This document package includes drawings and specifications for a facility wide security camera upgrade project. The project scope involves replacing existing security cameras at multiple buildings within the Salem VA Medical Center campus. Drawings show proposed camera locations, cabling routes, and connections to network equipment in telecommunications rooms. Specifications call for providing and installing new IP-based cameras from Avigilon, along with associated cabling, power supplies, and mounting hardware both interior and exterior. Network infrastructure will be upgraded as needed, including adding fiber optic cabling where runs exceed length limits. Construction documents are marked for full construction and include notes about coordinating work, verifying existing conditions, obtaining required permits, and turning over demolished equipment to authorities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06 36C24623B0019 0004.pdf | ||
| 36C24623B0019 0004_1.docx | DOCX document | |
| S05 36C24623B0019 Facility Wide Security Camera Upgrade Questions 3-20-2023.pdf | ||
| 36C24623B0019 0003_1.docx | DOCX document | |
| S06_36C24623B0019 0003.pdf | ||
| 36C24623B0019 0002_1.docx | DOCX document | |
| S02_ 0002_36C24623B0019 0002.pdf | ||
| S06_36C24623B0019 0001.pdf | ||
| 36C24623B0019 0001_1.docx | DOCX document | |
| S02 Salem Facility Wide Security Camera Upgrade Drawings11-20.pdf | ||
| 36C24623B0019_2.docx | DOCX document | |
| S02 Salem Facility Wide Security Camera Upgrade Drawings1-10.pdf | ||
| S02 Salem Facility Wide Security Camera Upgrade Drawings 31-40.pdf | ||
| S02 Salem Facility Wide Security Camera Upgrade Specs.pdf | ||
| S02 36C24623B0019_1 Fac. Wide Cameras.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NEUROLOGY
TO BUILDING 10
BASEMENT
GENERAL
STORAGE
1F
KITCHEN
11B
EMPLOYMENT
OFFICE
A/C EQUIP
4A
OFFICE
4B
OFFICE
4C
OFFICE
4D
OFFICE
WOMENS
TOILET
7B
MENS
TOILET
SOILED LINEN
7A
3C
OFFICE
3A
3B
OFFICE
STORAGE
11A12 11C
CHASE
13B
9A 10ELECTRICAL
CLOSET
1313A
5MECH
EARTHEN CRAWL SPACE
1K 1J
1A
OFFICE
1I
OFFICE
1B
1L
KITCHEN /
LOUNGE
1C
OFFICE
1D
OFFICE
1H
OFFICE
1E
OFFICE
1G
ELEVATOR
CORRIDOR
TOILET
STAIR
CORRIDOR CORRIDOR
STAIRTOILET
TOILET
CORRIDOR
GENERAL
STORAGE
OFFICE
CORRIDOR
OFFICE WAITING
OIT
2A 2
1PANEL '9-EQD'2
'9-EQD' - 45
3 '9-EQD' -
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
9TK101
BUILDING 9 BASEMENT FLOOR
SECURITY PLAN
1 BUILDING 9 BASEMENT FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
SHEET NOTES:
SHEET KEY NOTES:X
A. NO INTERIOR CAMERAS TO BE REMOVED,
REPLACED, OR ADDED. REFERENCE SHEET
TS101 FOR EXTERIOR CAMERA LOCATIONS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. RETAIN SERVICES TO SYSTEMS
DURING DEMOLITION AND REMODEL OF THE
RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS ARE BASED ON THE
BEST AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION. VERIFY
EXISTING CONDITIONS.
D. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
E. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY EC UNO. ALL CONDUIT
SHALL BE 3/4" MINIMUM. EC TO SIZE CONDUIT
PER THE MOST CURRENT EDITION OF THE NEC.
F. WHERE LENGTH FROM CAMERA TO RACK
EQUIPMENT EXCEED 295' (90M) CONTRACTOR
SHALL USE FIBER OPTIC CABLE AS ILLUSTRATED
IN DETAIL 7/T-502.
G. COORDINATE AND CONFIRM ALL ROUTING WITH
COR PRIOR TO ROUGH-IN.
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. PROPOSED LOCATION OF NEW PoE MID-SPAN
DEVICE, WALL SHELF, AND FLOOR MOUNTED UPS
ABOVE EXISTING WALL MOUNTED EQUIPMENT.
