S02 - Drawings Vol 3 of 4.pdf
PDF 17 MB Posted
- Solicitation number
- 36C25224B0016
About this file
This document appears to be a set of drawings (S02 - Drawings Vol 3 of 4.pdf) related to Solicitation Number 36C25224B0016, "Z1DA--607-22-101 Renovate Inpatient Ward 7B (VA-25-00007172)," issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12.
The solicitation is for the renovation of Inpatient Ward 7B. Key details include the renovation of the ward, the federal agency involved (Department of Veterans Affairs), and the solicitation number. No further details about required products/services, response dates, award dates, pricing terms, set asides, or incumbents are provided in this particular document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S06 - Updated Drawings - 0003.pdf | ||
| 36C25224B0016 0003.docx | DOCX document | |
| S06 - Updated Spec Sections - 0003.pdf | ||
| S06 - Drawing AC020204 - 0003.pdf | ||
| 36C25224B0016 0002.docx | DOCX document | |
| S06 - SF1442 Page 1 - Revised.pdf | ||
| S06 - Wage Determination Revised.pdf | ||
| 36C25224B0016 0001.docx | DOCX document | |
| S04 - Pre-Bid Attendance List.pdf | ||
| 36C25224B0016.docx | DOCX document | |
| S02 - Specs Vol 2 of 3.pdf | ||
| S02 - Specs Vol 1 of 3.pdf | ||
| S02 - Drawings Vol 2 of 4.pdf | ||
| S02 - Drawings Vol 1 of 4.pdf | ||
| S02 - Specs Vol 3 of 3.pdf | ||
| S02 - Drawings Vol 4 of 4.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KEY NOTES:
GENERAL NOTES:
AAP
7B-02
111111111111
1 1
SOILED UTILITY
B7073
NURSE ALCOVE
B7121A
HSKPG
B7059
EQUIP.
B7121I
CONSULT
B7081B
NURSE
MANAGER
B7077
NURSE STATION
B7081
ELEC
B7121F
PAT TLT
B7071A
PAT TLT
B7063B
PAT TLT
B7062B
BREAK / CONF
B7099
Unoccupied
Unoccupied
ELEC
B7121D
ANTE
B7074
ANTE
B7076
PAT TLT
B7098A
PAT TLT
B7094A
MEDS ALCOVE
B7121J
PATIENT RM
B7098
PATIENT RM
B7094
PATIENT RM
B7092
PAT TLT
B7092A
PAT TLT
B7088A
EPI PATIENT RM
B7088
EPI PATIENT RM
B7086
PAT TLT
B7082A
PAT TLT
B7086A
PAT TLT
B7080A
PAT TLT
B7076B
ISO PATIENT RM
B7076A
PATIENT RM
B7070
ISO PATIENT RM
B7074A
PAT TLT
B7074B
PAT TLT
B7070A
MEDS ALCOVE
B7121B
PATIENT RM
B7068
PAT TLT
B7068A
PAT TLT
B7064A
PATIENT RM
B7064
EPI/BARI
PATIENT RM
B7065
PAT TLT
B7069A
PAT TLT
B7065A
BARI PATIENT
RM
B7069
PATIENT RM
B7071
NOURISH
B7085
CLEAN UTILITY
B7087
PATIENT RM
B7082
PATIENT RM
B7080
LOCKER
B7099A
SHARED
EPI/PM&R
B7093
EQUIP.
STORAGE
B7095
PATIENT RM
B7089
CRASH CART
B7121E
ANTE
B7062
ISO PATIENT RM
B7062A
ASSIST NURSE
MANGER
B7060
PT TREATMENT
B7061
ISO PATIENT RM
B7063A
ANTE
B7063
CORRIDOR
B7121
STAFF TLT
B7097
PP171
C
D
E
G
292827262524232221201918
ZVB
7B-01
3/4" MA
1 1/4" O
2" MV
3/4" MA
3/4" O
3/4" MV
3/4" MA
1 1/4" O
3/4" MV
1 1/4" O
3/4" MV
3/ 4"
M A
3/ 4"
O 3/
4" M
V
3/4" MA
1" O
3/4" MV
1/2" MA
1/2" O
3/4" MV
3/4" MA 3/4" MA
3/4" MV
1 1/4" O
3/4" MA
2" MV
1 1/4" O
1" O
3/4" MV
3/4" MA
3/4" O
3/4" MV
3/4" MA
3/ 4"
M A
1/
4" O
3/ 4"
M V
3/4" MA
1 1/4" O
3/4" MV
1" O3/4" MV
3/4" O
3/4" MA
TYPICAL
1 EXTEND 1/2" OXYGEN, 1/2" MEDICAL AIR, AND 3/4" MEDICAL VACUUM
TO PREFABRICATED PATIENT HEAD WALL. REFER TO ARCHITECTURAL
ELEVATIONS FOR EXACT LOCATIONS.
4" CONCRETE SLAB ABOVE WITHIN AREA INDICATED BY DASHED LINE,
USE SHALLOW ANCHOR BOLTS FOR DUCTWORK AND PIPING
SUPPORTS.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
CONTRACTOR SHALL REFER TO THE VA MASTER SPECIFICATION
MANUAL EDITED FOR THIS PROJECT ALONG WITH ANY APPLICABLE
STANDARDS WITHIN THE VA DESIGN GUIDES. ALL REQUIREMENTS OF
THOSE MANUALS SHALL BE MAINTAINED IN ADDITION TO ALL NOTES
AND DESCRIPTIONS INDICATED WITHIN THESE DRAWINGS. ANY
CONFLICTS BETWEEN THE DOCUMENTS SHOULD BE BROUGHT TO THE
ATTENTION OF THE ENGINEER FOR INTERPRETATION.
CONTRACTOR WILL BE RESPONSIBLE TO REVIEW ACCESSIBILITY TO
AREAS OUTSIDE THE CONSTRUCTION LIMITS TO DETERMINE
APPROXIMATE AMOUNT OF OVERTIME REQUIRED TO PERFORM ALL
MECHANICAL WORK INDICATED. COORDINATION OF SCHEDULES WITH
ADJACENT DEPARTMENTS AND CLEANING OF ALL DEBRIS AFTER EACH
WORK SHIFT SHOULD BE ASSUMED IN THE BASE BID SCOPE.
ANY MAJOR OUTAGES INDICATED ON THESE DRAWINGS SHALL BE
SCHEDULED TO BE PERFORMED AFTER NORMAL BUSINESS HOURS OR
DURING WEEKEND PERIODS TO MINIMIZE HOSPITAL DISRUPTION. VA
HOSPITAL FACILITIES WILL REQUIRE A MINIMUM OF TWO (2) WEEKS
NOTICE PRIOR TO ANY SUCH OUTAGE.
COORDINATE ALL NEW MEDICAL GAS PIPING ROUTING WITH ALL OTHER
TRADES TO ENSURE ADEQUATE CLEARANCES FOR ELECTRICAL
CONDUIT, HVAC DUCTWORK & PIPING, STRUCTURAL SUPPORTS, ETC.
ANY UNAVOIDABLE CONFLICTS SHALL BE BROUGHT TO THE ATTENTION
OF THE ARCHITECT/ENGINEER OF RECORD. PROVIDE ALL OFFSETS &
TRANSITIONS AS REQUIRED FOR A CLEAN INSTALLATION.
SUPPORT ALL PIPING DIRECTLY TO STRUCTURE. DO NOT SUPPORT ANY
PIPING FROM DUCTWORK, CONDUIT OR OTHER PIPING ENCOUNTERED.
WHERE MECHANICAL SYSTEMS TO REMAIN ARE DAMAGED OR
DISTURBED DURING THE COURSE OF CONSTRUCTION, THE
CONTRACTOR WILL BE RESPONSIBLE TO REMOVE DAMAGED PORTIONS
AND INSTALL NEW PRODUCTS OF EQUAL QUALITY AND FUNCTIONALITY.
ALL EXISTING PIPING THROUGH NEW FIRE RATED WALLS SHALL BE
ADEQUATELY FIRE SEALED AS REQUIRED. PIPING PENETRATIONS
THROUGH INTERSTITIAL FLOOR SHALL BE DRILLED OR CUT BY THE
CONTRACTOR AND FIRE SEALED AS REQUIRED.
ALL CORE DRILLING OR ANY ACTIVITIES CAUSING EXTREME VIBRATION
OR NOISE SHALL BE COORDINATED TO BE PERFORMED AFTER
BUSINESS HOURS TO NOT AFFECT CRITICAL HOSPITAL FUNCTIONS
WITHIN ADJACENT AREAS. COORDINATE WITH VA REPRESENTATIVE AS
REQUIRED.
