This is a Replacement Parts List for McQuay Central Station Air Handlers, specifically for low-pressure models LHD, LYF, LSL, LML, and LWL (sizes 103-228, Vintage C) and LML and LSB (sizes 106-111, Vintage E). The document was last manufactured in 1999 and is maintained by Daikin Applied.

The parts list provides comprehensive component specifications across multiple sections including nomenclature for model and serial numbers, unit code indices, coils, drive section components, blower section assemblies, and low leak dampers. For coils, the document notes that all Central Station Air Handlers use contractor-style heating, cooling, reheat, and direct expansion coils offered in multiple fin heights and configurations. Contractor coils do not have standard nine-digit Daikin Applied part numbers and must be quoted as needed using model and serial number information. The blower section details multiple wheel types (airfoil and forward curved in various materials), inlet vane assemblies, fan housings, drive shafts, and bearings with specific part numbers for each unit size. The drive section includes motor specifications based on horsepower ratings (1/4 HP through 30 HP) with corresponding motor mount components. Low leak damper assemblies are listed separately for single-fan and dual-fan units with component-level parts for blades, plugs, bushings, and gaskets. Parts requiring special ordering through Daikin Applied are clearly identified, with instructions to contact the distributor at 1-800-377-2787 or www.DaikinApplied.com for availability and specifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

McQuay

Central Station Air Handlers Low Pressure

LHD, LYF, LSL, LML, LWL

103 - 228 Vintage C

LML, LSB

106 - 111

Vintage E

Last Manufactured: 1999

To find your Daikin Applied parts distributor, call 1-800-377-2787 or visit www.DaikinApplied.com

Replacement Parts List No. 055222600 Revision G 12/2019 https://inspectapedia.com/heat/Snyder-General-History-HVAC-Manuals.php Copy at InspectApedia.com

CLICK ANYWHERE on THIS PAGE to RETURN to HVAC MANUALS, AGE, DECODERS, & GUIDES at InspectApedia.com

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 2

Parts List Revision History

Nomenclature

Model Number............................................................................................................................................. 4
Serial Number............................................................................................................................................. 4
Unit Code Index ...................................................................................................................................... 5- 8

Coils

Notes........................................................................................................................................................... 9
Contractor Coil Code Strings..................................................................................................................... 10

Drive Section

Diagram & Components............................................................................................................................. 11
LSB Motor Location Diagram.................................................................................................................... 12
Motor Mount Components......................................................................................................................... 13

Blower Section

Diagram..................................................................................................................................................... 14
Blower Wheels.......................................................................................................................................... 15
Inlet Vane Assemblies............................................................................................................................... 16
Fan Housing.............................................................................................................................................. 17
Drive Shafts............................................................................................................................................... 18
Bearings.................................................................................................................................................... 19

Low Leak Dampers

Diagram & Assemblies.............................................................................................................................. 20
Components For Single Fan Units............................................................................................................ 21
Components For Dual Fan Units............................................................................................................... 22

Contents

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 3

RevisionDateDescription
-5/94Original scanned version.
-6/96Converted to electronic format.
A9/01Changed to single page layout, now 11 pages.
Page 2: Revision page updated
B8/04Page 10: Forward Curved Units with Inlet Vanes had wrong sizes the correction is as follows;
# 049708702 is size 106C/106E, # 049708802 is size 108C/108E & # 049709002 is size
111C/111E.
C5/10Converted file to current software and corrected formatting errors.
Updated Cover and Revision pages with current design logo.
Reorganized form into sections and updated TOC.
Page 4: Added Model Number Nomenclature section.
Page 5: Added Serial Number Nomenclature section.
Page 6- 9: Added Unit Code Index section.
Page 10: Added Coil Section.
Page 11: Changed Part Number note to "These Parts are ordered per Code Item on original
G.O. Contact McQuay Parts with model and serial number information"
Page 12: Added LSB Motor Location Diagram section.
Page 15: Changed footnote #1 to "Obsolete and no longer available. Contact McQuay
Parts for more information."
Page 21, 22: Added Low Leak Damper section.
D4/11Pages 21, 22: Changed Damper End Plug p/n 044951206 to 044961206.
E7/11Pages 6- 9: Clarified Drive Code 13 by adding in "C" vintage codes. Adjusted text fit.
F11/11Page 6: Added "A" code option to Code 06.
G12/19Various: Changed "McQuay Parts" to "Daikin Applied".
Page 2: Updated the TOC to current format.
Page 4- 8: Misc. updates. Fixed formatting issues & text threading.
Page 9: Rewrote Notes & pg. header. Moved updated coil code dwgs. to NEW pg. 10.
Page 10 (NEW): Added pg. for coil code dwgs. from pg. 9. Repaginated the form & updated the TOC.
Page 11 (OLD) 12 (NEW): Created new dwg.
Page 15 (OLD) 16 (NEW): Fixed misc. formatting issues. Added footnote.

