S02. RFQ 36C26326Q0775.pdf

PDF 1007 KB Posted

Attached to
H365--Copy of Medical Gas Maintenance & Repair (VA-25-00092109)
Solicitation number
36C26326Q0775
Issued by

About this file

This is a Request for Quotes (RFQ) for medical gas maintenance and repair services at two Veterans Affairs medical centers in Nebraska. The solicitation number is 36C26326Q0775, issued by the Department of Veterans Affairs Network Contracting Office 23 (VA Black Hills HCS), with an offer due date of June 18, 2026 at 5:00 PM CDT. This procurement is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) with a NAICS code of 541350 (Building Inspection Services) and an estimated contract value of $11.5 million. The contract will be awarded as a firm fixed-price agreement with one base year (June 26, 2026 to June 25, 2027) and four optional one-year extension periods.

The contractor must provide comprehensive preventative maintenance, inspection, and testing services for medical gas systems at two facilities: Omaha VAMC (813,984 sq. ft.) and Grand Island VAMC (253,358 sq. ft.). Required services include monthly on-site inspections (minimum 16 hours at Omaha, 8 hours at Grand Island), quarterly maintenance, semi-annual inspections, and annual outlet testing covering 1,138 outlets at Omaha and 234 outlets at Grand Island. The contractor must also provide emergency response within 4 hours and non-emergency callout services. The pricing schedule includes 12 monthly job orders, 4 quarterly job orders, 2 semi-annual job orders, and 1 annual job order per location across the base year and four option years, plus separate line items for 120 emergency hours and 192 non-emergency hours at Omaha, and 96 emergency hours and 128 non-emergency hours at Grand Island annually. All work must comply with NFPA 99, NFPA 55, OSHA standards, and industry best practices. The contractor must provide one OSHA Competent Person with at least 3 years of experience, evidence of NFPA 99 certification, and capability to respond to emergencies within 4 hours of each facility. Additional requirements include site security/PIV badging, records management compliance, job hazard analyses, and detailed documentation of all maintenance activities and recommendations.

View the file

Other files

File Type Posted
S02. RFQ Amendment 0001 36C26326Q0775.pdf PDF
36C26326Q0775 0001_1.docx DOCX document
P07. WD 2015-5005.pdf PDF
36C26326Q0775_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAGE 1 OF 1. REQUISITION NO.

2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NO. 5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE

a. NAME b. TELEPHONE NO. (No Collect Calls) 8. OFFER DUE DATE/LOCAL

TIME

9. ISSUED BY CODE 10. THIS ACQUISITION IS UNRESTRICTED OR SET ASIDE: % FOR:

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

8(A)

NAICS:

SIZE STANDARD:

11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

SEE SCHEDULE

12. DISCOUNT TERMS

13a. THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13b. RATING

14. METHOD OF SOLICITATION

RFQ IFB RFP

15. DELIVER TO CODE 16. ADMINISTERED BY CODE

17a. CONTRACTOR/OFFEROR CODE FACILITY CODE 18a. PAYMENT WILL BE MADE BY CODE

TELEPHONE NO. UEI: EFT:

PHONE: FAX:

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER

18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED

SEE ADDENDUM

19. 20. 21. 22. 23. 24.

ITEM NO. SCHEDULE OF SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

(Use Reverse and/or Attach Additional Sheets as Necessary)

25. ACCOUNTING AND APPROPRIATION DATA 26. TOTAL AWARD AMOUNT (For Govt. Use Only)

27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA ARE ARE NOT ATTACHED.

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________ 29. AWARD OF CONTRACT: REF. ___________________________________ OFFER

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DATED ________________________________. YOUR OFFER ON SOLICITATION

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY (BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)

30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED

AUTHORIZED FOR LOCAL REPRODUCTION (REV. NOV 2021)

PREVIOUS EDITION IS NOT USABLE Prescribed by GSA - FAR (48 CFR) 53.212

7. FOR SOLICITATION

INFORMATION CALL:

STANDARD FORM 1449

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

36C26326Q0775

Jesse Sweesy jesse.sweesy@va.gov 06-18-2026

17:00 CDT

36C263

DEPARTMENT OF VETERANS AFFAIRS

NETWORK CONTRACTING OFFICE 23

VA BLACK HILLS HCS FORT MEADE CAMPUS

113 COMANCHE RD

FORT MEADE SD 57741

X 100

X

541350

$11.5 Million

N/A

X

36C636

DEPARTMENT OF VETERAN AFFAIRS

OMAHA VA MEDICAL CENTER

4101 Woolworth Ave

OMAHA NE 68105-1850

DEPARTMENT OF VETERANS AFFAIRS

NETWORK CONTRACTING OFFICE 23

VA BLACK HILLS HCS FORT MEADE CAMPUS

113 COMANCHE RD

FORT MEADE SD 57741

FMS-VA-2(101)

FINANCIAL SERVICES CENTER

PO BOX 149971

AUSTIN TX 78714-9971

See CONTINUATION Page

Contractor to provide all labor, materials and transportation to provide all aspects of the Medical Gas

Services requirements as indicated in the below statement of work.