FIELD VERIFY EXISTING MEDICAL GAS PIPING SYSTEMS FOR
CONNECTIONS TO OUTLETS THAT MAY NOT BE IDENTIFIED ON PLANS
PRIOR TO SERVICE OUTAGES, DEMOLITION OR ALTERATIONS OF
EXISTING PIPE ROUTING. COORDINATE WITH FACILITIES AND ENGINEER
OF RECORD.
CONTRACTOR SHALL MAINTAIN ACCURATE RECORD DRAWINGS
SHOWING ALL DISCREPANCIES WITH ANY EXISTING PIPING INDICATED
OR REVISIONS TO THE NEW MEDICAL GAS LAYOUTS. ALL CHANGES WILL
BE UPDATED WITHIN THE FINAL RECORD DRAWING SET.
ALL CONTRACTORS TO REFERENCE THE INFECTION CONTROL NOTES
IDENTIFIED WITHIN THE VENTILATION GENERAL NOTES ON THESE
DRAWINGS. CONFORM TO ALL ICRA REQUIREMENTS.
ALL MEDICAL GAS PIPE BRANCHES AND TAKE-OFFS TO COME OFF TOP
OF PIPE MAIN.
ALL MEDICAL GAS PIPING MINIMUM SIZES TO BE 1/2" WITH THE
EXCEPTION OF MEDICAL VACUUM. MINIMUM MEDICAL VACUUM PIPE
SIZE TO BE 3/4".
POWER TO AREA ALARM PANELS AND ALARMS ARE TO BE PROVIDED BY
THE ELECTRICAL CONTRACTOR. ALL LOW VOLTAGE WIRING TO BE
PROVIDED BY THE MECHANICAL CONTRACTOR.
VENTILATOR MEDICAL GAS ASSUMPTIONS FOR PATIENT FLOOR:
- TOTAL DEVELOPED LENGTH FROM FURTHEST FIXTURE BACK TO
SYSTEM = 700 FT
- TOTAL PRESSURE DROP ACROSS PIPING = 4 PSI
- MAXIMUM PRESSURE DROP = 0.55 PSI PER 100 FT
- TOTAL MEDICAL AIR CAPACITY = 550 LITER PER MINUTE @ 3/4"
- TOTAL OXYGEN CAPACITY = 1,800 LITER PER MINUTE @ 1-1/4"
- VENTILATOR CONSUMPTION = 60 LITER PER MINUTE
MAXIMUM NUMBER OF VENTILATORS AT % OXYGEN:
% OXYGEN % MEDICAL AIR MAXIMUM NUMBER OF VENTILATORS
20% (12 LPM) 80% (48 LPM) 11
80% (48 LPM) 20% (12 LPM) 37
100% (60 LPM) 0% (0 LPM) 30
NORTH
KEY PLAN - B-WING OVERALL
B
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:5
P
M
PM170
LEVEL 7 - MEDICAL GAS PLAN
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
1/8" = 1'-0"
1 LEVEL 7 - MEDICAL GAS PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Revision# Description Date:
2" CW
3/4" RCW
1" CW
P-101
CW = 6
HW = 0
1" CW
P-701
CW = 1
HW = 1
P-401
CW = 0.5
HW = 0.5
3/4" RHW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
P-501
CW = 1.5
HW = 1.5
1/2" HW
1/2" CW
1" HW
CW = 9
HW = 3
P-501
CW = 1.5
HW = 1.5
1/2" CW
1/2" HW
P-502
CW = 1.5
HW = 1.5
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1
P-701
CW = 1
HW = 1
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
1" CW
1/2" HW
1/2" CW
P-101
CW = 6
HW = 0
1" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
P-501
CW = 1.5
HW = 1.5
P-501
CW = 1.5
HW = 1.5
2" CW
1 1/2" HW
CW = 30
HW = 12
P-501
CW = 1.5
HW = 1.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-101
CW = 6
HW = 0
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1
P-701
CW = 1
HW = 1
1/2" CW
1/2" HW
1" CW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
1" CW
1/2" HW
1/2" CW
HW = 16.5
CW = 46.5
P-501
CW = 1.5
HW = 1.5
P-101
CW = 6
HW = 0
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1
P-701
CW = 1
HW = 1
1" CW
1" CW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
P-501
CW = 1.5
HW = 1.5
P-501
CW = 1.5
HW = 1.5
2 1/2" CW
2" HW
HW = 24
CW = 66
P-101
CW = 6
HW = 0
P-101
CW = 6
HW = 0
P-501
CW = 1.5
HW = 1.5
P-501
CW = 1.5
HW = 1.5
P-701
CW = 1
HW = 1
P-701
CW = 1
HW = 1
1" CW
1" CW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
1" HW
1" CW
2 1/2" CW
2" HW
HW = 30
CW = 84
P-501
CW = 1.5
HW = 1.5
P-501
CW = 1.5
HW = 1.5
P-101
CW = 6
HW = 0
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1 P-701
CW = 1
HW = 1
1" CW
1" CW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
3" CW
2" HW
HW = 36
CW = 102
P-501
CW = 1.5
HW = 1.5
P-502
CW = 1.5
HW = 1.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-401
CW = 0.5
HW = 0.5
P-101
CW = 6
HW = 0
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1
P-701
CW = 1
HW = 1
1" CW
1" CW
1/2" CW
1/2" HW
1" CW
1" HW
3" CW
2" HW
CW = 120
HW = 42
P-501
CW = 1.5
HW = 1.5
P-101
CW = 6
HW = 0
P-401
CW = 0.5
HW = 0.5
1" CW
3" CW
2" HW
HW = 44
CW = 128
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1
P-401
CW = 0.5
HW = 0.5
P-501
CW = 1.5
HW = 1.5
1" CW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
1/2" CW
1/2" HW
P-501
CW = 1.5
HW = 1.5
1/2" CW
1/2" HW
2" HW
3" CW
CW = 138.5
HW = 48.5
P-501
CW = 1.5
HW = 1.5
P-502
CW = 1.5
HW = 1.5
P-501
CW = 1.5
HW = 1.5
P-401
CW = 0.5
HW = 0.5
P-101
CW = 6
HW = 0
P-701
CW = 1
HW = 1
P-601
CW = 0.25
HW = 0
1" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" CW
3" CW
2" HW
HW = 54.5
CW = 150.75
P-501
CW = 1.5
HW = 1.5P-102
CW = 6
HW = 0
P-102
CW = 6
HW = 0
P-402
CW = 0.5
HW = 0.5
P-402
CW = 0.5
HW = 0.5
P-501
CW = 1.5
HW = 1.5P-701
CW = 1
HW = 1
P-701
CW = 1
HW = 1
1" CW
1" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" CW
1/2" HW
1" HW
1" CW
2" HW
3" CW
CW = 168.75
HW = 60.5
P-501
CW = 1.5
HW = 1.5
P-401
CW = 0.5
HW = 0.5
P-701
CW = 1
HW = 1
P-101
CW = 6
HW = 0
1 1/2" CW
1/2" HW
1/2" CW
3" CW
CW = 177.75 HW = 63.5
1" CW
3/4" HW
3/4" HW
1" CW
1" HW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
1" HW
1" CW
1" HW
1" CW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
1" CW
1" HW
1" CW
1" HW
1/2" CW
1/2" HW
1" CW
1" HW
1/2" CW
1/2" HW
1/2" HW
1/2" CW 3/4" HW
1" CW
1" CW
3/4" HW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1" HW
3" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW1" CW
1/2" HW
1/2" CW
1/2" HW
1" HW
1" CW
1/2" HW
1/2" CW
1/2" HW
1/2" CW
1/2" CW
1/2" HW
3/4" HW
1" CW
1/2" CW
1/2" HW
3" CW
1" HW
1/2" CW
1/2" HW
2" HW
1" CW
1" HW
3/4" CW
3/4" HW
1 1/2" HW
2 1/2" CW
P-503
CW = 0
HW = 0
P-708
CW = 0
HW = 0
THERMOSTATIC
MIXING VALVE
SEE 2/P200 FOR
CONTINUATION
1/2" CW
1/2" HW
ICE MACHINE
1/2" FW
1/2" FW
P-802
P-802
P-802
P-802
SOLENOID
VALVE
BALANCING
VALVE
1.0 GPM
BALANCING
VALVE
1.0 GPM
1/2" TW
1/2" TW
1/2" TW
1/2" TW
3/4" TW
1" TW
1" TW
3/4" TW
1" TW
1/2" TW
1/2" TW
1/2" TW
BALANCING
VALVE
1.0 GPM
1" TW
1" TW
1/2" TW
1" TW
1" TW
1" TW
1/2" TW
BALANCING
VALVE
1.0 GPM
1" TW
1" TW
1" RPZ
THERMOSTATIC
MIXING VALVE
REFER TO DIALYSIS
CABINET WATER DRAIN
BOX ASSEMBLY DETAIL
REFER TO DIALYSIS
CABINET WATER DRAIN
BOX ASSEMBLY DETAIL
REFER TO DIALYSIS
CABINET WATER DRAIN
BOX ASSEMBLY DETAIL
PROVIDE
THERMOMETER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:4
P
M
P200
PLUMBING RISER DIAGRAMS -
DOMESTIC WATERStone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
NO SCALE
1 PLUMBING RISER DIAGRAMS - DOMESTIC WATER
PAT TLT
B7062B
ANTE
B7062
PATIENT RM
B7064
MEDS
ALCOVE
B7121B
PAT TLT
B7068A
PAT TLT
B7064A
PATIENT RM
B7068
PATIENT RM
B7070
PAT TLT
B7070A
PAT TLT
B7074A
ANTE
B7074
ANTE
B7076
PAT TLT
B7080A
PAT TLT
B7076B
PATIENT RM
B7080
PATIENT RM
B7082
PAT TLT
B7082A
PAT TLT
B7086A
EPI PATIENT
RM
B7088
EPI PATIENT
RM
B7086
PAT TLT
B7092A
PAT TLT
B7088A
PATIENT RM
B7092
PATIENT RM
B7094
PATIENT RM
B7098
PAT TLT
B7094A
PAT TLT
B7098A
MED ALCOVE
B7121J
BREAK/CONF
B7099
STAFF TLT
B7097
PAT TLT
B7089A
PATIENT RM
B7097
NOURISH
B7085
MEDS
B7081A
SOILED
UTILITY
B7073
PAT TLT
B7071A
PATIENT RM
B7071
BARI
PATIENT RM
B7069
PAT TLT
B7065A
PAT TLT
B7069A
EPI/BARI
PATIENT RM
B7065
ANTE
B7063
PAT TLT
B7063B
NO SCALE
2 PLUMBING RISER DIAGRAM - NON-POTABLE TEMPERED WATER
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAIN
LOW POINTS.