Parts List Revision History

Daikin Applied, 13600 Industrial Park Blvd., P.O. Box 1551, Minneapolis, MN 55440 (763) 553-5330

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 4

Nomenclature

Number of Fans 1 = Single Fan 2 = Dual Fan

Vintage C= C Vintage E= E Vintage

Unit Type SeasonMaster & SeasonVent

LSL=Low Pressure, Single Zone, Low Pressure
LML=Low Pressure, Multi Zone, Low Pressure
LWL=Low Pressure, Water Sprayed Coil, Low Pressure
LYF=Low Pressure, Ventilating, Draw Thru
LHD=Low Pressure, Heating and Ventilating, Draw Thru
LSB=Low Pressure, Single Zone, Blow Thru

Nominal Coil Face Area (in Square Feet)

Air Intake into Blower Section H = Horizontal Air Intake V = Vertical Air Intake I = Inverted

Model Number

LSL 1 06 C H

3 Z F 12345 00

Month of Manufacture A = January B = February C = March D = April E = May F = June G = July H = August

Sequence Number

Engineering Revision 3 = Faribault, MN 9 = Scottsboro, AL

Plant Identification

J = September K = October L = November M = December

Year of Manufacture A = 1971 B = 1972 C = 1973 D = 1974 E = 1975 F = 1976 G = 1977 H = 1978 J = 1979 K= 1980 L = 1981 M = 1982 N = 1983 P = 1984 Q = 1985

R = 1986 S = 1987 T = 1988 U = 1989 V = 1990 W = 1991 X = 1992 Y = 1993 Z = 1994 5 = 1995 6 = 1996 7 = 1997 8 = 1998 9 = 1999

Serial Number

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 5

Unit Code Index Code 01= Model (refer to the previous pg. for description)

LHD, LYF, LSL, LML, LWL, LML, LSB

Code 02= Unit Size AND Air Intake direction Five digit code eg.: "106CV".

103C - 228C OR LML, LSB 106E - 111E AND

H= Horizontal intake V= Vertical Intake

Code 03= Fan Wheel and Housing A= Forward Curved Steel Wheel B= Forward Curved Aluminum Wheel C= Forward Curved Hot Dipped Galvanized Wheel D= Airfoil Wheel E= Forward Curved Steel Wheel with Mechanical Speed Control F= Airfoil Wheel with Mechanical Speed Control L= Forward Curved Wheel with Variable Inlet Vanes V= Airfoil wheel with Variable Inlet Vanes

Code 04= Unit Arrangement Digit 1, Unit Arrangement

H= Horizontal
V= Vertical
I= Inverted

Digit 2, Cabinet

1= Standard Fan Cabinet
6= Vertical Discharge (LSB Only)
7= Vertical Discharge w/ Cabinet Extension (LSB Only)

Digit 3, Unit Options

0= Basic Unit LH Air Intake
1= Basic Unit RH Air Intake
2= Fan & Diffuser Section LH Air Intake (LSB Only)
3= Fan & Diffuser Section RH Air Intake (LSB Only)
4= Internal Face & Bypass LH Air Intake
5= Internal Face & Bypass RH Air Intake
5= Internal Face & Bypass Top or RH Duct; RH, Bottom or
Top Air Intake (LHD Only)
6= External Face & Bypass LH Air Intake
6= External Face & Bypass Top or LH Duct; LH, Bottom or
Top Air Intake (LHD Only)
7= External Face & Bypass RH Air Intake
7= External Face & Bypass Top or RH Duct; RH, Bottom or
Top Air Intake (LHD Only)

Digit 4, Section Options

1= No Access or Auxiliary Coil Section
1= No Access or Auxiliary Coil Section w/ 1 or 2 Row Coil
(LHD Only)
1= No Auxiliary Coil Section (LSB Only)
2= Leaving Air Access Section, no Auxiliary Coil Section
3= No Access Section w/ Auxiliary Coil Section
4= Entering Air Access Section w/ Auxiliary Coil Section
5= Leaving Air Access Section w/ Auxiliary Coil Section
7= Leaving Air Access Section w/ Auxiliary Coil Section
when Unit Option (Digit 3) is 6 or 7
8= No Access or Auxiliary Coil section w/ a 3 or 4 Row Coil

Code 05= Mounting Arrangement A= Top Mounting Holes B= Bottom Mounting Holes

Code 06= Fan Discharge and Motor Location

1= CH4= CCBH7= CD
2= CCH5= CU8= CCD
3= CBH6= CCUA= Std.

Code 07= Motor Location For LSB only see LSB Motor Location Diagram otherwise 07= Y.