VERIFY LOCATION WITH COR AND OIT
REPRESENTATIVE. REFERENCE 2/T-602 FOR MORE
INFORMATION.
3. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
4. PROVIDE 2 NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOMS 12 AND 2A. COORDINATE RECEPTACLE
LOCATION WITH COR AND OIT REPRESENTATIVE
PRIOR TO ROUGH-IN.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
10/26/2022
TO BUILDING 11
TO BUILDING 9
PIPE CHASE
4A
12 12A
PARTIALLY EXCAVATED
ELEVATOR
MECH
10D
OFFICE
10C
OFFICE
10B
OFFICE
10A
CODER
OFFICE
IRM /
STORAGE /
HOUSE
KEEPING
OFFICE
9A
OFFICE
9B
OFFICE
9C
CART
CHARGING
9D
9E
OFFICE
7A
KITCHEN
STORAGE/FILE ROOM
5A
MENS
TOILET
5B
2D
FILE RM / MAIL RM
2B
2C
TOILET
STAIR
TOILET
STAIR
CORRIDORCORRIDOR
MECH
GENERAL
STORAGE
HAC
TOILET
EXIT
CORRIDOR
EXISTING PANEL -
PANEL '10-LS2'
'10-LS2'
- 19
EF
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
10TK101
BUILDING 10 BASEMENT FLOOR
SECURITY PLAN
1 BUILDING 10 BASEMENT FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
SHEET NOTES:
SHEET KEY NOTES:X
A. NO INTERIOR CAMERAS TO BE REMOVED,
REPLACED, OR ADDED. REFERENCE SHEET
TS101 FOR EXTERIOR CAMERA LOCATIONS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. RETAIN SERVICES TO SYSTEMS
DURING DEMOLITION AND REMODEL OF THE
RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS ARE BASED ON THE
BEST AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION. VERIFY
EXISTING CONDITIONS.
D. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
E. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY EC UNO. ALL CONDUIT
SHALL BE 3/4" MINIMUM. EC TO SIZE CONDUIT
PER THE MOST CURRENT EDITION OF THE NEC.
F. WHERE LENGTH FROM CAMERA TO RACK
EQUIPMENT EXCEED 295' (90M) CONTRACTOR
SHALL USE FIBER OPTIC CABLE AS ILLUSTRATED
IN DETAIL 7/T-502.
G. COORDINATE AND CONFIRM ALL ROUTING WITH
COR PRIOR TO ROUGH-IN.
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. EXISTING PATCH PANELS, SWITCHES, AND UPS.
3. PROPOSED LOCATION OF NEW ETHERNET TO
FIBER CONVERTER-WITH POWER CORD-SERVING
CAMERA NUMBER 14, AND FLOOR MOUNTED UPS.
PROVIDE 4 PR UTP CABLING TO CONNECT
CONVERTER TO EXISTING PATCH PANEL. VERIFY
LOCATION WITH COR AND OIT REPRESENTATIVE.
REFERENCE 2/T-602 FOR MORE INFORMATION.
4. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
5. REMOVE EXISTING CAMERA FIELD DISTRIBUTION
BOX AND ENCODER. SURRENDER EQUIPMENT TO
THE POLICE.
6. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOM 11. COORDINATE RECEPTACLE LOCATION
WITH COR AND OIT REPRESENTATIVE PRIOR TO
ROUGH-IN.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
TO BUILDING 10 TO BUILDING 12
PSYCHIATRY
SERVICE
FIRE PROTECTION
RECEPTION
OFFICE
11F
STORAGE
4D
RECREATION
STORAGE
4B
OCCUPATIONAL
THERAPY
5OFFICE
4A
4C
DAY TREATMENT
3A
DAY TREATMENT
OFFICE
OFFICE
6A
STORAGE
2B
UTILITY
SOILED
2A
OFFICE
6B
OFFICE
1C
GROUP RM
7A
WOMEN
OFFICE
1A
1B
OFFICE
7B
OFFICE
7C IT/ELEC
8A
MEN
HOUSE
KEEPING
ADMIN
OFFICE
13G 13F
OFFICE
13E
OFFICE
13D
OFFICE
13H
OFFICE AREA
OFFICE
13C
CONFERENCE
RM
13B
STORAGE/
ELECTRICAL
11E
11D
WAITING
RM
OFFICE
10A
OFFICE
11C
OFFICE
10B
OFFICE
10C
OFFICE
10D
11B
OFFICE
11A
BREAK
RM/
STORAGE
OFFICE
10E
CORRIDOR
STAIR
CORRIDOR
TOILET
ELEVATOR
STAIR
CORRIDOR
TOILET
TOILET
TOILET
STAIR
CORRIDOR
4B
EXISTING PANEL -
PANEL - '11-LS3'
'11-LS3'
- 37
EF
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
11TK101
BUILDING 11 BASEMENT FLOOR
SECURITY PLAN
1 BUILDING 11 BASEMENT FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
SHEET NOTES:
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. INSTALL NEW PoE MID-SPAN DEVICE IN EXISTING, WALL MOUNTED DATA RACK (COORDINATE EXACT
LOCATION WITH COR AND OIT REPRESENTATIVE).