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAIN
LOW POINTS.
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAIN
LOW POINTS.
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAIN
LOW POINTS.
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAINS
LOW POINTS.
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAIN
LOW POINTS.
PROVIDE DRAIN
DOWN VALVES ON
CW AND HW MAIN
LOW POINTS.
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer
4" W P-101
DFU = 4
WCO
2" V
P-701
DFU = 2
2" V
2" W
P-401
DFU = 1
2" V
4" W
DFU = 10
2" W
2" W
P-501
DFU = 3
2" V
DFU = 10
4" V
2" FD-1
4" W
P-701
DFU = 2
4" W 2" V
2" V
P-701
DFU = 2
2" V
2" W
P-402
DFU = 1
2" W
2" V
P-402
DFU = 1
P-501
DFU = 3
P-102
DFU = 4
P-102
DFU = 4
2" V 2" V
P-501
DFU = 3
2" V
2" V
DFU = 17
2" W
DFU = 20
4" W
P-101
DFU = 4 P-701
DFU = 2
P-401
DFU = 1
4" W
2" V
2" V 5" W
DFU = 7
5" W
DFU = 24
2" FD-1
P-502
DFU = 3P-501
DFU = 3
P-601
DFU = 0.5
2" W
2" V
2" W
DFU = 8.5
DFU = 13.5
2" V
4" V UP
P-501
DFU = 3
2" V
2" W
4" W
DFU = 3
3" V UP
DFU = 3
P-501
DFU = 3
2" W
2" V
4" V UP
DFU = 3
P-501
DFU = 3
P-701
DFU = 2
P-101
DFU = 4
P-401
DFU = 1
2" FD-1
2" W
2" V
2" V
2" V
4" W
2" V
4" W
DFU = 53
4" V
DFU = 10
P-501
DFU = 3
P-101
DFU = 4
P-401
DFU = 1
2" FD-1
P-501
DFU = 3
2" W
2" V
2" W
4" W
2" V
2" V
4" W
DFU = 7
2" W
DFU = 1
2" V
DFU = 8
2" W
2" V
4" W
DFU = 3
P-101
DFU = 4
P-101
DFU = 4 P-401
DFU = 1
P-401
DFU = 1
P-701
DFU = 2
P-701
DFU = 2
2" V 2" V
2" V
P-502
DFU = 3
2" V
DFU = 2
DFU = 2
4" W
DFU = 19
4" V UP
DFU = 20
P-501
DFU = 3
P-501
DFU = 3
2" W
2" W
4" W
DFU = 6
P-101
DFU = 4
P-101
DFU = 4
P-701
DFU = 2
P-701
DFU = 2
P-401
DFU = 1
P-401
DFU = 1
2" V2" V
2" V
2" V
2" V
4" V UP
DFU = 48
2" W
4" W
DFU = 14
P-501
DFU = 3
P-501
DFU = 3
4" W
DFU = 20
2" W
2" V
2" V
P-101
DFU = 4
P-101
DFU = 4
P-701
DFU = 2
P-701
DFU = 2
P-401
DFU = 1
P-401
DFU = 1
4" W
4" W
DFU = 14
2" V 2" V
2" V
DFU = 20
P-501
DFU = 3
P-501
DFU = 3
P-101
DFU = 4
P-101
DFU = 4
P-401
DFU = 1
P-401
DFU = 1
P-701
DFU = 2
P-701
DFU = 2
4" W
DFU = 21
4" W
DFU = 21
4" V
DFU = 21
2" V
2" V
2" V
2" V
P-501
DFU = 3
2" V P-501
DFU = 3
P-401
DFU = 1
P-401
DFU = 1
P-701
DFU = 2
P-701
DFU = 2
P-101
DFU = 4
P-101
DFU = 4
2" W
4" W
2" V 2" V
4" W
DFU = 17
4" V
DFU = 10
4" V UP
DFU = 38
DFU = 2
P-401
DFU = 1
P-401
DFU = 1
P-701
DFU = 2
P-701
DFU = 2
P-101
DFU = 4
P-101
DFU = 4
P-501
DFU = 3
P-501
DFU = 3
2" V
4" W
2" W
2" W
4" V
DFU = 8
P-502
DFU = 3
4" V UP
DFU = 23
2" V
2" V
2" W 4" W
DFU = 10
P-501
DFU = 3
P-501
DFU = 3
P-101
DFU = 4
P-401
DFU = 1
P-701
DFU = 2
4" W
DFU = 32
4" W
DFU = 38
2" V
4" V UP
DFU = 13 2" V
2" W
SEE 2/P201 FOR
CONTINUATION
SEE 2/P201 FOR
CONTINUATION
SEE 2/P201 FOR
CONTINUATION
2" W
2" W 1 1/2" W
2" W
2" W
2" W UP
1 1/2" W UP
2" W
4" W UP
4" W
1 1/2" W
1 1/2" W UP
1 1/2" W UP
1 1/2" W
4" W UP
4" W
1 1/2" W UP
1 1/2" W
4" V UP
4" W UP
4" W
1 1/2" W UP
1 1/2" W
2" V 2" V
2" W
2" W
P-802
DFU = 3
P-802
DFU = 3
4" W UP
4" W
4" W
2" W
2" W
2" W
4" W
1 1/2" W UP
1 1/2" W
4" W UP
4" W
4" W UP
1 1/2" W UP
4" W 2" V
4" W UP
4" W
1 1/2" W UP
4" W UP
4" W
4" W 4" W
2" W
2" W
2" W UP
2" W UP
4" W UP
4" W
4" W
2" W
2" V
3" V
4" W
3" V
4" W
4" W UP
4" W
4" W
4" V
1 1/2" W
1 1/2" W
SEE 1/P201 FOR
CONTINUATION
4" FD-1
DFU = 4
4" FD-1
DFU = 4
4" FD-1
DFU = 4
4" W 4" W
4" VTR
4" W
4" W
4" W
2" W
2" V
4" W
2" V
4" W
4" W
2" V
P-708
4"FD-W
4"FD-W
DFU = 4
DFU = 4
DFU = 4
DFU = 0
DFU = 0
SEE 1/P201 FOR
CONTINUATION
SEE 1/P201 FOR
CONTINUATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:5
P
M
P201
PLUMBING RISER DIAGRAM - WASTE
AND VENTStone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
NO SCALE
1 PLUMBING RISER DIAGRAM - WASTE AND VENT - 7B
NO SCALE
2 PLUMBING RISER DIAGRAM - WASTE AND VENT - PENTHOUSE
PAT TLT
B7063B
PT
TREATMENT
B7061
ISO PATIENT
RM
B7063A
EPI/BARI
PATIENT RM
B7065
PAT TLT
B7065A
PAT TLT
B7069A
BARI
PATIENT RM
B7069
PATIENT RM
B7071
PAT TLT
B7071A
SOILED
UTILITY
B7073
MEDS
B7081A
CONSULT
B7081B
NOURISH
B7085
PATIENT RM
B7089
CLEAN LINEN
B7091
PAT TLT
B7089A EQUIP.
