S02. Drawings - Mechanical.pdf
PDF 22 MB Posted
- Attached to
- Y1NB--Renovate Operating Rooms - VAMC Cleveland
- Solicitation number
- Amend0002
About this file
This amendment to a federal solicitation adds mechanical drawings to a renovation project. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 is seeking bids to renovate operating rooms at the VA Medical Center in Cleveland, Ohio. Amendment 0002 provides all mechanical drawings for the project and maintains the original bid opening date and time of September 9, 2020 at 12:00 PM EST, with all other terms of the solicitation remaining the same. The renovation work includes operating rooms, with mechanical system plans and details now provided to support bid responses for the services required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN THE
SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED
WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE. COPYRIGHT C 2019.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
18067
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:4
:5
P
M
0-H0-1
10701 East Blvd. Cleveland, OH 44106
06/26/2020 LDH DML
541-19-101Renovate Operating RoomsBID ISSUEMECHANICAL LEGEND AND GENERAL NOTES
H
APM
LDU
CALL OUTS:
DUCTWORK SYMBOLS:
ABBREVIATIONS:
MECHANICAL SYMBOLS:
GENERAL SYMBOLS:
HVAC PIPING:
CONTROL SYMBOLS:
LIMIT OF DEMOLITION
(WALL TYPE)
(WALL TYPE)
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
AC
AD
AFF
AHU
AP
CF
CD
CO
CW
Db dB Dp
DX
AIR CONDITIONING UNIT
ACCESS DOOR
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ACCESS PANEL
CENTRIFUGAL FAN
COOLING COIL CONDENSATE
CLEAN OUT
COLD WATER
DRY BULB TEMPERATURE
DECIBELS
DEW POINT TEMPERATURE
DIRECT EXPANSION
EA
EF
EX.
FC
FLR.
FD
FSD
HC
HP
EXHAUST AIR
EXHAUST FAN
EXISTING
FORWARD CURVED FAN
FLOOR
FIRE DAMPER
COMBINATION FIRE/SMOKE DAMPER
HEATING COIL
HORSEPOWER
MAX.
MIN.
NOM.
OA
PD
PF
PH
REA
RF
RH
Rh
SA
Sp. Gr.
SP
SPS
MAXIMUM
MINIMUM
NOMINAL
OUTDOOR AIR
PRESSURE DROP
PRE-FILTER
PREHEAT
RELIEF AIR
RETURN FAN
REHEAT COIL
RELATIVE HUMIDITY
SUPPLY AIR
SPECIFIC GRAVITY
STATIC PRESSURE
STATIC PRESSURE SENSOR
VD
VFD
Wb
VOLUME DAMPER
VARIABLE FREQUENCY DRIVE
WET BULB TEMPERATURE
LIMIT OF DEMOLITION
AND EXISTING WORK
POINT OF CONNECTION BETWEEN NEW
COMBINATION FIRE/SMOKE DAMPER
FSD
FIRE DAMPER
FD
SS STAINLESS STEEL
N.T.S. NOT TO SCALE
TCP TEMPERATURE CONTROL PANEL
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
RA RETURN AIR
ECCENTRIC REDUCER
DIRECTION OF FLOW
GV GRAVITY VENTILATOR
CFM
CUH
CUBIC FEET PER MINUTE
CABINET UNIT HEATER
DDC DIRECT DIGITAL CONTROL
GPM GALLONS PER MINUTE
MOTORIZED DAMPER
M
HZ ZONE HUMIDIFIER
RTU ROOFTOP UNIT
X
XR
XRL
EXISTING
EXISTING TO BE REMOVED
EXISTING TO BE RELOCATED
GH
GHR
HOT GLYCOL WATER HEATING SUPPLY
HOT GLYCOL WATER HEATING RETURN
GRR GLYCOL WATER RUN-AROUND RETURN
GR GLYCOL WATER RUN-AROUND SUPPLY
MEDIUM PRESSURE STEAM CONDENSATE
HEATING HOT WATER SUPPLY
HEATING HOT WATER RETURN
MPR
MPS
CHWS
HHWS
HHWR
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
MEDIUM PRESSURE STEAM
SECTION/DETAIL/ELEVATION MARK
DETAIL NO.