PROVIDE NEW, FLOOR MOUNTED UPS CLOSE
ENOUGH FOR PoE MID-SPAN DEVICE TO PLUG INTO UPS. COORDINATE WITH PoE MID-SPAN
DEVICE MANUFACTURER FOR POWER CORD
LENGTH. REFERENCE 2/T-602 FOR MORE
INFORMATION.
3. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
4. REMOVE EXISTING CAMERA FIELD DISTRIBUTION
BOX AND ENCODER. SURRENDER EQUIPMENT TO
THE POLICE.
5. PROVIDE NEW 1P, 20A CIRCUIT BREAKER FOR
NEW OUTLET IN IT ROOM 8A.
6. PROVIDE ETHERNET TO FIBER CONVERTER AND
POWER CORD FOR CAMERA NUMBER 11. LOCATE
CONVERTER CLOSE ENOUGH TO UPS FOR
POWER CORD TO PLUG INTO UPS. PROVIDE 4 PR
UTP CABLING TO CONNECT CONVERTER TO
EXISTING PATCH PANEL.
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
SHEET KEY NOTES:X
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
1 1
'12-LS5'
EXISTING PANEL -
PANEL '12-LS5'
12TK101
BUILDING 12 BASEMENT FLOOR
SECURITY PLAN
1 BUILDING 12 BASEMENT FLOOR SECURITY PLAN
1/8" = 1'-0"
SHEET NOTES:
SHEET KEY NOTES:X
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
SHEET KEY NOTES:X
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
NORTH
0 4 8 16
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. EXISTING PATCH PANELS, SWITCHES, AND UPS.
3. PROPOSED LOCATION OF NEW PoE MID-SPAN
DEVICE AND SHELF ABOVE EXISTING SWITCHES
AND BELOW EXISTING PATCH PANELS. PROPOSED
LOCATION FOR UPS ON FLOOR BELOW WALL
MOUNTED EQUIPMENT. VERIFY LOCATION WITH
COR AND OIT REPRESENTATIVE. REFERENCE
2/T-602 FOR MORE INFORMATION.
4. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
5. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOM 5. COORDINATE RECEPTACLE LOCATION
WITH COR AND OIT REPRESENTATIVE PRIOR TO
ROUGH-IN.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
EXISTING PANEL -
PANEL '#1'
'#1' - 21
EXISTING PANEL -
PANEL 'C'EXISTING PANEL -
PANEL '14-MDP1'
EXISTING PANEL -
PANEL 'B'
14TK111
BUILDING 14 FIRST FLOOR
SECURITY PLAN
1 BUILDING 14 FIRST FLOOR SECURITY PLAN
1/8" = 1'-0"
SHEET NOTES:
SHEET KEY NOTES:X
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
NORTH
0 4 8 16
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. EXISTING PATCH PANELS, SWITCHES, AND UPS.
3. PROPOSED LOCATION OF NEW PoE MID-SPAN
DEVICE AND SHELF. PROPOSED LOCATION FOR
UPS ON FLOOR BELOW. VERIFY LOCATION WITH
COR AND OIT REPRESENTATIVE. REFERENCE
2/T-602 FOR MORE INFORMATION.
4. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
5. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOM 104A.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
EXISTING PANEL
- PANEL '1'
EXISTING PANEL
- PANEL '2'
'1' - 37
17TK111
BUILDING 17 FIRST FLOOR
SECURITY PLAN
1 BUILDING 17 FIRST FLOOR SECURITY PLAN
1/8" = 1'-0"
SHEET NOTES:
SHEET KEY NOTES:X
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
NORTH
0 4 8 16
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. EXISTING PATCH PANELS, SWITCHES, AND UPS.
3. PROPOSED LOCATION OF NEW PoE MID-SPAN
DEVICE AND SHELF. PROPOSED LOCATION FOR
UPS ON FLOOR BELOW WALL MOUNTED
EQUIPMENT. VERIFY LOCATION WITH COR AND OIT
REPRESENTATIVE. REFERENCE 2/T-602 FOR MORE
INFORMATION.
4. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
5. REMOVE EXISTING CAMERA FIELD DISTRIBUTION
BOX AND ENCODER. SURRENDER EQUIPMENT TO
THE POLICE.
6. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW OUTLET IN IT ROOM
114.
A. NO INTERIOR CAMERAS TO BE REMOVED,
REPLACED, OR ADDED. REFERENCE SHEET
TS101 FOR EXTERIOR CAMERA LOCATIONS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. RETAIN SERVICES TO SYSTEMS
DURING DEMOLITION AND REMODEL OF THE
RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS ARE BASED ON THE
BEST AVAILABLE INFORMATION AT THE TIME OF
SURVEY AND VISUAL INSPECTION. VERIFY
EXISTING CONDITIONS.
D. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
E. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY EC UNO. ALL CONDUIT
SHALL BE 3/4" MINIMUM. EC TO SIZE CONDUIT
PER THE MOST CURRENT EDITION OF THE NEC.
F. WHERE LENGTH FROM CAMERA TO RACK
EQUIPMENT EXCEED 295' (90M) CONTRACTOR
SHALL USE FIBER OPTIC CABLE AS ILLUSTRATED
IN DETAIL 7/T-502.
G. COORDINATE AND CONFIRM ALL ROUTING WITH
COR PRIOR TO ROUGH-IN.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
IRM
CLOSET
9A
CLOSET
SPRINKLER
VALVE
FP
IRM
STORAGE
10B
FP
13H
CHASE
RADIATION
OFFICE
19B
MALE
TOILET
19A
COMPUTER
TRAINING
RM
STORAGE
IRM
STORAGE
10A
HOUSE -
KEEPING
MED
ADMINISTRATIVE
SPECIALIST
13D
TRANSPORTATION
CO-ORDR
13C
SCHEDULING
CO-ORDR
13B
CLINIC
CONSTRUCTION
OFFICE
13A
OFFICE
CODER
OFFICE
13E
SUPV
OUTPATIENT
CLERKS
13F
IRM
STORAGE
13G
OFFICE
SUPPLIES
STORAGE
A/C MACH RM
14A
STORAGE
15A
WORKSHOP
STORAGE
15C
OFFICE
17A
OFFICE
15B
ELEVATOR
MACH RM
COMPUTER
HELP DESK
COMPUTER HELP
DESK
INTERN I S O
OFFICE
1A
INFO SECURITY
OFFICER
MAIL RM
4I
FILE RM
4H
OFFICE
4C
4G
BREAK RM
4B
MECH RM
4D
FEMALE REST RM
OFFICE
CUBICLES
TRAVEL
CLERK
OFFICE
6A
CHASE
5A
CHASE
PUMP
RM
6C
ELECTRICAL
RM
6B
STAIR
ELEVATOR
CHASE
STAIR
FP
MECH RM
CORRIDOR
CORRIDOR
CORRIDOR
C H
ASE
CORRIDOR
RV
RP
#77
'BLD 74' -
'BLD 74' -
N #78
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
74TK101
BUILDING 74 BASEMENT
FLOOR SECURITY PLAN
1 BUILDING 74 BASEMENT FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
1. REMOVE EXISTING CAMERA AND CABLING BACK
TO SOURCE.
2. INSTALL NEW CAMERA. PROVIDE AND INSTALL
NEW 4 PR UTP CABLING TO NEW PoE MID-SPAN
DEVICE IN IT ROOM 209 ON THE SECOND FLOOR.
REPAIR/REPLACE SURFACES AFFECTED BY
CAMERA EQUIPMENT INSTALLATION TO MATCH
SIMILAR/EXISTING CONDITIONS.
