA. 221+50.00
EX. TANK FILL LINE
EX. RESERVOIR
OUTLET
TANK FILL LINE
STA. 190+00.00
16 RELOCATED FLANGE COUPLING ADAPTER
17 RELOCATED FLANGED GATE VALVE
18 RESTORE AND REPLACE REMOVED SECTION(S) OF CHAINLINK FENCE
PER APWA STANDARD 600-4
16 15
19 REPAIR VAULT WALL FOLLOWING REMOVAL OF 12" WATER PIPE
1 15
STA. 99+75.00
BONSALL AVE
DEWEY AVE
W
ILS
HI
RE
B
LV
D
CO
NS
TI
TU
TI
ON
A
VE
NI
MITZ
AV
E
GRA
NT
AV
E
PATTON AVE
1 INSTALL 12" DI WATER MAIN PER CU-201
A
CU-201
A
CU-201
A
EX. 12" DI
WATER MAIN
MJ x MJ
EX. 12" DI
WATER MAIN
STA. 100+44.99
MJ x MJ10
STA. 100+66.60
MJ x MJ10
BACKFLOW PREVENTER
GATE VALVE
PRESSURE REGULATING VALVE
TRANSITION COUPLING
LEGEND
PIPE PLUG
6 INSTALL 12" PLUG
S6 5°
'27
"W
S6 5°
'27
"W
S29°15'44"W S29°15'54"W
N60°44'16"W
S29°15'44"W
N60°44'16"W S29°15'44"W
S29°15'44"W
CI-102
B
MP-103
A
CI-102
A
MP-102
A
MP-101
A
20 REMOVABLE BOLLARD
(TYP.)
3'-6"
55 ADJUST PRESSURE SETTING TO EXISTING PRESSURE REGULATING VALVE
5520 PSI
5515 PSI
55 8 PSI
4 PSI
10 PSI
TANK SITE PIPELINE PROFILES
CI-102
CONSTRUCT 4.00 LF OF 12" PVC PIPE
EX. SURFACE OVER ℄ OF
PROPOSED WATER MAIN
100+00
221+00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-C I-1
.D
W G
6/
/2
:3 9:
P
M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1
SCALE
VERT: 1"=4'
HORIZ: 1"=10'
101+00
SCALE
VERT: 1"=4'
HORIZ: 1"=10'
220+50 221+50
100+50
BE
G
IN
C
O N
ST
R
U C
TI
O
N
ST
A.
+7 5.0
BE
G
IN
C
O N
ST
R
U C
TI
O
N
0+
.00
EX. SURFACE OVER ℄ OF
PROPOSED WATER MAIN
CONSTRUCT 121.00 LF 12" PVC PIPE
36" MIN.
COVER
12" FW
INV. 468.36
12" SD
12" SD
6" W
60" MIN.
COVER
12" SD
8" W
INV. 470.50
12" W
6" W
8" W
INV. 473.11
EX. CURB
EX. CURB
EX. CHAINLINK
FENCE
EX. CURB
EX. CHAINLINK FENCE
(CROSSING)
CONSTRUCT 136.00 LF OF 8" PVC PIPE
MA
TC
H
LIN
E
ST
AT
IO
N
1+
.00
SE
E
DW
G
CU
-1
MA
TC
H
LIN
E
ST
AT
IO
N
1+
.00
SE
E
DW
G
CU
-1
STA. 100+46.49 TEE
INV. 481.48
STA. 100+54.02 TEE
INV. 481.48
STA. 100+55.52 TEE
INV. 481.48
STA. 100+62.60 TEE
INV. 481.48
HORIZONTAL SCALE: 1"=10'
PROFILE A - UPPER ZONE DOMESTIC WATER
VERTICAL SCALE: 1"=4'
HORIZONTAL SCALE: 1"=10'
PROFILE B - UPPER ZONE FIRE WATER
VERTICAL SCALE: 1"=4'
B
A
ST
A.
0+
.00
G B
IN
V.
1.2
ST
A.
0+
.00
G B
IN
V.
8.6
ST
A.
1+
.00
G B
IN
V.
6.5
ST
A.
1+
.00
G B
IN
V.
5.0
ST
A.
0+
.67
G B
IN
V.
3.4
ST
A.
0+
.07
.25
° B
EN
D
IN
V.
3.1
ST
A.
0+
.62
.25
° B
EN
D
IN
V.
4.0
ST
A.
0+
.98
° B
EN
D
IN
V.
4.0
ST
A.
+7
9 R
ED
UC
ER
IN
V.
6.2
4 (
ST
A.
0+
.10
° B
EN
D
IN
V.
1.9
ST
A.
0+
.00
G B
IN
V.
0.0
ST
A.
0+
.00
G B
IN
V.
9.1
ST
A.
1+
.00
G B
IN
V.
8.6
ST
A.
1+
.00
G B
IN
V.
6.1
12" FW
INV. 466.25
IN
V.
5.9
IN
V.
6.4
IN
V.
4.0
IN
V.
6.9
CONSTRUCTION NOTES
2 INSTALL 8" DI TEE WITH THRUST BLOCK PER LACWD STANDARD W-21
1 INSTALL 12" x 8" DI REDUCER WITH THRUST BLOCK PER LACWD STANDARD W-21
4 3
2 2
4 INSTALL 8" DI 11.25° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
3 INSTALL 8" DI 90° BEND WITH THRUST BLOCK PER LACWD STANDARD W-21
S=-0.0699
S=-0.0349 S=-0.0000 S=0.0199S=0.0000
S=-0.1210 S=-0.0857 S=-0.0506
S=-0.2483 S=-0.0506
S=-0.1325
S=-0.1300
S=-0.1030
S=-0.0770 S=-0.0507
IN
V.
6.3
4 ( 8"
101+15
102+00
103+00
104+00
105+00
106+00
107+00
108+00
109+00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
M :\V
A- W
LA
\G
LA
_P
R O
JE
C
TS
\W
AT
R
ES
\T
AS
KS
\D
ES
IG
N
\S H
EE
TS
\6
-2 1-
(L O
N G
T
ER
M
N
PD
)\L O
N G
T
ER
M P
AC
KA
G E
1\
VA
W
LA
-C U
-1
.D W
G 6/
/2
:3
9:
P M
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
INSTALL DEDICATED FIRE SUPPRESSION
WATER DISTRIBUTION SYSTEM AND
REPLACE POTABLE WATER LINES
WEST LOS ANGELES, CA 90073
691-21-120
Project Director
07.07.22 M.SALCEDO BHRevisions: Date:
ARCHITECT/ENGINEER OF RECORD
OF 47
PACKAGE 1
VAN
EV
EV
EV
EV
SCALE
VERT: 1"=4'
HORIZ: 1"=40'
PROPOSED WATER LINE - SIZE AS INDICATED
EXISTING WATER LINE - SIZE AS INDICATED
EXISTING SEWER LINE - SIZE AS INDICATED
EXISTING COMMUNICATIONS CONDUIT
EXISTING GAS LINE - SIZE AS INDICATED
EXISTING TELEPHONE CONDUIT
EXISTING CONCRETE CURB
EXISTING EDGE OF PAVEMENT (EP)
EXISTING GATE VALVE
EXISTING FIRE HYDRANT (FH)
EXIS…