PRESSURE GAUGE
FLEXIBLE METAL EXPANSION LOOP ASSEMBLY
HPR HIGH PRESSURE STEAM CONDENSATE
F FIRE SUPPRESSION PIPE
STRAINER
PIPE EXPANSION ANCHOR
PIPE GUIDE
FLEXIBLE PIPE CONNECTOR
THERMOMETER IN PIPE WELL
BALANCING VALVE
X
E.L.
HEIGHT OF BOTTOM OF PIPE ABOVE FLOOR9'-2"
SHUTOFF VALVE
REDUCER OR INCREASER
UNION
CHECK VALVE
3-WAY CONTROL VALVE
GAUGE PORT (PETE'S PLUG)
DRAIN VALVE WITH HOSE FITTING
HIGH PRESSURE STEAMHPS
2-WAY CONTROL VALVE
NO
NC
MAV
SECONDARY CHILLED WATER SUPPLY (AHU-S-2-2)
SECONDARY CHILLED WATER RETURN (AHU-S-2-2)
SCHWS
SCHWR
CD CONDENSATE PIPING
DRAWING
PRESSURE REDUCING VALVE
D DRAIN
V VENT LINE
SHUTOFF VALVE IN VERTICAL PIPE
PROCESS CHILLED WATER SUPPLY
PROCESS CHILLED WATER RETURN
PCWS
PCWR
LOW PRESSURE STEAM CONDENSATELPR
LPS LOW PRESSURE STEAM
THIS PROJECT CONSISTS OF MULTIPLE TRADES OF WORK PERFORMED WITHIN AN EXISTING
BUILDING, ALL OF WHICH ALLOWS VERY LITTLE PERMISSIBLE RANGE
OF VARIATION. THE CONTRACTOR SHALL TAKE CAREFUL CONSIDERATION WITH THE
COORDINATION AND INSTALLATION OF THE MULTITUDE OF NEW SYSTEMS WHILE ALSO
ACCOMMODATING ANY EXISTING SYSTEMS TO REMAIN.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED WITH
THIS PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE
OF CONSTRUCTION.
THE COORDINATION DRAWINGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS!
THE CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN
ORDER TO ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.
IF CONFLICTS ARE IDENTIFIED DURING THE DEVELOPMENT OF COORDINATION PLANS, THE
CONTRACTOR SHALL NOTIFY THE VA COR, ARCHITECT, AND/OR ENGINEER OF ANY
CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THE
PROJECT PLANS.
A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE
CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOWN CONFLICTS
HAVE BEEN ADDRESSED.
1-H1-1
INVERTED BUCKET STEAM TRAP SET
INCLUDING PIPING ACCESSORIES
FLOAT & THERMOSTATIC STEAM TRAP SET
INCLUDING PIPING ACCESSORIES
PRESSURE RELIEF VALVE
MANUAL AIR VENT
LOCAL DRAIN, VALVED WITH 3/4"
THREADED CONNECTOR
NORMALLY CLOSED
NORMALLY OPEN
LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED
FROM EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO
COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT
PERMIT THE WORK TO BE PERFORMED AS INDICATED ON THESE DRAWINGS.
COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH VA A MINIMUM
OF TEN WORKING DAYS IN ADVANCE.
PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW WALL MOUNTED DEVICES WITH
VA AND ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE
LOCATION OF CEILING MOUNTED DEVICES. COORDINATE ROOF MOUNTED EQUIPMENT WITH
ARCHITECT PRIOR TO INSTALLATION.
PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO
INSTRUCTIONS FROM THE EQUIPMENT MANUFACTURER. MAINTAIN A MINIMUM OF 18 INCH
CLEARANCE AT CONTROLS FOR VARIABLE AIR VOLUME TERMINALS AND VENTURI VAV
TERMINALS.
NEW DUCTS OR PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO
ELECTRICAL DRAWINGS FOR LOCATION OF PANELS.
UNLESS NOTED OTHERWISE, BRANCH DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS
THE NECK OF THE DIFFUSER.