3. REMOVE EXISTING CAMERA. REMOVE
ASSOCIATED EXISTING LOW-VOLTAGE WIRING
BACK TO SOURCE. REPAIR/REPLACE SURFACES
AFFECTED BY REMOVAL OF CAMERA EQUIPMENT
TO MATCH SIMILAR EXISTING CONDITIONS.
4. PROVIDE NEW 4", UL LISTED SLEEVE.
5. REMOVE EXISTING CAMERA FIELD DISTRIBUTION
BOX AND ENCODER. SURRENDER EQUIPMENT TO
THE POLICE.
SHEET NOTES:
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
SHEET KEY NOTES:X
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
FP
FP
RAMP
INFO RESOURCE
MGMT
ELECTRICAL
CLOSET
240C
HOUSEKEEPING
224A
SERVER
RM
227E
DIRECTORS
CONFERENCE
RM
FEMALE
TOILET
CHASE
129A
CHASE
TRAINING
RM
COMPUTER
SPECIALIST
227D
OFFICE
227B
OFFICE
227C
OFFICE
227A
STORAGE
OFFICE
OFFICE
UTILITY
OFFICE
OFFICE
CHIEF OI AND T
OFFICE
LOGISTICS
SVC LINE
201A
OFFICE
STORAGE
FEMALE
TOILET
219A
CHASE
KITCHEN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
COMPUTER
SPECIALIST
CLINICAL
APPLICATIONS
CO-ORDR
NURSING
INFORMATICS
KITCHEN
STORAGE
205A
CONFERENCE
RM
PGM
SUPPORT
212J
PGM ASST
212H
OFFICE
212G
OFFICE
212F
OFFICE
212E
STORAGE
212D
OFFICE
212C
ADMINISTRATIVE
OFFICER
212B
ENVIRONMENT
MGMT INTERN
212A
PGM SUPPORT ASST
TELEPHONE
CLOSET
CHASE
MENS
TOILET
208A
KITCHEN
ENGINEER
TECHNICIAN
OFFICE
207B
ENGINEER
SUPV
207A
ELEVATOR
LOBBY
ELEVATOR
P1-74
240A
241 240 242
STAIR
STAIR
STAIR
LOBBY
CORRIDOR
CORRIDOR
CORRIDORCORRIDORCORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
door/ half or sliding
207C
207D
207E207F
207G
207H
CORRIDOR
ENGINEERING
SERVICE
D6 N #79
'BLD 74' -
PANEL '74-EQ1'
3 '74-EQ1'
- 29
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
74TK121
BUILDING 74 SECOND FLOOR
SECURITY PLAN
1 BUILDING 74 SECOND FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
1. INSTALL NEW CAMERA. PROVIDE AND INSTALL
NEW 4 PR UTP CABLING TO NEW PoE MID-SPAN
DEVICE IN IT ROOM 209. REPAIR/REPLACE
SURFACES AFFECTED BY CAMERA EQUIPMENT
INSTALLATION TO MATCH SIMILAR/EXISTING
CONDITIONS.
2. PROPOSED LOCATION FOR NEW PoE MID-SPAN
DEVICE MOUNTED IN EXISTING, WALL MOUNTED
DATA RACK. PROVIDE NEW, FLOOR MOUNTED UPS
CLOSE ENOUGH FOR PoE MID-SPAN DEVICE TO PLUG INTO UPS. COORDINATE WITH PoE MID-SPAN
DEVICE MANUFACTURER FOR POWER CORD
LENGTH. REFERENCE 2/T-602 FOR MORE
INFORMATION.
3. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
4. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOM 209.
5. NEW CCTV HEAD END EQUIPMENT TO BE
MOUNTED IN NEW CABINET. COORDINATE
LOCATION WITH COR.
6. PROVIDE AND INSTALL NEW
TELECOMMUNICATIONS GROUND BAR.
7. EXISTING UPS WITH 120/208V POWER
DISTRIBUTION PANEL.
8. PROVIDE 1P, 20A CIRCUIT BREAKERS IN THE
EXISTING 120/208V UPS DISTRIBUTION PANEL.
RECEPTACLE AND CIRCUITING TO BE LOCATED
UNDER RAISED FLOOR.