Anticipated Periods of Performance:

Base: 06/26/2026 – 06/25/2027

OY1: 06/26/2027 – 06/25/2028

OY2: 06/26/2028 – 06/25/2029

OY3: 06/26/2029 – 06/25/2030

OY4: 06/26/2030 – 06/25/2031

Service Contract Labor standards and wage determinations are applicable for Douglas County Nebraska 2015-5005.

$0.00

See CONTINUATION Page

X X

X 1

Jesse Sweesy

VA-VHA-RPOC-2023-0042

Table of Contents

SECTION A

A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS

AND COMMERCIAL SERVICES

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

References

B.2 PRICE/COST SCHEDULE

ITEM INFORMATION

SECTION C - CONTRACT CLAUSES

C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS

AND COMMERCIAL SERVICES (NOV 2023)

C.2 52.217-8 OPTION TO EXTEND SERVICES (NOV 1999)

C.3 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000) ...39

C.4 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS

(DEVIATION APR 2026)

C.5 SUPPLEMENTAL INSURANCE REQUIREMENTS

C.6 52.240-91 SECURITY PROHIBITIONS AND EXCLUSIONS (NOV 2025)

(DEVIATION)

C.7 VAAR 852.204-72 PERSONNEL VETTING AND CREDENTIALING (DEVIATION)

(MAR 2026)

C.8 VAAR 852.219-73 VA NOTICE OF TOTAL SET-ASIDE FOR CERTIFIED

SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESSES (JAN 2023)

(DEVIATION)

C.9 VAAR 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING—

CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (JAN 2023)

(DEVIATION)

C.10 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)

SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS

SECTION E - SOLICITATION PROVISIONS

E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND

COMMERCIAL SERVICES (SEP 2023)

E.2 52.209-7 INFORMATION REGARDING RESPONSIBILITY MATTERS (OCT 2018)

E.3 52.216-1 TYPE OF CONTRACT (NOV 2025) (DEVIATION)

E.4 52.233-2 SERVICE OF PROTEST (SEP 2006)

E.5 52.240-90 SECURITY PROHIBITIONS AND EXCLUSIONS REPRESENTATIONS

AND CERTIFICATIONS (NOV 2025) (DEVIATION)

E.6 VAAR 852.233-71 ALTERNATE PROTEST PROCEDURE (OCT 2018)

E.7 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB

1998)

E.8 52.212-2 EVALUATION—COMMERCIAL PRODUCTS AND COMMERCIAL

SERVICES (NOV 2021)

E.9 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—

COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION

FEB 2025)

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

1. Contract Administration: All contract administration matters will be handled by the following individuals:

a. CONTRACTOR:

b. GOVERNMENT: Contracting Officer 36C263

NETWORK CONTRACTING OFFICE 23

VA BLACK HILLS HCS FORT MEADE CAMPUS

113 COMANCHE RD

FORT MEADE SD 57741

2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:

[X] 52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or

[] 52.232-36, Payment by Third Party

3. INVOICES: Invoices shall be submitted in arrears:

a. Quarterly []

b. Semi-Annually []

c. Other [X] Upon Receipt and Completion

4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment

Requests.

ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:

AMENDMENT NO DATE

B.2 STATEMENT OF WORK

Medical Gas Maintenance & Repair - NWI

Purpose

The purpose of this performance work statement is to outline the preventative maintenance services to be provided for the medical gas system, vacuum pumps, reserve manifold, alarm panels ,compressors and associated components in the hospital. These systems are critical for patient care, and regular maintenance ensures that they function optimally, reducing downtime and ensuring compliance with healthcare standards.

Contractor shall perform all work in accordance with most current NFPA 99, NFPA 55, CGA, ASSE, VHA

7515, OSHA, Joint Commission, VA Plumbing Design Manual and industry standards.

Location of Services

Omaha VAMC, 4101 Woolworth Ave, Omaha, NE 68105

Facility Size: 813,984 sq. ft

Grand Island VAMC, 2201 N Broadwell Ave, Grand Island, NE 68803

Facility Size: 253,358 sq. ft

Site Visit

Site visits for both the Omaha VAMC and the Grand Island VAMC listed at the above addresses have been scheduled as follows:

Omaha VAMC - June 10 from 1300-1500

Grand Island VAMC – June 11th from 1300-1500

Site Visit POC: Paul Karnish (402) 995-3741 ext 203741 paul.karnish@va.gov

Performance Work Statement Scope

Inspection, testing, and maintenance shall be performed on all components of the system or portions thereof, including but not limited to:

mailto:paul.karnish@va.gov

Gas bulk sources, Manifolds, Compressed air source systems (e.g., compressors, dryers, filters, regulators), Source alarms and monitoring safeguards, Master alarms, Pipelines, Isolation valves, Area alarms, Zone valves, Station inlets (vacuum) and outlets (pressure gauges)

The VA will initiate separate commodity purchases for one-time corrective maintenance. Parts needed for one-time corrective repairs include:

Outlet replacement, Valve replacement, Vacuum pump replacement, Medical air compressor replacement, Piping or manifold replacement, Soft start replacements, Starter replacement

These one-time repair or service components are not intended to substitute for the contractor's responsibility to provide adequate materials for preventative maintenance purposes under this contract. The contractor shall update the existing inventory on hand as parts are utilized. Parts included under this contract for preventative maintenance include, oil, gaskets, belts, check valves, filters, lubricants, dew point or CO2 sensors.