ALL REFRIGERANT PIPING SHALL BE SIZED, SLOPED, TRAPPED, ROUTED AND CHARGED IN
STRICT ACCORDANCE WITH WRITTEN INSTRUCTIONS FROM THE EQUIPMENT MANUFACTURER.
SIZING AND ROUTING SHOWN ON THE DRAWINGS IS FOR BIDDING PURPOSES ONLY.
IN GENERAL, REFRIGERANT SYSTEMS SHALL BE THOROUGHLY EVACUATED, AND REFRIGERANT
CHARGE SHALL BE DETERMINED BY WEIGHT.
NO TEMPERATURE SENSING CONTROL DEVICES SHALL BE LOCATED OVER HEAT PRODUCING
DEVICES.
MECHANICAL DRAWINGS ARE DIAGRAMMATIC. WHERE DUCT SIZE SHOWN IS IN CONFLICT WITH
STRUCTURE OR OTHER BUILDING SYSTEM, CONTRACTOR MAY MODIFY DUCT SIZE AND PROVIDE
EQUIVALENT FREE AREA DUCT.
WHERE EQUIPMENT IS TO BE REMOVED, REMOVE ALL ASSOCIATED PIPING, DUCTWORK,
CONTROLS, CONCRETE PADS, SUPPORTS, ETC. PATCH WALL AND FLOOR OPENINGS TO
MATCH ADJACENT SURFACES.
CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO
COMPLETE DEMOLITION AND NEW WORK IN AREAS OUTSIDE OF RENOVATION PROJECT.
CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO
THIS WORK.
MANUAL BALANCING DAMPER ON DUCT
ROUND DUCT SIZE12"∅
RECTANGULAR DUCT SIZE24x18
REFERENCE TO CODED NOTE
SUPPLY AIR DUCT
HUMIDITY SENSOR
DDC THERMOSTATT
TO BE MOUNTED OVER ACCESSIBLE CEILING
SUPPLY AIR DIFFUSER
SHADING INDICATES TO PROVIDE QUADRANT BLANK-OFF
IN NECK OF DIFFUSER. TO BE FURNISHED WITH DIFFUSER.
INDICATES TRANSITION
SINGLE LINE
PNEUMATIC THERMOSTATT
RETURN AIR DUCT
EXHAUST AIR DUCT
EXISTING TO REMAIN
EXISTING TO BE REMOVED
EQUIPMENT OR FIXTURE MARK
AIR DISTRIBUTION DEVICE
EXISTING TO BE RELOCATED
RETURN AIR GRILLE
EXHAUST AIR GRILLE
AIR PRESSURE MONITOR
PIPE TRANSITION
LOCAL DISPLAY UNIT
TYPE
CONNECTION SIZE
AT DEVICE
EQUIPMENT
TYPE
UNIT NUMBER
PROJECT COORDINATION NOTES
HVAC GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
A.
B.
C.
D.
E.
X X-X
XXX
X
X
AIRFLOW (CFM)
Db SUMMER
OUTDOOR DESIGN
Wb SUMMER
Db WINTER
DESIGN ALTITUDE: 800 FT.
INDOOR AREA
SUMMER
Db Db
°F
TEMPERATURES
89.4°F
73.9°F
-4.0°F
WINTER
°F
75 70 20
OPERATING ROOM (ORTHO, GENERAL, ROBOTIC, CARDIO)
LABORATORY, FROZEN SECTION
CARDIO PUMP ROOM
DESIGN CONDITIONS RELATIVE
HUMIDITY (%)
RELATIVE
HUMIDITY (%)
OFFICE SPACE
CLEAN CORRIDOR
SEMI-RESTRICTED CORRIDOR
STORAGE ROOM (EQUIPMENT, ORTHO, CART HOLDING,
IMPLANT, CARDIO EQUIPMENT, ROBOTIC EQUIPMENT)
MECHANICAL ROOM
6075 70 20
6075 70 20
6070 70 30
NA84 50 NA
6066 75 30
6075 70 20
6066 75 30
HVAC DESIGN DATA
SOILED HOLDING -- - -
ANESTHESIA WORKROOM 6075 70 20
GAS ROOM -- - -
HOUSEKEEPING / EMS -- - -
ELECTRICAL ROOM -86 40 -
IMMEDIATE USE STERILIZATION ROOM 5569 69 30
LOCKER ROOM 6075 70 20
MEDICATION PREP ROOM 6075 70 20
Revisions: Date:
Bid Issue 06/26/2020
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN THE
SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED
WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE. COPYRIGHT C 2019.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
18067
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:4
:0
P
M
0-H0-2
10701 East Blvd. Cleveland, OH 44106
06/26/2020 LDH DML
541-19-101Renovate Operating RoomsBID ISSUEMECHANICAL DETAILS
R
R
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
TUBING 5 FT
NOM. SIZE
PIPE
THRU (20)
6 8 10
(32)(25) (40)
(65)
(50)
(75)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
SADDLE
WELD
1312 14 16
(125)(100)
(150)
(200)
TO 1000 LB. (453 KG) UNIFORM LOAD
TRAPEZE HANGER FOR UP
PROVIDE INSULATION SHIELD
SIDE VIEW
1 5/8" (43 MM) 12 GAGE1" (25 MM) MAX.