9. PROVIDE NEW 4", UL LISTED SLEEVE.
SHEET NOTES:
SHEET KEY NOTES:X
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
FP
STORAGE
12C
19 1817
STORAGE
13A
STORAGE
FP RM
13B
13C
15A
MEN LOCKER RM
STORAGE
WHEEL
CHAIR
REPAIR
WHEEL CHAIR REPAIR
VENT
4B
STORAGE
4A
STORAGE
12A
STORAGE
STORAGE
12C
ELECTRICAL
12B
STORAGE
STORAGE
9BWOMEN
LOCKER
9ASTORAGE
8A
STORAGE
CLEAN TOWEL
5C
MECH
5A
FITNESS CENTER
MECH
RM
5B
TOILET
STAIR
STAIR
ELEVATOR
TOILET
CORRIDOR
CORR.CORRIDOR
STAIR
16A
OIT
EXISTING PANEL -
PANEL '75-LS3'
'75-LS3'
- 19
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
75TK101
BUILDING 75 BASEMENT FLOOR
SECURITY PLAN
1 BUILDING 75 BASEMENT FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
1. PROVIDE NEW 4", UL LISTED SLEEVE.
2. EXISTING PATCH PANELS AND SWITCHES.
3. PROPOSED LOCATION OF NEW PoE MID-SPAN
DEVICE AND SHELF ABOVE EXISTING SWITCHES
AND BELOW EXISTING PATCH PANELS. PROPOSED
LOCATION FOR UPS ON FLOOR BELOW WALL
MOUNTED EQUIPMENT. VERIFY LOCATION WITH
COR AND OIT REPRESENTATIVE. REFERENCE
2/T-602 FOR MORE INFORMATION.
4. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
5. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOM 14.
6. EXISTING CAMERA FIELD DISTRIBUTION BOX AND
ENCODER TO BE REMOVED AND TURNED OVER
TO COR.
SHEET NOTES:
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
SHEET KEY NOTES:X
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
N #80
'BLD 75' -
N #81
N #82
'BLD 75' -
'BLD 75' -
'75-EQ2'
EXISTING PANEL -
PANEL '75-EQ2'
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
Revisions: Date
CONSULTANTS:
OCTOBER 24, 2022 ADRKTK
658-20-10520-210
CONSTRUCTION DOCUMENTS - FOR CONSTRUCTION
FULLY SPRINKLERED
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 © COPYRIGHT Apogee Consulting Group, P.A. 34Engineers Architects
U.S. Department of Veterans Affairs
FACILITY WIDE SECURITY
CAMERAS UPGRADE
SALEM VA MEDICAL CENTER
1970 ROANOKE BLVD.
SALEM, VA 24153
CAMERA SYMBOL LEGENDCAMERA SYMBOL LEGEND
SYMBOL HEIGHT DESCRIPTION
CCTV FISH EYE
(WP-WEATHER PROOF)
TYPE
12 MP
H4F-DO1-IR
5 MP H5A
24 MP
24C-H4A-3MH
CCTV FIXED DOME
(WP-WEATHER PROOF)
6 MP H5A
360 32 MP
32C-H4A-4MH
3 MP
H4 LPC
FE
MANUFACTURER
AVIGILON
TOTAL
DEVICES
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
AVIGILON
CCTV FIXED DOME
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV MULTISENSOR
(WP-WEATHER PROOF)
CCTV LICENSE PLATE
(WP-WEATHER PROOF)
24 MP
24C-H4A-3MH
24 MP
24C-H4A-3MH
D6
360L
CAMERA ABBREVIATIONS
N
RP
RV
WP
PROVIDE AND INSTALL NEW CAMERA
REPLACE EXISTING CAMERA WITH NEW CAMERA
REMOVE EXISTING CAMERA
WEATHER PROOF
SPECIAL NOTE
ALL CAMERAS LOCATED ON THE EXTERIOR OF THE
BUILDING ARE SHOWN ON SHEET TS101 UNLESS
NOTED OTHERWISE.
WALL RATINGS LEGEND:
SMOKE WALLS S S S
1 HOUR FIRE WALL
S
2 HOUR FIRE WALL
3 HOUR FIRE WALL
D5
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
CEILING
MOUNTED
AVIGILON
75TK121
BUILDING 75 SECOND FLOOR
SECURITY PLAN
1 BUILDING 75 SECOND FLOOR SECURITY PLAN
1/8" = 1'-0"
00 4 8 16
NORTH
1. INSTALL NEW CAMERA. PROVIDE AND INSTALL
NEW 4 PR UTP CABLING TO NEW PoE MID-SPAN
DEVICE IN IT ROOM 246. REPAIR/REPLACE
SURFACES AFFECTED BY CAMERA EQUIPMENT
INSTALLATION TO MATCH SIMILAR/EXISTING
CONDITIONS.