STORAGE
B7095
BREAK/CONF
B7099
STAFF TLT
B7097
LOCKER
B7099A
PATIENT RM
B7098
PAT TLT
B7094A
PAT TLT
B7098A
PATIENT RM
B7094
PATIENT RM
B7092
PAT TLT
B7088APAT TLT
B7092A
EPI PATIENT
RM
B7086
EPI PATIENT
RM
B7088
PAT TLT
B7086A
PAT TLT
B7082A
PATIENT RM
B7082
PATIENT RM
B7080
PATIENT TLT
B7080A
PATIENT TLT
B7076B
ISO PATIENT
RM
B7076A
ISO PATIENT
RM
B7074A
PATIENT TLT
B7074B
PATIENT TLT
B7070B
PATIENT RM
B7070
PATIENT RM
B7068
MEDS
ALCOVE
B7121B
PATIENT TLT
B7064A
PATIENT TLT
B7068A
PATIENT RM
B7064
ANTE
B7062
PATIENT TLT
B7062B
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer
4" ORD-1
1,612 SQFT
62 GPM
4" RD-1
1,612 SQFT
62 GPM
4" SD
FCO
FCO
CO
SEE CIVIL FOR
CONTINUATION
SEE CIVIL FOR
CONTINUATION
WCO
124 GPM
4" SD
124 GPM
4" ORD-1
1,612 SQFT
62 GPM 4" RD-1
1,612 SQFT
62 GPM
4" SD
124 GPM
4" SD
124 GPM
4" SD
124 GPM
4" RD-1
650 SQFT
25 GPM
4" RD-1
1370 SQFT
53 GPM
4" SD
25 GPM
4" SD
78 GPM
78 GPM
6" SD
202 GPM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:5
P
M
P202
PLUMBING RISER DIAGRAM - STORM
DRAINAGEStone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
NO SCALE
1 PLUMBING RISER DIAGRAM - STORM DRAINAGE
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer
PROVIDE 2" 'GAP-CAP' MODEL 8500 TO
MAINTAIN THE REQUIRED DRAIN CONNECTION
AIR GAP. (COORDINATE EXACT DIMENSION)
QUICK CONNECTION FITTING PIPED
DOWN TO 'GAP-CAP' ASSEMBLY,
COLDER MODEL HFC12 OR EQUAL.
CIRCUIT SETTER VALVE BALANCED
EACH TO PROVIDE APPROXIMATELY 1.0 GPM (TYPICAL)
3/4"NON-POTABLE WATER
FOR TRAP PRIMERS
ATTACH QUICK CONNECTION FITTING, COLDER
MODEL NS6 OR EQUAL, TO STAINLESS PIPE.
PIPING TEE CONNECTION WITH 1/2"
ISOLATION VALVE INSIDE CABINET
11/2"VENT
2"C.I. SANITARY PIPE
2"PVC TRAP WITH
WALL ACCESS PANEL
1/2"CONNECTION TO TAILPIECE
FOR TRAP PRIMER SYSTEM
MECHANICAL CONTRACTOR TO VERIFY
SUPPORT SPACING WITH SITE CONDITIONS
1/2"NON-POTABLE
TRAP PRIMER PIPE
1" NON-POTABLE WATER
LOOP PIPING (FLOW UPWARD)
PROVODE STAINLESS STEEL WALL
BOXES DESIGNED TO FIT BETWEEN 16" STUDS.
BOXES EACH WITH STAINLESS PIANO
HINGE AND FULL FRONT COVER WITH CYLINDER
LOCK. LABEL BOXES WITH BLACK LETTERING
ON EXTERIOR ON COMPLETION.
PIPE SLEEVE WITH FIRE
CAULKING THROUGH FLOOR
BACK-TO-BACK BOXES TO
BE IN ADJACENT STUD SPACES
"A
F F
A T
T O
P
"A
F F
A T
T O
P
FRONT VIEWSIDE VIEW
1"FLANGE
DETERMINE DEPTH NEEDED
FOR SERVICE VALVE (3.5"-4.5")
RETURN FLANGE AS REQUIRED
8-1/2"INSIDE BOX
8- 1/
2"
IN
S
ID
E B
O X
CYLINDER LOCK AND
EXAMPLE #1 (FLUSH MOUNT)
SECURITY HASP
1" NON-POTABLE WATER
LOOP PIPING (FLOW DOWNWARD)
SPRINKLER RISER
BUTTERFLY
VALVE WITH
TAMPER
SWITCH
CHECK VALVE
TO WET PIPE FIRE
SPRINKLER
SYSTEM.
FLOW SWITCH
PRESSURE GAUGE
TEST VALVE
AND
DRAIN
PRESSURE
RELIEF
VALVE
BALL VALVE WITH
LATCH LOCK
(TYPICAL) THERMOMETER
TW
CEILING
CW
HW
WALL
TW
FLOOR
VENT
WASTE
UNION
(TYPICAL) THERMOSTATIC
MIXING VALVE
CHECK VALVE
(TYPICAL)
APPROVED PANNING
MATERIAL
CONNECT
PIPING TO
DRAIN BODY.
SEE PLANS
FOR SIZE.
SEE PLANS
FOR TYPE
18"
18" WITH 1/2"
SLOPE
NOTES:
1. MAINTAIN 1/4" AIR GAP
BETWEEN SURFACE AND
SUB-SURFACE DRAIN
(NOT IN CONTRACT).
H O
T W
A
TE
R
C O
LD
W
A T E
R
FLOOR
MOP BASIN
WALL FAUCET
THRU
WALL
JANITOR SINK FAUCET
ACCESSIBLE
CHECK VALVES
ABOVE CEILING
COLD WATER
IN WALL
THRU
WALL
EXPOSED
BACKFLOW
PREVENTOR
INSTALLED
AT MAXIMUM
5'-0" A.F.F
NOTES:
1. PIPE LABEL SHALL INCLUDE DETAILS OUTLINED IN DIVISION 21, 22, 23 SPECIFICATIONS.
2. LABELS SHALL BE LOCATED IMMEDIATELY AT BOTH SIDES OF A WALL.
PIPE LABEL PIPE LABEL
P
IP
E L
A B
E L
P
IP
E L
A B
E L
' M
A X
IM
U
M
PIPE LABEL
25' MAXIMUM
FLOOR
WALL
NOTES:
1. SET DRAINS AT INSULATION HEIGHT. VERIFY HEIGHT AND TYPE OF INSULATION.
ROOFING
MATERIAL
FLASHING
PRESSURE
TREATED WOOD
BLOCKING
STEEL DECK
DECK CLAMP
SEE PLAN FOR
PIPE SIZES
INSULATION
INSULATION
BASE
STOP VALVE
(TYPICAL)
STAINLESS STEEL
FLEX HOSE (TYPICAL)
THERMOMETER
EYEWASH/FAUCET
THERMOSTATIC
MIXING VALVE
COUNTER TOP
ANGLE STOP
VALVE
(TYPICAL)
FAUCET
COUNTER TOP
HOT
COLD
COLD
MIXED
ASSE 1070 THERMOSTATIC
MIXING VALVE, INLET CHECKS
AND SCREENS, MOUNT MIXING
VALVE TO MAINTAIN
ACCESIBILITY TO TEMPERATURE
ADJUSTMENT SCREW
FAUCET SUPPLIES
(RIGID OR FLEX)
STRAIGHT
STOP VALVE
INLINE CHECK, CHICAGO
243.315.AB.1 OR EQUAL
3/8" HOT WATER
BYPASS, CHROME
PLATED COPPER
TUBE
COLD
WATER
SUPPLY
VENT PIPE
WASTE PIPE
P-TRAP
BALL VALVE
(TYPICAL)
VENT PIPE
BACKFLOW PREVENTER
FILTERED WATER TO
ICE/COFFEE MAKER
WALL CASEWORK
WATER FILTER PROVIDED
BY OWNER AND INSTALLED
BY PLUMBING CONTRACTOR
DRAIN FROM ICE/COFFEE MAKER
FLOOR
TOE KICK ATTACHED TO
CABINET WITH 3/4" GAP
ABOVE FLOOR
LOCATE FLOOR SINK AS FAR
BACK IN CABINET SPACE AS
POSSIBLE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:5
P
M
P300
PLUMBING DETAILS
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
NO SCALE
1 WET SPRINKLER SYSTEM ZONE CONTROL ASSEMBLY DETAIL
NO SCALE
2 EYEWASH PIPING DETAIL
NO SCALE
3 FLOOR DRAIN DETAIL
NO SCALE
5 MOP SINK PIPING DETAIL
NO SCALE
6 PIPE LABEL DETAIL
NO SCALE
7 ROOF DRAIN DETAIL
NO SCALE
8 EYEWASH/FAUCET PIPING DETAIL
NO SCALE
9 TYPICAL LAVATORY AND SINK SUPPLY DETAIL
NO SCALE
10 DIALYSIS CABINET WATER DRAIN BOX ASSEMBLY DETAIL
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
NO SCALE
4 ICE/COFFEE SUPPLY AND FLOOR DRAIN DETAIL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:5
P
M
P400
PLUMBING SCHEDULES
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
PLUMBING FIXTURE SCHEDULE
MECHANICAL (224200, 224223, 224300)
FIXTURE
TAG
FIXTURE
DESCRIPTION MOUNTING ADA FIXTURE TRIM STOP TRAP CARRIER
WASTE
(IN)
TRAP
(IN)
VENT
(IN)
CW
(IN)