For the purposes of NFPA 99, the contractor shall prioritize Category 1 and then Category 2 spaces when performing inspection, testing, or maintenance activities. These categories will be defined as critical spaces. Impacts to critical spaces (such as shutting down or inhibiting the function of source equipment, piping, or alarms) shall be coordinated in advance with the technical POC. Most work resulting in the loss of medical gases to critical spaces shall be performed after hours, on weekends, or during federal holidays.

The contractor shall provide the VA with their proposed maintenance schedule to meet the manufacturer's recommendations as well as the requirements of this PWS prior to onsite services. The contractor shall utilize appropriate, calibrated instruments and methods for testing air quality. This could involve gas analyzers, dew point meters, particulate counters, and other specialized equipment.

Monthly

For the purposes of monthly inspection, it is expected that the contractor be onsite no less than 16 hours at the Omaha site and 8 hours at the Grand Island site. Should the contractor perform preventative maintenance tasks within time specified, the contractor is expected to initiate repair or troubleshooting systems to ensure reliability and operation of systems to fulfill duration specified.

• Area alarm - activate all audible and visual signals using test buttons.

• Test master alarm functions for audible and visual signal.

• Vacuum area alarm panel with test buttons - activate audible and visual alarm signals.

• Area alarm panel gauges/pressure readouts - check line pressures.

• System main line low and high pressure alarms - test audible and visual signals at the master alarm panel(s).

• Manifold reserve in use alarm - test audible and visual signals.

• Reserve supply low warning signals - test audible and visual signals.

• Dew point and CO alarm - test audible and visual signals.

• Vacuum main line low vacuum alarm - test audible and visual signals at the master alarm panel(s).

• SPS compressors, dental equipment (air and vacuum), medical air compressors, and medical vacuum systems - check for proper operation and preventive maintenance per manufacturers specifications including but not limited to necessary oil and filter changes.

• Pressure check across filters.

Quarterly

• Intake for medical air compressors - check intake location and filter for trash and debris

• Source evaluation on medical air, dental equipment (air and vacuum) and vacuum systems o Function of automatic alternating controls.

o Correct pressure/vacuum switch.

o Frequency of pump starts and duration of runs.

o Cut in/out pressure/vacuum.

• Proper water flow to water-cooled aftercoolers (where present).

• Check hour meters for required maintenance schedule for pumps and compressors. Service in accordance with manufacturer’s instructions.

Semi-Annually

• Manifold system - leak check (valves, pigtails, and regulators). Visually check cylinder pigtails for physical damage.

Annually

• Check 114 (Omaha) outlets in critical care areas and 24 (Grand Island) outlets (note: future outlet inspection under option years (if pursued) shall ensure testing is not repeated on an outlet until all outlets in the hospital have been tested once. Additionally testing of newly installed outlets must not supersede the testing of existing outlets.) It is expected - flow, pressure/vacuum, damage and wear will be inspected. Note outlet inventory and critical/non critical designation will be provided during solicitation.

• Outlet check shall include cross connection verification and concentration.

• Purity verification to ensure gas delivered meets needs of patient to include dew point, hydrocarbons, contaminants, percentage of desired gas component within mixture

• Bulk liquid systems- test the operation of the reserve and activation of reserve-in- use signal Bulk system supply - check proper level activating switch.

• Manifold reserve-in-use alarm - test proper function of switch.

• Manifold - test operation of the changeover for the secondary supply.

• Pressure gauges - assure gauges are mechanically functional.

• Air compressor - performance testing.

• Dew point and CO monitor - calibrate and test operation.

• Perform manufacturer-recommended maintenance on SPS compressors, dental equipment (air and vacuum), medical air compressors, and medical vacuum systems as specified.

• Maintenance and periodic testing of the bulk system in conjunction with the bulk gas supplier.

• Verify that all zone valve boxes are properly labeled and accessible for emergency use. Install zone valve labels should labeling be improper or changes have been made that result in inaccurate depiction.

• Operate zone valves in critical spaces after hours during approved time from the VA to ensure that it remains functional and free from sticking or seizing.

Contractor shall make all attempts to perform this work during station inlet/outlet testing of the space impacted for increased efficiency.

• Calibration of sensors and gauges associated with alarm panels.

• Detailed inspection of backup power systems for the alarm panels.

• Boom inspection and testing IAW NFPA 99 (10.2.3) and manufacturer’s specifications

• Master Alarm Panel inspection and testing IAW NFPA 99 (5.1.9.2.3 – 5.1.9.2.5) and manufacturer’s specifications

• Emergency oxygen supply connection (EOSC) - inspect and test the exterior emergency supply connection for physical condition, secure fittings, valve operation, leak integrity, clear labeling, and system readiness. Ensure all protective covers are reinstalled and the connection is properly secured after maintenance.

• Shut-off valves - External leakage test.

• Calibration of pressure gauges.