2. EXISTING WALL MOUNTED PATCH PANELS AND
SWITCHES.
3. PROPOSED LOCATION FOR NEW PoE MID-SPAN
DEVICE AND NEW WALL MOUNTED SHELF. MOUNT
SHELF ABOVE SWITCHES AND BELOW PATCH
PANELS (VERIFY LOCATION WITH COR AND OIT
REPRESENTATIVE). PROVIDE NEW, FLOOR
MOUNTED UPS CLOSE ENOUGH FOR PoE
MID-SPAN DEVICE TO PLUG INTO UPS.
COORDINATE WITH PoE MID-SPAN DEVICE
MANUFACTURER FOR POWER CORD LENGTH.
REFERENCE 2/T-602 FOR MORE INFORMATION.
4. PROVIDE POWER OUTLET FOR NEW CCTV
EQUIPMENT. INSTALL POWER OUTLET WITHIN 5
FEET OF NEW UPS LOCATION.
5. PROVIDE NEW 1P, 20A CIRCUIT BREAKER IN
EXISTING PANEL FOR NEW RECEPTACLE IN IT
ROOM 246.
6. PROVIDE NEW 4", UL LISTED SLEEVE.
SHEET NOTES:
SHEET KEY NOTES:X
A. HOME RUN FROM CAMERAS INDICATES THE
TELECOMMUNICATIONS ROOM TO BE USED FOR
NEW CABLING TERMINATIONS ON EXISTING
PATCH PANELS.
B. CCTV SERVICES ARE TO REMAIN ACTIVE
OUTSIDE AREAS UNDER ACTIVE CONSTRUCTION
AT ALL TIMES. FIELD VERIFY CIRCUITS SHOWN
AND RETAIN SERVICES TO ALL DEVICES AND/OR
SYSTEMS DURING DEMOLITION AND REMODEL
OF THE RESPECTIVE AREAS.
C. ALL EXISTING CONDITIONS AND DEVICES ARE
BASED ON THE BEST AVAILABLE INFORMATION
AT THE TIME OF SURVEY AND VISUAL
INSPECTION. VERIFY EXISTING CONDITIONS IN
FIELD.
D. REMOVE ALL UNUSED CONDUIT AND CABLING.
E. INSTALL CONDUCTORS AND CONDUITS
CONCEALED IN NEW WALLS AND PROVIDE A NEW
FACEPLATE.
F. ALL NEW RECEPTACLES SHALL BE LABELED
WITH THEIR SOURCE PANEL AND CIRCUIT
NUMBER.
G. NEW CCTV CABLING TO BE RUN ON J-HOOKS 2'
OC ABOVE CEILING IN CORRIDORS.
H. ALL CONDUIT SECURITY JUNCTION BOXES AND
RACEWAY PROVIDED BY ELECTRICAL
CONTRACTOR UNO. ALL CONDUIT SHALL BE 3/4"
MINIMUM. ELECTRICAL CONTRACTOR TO SIZE
CONDUIT PER THE MOST CURRENT EDITION OF
THE NEC.
I. ALL DEMOLISHED CAMERAS AND ASSOCIATED
EQUIPMENT SHALL BE TURNED OVER TO THE
POLICE DEPARTMENT. COORDINATE WITH COR.
J. COORDINATE EXACT LOCATION OF ALL CAMERAS
DESIGNATED TO BE REMOVED PRIOR TO ANY
WORK BEING DONE.
K. CONTRACTOR TO REPLACE DAMAGED CEILING
TILE AND GRID ASSOCIATED WITH WORK AT NO
ADDITIONAL COST TO THE GOVERNMENT.
L. COORDINATE AND CONFIRM ALL CABLE ROUTING
WITH COR PRIOR TO ROUGH-IN.
DocuSign Envelope ID: 3ADC3376-EFA9-4753-9EE8-D15D0B94D50D
S02 Salem Facility Wide Security Camera Upgrade Drawings