STRENGTH INSULATION
PROVIDE HIGH COMPRESSIVE
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
HANGER ROD
UNDER INSULATION SHIELD
AT HANGER
INSULATION SHIELD
TEMPERATURE PIPE)
REQUIRED FOR LOW
BARRIER TYPE IS
INSULATION (VAPOR
SPACING ON
36" (900 MM) MAX.
BAND
(9 PCF MIN. DENSITY)
HANGER RODS WITH
(8" (200 MM) MIN.)
CHANNEL OR 2"x2"x1/4"
(50x50x8 MM) ANGLE
864 532 2 1/21 1/21 1 1/4IN.
(MM)
(M)
FT.
FT.
(M)
(5.8)(5.2)(4.1) (4.9)(3.7)(3.0) (3.4)(2.7)(2.1)
(4.9)(4.1)(3.7) (4.0)(3.0)(2.4)(1.8)5 FT
THRU 3/4
(2.1) (2.1)
(2.1)
(2.7)
(2.4)
1/2" (15 MM) DIA.
EACH CHANNEL
AND INSERT FOR ALL PIPING
3/8" (10 MM) PLATE
AND INSULATION THICKNESS
INSULATION
PIPE &
CUT TO SUIT PIPE DIA.
STRUCTURE
1/2" (15 MM) U-BOLT
PIPE & INSULATION
WELD
ANCHOR BOLTS,
2 AT EACH PLATE.
MIN. SIZE 5/8" (18 MM)
STRUCTURAL CHANNEL
OR ANGLES
BASE PLATE
3/8" (10 MM)
(2"x2"x1/4"
(50x50x8 MM))
STEEL EXPANSION SHIELD FOR
THIS TYPE SHALL BE USED ONLY
INSERTS FOR NEW CONSTRUCTION
FOR EXISTING CONSTRUCTION AND
3/8" (10 MM) MIN DIA EXPANSION BOLTS
NUTS & WASHERS
HANGER RODS
3/8" (10 MM) MIN DIA
FLOOR SLAB
CLIP
ANGLE
HANGER RODS
3/8" (10 MM) MIN DIA
TURNBUCKLE
NEW CONSTRUCTION ONLY.
3/8" (10 MM) MIN DIA INSERTS
IN SLABS OR BEAMS OF
INSERTS FOR NEW CONSTRICTION
EXISTING CONSTRUCTION AND
4" (100 MM) MIN DEPTH
CONCRETE
VANE
VANE
MAIN EXHAUST OR RETURN
PLAN VIEW
ALTERNATE AIR TERMINAL UNIT TAKE-OFF
PLAN VIEW
°M
A X
"D
MAIN SUPPLY
ROUND SHEET METAL
DUCT.
RIGID DUCT TO AIR TERMINAL
UNIT.
F L O
W
FLOW
AIR TERMINAL UNIT TAKE-OFF
PLAN VIEW
MAIN SUPPLY
SMACNA FIGURE 4-6
45° LEED IN
RIGID DUCT TO AIR TERMINAL
UNIT.
W1
W
ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE REGARDLESS
OF W DIMENSION.
ALL SINGLE VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM
SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE
DOUBLE VANE TYPE.
NOTE:
1.