HW
(IN) MECHANICAL NOTES
P-101 WATER CLOSET WALL YES AMERICAN STANDARD AFWALL
2257.103, VITREOUS CHINA, WALL
HUNG, ELONGATED BOWL, TOP SPUD,
1.6 GPF.
SLOAN FLUSHOMETER MODEL UPPERCUT WES 111,
1.6/1.1 GPF LOW CONSUMPTION, ANGLE STOP, 1"IPS,
TOP SPUD, SANIGUARD HANDLE, POLISHED CHROME.
ADA EXPOSED DUAL FLUSH VALVE, 1.6 GPF AND 1.0
GPF.
INTEGRAL ANGLE STOP ON FLUSH
VALVE.
INTEGRAL COMMERCIAL GRADE, ADJUSTABLE,
FLOOR MOUNTED WITH SHORT FEET.
4 NA 2 1 NA ELONGATED, WHITE, OPEN FRONT LESS COVER, WITH STAINLESS STEEL
SELF-SUSTAINING CHECK HINGE. ADA EXPOSED DUAL FLUSH VALVE, 1.6 GPF AND 1.0
GPF.
P-102 BARI WATER
CLOSET
WALL YES ACORN 2105BAR-ADA-EG
WHITE-HSBJ-MC-FV80-8L-T-1, FRONT
WALL MOUNT 1.6 GPM SIPHON JET TOP
SPUD BARIATRIC WATER CLOSET OF
HEAVY GAUGE TYPE 304 STAINLESS
STEEL, ELONGATED BOWL WITH
INTEGRAL TOILET SEAT WITH
SANITARY HIGH WHITE POLISH FINISH
AND MOUNTING PLATE.
SLOAN FLUSHOMETER MODEL UPPERCUT WES 111,
1.6/1.1 GPF LOW CONSUMPTION, ANGLE STOP, 1"IPS,
TOP SPUD, SANIGUARD HANDLE, POLISHED CHROME.
ADA EXPOSED DUAL FLUSH VALVE, 1.6 GPF AND 1.0
GPF.
INTEGRAL ANGLE STOP ON FLUSH
VALVE.
INTEGRAL COMMERCIAL GRADE, ADJUSTABLE,
FLOOR MOUNTED WITH SHORT FEET.
4 NA 2 1 NA HINGED WHITE SEAT WITH OPEN FRONT, LESS COVER. EXPOSED FLUSH VALVE, BEDPAN
WASHER, 1.6 GPH. STAINLESS STEEL RECESSED COLD WATER SUPPLY AND WASTE
HOSE BOX.
P-401 LAVATORY INTEGRAL YES SOLID SURFACE COUNTERTOP WITH
INTEGRAL BOWL BY OTHERS.
CHICAGO FAUCET 895-317GN2AE36ABCP, DECK
MOUNTED FAUCET WITH GOOSENECK SPOUT,
WRISTBLADE HANDLES, 4" CENTERS, CERAMIC DISC
CARTRIDGES, 1020-034KJKABNF LAMINAR FLOW
CONTROL ASSEMBLY IN BASE OF SPOUT.
McGUIRE 155A, PERFORATED GRID STRAINER AND TAIL PIECE. McGUIRE H2165CC, 1/2" x 3/8" HEAVY SUPPLIES
WITH HANDLE STOPS.
McGUIRE PW 2150 WC, PRE-WRAPPED OFFSET
DRAIN AND 1-1/2" P-TRAP WITH REDUCING SLIP
NUT, TAIL-PIECE COVER, (2) SUPPLY COVERS
AND CHROME ESCUTCHEON.
NA 1-1/2 1-1/4 1-1/2 1/2 1/2 PROVIDE CHICAGO FAUCETS 131-FMAB THERMOSTATIC MIXING VALVE. LOCATE BELOW
LAVATORY. PROVIDE MOLDED COVERING FOR WATER AND WASTE PIPING EQUAL TO
TRUEBRO "LAV GUARD 2". PROVIDE McGUIRE CAST BRASS CHROME PLATED TAILPIECE
& OPEN GRID STRAINER, ALL METAL PARTS TREATED INSIDE & OUTSIDE WITH
SANIGUARD.
P-402 BARI LAVATORY INTEGRAL YES SOLID SURFACE COUNTERTOP WITH
INTEGRAL BOWL BY OTHERS.
CHICAGO FAUCET 895-317GN2AE36ABCP, DECK
MOUNTED FAUCET WITH GOOSENECK SPOUT,
WRISTBLADE HANDLES, 4" CENTERS, CERAMIC DISC
CARTRIDGES, 1020-034KJKABNF LAMINAR FLOW
CONTROL ASSEMBLY IN BASE OF SPOUT.
McGUIRE 155A, PERFORATED GRID STRAINER AND TAIL PIECE. McGUIRE H2165CC, 1/2" x 3/8" HEAVY SUPPLIES
WITH HANDLE STOPS.
McGUIRE PW 2150 WC, PRE-WRAPPED OFFSET
DRAIN AND 1-1/2" P-TRAP WITH REDUCING SLIP
NUT, TAIL-PIECE COVER, (2) SUPPLY COVERS
AND CHROME ESCUTCHEON.
NA 1-1/2 1-1/4 1-1/2 1/2 1/2 PROVIDE CHICAGO FAUCETS 131-FMAB THERMOSTATIC MIXING VALVE. LOCATE BELOW
LAVATORY. PROVIDE MOLDED COVERING FOR WATER AND WASTE PIPING EQUAL TO
TRUEBRO "LAV GUARD 2". PROVIDE McGUIRE CAST BRASS CHROME PLATED TAILPIECE
& OPEN GRID STRAINER, ALL METAL PARTS TREATED INSIDE & OUTSIDE WITH
SANIGUARD.
P-501 SINGLE BOWL SINK COUNTER -
DROP IN
NO ELKAY LR-1919, SINGLE
COMPARTMENT, 18 GAUGE, TYPE 304
SELF-RIMMING STAINLESS STEEL SINK,
19-1/2" x 19" O.A., 7-1/2" DEEP.
CHICAGO FAUCETS 786-XK-E29-CP, DECK MOUNTED
FAUCET WITH RIGID GOOSENECK SPOUT,
1020-034KJKABNF LAMINAR FLOW CONTROL
ASSEMBLY IN BASE OF SPOUT, WRISTBLADE
HANDLES, 8" CENTERS AND CERAMIC DISC
CARTRIDGES.
McGUIRE LK-18, PERFORATED GRID STRAINER AND TAIL PIECE. McGUIRE H2165CC 1/2" x 3/8" HEAVY SUPPLIES
WITH WHEEL HANDLE STOPS.
McGUIRE 8912, 1-1/2", 17 GAUGE, C.P. CAST
BRASS P-TRAP WITH CLEANOUT PLUG.
NA 1-1/2 1-1/2 1-1/2 1/2 1/2 PROVIDE CHICAGO FAUCETS 131-FMAB THERMOSTATIC MIXING VALVE. LOCATE BELOW LAVATORY. PROVIDE McGUIRE CAST BRASS CHROME PLATED TAILPIECE & OPEN GRID
STRAINER, ALL METAL PARTS TREATED INSIDE & OUTSIDE WITH SANIGUARD.
P-502 LAVATORY WALL NO AMERICAN STANDARD LUCERNE
0355.012, 20"X18" VITREOUS CHINA
LAVATORY WITH 4" FAUCET CENTERS.
CHICAGO FAUCETS 8452-TE64VPABCP EYEWASH
FAUCET, DECK MOUNTED, GOOSENECK SPOUT WITH
INDEPENDENTLY OPERATED EYEWASH, 4" CENTERS,
WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 1.0
GPM LAMINAR FLOW OUTLET, POLISHED CHROME,
PUSH HANDLE EYEWASH ACTIVATION,
THERMOSTATIC MIX
ELKAY LK-35B, STAINLESS STEEL
CONICAL STRAINER BASKET WITH FLEX
STEM RUBBER STOPPER AND
STAINLESS STEEL TAILPIECE.