Code 08= Motor Size

A= .25 HPF= 1.5 HPL= 10.0 HPQ= 40.0 HP
B= .33 HPG= 2.0 HPM= 15.0 HPR= 50.0 HP
C= .50 HPH= 3.0 HPN= 20.0 HPS= 60.0 HP
D= .75 HPJ= 5.0 HPO= 25.0 HPT= 75.0 HP
E= 1.0 HPK= 7.5 HPP= 30.0 HP

Code 09= Unit Voltage

11= 115/60/121= 230/460/329= 230/60/3
12= 200/60/327= 460/60/337= 575/60/3
16= 115/230/60/128= 380/50/3

Code 10= Motor Base and Bearings Y= None 1= Rigid base, Ball Bearing 2= Resilient Base, Sleeve Bearing (LSB Only) 3= Resilient Base, Ball Bearing (LSB Only)

Code 11= Motor RPM and Enclosure Y= None A= 1800 RPM, Open Dripproof (ODP) B= 1800 RPM, Totally Enclosed Fan Cooled (TEFC) C= 1800 RPM, Explosion Proof D= 1800/900 RPM, Two Speed, One Winding E= 1800 RPM, Open Dripproof High Efficiency (ODP)

Code 12= Motor Mounting Y= None 1= Factory Mounted Motor 2= With Motor, Field Mounted

Code 13= Fan Type/Fan Mount/Drive Selection Digit 1, Fan and Drive Type Selection A= Standard Forward Curve Fan, Rigid Fan mount, Variable

Speed Drive
B= Low Pressure Forward Curve Fan, Adjustable Speed Drive
(C Vintage)
B= Standard Forward Curve Fan, Isolated Fan mount, Variable
Speed Drive
C= Medium Pressure Forward Curve Fan, Adjustable Speed
Drive (C vintage)
C= Optional Forward Curve Fan, Rigid Fan mount, Variable
Speed Drive
D= Airfoil Fan, Adjustable Speed Drive (C vintage)
D= Optional Forward Curve Fan, Isolated Fan mount, Variable
Speed Drive
E= Standard Airfoil Fan, Rigid Fan mount, Variable Speed Drive
F= Airfoil Fan, Fixed Drive (C Vintage)
F= Standard Airfoil Fan, Isolated Fan mount, Variable Speed
Drive or Fixed Drive with Maxi Drive
G= Optional Airfoil Fan, Rigid Fan mount, Variable Speed Drive
H= Optional Airfoil Fan, Isolated Fan mount, Variable Speed Drive
J= Standard Forward Curve Fan, Rigid Fan mount, Fixed
Speed Drive
K= Standard Forward Curve Fan, Isolated Fan mount, Fixed
Speed Drive
L= Low Pressure Forward Curve Fan, Fixed Drive (C Vintage)
L= Optional Forward Curve Fan, Rigid Fan mount, Fixed
Speed Drive or Fixed Speed Drive with Maxi Drive
M= Medium Pressure Forward Curve Fan, Fixed Drive
(C Vintage)
M= Optional Forward Curve Fan, Isolated Fan mount, Fixed
Speed Drive or Fixed Speed Drive with Maxi Drive
N= Standard Airfoil Fan, Rigid Fan mount, Fixed Speed Drive
P= Standard Airfoil Fan, Isolated Fan mount, Fixed Speed Drive
Q= Optional Airfoil Fan, Rigid Fan mount, Fixed Speed Drive
R= Optional Airfoil Fan, Isolated Fan mount, Fixed Speed Drive
Continued on next page.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 6

Code 13= Fan/Fan Type/Fan Mount/Drive Selection, Cont.

Digit 2 & 3, Drive Selection Contact Daikin Applied with model and serial number information in order to identify the needed part(s).

Digit 4, Fan Discharge

1= Code 06 equals 1, or 2
2= Code 06 equals 3, or 4
3= Code 06 equals 5, or 6
4= Code 06 equals 7, or 8

Digit 4, Fan Discharge (LSB Only)

1= Code 07 equals 1
2= Code 07 equals 2
3= Code 07 equals 3
4= Code 07 equals 4

Code 14= Lubrication Lines & Insulation 1= Standard Lube lines 1", 3/4# Insulation 2= Standard Lube lines No Insulation 3= Standard Lube lines 1", 1 1/2# Insulation 4= Standard Lube lines 1", 3# Insulation 5= Copper Lube Lines 1", 3/4# Insulation 6= Copper Lube lines No Insulation 7= Copper Lube Lines 1", 1 1/2# Insulation 8= Copper Lube lines 1", 3# Insulation A= Standard Lube Lines & Liner Options (LSB Only. Code 39 must not be YY.)

B= Copper Lube Lines & Liner Options (LSB Only. Code 39 must not be YY.)