2.
3.
4.
M A
X
M A X.
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
AIR
FLOW
AIR
FLOW
E Q
U
IP
M E
N T
M A
X
M A
X
M A X.
M A
X
0°
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
A
IR
F L O
W
W
MAIN SUPPLY
DUCT
AIR
FLOW
1/4 W OR 4"
[102mm] MIN.
AIR
FLOW
AIR
FLOW
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
MAIN
SUPPLY
DUCT
TOP REGSTER
ADJUSTABLE
METAL ROD
OR LINKAGE
PROVIDE VOLUME
DAMPER WHEN
SHOWN ON
FLOOR PLANS
PROVIDE VOLUME
DAMPER WHEN
SHOWN ON FLOOR
PLANS
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON FLOOR
PLANS
SEE FLOOR PLAN FOR
SPLIT DIMENSION
MAIN
SUPPLY
DUCT
TURNING VANES
SUPPLY REGISTER
OR BRANCH DUCT
A
IR
F L O
W
AIR
FLOW
AIR
FLOW
SUPPLY REGISTER TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF
PLAN VIEW
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR
UP UP TO 25% OF THE MAIN DUCT CFM. THE BRANCH
DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF
THE MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN
THE MAIN DUCT VELOCITY IS 1000 FPM [5 M/S] OR
LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED
IN ALL OTHER CASES AND MAY BE USED AT ANYTIME.
SHOW VOLUME DAMPERS ON FLOOR PLANS.
NOTE:
1.
2.
BRANCH DUCT
1/4W OR 4"
[102mm] MIN.
PROVIDE VOLUME DAMPER
WHEN SHOWN ON FLOOR
PLANS
W
AIR
FLOW
AIR
FLOW
1/6W
/3
W
1/2W
WW
SHORT RADIUS ELBOW
WITH TWO VANES
SHORT RADIUS ELBOW
WITH ONE VANE
STANDARD RADIUS
ELBOW
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
/3
W
2/3W
R
W
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT
RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL
BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
NOTE:
1.
2.
SECTIONSIDE ELEVATION
STIFFEN BLADE
AS REQUIRED
DUCT
1/2" [15mm]
ROUND ROD PIN
2" INSULATION
STAND-OFF
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
OUTSIDE END BEARING
1/8" [6mm]
CLEARANCE
ALL AROUND
DAMPER BLADE
INSULATION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
NOTE:
1.
2.
INSULATED
PIPE OR
DUCT
DRYWALL PARTITION
3/4" [19mm] APPROVED
FIRESTOP INSULATION WITH
VAPOR BARRIER
[152mm]
6"
[152mm]
6"
FIRESTOP
MATERIAL
PARTITION SUPPORT
MASONRY
PARTITION
[152mm]
6"
[152mm]
6"
PARTITION OR CHASE PENETRATION
FLOOR OR DECK PENETRATION
WELD
1/4" [6mm]∅
ANCHOR ROD FOR
NEW CONSTRUCTION
PIPE SLEEVE
WHERE SPECIFIED
3/4" [19mm]
APPROVED FIRESTOP
INSULATION WITH
VAPOR BARRIER
FIRESTOP MATERIAL
FLOOR
INSULATED
PIPE OR DUCT
APPLICABLE TO PENETRATIONS OF
ALL FIRE RATED MEMBRANES, IN
ACCORDANCE WITH NFPA 101.
REFER TO SPECIFICATIONS SECTION
FOR FIRE STOPPING SYSTEMS.
NOTE:
1.
ROOF
OVER EXISTING
LAP NEW MEMBRANE
FIBER CANT.
16"-18" TALL ROOF CURB
BY MECHANICAL CONTRACTOR
BY MECHANICAL CONTRACTOR.
SOLDER ALL SEAMS
ALUMINUM CAP FABRICATED
WATERTIGHT.
DUCT
SOLDER SEAMS
COLLAR AT DUCT.
WATERTIGHT.