McGUIRE 8912, 1-1/2", 17 GAUGE, C.P. CAST
BRASS P-TRAP WITH CLEANOUT PLUG.
FLOOR MOUNTED, CONCEALED
ARMS, LEVELING AND SECURING
SCREWS, STRUCTURAL UPRIGHTS
AND WELDED FEET.
1-1/2 1-1/2 1-1/2 1/2 1/2 PROVIDE CHICAGO FAUCETS 131-FMAB THERMOSTATIC MIXING VALVE. McGUIRE H2165CC, 1/2" x 3/8" HEAVY SUPPLIES WITH WHEEL HANDLE STOPS.
P-503 MOP BASIN FLOOR NA CRANE/FIAT MSB 2424 MOP SERVICE
BASIN, 24" X 24" X 10" DEEP, MOLDED
STONE, STAINLESS STEEL DRAIN WITH
COMBINATION DOME STRAINER & LINT
BASKET.
CHICAGO FAUCET 782-ISCP-E27, CONCEALED FITTING
WALL FAUCET WITH INTEGRAL STOP ARMS, PAIL
HOOK WITH WALL BRACE, AND APPROVED OUTLET
VACUUM BREAKER WITH 3/4" HOSE THREAD OUTLET,
CHROME PLATE FINISH.
ACCESSIBLE CHECK VALVES &
SHUTOFFS ON HOT & COLD SUPPLIES.
3" 'P' TRAP NA 3 3 1-1/2 3/4 3/4 31" REINFORCED RUBBER HOSE WITH BRASS COUPLING ON ONE END, SPRING LOADED
HOSE HOLDER. HIGH IMPACT RIGID VINYL BUMPERS ON EXPOSED EDGES. STAINLESS (3)
MOP, MOP HANGER. TWO 12" HIGH, 20 GAUGE, TYPE 304 STAINLESS STEEL PANELS &
CORNER BRACKET FOR 24" x 36" CORNER.
P-601 ELECTRONIC WATER
COOLER
WALL YES ELKAY LZ8WSSSMC, WALL MOUNTED
STAINLESS STEEL BOTTLE FILLING
STATION, WATER SYSTEM FREE OF
LEAD CONTAINING BRASS PARTS,
CAPACITY AT 8 GPH OF 50 DEGREES F
WATER IN AMBIENT TEMPERATURE OF
90 DEGREES F, VINYL CLAD CABINET,
COLOR AS SELECTED BY ARCHITECT.
- McGUIRE QUARTER TURN BRASS BALL
VALVE POLISHED CHROME PLATED
CAST BRASS ANGLE VALVE KITS,
LOOSE KEY, FLEXIBLE RISERS,
ESCUTCHEON.
McGUIRE 8872, PVC 1-1/4" P-TRAP. NA 1-1/2 1-1/2 1-1/2 1/2 1/2 McGUIRE H2165CC, ANGLE SUPPLY STOP WITH TUBE RISER, AND WHEEL HANDLE.
P-701 SHOWER WALL YES NA CHICAGO FAUCET SH-TP4-00-024, THERMOSTATIC
AND PRESSURE BALANCING MIXING VALVE WITH
INTEGRAL SERVICE STOPS AND ADJUSTABLE HOT
WATER LIMIT STOP, AND CERAMIC VOLUME
CONTROL WITH AUTO-DRAIN. (2) 34" STAINLESS
STEEL HOSES WITH AUTO-DRAIN FITTING, 2.5 GPM
HAND SPRAY WITH PAUSE CONTROL, 36" VERTICAL
ADA GRAB BAR WITH HAND SPRAY HOLDER, WALL
CONNECTION AND FLANGE. CHICAGO FAUCETS
600-ACP SHOWER HEAD, SHOWER ARM, AND WALL
FLANGE KIT.
INTEGRAL NA NA 2" FD-C NA NA 1/2 1/2 PROVIDE SAFING PER CODE UNLESS SPECIFICALLY DETAILED OR SPECIFIED IN OTHER
CONTRACT DIVISIONS.
P-708 EMERGENCY EYE
AND FACE WASH
WALL YES CHICAGO FAUCETS 8401-NF WALL
MOUNTED EYE/FACE WASH WITH PUSH
PADDLE HANDLE, HIGH-FLOW
AERATED WATER SPRAY, SAFETY
SIGN, AND MAINTENANCE CARD.
- McGUIRE QUARTER TURN BRASS BALL
VALVE POLISHED CHROME PLATED
CAST BRASS STRAIGHT VALVE KITS,
LOOSE KEY.
McGUIRE 8912, 1-1/2", 17 GAUGE, C.P. CAST
BRASS P-TRAP WITH CLEANOUT PLUG.
NA 2 1-1/2 2 1/2 1/2 PROVIDE THERMOSTATIC MIXING VALVE AND 1/2" TEMPERED WATER PIPING TO
EYEWASH FITTING.
P-801 WALL FAUCET WALL NA WOODFORD MODEL 17 WALL FAUCET
3/4" MALE HOSE THREAD NOZZLE.
- INTEGRAL NA NA - - - 1/2 - -
P-802 DIALYSIS BOX WALL NA ACORN 8196-SFI RECESSED DIALYSIS
SUPPLY AND WASTE BOX, 316
STAINLESS STEEL, CONCEALED HINGE
DOOR WITH KEYED LOCK, PVC VALVE
AND HOSE CONNECTION, (2) KEYS.
NA NA 2" 'P' TRAP NA 2 2 1-1/2 3/4 - COORDINATE LOCATION & MOUNTING HEIGHT OF WALL BOX WITH EQUIPMENT
REQUIREMENTS.REFER TO DIALYSIS BOX DETAIL FOR ADDITIONAL REQUIREMENTS.
MECHANICAL NOTES:
1. 8" INLET AND 4" OUTLET.
FLOOR DRAIN SCHEDULE
MECHANICAL (221319)
EQUIPMENT
TAG SIZE (IN) MANUFACTURER
MODEL
NUMBER
MECHANICAL
NOTES
FD-B SEE PLAN JOSAM 32200-AE -
FD-C SEE PLAN JOSAM 30000-6A -
FD-W SEE PLAN ZURN Z1870-51-NH 1
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
MECHANICAL NOTES:
1. COATED CAST IRON WITH LARGE SUMP, BOTTOM OUTLET, ADJUSTABLE EXTENSION (-AE), DECK CLAMP ASSEMBLY (-1), ALUMINUM DOME (-26), INTERNAL WATERGUARD (-16).
2. COATED CAST IRON WITH LARGE SUMP, BOTTOM OUTLET, ADJUSTABLE EXTENSION (-AE), DECK CLAMP ASSEMBLY (-1), ALUMINUM DOME (-26).
3. COORDINATE BODY WITH EXISTING STRUCTURAL CONDITIONS TO HAVE EITHER STRAIGHT OR 45 DEGREE THREADED OUTLET.
4. MOUNT OVERFLOW PARAPET DRAIN 2" HIGHER THAN ADJACENT ROOF DRAIN (RD-2) AND MODIFY ROOF INSULATION TO COMPENSATE FOR ELEVATION DIFFERENCE.
ROOF AND OVERFLOW DRAIN SCHEDULE
MECHANICAL (221423)
EQUIPMENT
TAG SIZE (IN) MANUFACTURER MODEL NUMBER MECHANICAL NOTES
ORD-1 SEE PLAN JOSAM 21500-AE-1-26-16 1
ORD-2 SEE PLAN JOSAM 24700-45 (-T) 3,4
RD-1 SEE PLAN JOSAM 21500-AE-1-26 2
RD-2 SEE PLAN JOSAM 24700-45 (-T) 3
R E
F.
R E
F.
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
KEY NOTES:
GENERAL NOTES:
1 11
1 1
1 1 1 1
1 1
C
D
E
G
292827262524232221201918
M200
1 REMOVE DIFFUSER/GRILLE AND DEMOLISH DUCTWORK BACK TO
POINTS INDCATED AND CAP.
REMOVE REHEAT COIL AND DEMOLISH BACK TO POINT INDICATED
AND CAP.
DEMOLISH 12X12 ABANDONED EXHAUST DUCT DOWN TO 6TH FLOOR
CEILING AND CAP.
DEMOLISH 14X6 UP TO FLOOR ABOVE.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
COORDINATE ALL DUCTWORK ROUTING WITH ALL OTHER TRADES TO
ENSURE ADEQUATE CLEARANCES FOR PLUMBING, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER. PROVIDE ALL OFFSETS AND TRANSITIONS AS
REQUIRED FOR A CLEAN INSTALLATION WITH ADEQUATE SERVICE
ACCESSIBILITY.