Code 15= Zone Dampers (LML Only) AA= Zone Damper with Hot Deck Shaft Extension BB= Zone Damper with Cold Deck Shaft Extension CC= Double Duct Collar Only 2A= 2 Deck Zone Damper with Hot Deck Shaft Extension 2B= 2 Deck Zone Damper with Cold Deck Shaft Extension 2C= Double Duct Collar 3A= 3 Deck Zone Damper with Hot Deck Shaft Extension 3B= 3 Deck Zone Damper with Cold Deck Shaft Extension 3C= Triple Duct Collar XX= Special

Code 16= Accessory Arrangement Digit 1, Accessory Section Code 04= H*** or I***

Y= None
A= Filter Section Only
B, C, D= Filter Section and or Mixing Box with Dampers
E, F, G= Filter Section and or Mixing Box without Dampers

Digit 1, Accessory Section Code 04= V***

Y= None
H, K, M= Base Mounted Filter Section and or Mixing Box with
Dampers
J, L, N= Base Mounted Filter Section and or Mixing Box
without Dampers

Digit 2, Filter Section

0= No Filters
1= Flat Filters End Removal
2= Flat Filters Right Side or Bottom Removal
3= Flat Filters Left Side or Top Removal
4= Angular Filters
5= Heavy Duty Angular Filters

Digit 3, Filter Type

0= None
1= Throwaway
2= Cleanable Low Velocity
3= Cleanable High Velocity
4= Throwaway, 35% Pleated

Code 17= Auxiliary Coil Section Y= None S= Small Coil L= Large Coil

Code 18= Auxiliary Coil Type and Rows For coil features see Contractor Coil codes in Unit Coil Section.

YYYYYYYYYY= None XXXXXXXXXX= Special Coil

Code 19= Auxiliary Coil Connection Location Y= None D= Drive End E= Opposite Drive End

Code 20= Standard Coil Section, 1st Coil Y= None S= Small Coil L= Large Coil E= Extra Large Coil

Code 21= Coil Types and Rows, 1st Coil For coil features see Contractor Coil codes in Unit Coil Section.

YYYYYYYYYYYYYYY= None XXXXXXXXXXXXXXX= Special Coil

Code 22= Coil Connection Location, 1st Coil D= Drive End E= Opposite Drive End

Code 23= Standard Coil Section, 2nd Coil Y= None H= Heating Coil S= Small Coil L= Large Coil E= Extra Large Coil

Code 24= Coil Types and Rows, 2nd Coil For coil features see Contractor Coil codes in Unit Coil Section.

YYYYYYYYYYYYYYY= None XXXXXXXXXXXXXXX= Special Coil

Code 25= Coil Connection Location, 2nd Coil Y= None D= Drive End E= Opposite Drive End

Code 26= Standard Coil Section, 3rd Coil Y= None S= Small Coil L= Large Coil E= Extra Large Coil

Code 27= Coil Types and Rows, 3rd Coil For coil features see Contractor Coil codes in Unit Coil Section.

YYYYYYYYYYYYYYY= None XXXXXXXXXXXXXXX= Special Coil

Code 28= Coil Connection Location, 3rd Coil Y= None D= Drive End E= Opposite Drive End

Unit Code Index, Continued

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 7

Code 29= Optional Features Y= None A= Gasketed Damper Blades on Mixing Box & Bypass Dampers C= Flex Connector on Blower Intake D= Flex Connector on Blower Discharge E= Flex Connector on Blower Intake & Discharge F= Stainless Steel Drain Pan or Liner H= Galvanized Steel Moisture Eliminators J= Stainless Steel Moisture Eliminators K= Insulated Mixing Box L= Items A & F M= Enclosed Belt Guard W= Outdoor Construction less Weatherhood X= Special

Code 30= Plug-In Door (Blower Section) Digit 1, Access Door Location

Y= None
1= Top Opposite Drive End
2= Side Opposite Drive End
X= Special

Digit 2, Access Door Dimensions

Y= None
A= 8" x 9"
B= 12" x 24"
C= 18" x 24"
D= 36" x 48"
X= Special

Code 31= Plug-In Door (Coil Section) Digit 1, Access Door Location

Y= None
6= Drive End
7= Opposite Drive End
X= Special

Digit 1, Access Door Location (LML/LSB Only)

Y= None
8= Drive End
9= Opposite Drive End
X= Special

Digit 2, Access Door Dimensions

Y= None
B= 12" x 24"
C= 18" x 24"
X= Special

Digit 2, Access Door Dimensions (LML/LSB Only)

Y= None
D= Full Hinged
B= 12" x 24"
C= 18" x 24"
X= Special

Code 32= Miscellaneous Y= None X= Special

Code 33= Balance Plate (LML Only) Digit 1, Coil Type

Y= None
H= Heating
C= Cooling
X= Special

Digit 2 & 3, Balance Plate Size For more information contact Daikin Applied

Unit Code Index, Continued Code 34= ARI Approval

Code 35= Packaging

Code 36= Latest Code Sheet Revision

Code 36= Coil or Diffuser Sections Insulation Liners 1" Only (LSB Only) Digit 1, Type of Liners (LSB Only)

Y= None
1= 1", 3/4# Insulation
2= 1", 1 1/2# Insulation
3= 1" 3# Insulation
4= 1", 3/4# Foil Faced Insulation

Digit 2, Type of Liners (LSB Only)

Y= None
P= Perforated Liners
S= Solid Liners
X= Special

Code 37, 38= Warranty Codes (LSB Only)