MANUFACTURER
INSULATION BY CURB
NOT TO SCALE NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALENOT TO SCALE
NOT TO SCALE
NOT TO SCALE NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
EXHAUST OR RETURN BRANCH DUCTWORK
PIPE/DUCT PENETRATION OF FIRE/SMOKE BARRIERS
HORIZONTAL PIPE ANCHOR DETAIL
DUCTWORK SQUARE VANED ELBOWS
TYPICAL PIPE HANGERS
TYPICAL METHOD OF SECURING HANGER RODS IN CONCRETE SLABS AND
BEAMS
DUCTWORK RADIUS ELBOWS
TYPICAL DUCTWORK TRANSITION WITH EQUIPMENT MOUNTED IN DUCTDUCT ROOF PENETRATION DETAIL
VOLUME DAMPER DETAILSUPPLY DUCTWORK TAKE-OFFS
NOTE:
VAV TERMINAL DETAIL
AVAILABLE.
OR LEFT SIDE) BASED ON SPACE
DETERMINE CONTROL PANEL LOCATION (RIGHT
MAINTAIN ADEQUATE SERVICE
ACCESS TO CONTROLS. T.C.C. SHALL
MINIMUM OF (1) 90° CHANGE
OF DIRECTION BETWEEN EACH
DIFFUSER AND VAV TERMINAL
(TYPICAL)
DIFFUSER PER PLAN
UNLESS OTHERWISE
BE SAME SIZE AS
DIFFUSER NECK.
NOTED, BRANCH DUCTS
TO DIFFUSERS SHALL
VAV
TERMINAL
FLEX DUCT
INSTALL MANUAL BALANCING
DAMPER FOR EACH DIFFUSER
WITHIN DUCT AS FAR FROM
DIFFUSER AS POSSIBLE. ALL
MANUAL BALANCING DAMPERS
SHALL HAVE 2" INSULATION
STAND-OFF AND LOCKING
QUADRANT. NOTE: WHERE
VAV TERMINAL SERVES ONLY
ONE DIFFUSER MANUAL
BALANCING DAMPER IS NOT
REQUIRED.
PROVIDE MINIMUM OF FOUR
STRAIGHT DUCT DIAMETERS TO
INLET OF VAV BOX. NO FLEX
SHALL BE USED TO INLET OF
VAV BOX.
1. PROVIDE 12"x12" DUCT
ACCESS PANEL DOWNSTREAM
OF REHEAT COIL.
NOTES:
1. DETAIL APPLIES TO TERMINAL VAV BOX INSTALLATION. VAV BOXES
ARE PART OF AHU-S-2-1 AND AHU-S-2-3 SYSTEMS.NOT TO SCALE
M
IN
M
IN
F&T TRAP
GLOBE VALVE
BYPASS (NORMALLY
CLOSED)
STRAINER
UNION (TYP.)
SHUTOFF VALVE (TYP.)
NOTE:
1.
2.
3.
SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG
BOLTS NOT OVER 12" [300mm] ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS (CONCRETE
ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).
RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN
THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
GRAVITY BACKDRAFT DAMPER
RIGID CONDUIT TO
ACCOMMODATE
ELECTRICAL WIRES
SEE NOTE 2
PREFABRICATED
ROOF CURB
WOOD NAILING
STRIP
ELECTRICAL
CONDUIT GUIDE
MOTOR HOUSING
DUCT
TRANSITION DUCT TO
FULL SIZE OF
DAMPER SUPPLIED
WITH ROOF VENTILATOR
ROOF
SEE NOTE 2
SEE NOTE 1
CURB CAP
DIRT LEG FULL
MAIN SIZE
INVERTED
BUCKET TRAP
DIRT LEG FULL
MAIN SIZE
GLOBE VALVE
BYPASS (NORMALLY
CLOSED)
STRAINER
UNION (TYP.)
CHECK VALVE
SHUTOFF VALVE (TYP.)
VENT ALL HIGH POINTS INDICATED ABOVE.
IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN
NOTES:
1.
2.
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" (20 MM) GATE VALVE
ADAPTER TO 20 MM (3/4") HOSE THREAD.
PROVIDE HOSE CAP NUT
NOTES:
ELEVATION
THREADED PIPING WELDED PIPING
ELEVATION
1/4" (8 MM)
COPPER TUBING
1/2" (15 MM)
GATE VALVE
1/2" (15 MM) x 4" (100 MM)
REDUCER
CIRCULATING WATER PIPING
WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
DRAIN ALL LOW POINTS AS INDICATED ABOVE.