Emergency and Corrective Maintenance

Preventative Maintenance and Urgent Repairs:

While this scope primarily covers preventive maintenance, any urgent repairs or corrective services required between scheduled visits shall also be covered.

Each unscheduled visit will be classified as either emergency or non-emergency, with a set maximum number of labor hours covered under this contract per year.

The predicted amounts for labor hours are based on historical data. If the VA does not utilize the callouts or labor hours, they shall be de-obligated at the end of the contracted period of performance.

Definitions and Classifications:

An emergency is classified as events that present immediate or imminent danger to life, health, safety, security, or significant damage to buildings, equipment, or other property.

The VA Point of Contact (POC) has the ultimate decision as to the classification of each callout type.

Omaha and Grand Island VAMC:

• Emergency: General contractor to be onsite within 4 hours.

• Non-emergency: General contractor to be onsite within 5 business days.

Response Procedures:

The service ticket response window will be initiated after the VA POC has confirmed verbally or through email with the contractor.

The contractor is expected to respond and confirm receipt no later than 2 hours after initial contact (voicemail, email, text) to initiate the response window above.

Non-Emergency Callouts:

• Non-emergency callouts may include:

• Issuance or verification of permits to work per NFPA 99.

• Educational training for ASSE 6040.

• Maintenance or repair of redundant non-category 1 or 2 spaces.

• Verification of medical gas drawings or as-builts.

• Hourly based preventative maintenance (not subject to the monthly/quarterly frequency stated above).

• Services may also be requested to include testing piped medical gas and vacuum systems for purity, correct gas, and proper pressure when these systems are installed, modified or repaired, as well as third-party verifications or risk assessments to estimate usage during peak demands.

Corrective Maintenance and Parts Procurement:

The VA will initiate separate government purchase orders locally for any parts needed under corrective maintenance.

Upon conclusion of each repair, the contractor shall ensure affected portions of the systems are correctly tested in accordance with NFPA 99 5.1.12 and 5.1.13 and demonstrated to be acceptable for patient use.

Documentation and Deliverables:

The contractor shall provide an up-to-date quantity per location for each type of callout each month. Required maintenance documentation shall be located within the

"Deliverables" section of this Performance Work Statement (PWS). The Contractor is required to comply with all other applicable regulations and guidelines to ensure the continued safe and efficient operation of the medical gas and vacuum systems.

Equipment List

Brand Name Item - 01: Air Star 100 Applicable model/make/catalog number – Air Techniques Duplex / Model #: AS70X

Brand Name Item - 02: Air Techniques Drystar Monitor Applicable model/make/catalog number – Air Techniques Duplex / Model #: MOJAVE – V7

Brand Name Item - 03: Ohio Medical Applicable model/make/catalog number – Triplex Ohio Medical Air / Model #: AS1000B-

ST-3-

Brand Name Item - 04: Ohio Medical Applicable model/make/catalog number – Duplex Ohio Medical / Model #: D500B-T3

Brand Name Item - 05: Ohio Medical Applicable model/make/catalog number – Sixplex Ohio Medical Air / Model #: AS500B-

ST6-DD

Brand Name Item - 06: Ohio Medical Applicable model/make/catalog number – Duplex Ohio Medical Air / Model #: AS750B-

ST2-DD

Brand Name Item - 07: Powerex Medical Air Applicable model/make/catalog number – Quadplex Powerex Medical Air / Model #:

MSQ05A42P

Brand Name Item - 08: Ohio Medical Applicable model/make/catalog number – Quadplex Ohio Medical / Model #: C750B-T4

Brand Name Item - 09: Ohio Medical Applicable model/make/catalog number – Quadplex Ohio Medical / Model #: C750B-T2

Brand Name Item - 10: Ohio Medical Applicable model/make/catalog number – Quadplex Ohio Medical / Model #: C750B-

ST4

Brand Name Item - 08: Becker Pumps Applicable model/make/catalog number – Duplex Becker / Model #: D500B-T3

Brand Name Item - 09: Ohio Medical Applicable model/make/catalog number – Triplex Ohio Medical / Model #: AS1000B-ST-

3-DD

Brand Name Item - 10: Becker Pumps Applicable model/make/catalog number – Duplex Becker / Model #: D500B-T3

Brand Name Item - 11: Air Techniques Applicable model/make/catalog number: Airstar AS50 / SN: AS500-18030061

Brand Name Item - 12: Enviroaire Applicable model/make/catalog number: S10 / 303SMB496

Total Omaha Medical Gas Outlets: 1138 Total Grand Island Medical Gas Outlets: 234

Period of Performance

• Base 6/26/2026 – 6/25/2027

• Option Year 1 6/26/2027 – 6/25/2028

• Option Year 2 6/26/2028 – 6/25/2029

• Option Year 3 6/26/2029 – 6/25/2030

• Option Year 4 6/26/2030 – 6/25/2031

Contracting Officer Representative / Technical Representative Contact Information

For the purposes of this contract, contracting officer representative (COR) and VA technical point of contact (TPOC) will be used interchangeably to delineate an individual employee by the government at the facilities where work will take place.