Code 39= Blower Section Liners (LSB Only) Digit 1, Type of Insulation (LSB Only)

Y= None
A= 2" 1 1/2# Insulation
X= Special

Digit 2, Type of Liner (LSB Only)

Y= None
S= Solid Liner
P= Perforated Liner
X= Special

Code 40= Coil Section Liners (LSB Only) Digit 1, Type of Insulation (LSB Only)

Y= None
A= 2" 1 1/2# Insulation
X= Special

Digit 2, Type of Liner (LSB Only)

Y= None
S= Solid Liner
P= Perforated Liner
X= Special

Code 41= Auxiliary Coil Section Liners (LSB Only) Digit 1, Type of Insulation (LSB Only)

Y= None
A= 2" 1 1/2# Insulation
X= Special

Digit 2, Type of Liner (LSB Only)

Y= None
S= Solid Liner
X= Special

Code 42= Filter Section Liners (LSB Only) Digit 1, Type of Insulation (LSB Only)

Y= None
A= 2" 1 1/2# Insulation
X= Special

Digit 2, Type of Liner (LSB Only)

Y= None
S= Solid Liner
X= Special

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 8

Unit Code Index, Continued Code 43= Mixing Box Liners (LSB Only) Digit 1, Type of Insulation (LSB Only)

Y= None
A= 2" 1 1/2# Insulation
X= Special

Digit 2, Type of Liner (LSB Only)

Y= None
S= Solid Liner
X= Special

Code 44= Not A Central Station Air Handler Code YY= None

Code 45= Auxiliary Coil Section Liners (LSB Only) Digit 1, Type of Insulation (LSB Only)

Y= None
A= 2" 1 1/2# Insulation
X= Special

Digit 2, Type of Liner (LSB Only)

Y= None
S= Solid Liner
X= Special

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 9

Coils Notes

All Central Station Air Handlers use Contractor style Heating, Cooling, Reheat, and/or DX Coils.

Contractor Coils are offered in multiple fin heights to allow the user to select the coil size to match the air flow. Contractor Coils offer a wider range of circuitings, rows and fins, and materials than the standard Unit Coil.

Contractor Coils are always quoted as needed when needed, so they DO NOT HAVE STANDARD

ORDERABLE OR “HARD/PERMANENT” NINE DIGIT DAIKIN APPLIED PART NUMBERS.

When a replacement Coil is required, a Contractor Coil quote needs to be prepared. To quote a replacement Contractor Coil it is necessary to obtain model and serial number information from the Unit Nameplate and then contact Daikin Applied.

If the unit has more than one Coil it will also be necessary to confirm which Coil(s) are needed BEFORE quoting. If there is more than one coil in the unit, confirm WHICH coil is needed and the TOTAL NUMBER of coils required BEFORE ordering.

In some instances coils were manufactured separately from the unit and may have a unique serial number eg.: 9Z12345-00. A coil with a serial number starting with a "9" was built in Scottsboro AL and may or may not have been installed in a unit before shipment.

Note that the sample code strings shown on the following page are INCOMPLETE and DO NOT furnish enough information for Daikin Applied to quote. General Order (GO) and/or serial number information is required in order to properly quote a Contractor Coil.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 10

Coils Contractor Coil Code Strings 1

5W H - 10 02 C - 033.00 - 090.00

COIL TYPE

Water: 5M, 5W, 5K, 5P, 5Q Booster: 5B

CIRCUITING

Water:

Q = 1/4 Serpentine H = 1/2 Serpentine L = 3/4 Serpentine S = 1 Serpentine M = 1-1/2 Serpentine D = 2 Serpentine B = 3” Tube Center

Booster:

S = 1 Circuit D = 2 Circuit B = 3” Tube Center

FINNED LENGTH (INCHES)

FIN HEIGHT (INCHES)

FIN DESIGN

B = 01, 02, 03 & 04 ROW E-F5

C = 01, 02, 03 & 04 ROW HI-F5

ROWS DEEP (01, 02, 03, 04)

FINS PER INCH

(06, 07, 08, 09, 10, 11, 12, 13, 14)

5 SA - 12 02 C - 033.00 - 090.00

COIL TYPE:

5SA = Single tube, opposite end connection 5JA,8JA = Distributing tube, same end connection 8RA = Distributing tube, opposite end connection 5HA = High pressure construction, single tube, opposite end connection 5GA,8GA = High pressure construction, distributing tube, same end connection 8TA = High pressure construction, distributing tube, opposite end connection

FIN DESIGN:

B = 01 & 02 ROW E-F5

C = 01 & 02 ROW HI-F5

B = 01 ROW HI-F8 (1”)

ROWS DEEP:

HI-F5, E-F5 (01, 02)

HI-F8 (01)

FINS PER INCH:

HI-F5, E F5 (06, 07, 08, 09, 10, 11, 12, 13, 14)

HI-F8 (03, 04, 05, 06, 07, 08, 09, 10, 11, 12, 13, 14)