SUPPORT ALL DUCTWORK DIRECTLY TO STRUCTURE. DO NOT
SUPPORT ANY DUCTS FROM DUCTWORK, CONDUIT, OR OTHER PIPING.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO VAV BOXES SHALL BE
THE SAME SIZE AS THE VAV INLET CONNECTION.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO DIFFUSERS, GRILLES
AND REGISTERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK OR
GRILLE/REGISTER CONNECTION.
ALL FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED
IN SHAFT WALLS SHALL BE INSTALLED TO ALLOW FOR SERVICE OF
THEIR FUSABLE LINK/ACTUATOR PER FACILITY STANDARDS. ANY
CONFLICTS WHICH WILL PREVENT ACCESS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND/OR ENGINEER.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD. DO NOT INSTALL VALVES,
VRF TERMINAL UNITS, SENSORS, OR DAMPERS ABOVE GYPSUM BOARD
CEILINGS WITHOUT ARDCHITECT APPROVAL OF ACCESS PANELS.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD CEILINGS AND BULKHEADS.
ADJUST PIPE AND DUCT THAT RUN PARALLEL TO BULKHEAD FRAMING
TO BE EITHER OUTSIDE OF FRAMING OR BETWEEN FRAMING.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR FOR MODIFIED BULKHEAD FRAMING WHERE EXISTING
AND NEW PIPING AND DUCT WILL CAUSE INTERFERENCE.
PROVIDE EACH NEW SUPPLY DIFFUSER/GRILLES WITH A SINGLE BLADE
TAKE-OFF DAMPER WITH QUADRANT LOCKING DEVISE. PERFORM ALL
BALANCING OF NEW DIFFUSERS THROUGH THOSE TAKE-OFF DAMPERS.
ALL NEW RETURN/EXHAUST GRILLES WILL BE PROVIDED WITH
OPPOSED BLADE BALANCING DAMPERS POSITIONED UPSTREAM PAST A
MINIMUM OF ONE TRANSITION FOR SOUND ABATEMENT. BALANCING
ANY DIFFUSERS/GRILLES USING INTEGRAL DAMPERS WILL NOT BE AN
APPROVED METHOD OF BALANCING.
CONTRACTOR TO KEEP ACCURATE REDLINES OF ALL AS-BUILT
CONDITIONS TO TURN OVER TO ARCHITECT/ENGINEER AT COMPLETION
OF PROJECT TO INCORPORATE INTO FINAL RECORD SET.
NORTH
KEY PLAN - B-WING OVERALL
B
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:2
P
M
MHD170
LEVEL 7 - DEMOLITION HVAC PLAN
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
1/8" = 1'-0"
1 LEVEL 7 - DEMOLITION HVAC PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer
C
D
E
G
2827262524232221201918
TT
T T
2 2
14x8
CAP
1 PERFORM AIRFLOW PREREADINGS FOR REBALANCING AFTER FINAL
CONNECTIONS. REMOVE AND REINSTALL EXHAUST GRILLES AND
DEMOLISH ASSOCIATED DUCTWORK BACK TO MAIN AND CAP.
2 PERFORM AIRFLOW PREREADINGS FOR REBALANCING AFTER FINAL
CONNECTIONS. REMOVE AND REINSTALL SUPPLY DIFFUSERS AND
DEMOLISH ASSOCIATED DUCTWORK BACK TO MAIN AND CAP.
DEMOLISH 14X6 EXHAUST FROM BELOW BACK TO MAIN AND CAP.
DEMOLISH EXHAUST DUCT UP TO EXHAUST FAN FOR THE
RELOCATION OF THE FAN.
COORDINATE ALL DUCTWORK ROUTING WITH ALL OTHER TRADES TO
ENSURE ADEQUATE CLEARANCES FOR PLUMBING, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER. PROVIDE ALL OFFSETS AND TRANSITIONS AS
REQUIRED FOR A CLEAN INSTALLATION WITH ADEQUATE SERVICE
ACCESSIBILITY.
SUPPORT ALL DUCTWORK DIRECTLY TO STRUCTURE. DO NOT
SUPPORT ANY DUCTS FROM DUCTWORK, CONDUIT, OR OTHER PIPING.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO VAV BOXES SHALL BE
THE SAME SIZE AS THE VAV INLET CONNECTION.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO DIFFUSERS, GRILLES
AND REGISTERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK OR
GRILLE/REGISTER CONNECTION.
ALL FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED
IN SHAFT WALLS SHALL BE INSTALLED TO ALLOW FOR SERVICE OF
THEIR FUSABLE LINK/ACTUATOR PER FACILITY STANDARDS. ANY
CONFLICTS WHICH WILL PREVENT ACCESS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND/OR ENGINEER.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD. DO NOT INSTALL VALVES,
VRF TERMINAL UNITS, SENSORS, OR DAMPERS ABOVE GYPSUM BOARD
CEILINGS WITHOUT ARDCHITECT APPROVAL OF ACCESS PANELS.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD CEILINGS AND BULKHEADS.
ADJUST PIPE AND DUCT THAT RUN PARALLEL TO BULKHEAD FRAMING
TO BE EITHER OUTSIDE OF FRAMING OR BETWEEN FRAMING.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR FOR MODIFIED BULKHEAD FRAMING WHERE EXISTING
AND NEW PIPING AND DUCT WILL CAUSE INTERFERENCE.
PROVIDE EACH NEW SUPPLY DIFFUSER/GRILLES WITH A SINGLE BLADE
TAKE-OFF DAMPER WITH QUADRANT LOCKING DEVISE. PERFORM ALL
BALANCING OF NEW DIFFUSERS THROUGH THOSE TAKE-OFF DAMPERS.
ALL NEW RETURN/EXHAUST GRILLES WILL BE PROVIDED WITH
OPPOSED BLADE BALANCING DAMPERS POSITIONED UPSTREAM PAST A
MINIMUM OF ONE TRANSITION FOR SOUND ABATEMENT. BALANCING
ANY DIFFUSERS/GRILLES USING INTEGRAL DAMPERS WILL NOT BE AN
APPROVED METHOD OF BALANCING.
CONTRACTOR TO KEEP ACCURATE REDLINES OF ALL AS-BUILT
CONDITIONS TO TURN OVER TO ARCHITECT/ENGINEER AT COMPLETION
OF PROJECT TO INCORPORATE INTO FINAL RECORD SET.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
NORTH
KEY PLAN - B-WING OVERALL
B
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:3
P
M
MHD180
LEVEL 8 - DEMOLITION HVAC PLAN
Stone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
1/8" = 1'-0"
1 LEVEL 8 - DEMOLITION HVAC PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer
S D
1 REMOVE EXHAUST FAN SERVING 8TH FLOOR TO NEW PENTHOUSE
ROOF. SEE M192 FOR RELOCATION OF SALVAGED FAN. COORDINATE
WITH GENERAL CONTRACTOR FOR WEATHERPROOF PATCHING OF
REMAINING OPENING.
DISCONNECT EXHAUST DUCTWORK AT ROOF TO COORDINATE WITH
INSTALLATION OF NEW PENTHOUSE. PREPARE REMAINING
DUCTWORK FOR NEW CONNECTION, SEE M191 FOR RECONNECTION.
DISCONNECT SUPPLY DUCTWORK AT ROOF TO COORDINATE WITH
INSTALLATION OF NEW PENTHOUSE. PREPARE REMAINING
DUCTWORK FOR NEW CONNECTION, SEE M191 FOR RECONNECTION.
DISCONNECT RETURN DUCTWORK AT ROOF TO COORDINATE WITH
INSTALLATION OF NEW PENTHOUSE. PREPARE REMAINING
DUCTWORK FOR NEW CONNECTION, SEE M191 FOR RECONNECTION.
REMOVE EXHAUST FAN SERVING 8TH FLOOR TO NEW PENTHOUSE
ROOF. SEE MH190 FOR RELOCATION OF SALVAGED FAN.
COORDINATE WITH GENERAL CONTRACTOR FOR WEATHERPROOF
PATCHING OF REMAINING OPENING.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
COORDINATE ALL DUCTWORK ROUTING WITH ALL OTHER TRADES TO
ENSURE ADEQUATE CLEARANCES FOR PLUMBING, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER. PROVIDE ALL OFFSETS AND TRANSITIONS AS
REQUIRED FOR A CLEAN INSTALLATION WITH ADEQUATE SERVICE
ACCESSIBILITY.
SUPPORT ALL DUCTWORK DIRECTLY TO STRUCTURE. DO NOT
SUPPORT ANY DUCTS FROM DUCTWORK, CONDUIT, OR OTHER PIPING.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO VAV BOXES SHALL BE
THE SAME SIZE AS THE VAV INLET CONNECTION.