1.
2.
NIPPLE
ELEVATION
ROUND FLEXIBLE CONNECTION
FLANGED
CONNECTION ON
FAN SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED. 6" [150mm] NOMINAL WITH MATERIAL
TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW
BAND
1"x1/8" [25x3mm] BAND
IRON
BOLT ON 4" [100mm]
CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS
ON 12" [300mm]
CENTERS
RIVET ON 4"
[100mm]
CENTERS
1/2" 1 1/2"
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
SCREWHEAD VENT
UNIONS OR SOLDER
CONNECTION (TYP.)
WATER SUPPLY
2-WAY VALVE
1/2"
LPR
L P
S
HPR
H P
S
BRANCH PIPING VALVES SHALL BE PROVIDED WITH PACKING GLANDS.
NOTES:
1.
SHUT-OFF/BALANCE VALVE
SHUT-OFF VALVE
STRAINER
BRANCH TAKE-OFFS
ON TOP OF MAINS H
H W
S
H H
W R
SHUTOFF VALVE (TYP.)
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN THE
SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED
WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE. COPYRIGHT C 2019.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
18067
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:4
:1
P
M
0-H0-3
10701 East Blvd. Cleveland, OH 44106
06/26/2020 LDH DML
541-19-101Renovate Operating RoomsBID ISSUEMECHANICAL DETAILS
ANCHOR DUCT TO ANGLE
IRON IN FOUR PLACES
ANGLE IRON POST
ANCHOR BASE TO STRUCTURE
PENTHOUSE FLOOR
POST BASE ANCHORED TO
FLOORANGLE IRON ACROSS BOTTOM
OF DUCT ANCHORED TO
POST
UNISTRUT TO SPAN TOP
AND BOTTOM OF DUCT
2" RIGID INSULATION.
INSULATION SHALL BE
CONTINUOUS THROUGH
SUPPORTS.
ALUMINUM FLASHING
NAIL FLASHING 8"O.C. THROUGH
ROOF MEMBRANE FLASHING &
COVER HEADS WITH SILICONE
SEALANT
NEW RIGID INSULATION
NEW ROOF
INSULATION
EXISTING ROOFING AND
INSULATION
NEW MEMBRANE
FLASHING
METAL CURB
WOOD BLOCKING
EXISTING ROOFING AND
INSULATION
EXISTING METAL
ROOF DECK
SEAL NEW MEMBRANE
FLASHING TO EXISTING EPDM
ROOF MEMBRANE.
BY ROOFING
SUBCONTRACTOR.
MECHANICAL CONTRACTOR TO FURNISH
PREFABRICATED METAL CURB WITH WOOD BLOCKING
AND ALUMINUM FLASHING. PATE MODEL ES-2B OR
OTHER AS APPROVED.
ABOVE 2" (50 MM) DIA. PIPE
2 1/2" (65 MM) DIA.
2" (50 MM) DIA. & SMALLER
HORIZONTAL
ABOVE 2" (50 MM) DIA. PIPE 2" (50 MM) DIA. & SMALLER
VERTICAL
2 1/2" (65 MM) DIA.
NOT TO SCALE
FLOOR MOUNTED DUCT SUPPORT DETAIL
TYPICAL ROOF SUPPORT DETAIL
TYPICAL COIL PIPING CONNECTIONS VAV AND DUCT-MOUNTED REHEAT
COILS
INSTALLATION OF THERMOMETER WELLS
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
TYPICAL AIR VENT
FLEXIBLE DUCT CONNECTION DETAILS
TYPICAL CHILLED AND HOT WATER PIPING DRAIN VALVE CONNECTIONS
NOT TO SCALE
NOT TO SCALE
LOW PRESSURE STEAM DRIP DETAIL
HIGH/MEDIUM PRESSURE STEAM DRIP DETAIL
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
TYPICAL HEATING HOT WATER PIPING TAKE-OFFS
WELD AND SEAL AT JOINED LENGTHS.
E. DETAIL ILLUSTRATES TYPICAL 60" LENGTH. PROVIDE 1" OVERLAP FOR JOINED LENGTHS. TACK
ADDITIONAL INFORMATION.