Omaha:

TBD

Grand Island:

TBD

Work Hours Expected

The contractor shall limit all patient or staff impacts by phasing work during or after hours. Normal business hours are 0730-1600. Should services provided not impact patient or staff services work can be performed during normal business hours.

Questions on local facility impacts and work proposed by the contractor shall be directed to the contracting officer representative for approval of work to be performed during or after hours.

Kickoff Meeting

The general contractor shall schedule a kickoff meeting no later than 5 business days following notice to proceed. At a minimum the local site COR, and the contracting officer shall attend.

Certifications

It is the expectation that all contractors meet the below qualifications. If contracted employees change from the proposal provided in the solicitation the general contractor shall provide credentials for VA review and approval prior to work.

• General contractor shall provide one OSHA “Competent Person” (CP) to be physically present at all job sites. This individual shall be directly employed by the general contractor with authority to speak on behalf of the general contractor.

This individual shall be capable of identifying existing and predictable hazards in the surroundings and working conditions which are unsanitary, hazardous or dangerous to employees, and who has the authorization to take prompt corrective measures to eliminate them (see 29 CFR 1926.32(f)). The prime contractor(s) are responsible for informing their subcontractors of the safety provisions under the terms of the contract and the penalties for noncompliance, coordinating the work to prevent one craft from interfering with or creating hazardous working conditions for other crafts, and inspecting subcontractor operations to ensure that Mishap prevention responsibilities are being carried out. This individual shall have a current OSHA 30 certification and provide no less than 3 years worth of job related experience similar to that being asked in this contract.

• contractor shall provide evidence of meeting NFPA 99 5.1.14.4.2.5 ((2) AND (3)) and 5 years of experience performing work in similar size and scope

• Contractor shall provide evidence that in emergent conditions services can be provided within 4 hours at each VAMC (Grand Island, Omaha)

All maintenance personnel performing the services will be properly trained and certified in the maintenance of medical gas systems, vacuum pumps, in building manifolds, alarm panels and compressors as per industry standards, such as those from NFPA 99, NFPA 70E, and relevant manufacturer guidelines. Specifically the general contractor shall provide evidence of meeting

NFPA 99 5.1.14.4.2.5 ((2) AND (3)) and 5 years of experience performing work in similar size and scope within 4 hour commuting distance to each VAMC (Grand Island, Omaha) to meet emergency callout requirement stated in PWS. Please note that this requirement is for the general contractor and shall promote efficiency, prevent over-management and communication complexity.

The competent person and ASSE maintenance personnel be the same individual at the general contractor’s discretion. Contractor shall include this information in any proposals to the solicitation with the credentials of the proposed staff. Should staff change over duration of procurement the contractor shall provide new credentials for VA acceptance prior to work.

General Requirements

Should contractors work involve any of the below, the stated requirements below shall be met.

All work shall comply with the most recent edition of USACE EM 385-1-1, comply with

29 CFR 1926, comply with 29 CFR 1910 as incorporated by reference within 29 CFR

1926, comply with ASSP A10.34, and all applicable federal, state, and local laws, ordinances, criteria, rules and regulations. Submit matters of interpretation of standards for resolution before starting work. Where the requirements of this specification, applicable laws, criteria, ordinances, regulations, and referenced documents vary, the most stringent requirements govern except with specific approval and acceptance.

All electrical work shall comply with VHA Directive 1028, NFPA 70 (NEC), NFPA 70B, NFPA 70E, 29 CFR Part 1910 Subpart J – General Environmental Controls, 29 CFR

Part 1910 Subpart S – Electrical, and 29 CFR 1926 Subpart K.

All installation, maintenance, and servicing of equipment or machinery shall comply with

29 CFR 1910.147 except for specifically referenced operations in 29 CFR 1926

All hot work shall be safeguarded in accordance with NFPA 241 and NFPA 51B. Hot work permits shall be issued daily for work in accordance with local policy.

All confined space entry shall comply with 29 CFR 1926, Subpart AA except for specifically referenced operations in 29 CFR 1926.

All floor and wall openings shall comply with 29 CFR 1926 Subpart M and EM 385-1-1..

Contractor shall maintain free and unobstructed access to facility emergency services and for fire, police and other emergency response forces in accordance with NFPA 241

Government Furnished Property or Space

The contractor will not be provided government furnished property.

Job Hazard Analysis

Shall any of the below hazards be expected or present themselves during the work, an activity hazard analysis also known as a job hazard analyses, job safety analyses and activity safety analyses shall be performed meeting all of the requirements from the below. Deviations will be only be approved by the contracting officer.