TUBE O.D.:

5 = 5/8 inch 8 = 1 inch FIN HEIGHT (INCHES)

FINNED LENGTH (INCHES)

5W S - 10 06 C - 18 x 45

COIL TYPE

Water: 5M, 5W Evaporator: 5E

CIRCUITING

Water:

H = 1/2 Serpentine L = 3/4 Serpentine S = 1 Serpentine M = 1-1/2 Serpentine D = 2 Serpentine

Evaporator:

N = Normal F = Face Control R = Row Control J = Interlaced K = Interlaced Face Control

FINNED LENGTH (INCHES)

FIN HEIGHT (INCHES)

FIN DESIGN

C = HI-F5

B = E-F5

ROWS DEEP ( 02, 03, 04, 05, 06, 08, 10, 12)

FINS PER INCH

(06, 07, 08, 09, 10, 11, 12, 13, 14)

1 Note that the sample code strings shown above are INCOMPLETE and DO NOT furnish enough information for Daikin Applied to quote.

General Order (GO) and/or serial number information is required in order to properly quote a Contractor Coil.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 11

1 MOTOR •

2 BELT •

3 BELT GUARD •

4 SHEAVES •

N/S BUSHING •

Drive Section Diagram & Components

Unit Sizes

3C

4C

6C

, 1

E

8C

, 1

E

1C

, 1

E

6C

9C

4C

7C

2C

8C

DescriptionBub.

No. Part Number

These Parts are ordered per Code Item on original G.O.

Contact Daikin

Applied with model and serial number information.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 12

Drive Section LSB Motor Location Diagram

A= Motor Location.

= Air intake direction.

Code 06= 1 Code 07= 3

A A

A

A

A

Code 06= 2 Code 07= 3

Code 06= 3 Code 07= 2

Code 06= 4 Code 07= 2

A

Code 06= 1 Code 07= 4

Code 06= 2 Code 07= 4

Code 06= 3 Code 07= 3

Code 06= 4 Code 07= 3

A

A

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 13

48 56 14 3T

5T

2T

4T

3T

5T

4T

6T

4T

6T

Drive Section Motor Mount Components

Motor Frame Size 1

Description Part Number

1/4 HP THRU 2 HP MOTOR
MOTOR MOUNT WITH MOUNTING HARDWARE0293044011111
3 HP THRU 5 HP MOTOR
MOTOR MOUNT WITH MOUNTING HARDWARE02930440211
7-1/2 HP THRU 10 HP MOTOR
MOTOR MOUNT WITH MOUNTING HARDWARE02930440311
15 HP THRU 20 HP MOTOR
MOTOR MOUNT WITH MOUNTING HARDWARE02930440411
25 HP THRU 30 HP MOTOR
MOTOR MOUNT WITH MOUNTING HARDWARE02930440511

1 Based on normal NEMA frame sizes.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 14

Blower Section Diagram

13 8

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 15

3C

4C

6C

, 1

E

8C

, 1

E

1C

, 1

E

6C

9C

4C

7C

2C

8C

Unit Sizes

DescriptionBub.

No. Part Number

Blower Section Blower Wheels

1 Obsolete and no longer available. Contact Daikin Applied for more information.

AIRFOIL UNITS - OPTIONAL
5NO. 1225, DIDW, CLASS ll0233924121
5NO. 1350, DIDW, CLASS ll0233924131
5NO. 1500, DIDW, CLASS ll0233924141
5NO. 1825, DIDW, CLASS ll02339241511
5NO. 2225, DIDW, CLASS ll02339241611
FORWARD CURVED, HOT DIPPED GALVANIZED 1
5NO. 1225, FCDW, CLASS l02855311912
5NO. 1550, FCDW, CLASS l0285533191
5NO. 1650, FCDW, CLASS l02855342312
5NO. 1350, FCDW, CLASS l0285532192
5NO. 1500, FCDW, CLASS l0285533232
5NO. 2000, FCDW, CLASS l0285535312
FORWARD CURVED, ALUMINUM - OPTIONAL
5NO. 1225, FCDW, CLASS l01273001912
5NO. 1550, FCDW, CLASS l0145754191
5NO. 1650, FCDW, CLASS l01272942312
5NO. 1350, FCDW, CLASS l0145763192
5NO. 1500, FCDW, CLASS l0145754232
5NO. 2000, FCDW, CLASS l0145771312
FORWARD CURVED, STEEL - FCDW
5STANDARD, 1.0" BORE0190894001
5OPTIONAL, HI STATIC, 1.1875" BORE0276667001
5STANDARD, 1.0" BORE0190893001
5OPTIONAL, HI STATIC, 1.4375" BORE0179624001
5STANDARD, CLASS l0280365002
5STANDARD, NO. 1225, CLASS l01258711912
5STANDARD, NO. 1350, CLASS l0125875192
5STANDARD, NO. 1500, CLASS l0125879191
5STANDARD, NO. 1500, CLASS l0125879232
5STANDARD, NO. 1650, CLASS l01258832312
5STANDARD, NO. 2000, CLASS l0125891312

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 16

3C

4C

6C

, 1

E

8C

, 1

E

1C

, 1

E

6C

9C

4C

7C

2C

8C

Unit Sizes

DescriptionBub.