UNLESS NOTED OTHERWISE, ALL TAKE-OFFS TO DIFFUSERS, GRILLES
AND REGISTERS SHALL BE THE SAME SIZE AS THE DIFFUSER NECK OR
GRILLE/REGISTER CONNECTION.
ALL FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED
IN SHAFT WALLS SHALL BE INSTALLED TO ALLOW FOR SERVICE OF
THEIR FUSABLE LINK/ACTUATOR PER FACILITY STANDARDS. ANY
CONFLICTS WHICH WILL PREVENT ACCESS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND/OR ENGINEER.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD. DO NOT INSTALL VALVES,
VRF TERMINAL UNITS, SENSORS, OR DAMPERS ABOVE GYPSUM BOARD
CEILINGS WITHOUT ARDCHITECT APPROVAL OF ACCESS PANELS.
MECHANICAL CONTRACTOR SHALL REVIEW ARCHITECTURAL CEILING
PLANS FOR LOCATIONS OF GYPSUM BOARD CEILINGS AND BULKHEADS.
ADJUST PIPE AND DUCT THAT RUN PARALLEL TO BULKHEAD FRAMING
TO BE EITHER OUTSIDE OF FRAMING OR BETWEEN FRAMING.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR FOR MODIFIED BULKHEAD FRAMING WHERE EXISTING
AND NEW PIPING AND DUCT WILL CAUSE INTERFERENCE.
PROVIDE EACH NEW SUPPLY DIFFUSER/GRILLES WITH A SINGLE BLADE
TAKE-OFF DAMPER WITH QUADRANT LOCKING DEVISE. PERFORM ALL
BALANCING OF NEW DIFFUSERS THROUGH THOSE TAKE-OFF DAMPERS.
ALL NEW RETURN/EXHAUST GRILLES WILL BE PROVIDED WITH
OPPOSED BLADE BALANCING DAMPERS POSITIONED UPSTREAM PAST A
MINIMUM OF ONE TRANSITION FOR SOUND ABATEMENT. BALANCING
ANY DIFFUSERS/GRILLES USING INTEGRAL DAMPERS WILL NOT BE AN
APPROVED METHOD OF BALANCING.
CONTRACTOR TO KEEP ACCURATE REDLINES OF ALL AS-BUILT
CONDITIONS TO TURN OVER TO ARCHITECT/ENGINEER AT COMPLETION
OF PROJECT TO INCORPORATE INTO FINAL RECORD SET.
C
D
E
G
292827262524232221201918
EF
NORTH
KEY PLAN - B-WING OVERALL
B
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT OF RECORD
A/E:
STAMPCONSULTANTS
o n e e ig h th in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s in c h o n e f o o t o n e h a lf in c h o n e f o o t th re e q u a rt e rs in c h o n e f o o t o n e in c h o n e f o o t o n e a n d o n e h a lf in c h e s o n e f o o t th re e in c h e s o n e f o o t
A
2 3 4 5 6
B
C
D
1 2 3 4 5 6
A
B
C
D
MECHANICAL / ELECTRICAL / PLUMBING: STRUCTURAL:HEALTHCARE ARCHITECT:
2550 UNIVERSITY AVE. W. SUITE 423-S
ST. PAUL, MN 55114
651.251.7570
50 SOUTH 6TH ST UNIT 1100
MINNEAPOLIS, MN 55402
612.465.7550
380 ST. PETER ST. UNIT 600
ST. PAUL, MN 55102
651.222.3701
C :\U se rs
\to ny m \D oc um en ts
\2
M D
In P at
B
M
_t on y.
m iz uh at a.
rv t
5/
/2
6:
:3
P
M
MHD190
PENTHOUSE - DEMOLITION HVAC
PLANStone Group Architects
600 E 7th Street
Sioux Falls, SD 57103
605-271-1144
VA Madison Renovate Inpatient Ward
7B
2500 Overlook Terrace, Madison, WI 53705
05/17/24 JRG TMM
100% CONSTRUCTION
DOCUMENTS
SGA #231919
VA #607-22-101
05/17/24
1/8" = 1'-0"
1 PENTHOUSE - DEMOLITION HVAC PLAN
Name
Date Reg. No.
Jason R. Gottwalt, P.E.
41360
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer
R E
F.
R E
F.
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
KEY NOTES:
GENERAL NOTES:
T
T
T
T T T T
T
T T
T
T T T
T
T
T
T T
T
TTT
T
TT
T
T T
T
T
T
T
1 1 1
1 1
1 1 1 1
1 1 1 1 1 1
11111111111111
111111 C
D
E
G
292827262524232221201918
1 DEMOLISH FAN COIL UNIT. DEMOLISH CONTROLS AND ASSOCIATED
THERMOSTAT. BRANCH PIPING WITHIN WALL TO REMAIN.
DEMOLISH REHEAT COIL AND DEMOLISH ASSOCIATED PIPING BACK
TO MAINS AND CAP.
DEMOLISH UNIT HEATER AND DEMOLISH ASSOCIATED PIPING BACK
TO MAINS AND CAP.
DISCONNECT 6" LOW PRESSURE STEAM PIPE FROM PRESSURE
REDUCING STATION. DEMOLISH 6" LPS DOWN TO LEVEL 5.
DISCONNECT 6" LOW PRESSURE STEAM PIPES GOING DOWN.
DEMOLISH 6" LOW PRESSURE STEAM UP TO PENTHOUSE. CAP PIPING
GOING DOWN AT THE FLOOR AND ABANDON REMAINING PIPING.
DEMOLISH SECTION OF DEAD END 5" CHILLED WATER PIPING TO
CLEAR PATH FOR NEW STEAM PIPING PENETRATIONS THROUGH
WALL. REFER TO DRAWING MP190 FOR NEW PIPE ROUTING. CAP
END OF PIPE AND REPAIR INSULATION COVERING AS REQUIRED.
DEMOLISH 6" LOW PRESSURE STEAM UP AND DOWN.
A.
B.
C.
D.
E.
F.
G.
H.
I.
MECHANICAL CONTRACTOR WILL BE RESPONSIBLE TO REVIEW
ACCESSIBILITY TO AREAS OUTSIDE THE CONSTRUCTION LIMITS TO
DETERMINE APPROXIMATE AMOUNT OF OVERTIME REQUIRED TO
PERFORM ALL MECHANICAL WORK INDICATED. COORDINATION OF
SCHEDULES WITH ADJACENT DEPARTMENTS AND CLEANING OF ALL
DEBRIS AFTER EACH WORK SHIFT SHOULD BE ASSUMED IN THE BASE
BID SCOPE.
ANY MAJOR OUTAGES INDICATED ON THESE DRAWINGS SHALL BE
SCHEDULED TO BE PERFORMED AFTER NORMAL BUSINESS HOURS OR
DURING WEEKEND PERIODS TO MINIMIZE DISRUPTION.
COORDINATE ALL NEW PIPE ROUTING WITH ALL OTHER TRADES TO
ENSURE ADEQUATE CLEARANCES FOR DUCTWORK, ELECTRICAL
CONDUIT, STRUCTURAL SUPPORTS, PIPING, ETC. ANY UNAVOIDABLE
CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER. PROVIDE ALL OFFSETS AND TRANSITIONS AS
REQUIRED FOR A CLEAN INSTALLATION.
SUPPORT ALL PIPING DIRECTLY TO STRUCTURE. DO NOT SUPPORT
ANY PIPING FROM DUCTWORK, CONDUIT, OR OTHER PIPING.
WHERE MECHANICAL SYSTEMS TO REMAIN ARE DAMAGED, OR
DISTURBED, DURING THE COURSE OF CONSTRUCTION THE
CONTRACTOR WILL BE RESPONSIBLE TO DEMOLISH DAMAGED
PORTIONS
AND INSTALL NEW PRODUCTS OF EQUAL QUALITY AND FUNCTIONALITY.
ALL EXISTING PIPING THROUGH NEW FIRE RATED WALLS SHALL BE
FIRE SEALED AS REQUIRED.
UNLESS NOTED OTHERWISE, HEATING WATER SUPPLY AND RETURN
PIPING TAKE-OFFS TO REHEAT COILS OR RADIANT PANELS SHALL BE
3/4" DIAMETER. HEATING WATER SUPPLY AND RETURN PIPING TAKE-
OFFS SHALL BE FROM OFF THE TOP OF MAIN WHERE POSSIBLE.
PROVIDE 1/2" DRAIN VALVE AT NEW HEATING WATER SUPPLY AND
RETURN PIPE LOW POINTS, DOWNSTREAM OF ISOLATION VALVES.
THE MECHANICAL CONTRACTOR SHALL MAINTAIN ACCURATE RECORD
DRAWINGS SHOWING ALL DISCREPANCIES…