Job Site Risks associated with the below

1) Emergency response;

2) Contingency for severe weather;

3) Fire Prevention;

4) Medical Support;

5) Posting of emergency telephone numbers;

6) Prevention of alcohol and drug abuse;

7) Site sanitation (housekeeping, drinking water, toilets);

8) Night operations and lighting;

9) Hazard communication program;

10) Welding/Cutting “Hot” work;

11) Electrical Safe Work Practices (Electrical LOTO/NFPA 70E);

12) General Electrical Safety;

13) Hazardous energy control (LOTO);

14) Site-Specific Fall Protection & Prevention;

15) Excavation/trenching;

16) Asbestos abatement;

17) Lead abatement;

18) Crane Critical lift;

19) Respiratory protection;

20) Health hazard control program;

21) Radiation Safety Program;

22) Abrasive blasting;

23) Heat/Cold Stress Monitoring;

24) Crystalline Silica Monitoring (Assessment);

25) Demolition plan (to include engineering survey);

26) Formwork and shoring erection and removal;

27) Pre-Cast Concrete;

28) Public (Mandatory compliance with ANSI/ASSP A10.34-2012);

29) Sub-contractor or cross-trade coordination;

Before beginning each work activity involving a type of work presenting hazards not experienced in previous project operations or where a new work crew or sub-contractor is to perform the work, the Contractor(s) performing that work activity shall prepare an

AHA (Example electronic AHA forms can be found on the US Army Corps of Engineers web site)

AHAs shall define the activities being performed and identify the work sequences, the specific anticipated hazards, site conditions, equipment, materials, and the control measures to be implemented to eliminate or reduce each hazard to an acceptable level of risk.

Work shall not begin until the AHA for the work activity has been accepted by the

Contracting Officer Representatives and discussed with all engaged in the activity, including the Contractor, subcontractor(s), and Government on-site representatives at preparatory and initial control phase meetings.

The names of the Competent/Qualified Person(s) required for a particular activity (for example, excavations, scaffolding, fall protection, other activities as specified by OSHA, EM 385-1-1, or other State and Local agencies) shall be identified and included in the

AHA. Certification of their competency/qualification shall be submitted to the contracting officer representative for acceptance prior to the start of that work activity.

The AHA shall be reviewed and modified as necessary to address changing site conditions, operations, or change of competent/qualified person(s).

If more than one Competent/Qualified Person is used on the AHA activity, a list of names shall be submitted as an attachment to the AHA. Those listed must be

Competent/Qualified for the type of work involved in the AHA and familiar with current site safety issues.

If a new Competent/Qualified Person (not on the original list) is added, the list shall be updated (an administrative action not requiring an updated AHA). The new person shall acknowledge in writing that he or she has reviewed the AHA and is familiar with current site safety issues.

Submit AHAs to the contracting officer, primary contracting officer representative and alternate contracting officer representative.

Preconstruction Risk Assessment / Infection Control Risk Assessment

Contractor shall control all construction-associated hazards that affect VA medical facilities, their occupants, services and mission-essential functions and capabilities is critical in all medical center facilities.

Contractor shall ensure interior construction activities causing disturbance of existing dust, or creating new dust, must be conducted within ventilation-controlled areas that minimize the flow of airborne particles into patient areas.

Contractor shall ensure compliance VHA 7715 and post a copy of the latest PCRA and

ICRA forms at all jobs sites found at

• VHA PCRA: http://vaww.hefp.va.gov/resources/vha-pre-construction-risk-assessment-pcra

• VHA ICRA: http://vaww.hefp.va.gov/resources/vha-infection-control-risk-assessment-icra

VHA-PCRAs and ICRAs will be re-validated and updated as needed based on but not limited to changes from affected individuals, areas/locations, scope, contractor means and methods, safety requirements, phasing, contractor competencies and capabilities.

The COR with concurrence from a VHA infection control specialist, VHA patient safety and VHA occupational health and safety officer will have ultimate decision on activity type and the level of precautions the contract needs to take.

Deliverables

Reporting and Documentation: Contractor shall provide a written inspection report for each piece of equipment, including:

• Maintenance Log: All tasks completed during the preventative maintenance service will be recorded in a log, noting any parts replaced, issues found, and corrective actions taken.

• Compliance Report: A detailed compliance report will be provided, verifying that all systems are in accordance with applicable standards (e.g., NFPA 99 for medical gas systems) https://gcc02.safelinks.protection.outlook.com/?url=http%3A%2F%2Fvaww.hefp.va.gov%2Fresources%2Fvha-pre-construction-risk-assessment-pcra&data=05%7C01%7C%7C35fabe489a224e29ca4e08db6379f655%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C638213147692050152%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=O%2B4gD79A6%2BxSKltZgLa95UUPtMlvZHR9j1fVypepzpM%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=http%3A%2F%2Fvaww.hefp.va.gov%2Fresources%2Fvha-pre-construction-risk-assessment-pcra&data=05%7C01%7C%7C35fabe489a224e29ca4e08db6379f655%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C638213147692050152%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=O%2B4gD79A6%2BxSKltZgLa95UUPtMlvZHR9j1fVypepzpM%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=http%3A%2F%2Fvaww.hefp.va.gov%2Fresources%2Fvha-infection-control-risk-assessment-icra&data=05%7C01%7C%7C35fabe489a224e29ca4e08db6379f655%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C638213147692050152%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=KxMLKZWCHwpofa25RiHcYe1kKwSqEL9doVcRTmxnsNw%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=http%3A%2F%2Fvaww.hefp.va.gov%2Fresources%2Fvha-infection-control-risk-assessment-icra&data=05%7C01%7C%7C35fabe489a224e29ca4e08db6379f655%7Ce95f1b23abaf45ee821db7ab251ab3bf%7C0%7C0%7C638213147692050152%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=KxMLKZWCHwpofa25RiHcYe1kKwSqEL9doVcRTmxnsNw%3D&reserved=0

• Recommendations: Any recommendations for system upgrades, replacements, or repairs will be documented and submitted for hospital review. These recommendations shall include pricing.