No.

Blower Section Inlet Vane AssembIies 1

Part Number

N/SFORWARD CURVE ASSEMBLY, CW0497526151
N/SFORWARD CURVE ASSEMBLY, CCW0497526161
N/SFORWARD CURVE ASSEMBLY, CW0497526031
N/SFORWARD CURVE ASSEMBLY, CCW0497526041
N/SFORWARD CURVE ASSEMBLY, CW0497526051
N/SFORWARD CURVE ASSEMBLY, CCW0497526061
N/SAIRFOIL, CW02402970911
N/SAIRFOIL, CCW02402971011
N/SAIRFOIL, CW02402971311
N/SAIRFOIL, CCW02402971411

N/S = Not shown on diagram.

1 Note that Inlet Vane Assemblies may be obsolete and no longer available. Contact Daikin Applied with model and serial number information to confirm part availability BEFORE ordering.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 17

Fan Housings

Unit Sizes

3C

4C

6C

, 1

E

8C

, 1

E

1C

, 1

E

6C

9C

4C

7C

2C

8C

DescriptionBub.

No. Part Number

For units with Inlet Vanes consult Daikin Applied.

FOR USE WITH FORWARD CURVED WHEELS
WITHOUT INLET VANES
6STANDARD - FCDW0494878001
6OPTIONAL - FCDW, HI STATIC0658927001
6STANDARD - FCDW0190936001
6OPTIONAL - FCDW, HI STATIC0494874001
6STANDARD - FCDW, NO. 1202796560112
6STANDARD - FCDW, NO. 130279656022
6STANDARD - FCDW, NO. 1502796560312
6STANDARD - FCDW, NO. 1602796560412
6STANDARD - FCDW, NO. 200279656052
6STANDARD - FCDW0494879002
WITH INLET VANES
6DESIGN U NO. 120497072011
6DESIGN U NO. 150497072021
6DESIGN U NO. 160497072031
FOR USE WITH AIRFOIL WHEELS WITHOUT INLET VANES.
6DWAF, DESIGN UR NO. 120274641011
6DWAF, DESIGN UR NO. 150274641021
6DWAF, DESIGN UR NO. 160274641031
6DWAF, DESIGN URA NO. 1802746410411
6DWAF, DESIGN URA NO. 2202746410511

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 18

Unit Sizes

3C

4C

6C

, 1

E

8C

, 1

E

1C

, 1

E

6C

9C

4C

7C

2C

8C

DescriptionBub.

No. Part Number

Drive Shafts

AIRFOIL UNITS - CCW
71-3/16" DIA.45.00" L0275553011
71-7/16" DIA.46.00" L0275554011
71-7/16" DIA.54.00" L0275555011
71-15/16" DIA.66.00" L0276924001
71-15/16" DIA.73.00" L0276925001
72-3/16" DIA.80.00" L0276926001
72-3/16" DIA.92.00" L0276927001
AIRFOIL UNITS - CW
71-3/16" DIA.45.00" L0275553011
71-7/16" DIA.46.00" L0275554011
71-7/16" DIA.54.00" L0275555011
71-15/16" DIA.66.00" L0275556001
71-15/16" DIA.73.00" L0275557001
72-3/16" DIA.80.00" L0275558011
72-3/16" DIA.92.00" L0275550001
FORWARD CURVED UNITS WITHOUT INLET VANES
71" DIA. , STANDARD42.00" L0280721011
71-3/16" DIA., HI STATIC42.00" L0277858011
71" DIA., STANDARD48.00" L0280722011
71-7/16" DIA. HI STATIC47.50" L0166804011
71-3/16" DIA.45.00" L0280723011
71-3/16" DIA.65.00" L0280724011
71-3/16" DIA.45.00" L0280725011
71-3/16" DIA.78.00" L0280726011
71-7/16" DIA.52.00" L0280727011
71-3/16" DIA.78.00" L0280728001
71-7/16" DIA.90.00" L0280729001
71-7/16" DIA.96.00" L0280730001
71-15/16" DIA.116.00" L0280732001

FORWARD CURVED UNITS WITH INLET VANES

71-3/16" DIA.47.00" L0497087021
71-3/16" DIA.47.00" L0497088021
71-7/16" DIA.55.50" L0497090021

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 19

3C

4C

6C

, 1

E

8C

, 1

E

1C

, 1

E

6C

9C

4C

7C

2C

8C

Unit Sizes

DescriptionBub.

No. Part Number

Blower Section Bearings

N/S = Not shown on diagram.