• Inventory: Contractor shall provide and update as modifications are made the inventory of critical components to include all source subsystems, control valves, alarms, manufactured assemblies containing patient gases and inlets and outlets.

Invoice Documentation: The contractor shall provide a list of tasks completed with the corresponding CLIN information to include how many additional quantities remain. This bill to date information shall be submitted to the VA during invoice upload for verification.

Schedule

Contractor shall provide a schedule to meet each aspect covered in the performance work statement NLT 10 calendar days from notice to proceed. Changes to this schedule shall be communicated to the Contracting Officer, primary and alternate contracting officer representatives immediately.

The contractor shall provide an updated list of equipment, the date of last inspection or certification and the planned date of next inspection to ensure equipment testing frequency is adequate.

Due to the continuous operations of the hospital and sensitive populations served, all equipment or utility outages shall be communicated to the contracting officer, primary and alternate COR for VA approval. The contractor shall build time for the VA to receive adequate approvals for such outages into their schedule and be prepared to work outside of normal business hours to accomplish any outages to limit impact to the patients, staff and visitors of the NWIHCS.

Site Security

In accordance with FAR 52.204-9 and VA Directive 0735 – Personal Identity Verification of Federal Employees and Contractors, any contract person who requires routine physical access to a Federally-controlled facility and/or routine access to a Federally-controlled information system will be required to verify their identity prior to providing services under the contract. Prior to providing services under the contract, each contract person will be asked to provide two (2) forms of identification from the Accepted

Identification Documentation List to the appropriate VA representative in order to obtain a proper VA-issued identification card (PIV badge). No work onsite shall ensue without issuance of a VA PIV badge or internal escorting. Contractor is expected to build lead times for PIV issuance into schedules. The general contractor shall be onsite for any subcontractors who do not have a PIV card issued to them for the duration of the subcontractor’s work including escorting subcontractors. The prime contractor shall check in all subcontractors prior to performing work each day in the engineering office space.

Contractors must provide two forms of ID and will be sponsored in US Access by VA representatives. After sponsorship, the contractor will schedule a fingerprinting appointment, receiving an email with instructions for the local PIV office at Omaha

VAMC, B804. Once fingerprinting is complete, the personnel security team will email the applicant to initiate the background check. If the check is favorable, the contractor will then schedule a PIV appointment for card printing at B804.”

National Archives and Records Administration (NARA) Records Management Language for Contracts RECORDS MANAGEMENT OBLIGATIONS

Contractor will be required to complete “ VA Privacy Training for Personnel without Access to VA Computer Systems or Direct Access to or the Use of VA Sensitive Information”, TMS 20939 No Access. Form will be provided upon award.

Applicability

This clause applies to all Contractors whose employees create, work with, or otherwise handle Federal records, as defined in Section B, regardless of the medium in which the record exists.

Definitions

“Federal record” as defined in 44 U.S.C. § 3301, includes all recorded information, regardless of form or characteristics, made or received by a Federal agency under

Federal law or in connection with the transaction of public business and preserved or appropriate for preservation by that agency or its legitimate successor as evidence of the organization, functions, policies, decisions, procedures, operations, or other activities of the United States Government or because of the informational value of data in them.

The term Federal record:

includes Department of Veteran Affairs records.

does not include personal materials.

applies to records created, received, or maintained by Contractors pursuant to their

Department of Veteran Affairs contract.

may include deliverables and documentation associated with deliverables.

Requirements

Contractor shall comply with all applicable records management laws and regulations, as well as National Archives and Records Administration (NARA) records policies, including but not limited to the Federal Records Act (44 U.S.C. chs. 21, 29, 31, 33), NARA regulations at 36 CFR Chapter XII Subchapter B, and those policies associated with the safeguarding of records covered by the Privacy Act of 1974 (5 U.S.C. 552a).

These policies include the preservation of all records, regardless of form or characteristics, mode of transmission, or state of completion.

In accordance with 36 CFR 1222.32, all data created for Government use and delivered to, or falling under the legal control of, the Government are Federal records subject to the provisions of 44 U.S.C. chapters 21, 29, 31, and 33, the Freedom of Information Act

(FOIA) (5 U.S.C. 552), as amended, and the Privacy Act of 1974 (5 U.S.C. 552a), as amended and must be managed and scheduled for disposition only as permitted by statute or regulation.

In accordance with 36 CFR 1222.32, Contractor shall maintain all records created for

Government use or created in the course of performing the contract and/or delivered to, or under the legal control of the Government and must be managed in accordance with

Federal law. Electronic records and associated metadata must be accompanied by sufficient technical documentation to permit understanding and use of the records and data.

Department of Veteran Affairs and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation.

Records may not be removed from the legal custody of Department of Veteran Affairs or destroyed except for in accordance with the provisions of the agency records schedules and with the written concurrence of the Head of the Contracting Activity. Willful and unlawful destruction, damage or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. In the event of any unlawful or accidental removal, defacing, alteration, or destruction of records, Contractor must report to

Department of Veteran Affairs. The agency must report promptly to NARA in accordance with 36 CFR 1230.

The Contractor shall immediately notify the appropriate Contracting Officer upon discovery of any inadvertent or unauthorized disclosures of information, data, documentary materials, records or equipment. Disclosure of non-public information is limited to authorized personnel with a need-to-know as described in the contract action.

The Contractor shall ensure that the appropriate personnel, administrative, technical, and physical safeguards are established to ensure the security and confidentiality of this information, data, documentary material, records and/or equipment is properly protected. The Contractor shall not remove material from Government facilities or systems, or facilities or systems operated or maintained on the Government’s behalf, without the express written permission of the Head of the Contracting Activity. When information, data, documentary material, records and/or equipment is no longer required, it shall be returned to Department of Veteran Affairs control or the Contractor must hold it until otherwise directed. Items returned to the Government shall be hand carried, mailed, emailed, or securely electronically transmitted to the Contracting Officer or address prescribed in the contract action. Destruction of records is EXPRESSLY

PROHIBITED unless in accordance with Paragraph (4).

The Contractor is required to obtain the Contracting Officer's approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material and/or records generated under, or relating to, contracts. The Contractor (and any sub-contractor) is required to abide by

Government and Department of Veteran Affairs guidance for protecting sensitive, proprietary information, classified, and controlled unclassified information.

The Contractor shall only use Government IT equipment for purposes specifically tied to or authorized by the contract and in accordance with Department of Veteran Affairs policy.

The Contractor shall not create or maintain any records containing any non-public

Department of Veteran Affairs information that are not specifically tied to or authorized by the contract.

The Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected from public disclosure by an exemption to the Freedom of Information Act.

The Department of Veteran Affairs owns the rights to all data and records produced as part of this contract. All deliverables under the contract are the property of the U.S.

Government for which Department of Veteran Affairs shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest. Any Contractor rights in the data or deliverables must be identified as required by FAR 52.227-11 through FAR 52.227-20.

Training. All Contractor employees assigned to this contract who create, work with, or otherwise handle records are required to take Department of Veteran Affairs-provided records management training. The Contractor is responsible for confirming training has been completed according to agency policies, including initial training and any annual or refresher training.

[Note: To the extent an agency requires contractors to complete records management training, the agency must provide the training to the contractor.]

Flowdown of requirements to subcontractors

The Contractor shall incorporate the substance of this clause, its terms and requirements including this paragraph, in all subcontracts under this contract action, and require written subcontractor acknowledgment of same.

Violation by a subcontractor of any provision set forth in this clause will be attributed to the Contractor.

References

• VHA 7515

B.3 PRICE/COST SCHEDULE

ITEM INFORMATION

ITEM

NUMBER

DESCRIPTION OF

SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

12.00 JB __________________ __________________

Monthly MG Maintenance Omaha Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

NATIONAL STOCK NUMBER: N/A

LOCAL STOCK NUMBER: N/A

Monthly Medical Gas Maintenance Grand Island Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027

4.00 JB __________________ __________________

Quarterly Medical Gas Maintenance Omaha Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Quarterly Medical Gas Maintenance Grand Island Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

2.00 JB __________________ __________________

Semi-Annual Medical Gas Maintenance Omaha Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Semi-Annual Medical Gas Maintenance Grand Island Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

1.00 JB __________________ __________________

Annual Medical Gas Maintenance Omaha (Note: 114 Outlets, 10% Total) Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Annual Medical Gas Maintenance Grand Island (Note: 24 Outlets, 10% Total) Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

120.00 HR __________________ __________________

Emergency Callout - Corrective Maintenance Omaha Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

96.00 HR __________________ __________________

Emergency Callout - Corrective Maintenance Grand Island Contract Period: Base POP Begin: 06-26-2026

POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

192.00 HR __________________ __________________

Non-Emergency Callout - Corrective Maintenance Omaha Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

128.00 HR __________________ __________________

Non-Emergency Callout - Corrective Maintenance Grand Island Contract Period: Base POP Begin: 06-26-2026 POP End: 06-25-2027 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Monthly MG Maintenance Omaha Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Monthly Medical Gas Maintenance Grand Island Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028

Quarterly Medical Gas Maintenance Omaha Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services

PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Quarterly Medical Gas Maintenance Grand Island Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Semi-Annual Medical Gas Maintenance Omaha Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Semi-Annual Medical Gas Maintenance Grand Island Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Annual Medical Gas Maintenance Grand Island (Note: 24 Outlets, 10% Total) Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Emergency Callout - Corrective Maintenance Omaha Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Emergency Callout - Corrective Maintenance Grand Island Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Non-Emergency Callout - Corrective Maintenance Omaha Option Year 1 Contract Period: Option 1 POP Begin: 06-26-2027 POP End: 06-25-2028 PRINCIPAL NAICS CODE: 541350 - Building Inspection Services PRODUCT/SERVICE CODE: H365 - Inspection - Medical, Dental, and Veterinary Equipment and Supplies

MANUFACTURER PART NUMBER (MPN): N/A

Non-Emergency Callout - Corrective Maintenance…