AIRFOIL UNITS - FLANGE
81-3/16" BORE0206493021
81-7/16" BORE02064930311
81-15/16" BORE02064930511
82-3/16" BORE02064930611
AIRFOIL UNITS - PILLOW BLOCK
N/S1-3/16" BORE0206486122
N/S1-7/16" BORE02064860122
N/S1-15/16" BORE02064860322
N/S2-3/16" BORE02064860422
FORWARD CURVED UNITS - FLANGE
81" BORE, STANDARD WHEEL02064930122
81-3/16" BORE, HI STATIC WHEEL0206493022
81-7/16" BORE, HI STATIC WHEEL0206493032
81-3/16" BORE02064930211111
81-7/16" BORE020649303111
81-15/16" BORE0206493051

FORWARD CURVED UNITS - PILLOW BLOCK

N/S1-3/16" DIA. BORE02064861211222
N/S1-7/16" DIA. BORE020648601122
N/S1-15/16" DIA. BORE0206486032

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 20

Low Leak Dampers Diagram & Assemblies

5Low Leak Damper Assembly 12 3/8" x 25 3/8"0458142001
5Low Leak Damper Assembly 12 3/8" x 31 3/8"0458143001
5Low Leak Damper Assembly 12 3/8" x 41 3/8"0458144001
5Low Leak Damper Assembly 18 3/8" x 39 3/8"0458148001
5Low Leak Damper Assembly 18 3/8" x 54 3/8"0458149001

111108106104103 Part

Number

Unit Size Bub.

No.

Damper Assemblies, Single Fan Units 1

5Low Leak Damper Assembly 12 3/8" x 60 3/8"0458145001
5Low Leak Damper Assembly 12 3/8" x 74 3/8"0458146001
5Low Leak Damper Assembly 18 3/8" x 69 3/8"0458152001
5Low Leak Damper Assembly 18 3/8" x 84 3/8"0458151001
5Low Leak Damper Assembly 24 1/8" x 88 3/8"0458152001
5Low Leak Damper Assembly 24 1/8" x 111 3/8"048544901 21

228222217214209 Part

Number

Unit Size Bub.

No.

Damper Assemblies, Dual Fan units 1

1 No actuator motors, actuator linkage, sensors, or controls were supplied with Central Station Air Handlers.

2 For units built before 12/86 use Damper p/n: 045815300.

Description

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 21

Components for Single Fan Units

6Damper Blade (Less Gasket)0441932012
Damper Blade (Less Gasket)0441932022
Damper Blade (Less Gasket)0441932032
Damper Blade (Less Gasket)0583868063
Damper Blade (Less Gasket)0441932073
7Damper Blade Center Support045812800NANANANA2
15Damper Blade Gasket
Gasket ordered by the foot as required029870900-----
16Driven Damper Blade End Plug Assy. RH04496120511111
17Driven Damper Blade End Plug Assy. LH04496120611111
18Non Driven Damper End Plug RH04100350511122
19Non Driven Damper End Plug LH04100350611122
20Nylon Damper Blade Bushing04373040022244
21Nylon Damper Blade Drive Shaft Bushing04373400044444
22Nylon Linkage Bar Bushing04609830044466
230.50" Locking Collar04911590222222

111108106104103 Description

Part Number

Qty. for Unit Size Bub.

No.

Air Handlers; LHD,LYF,LSL,LML,LWL 103-228 Vint. C/ LML,LSB 106-111 Vint. E Rev. G 12/19 RPL 0552226 / Page 22

Components For Dual Fan Units

2Blade Support (After 12/86)048544401NANANANANA1
6Damper Blade (Less Gasket)0583868042
Damper Blade (Less Gasket)0583868052
Damper Blade (Less Gasket)0583868083
Damper Blade (Less Gasket)0441932093
Damper Blade (Less Gasket)0441933013
Damper Blade (Less Gasket Before 12/86)0462803013
Damper Blade (Less Gasket After 12/86)0477933013
7Damper Blade Center Support04581290022
Damper Blade Center Support04581280022
Damper Blade Center Support0449613002
Damper Blade Center Support (Before 12/86)0449613002
Damper Blade Center Support (After 12/86)0485446011
15Damper Blade Gasket
Gasket ordered by the foot as required029870900------
16Driven Damper Blade End Plug Assy. RH044961205111
Driven Damper Blade End Plug Assy. RH0672492051
Driven Damper Blade End Plug Assy. RH04496120811
17Driven Damper Blade End Plug Assy. LH044961206111
Driven Damper Blade End Plug Assy. LH0672492061
Driven Damper Blade End Plug Assy. LH04496120911
18Non Driven Damper End Plug RH0410035051222
18Non Driven Damper End Plug RH04100350822
19Non Driven Damper End Plug LH0410035061222
19Non Driven Damper End Plug LH04100350922
20Nylon Damper Blade Bushing043730400224444
21Nylon Damper Blade Drive Shaft Bushing043734000444444
22Nylon Linkage Bar Bushing046098300446666
230.50" Locking Collar049115902222222

228222217214209

Qty. for Unit Size Bub.

No.

Part Number 206

Blank Page