OTHER DETAILS FOR
JACKETING. REFER TO
INSULATION W/30 MIL PVC
2" POLYISOCYANURATE
NOTES:
D. TACK WELD AS REQUIRED.
C. DUCT SYSTEMS SHALL BE DRIED PRIOR TO INSULATION.
B. 18 GA GALVANIZED STEEL CONSTRUCTION.
A. "H" SHALL BE HEIGHT NECESSARY TO PROVIDE 1" PITCH PER FOOT. "W" IS EXISTING DUCT WIDTH.
SHEET METAL CAP WITH 1" LIP ON EACH SIDE. TACK WELD 3 SUPPORTS.
3 SUPPORTS
H
W
L=60"
1" LIP ON EACH SIDE
H
W
SUPPORT X 3
EXISTING DUCTWORK
1" LIP1" LIP
NEW CAP
GALVANIZED SHEET STEEL
ALL MATERIAL SHALL BE 18 GA.
DUCTS.
2" INSULATION SIDES AND BOTTOM OF
3. TWO (2) SIDE-BY-SIDE DUCTS MAY OCCUR ON SAME FRAMES.
BE MADE TO AVOID PENETRATION OF INSULATION OR JACKETING.
2. DETAIL IS TYPICAL. WHERE OTHER SUPPORT TYPES EXIST, ADJUSTMENTS SHALL
DUCT INSULATION OR JACKETING.
1. ADJUST ROOF SUPPORTS AND ANGLES SO THAT THERE IS NO PENETRATION OF
NOTES:
(TYPICAL)
POINT 2" THICK AT EDGES.
INSULATION PITCH 1" PER FOOT. LOW
ROOF INSULATION ON TOP OF 2"
TAPERED RIGID POLYISOCYANURATE
JACKET (TYPICAL)
INSULATION WITH 30 MIL PVC
2" RIGID POLYISOCYANURATE
ROOF MEMBRANE
ROOF INSULATION
METAL DECK
16"-18" ROOF CURB
(TYPICAL)
SUPPORT TO CURB
ANCHOR UNISTRUT
(TYPICAL)
UNISTRUT SUPPORT
EXTERIOR DUCT TOP-SIDE REINFORCEMENT DETAIL
ROOF MOUNTED DUCT SUPPORT DETAIL
NOT TO SCALE
NOT TO SCALE
POWER ROOF VENTILATOR DETAIL
ROOF INSULATION
ROOF
8"
1. ADEQUATE PIPE CURB AREA AND BOOT
OPENINGS SHALL BE PROVIDED FOR ELECTRICAL
CONDUIT ROOF PENETRATIONS WHERE REQUIRED.
MECHANICAL CONTRACTOR SHALL COORDINATE
LOCATIONS AND SIZES WITH ELECTRICAL
CONTRACTOR.
2. CURB SHALL BE FURNISHED BY THE
MECHANICAL CONTRACTOR TOTHE GENERAL
CONTRACTOR AT THE JOB SITE. THE GENERAL
CONTRACTOR SHALL INSTALL CURB AND
INCORPORATE CURB INTO ROOFING SYSTEM.
2" x 2" WOOD NAILER - SCREW TO BASE SECTION
ACRYLIC CLAD THERMOPLASTIC COVER (COUNTER FLASHING)
GALV. STEEL PIPE CURB BASE SECTION
SEE PLAN VIEW DWG. FOR PIPE CURB SIZE
3# DENSITY CURB INSULATION
NOTES:
GRADUATED STEP BOOT WITH STAINLESS STEEL CLAMPS
ACRYLIC CLAD THERMOPLASTIC COVER (COUNTER FLASHING)
NOT TO SCALE
PIPE ROOF CURB PENETRATION DETAIL
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN THE
SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED
WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE. COPYRIGHT C 2019.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
18067
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:4
:2
P
M
0-H0-4
10701 East Blvd. Cleveland, OH 44106
06/26/2020 LDH DML
541-19-101Renovate Operating RoomsBID ISSUEMECHANICAL SCHEDULES
NOTES:
NOTES:
MARK
SERVICE
AIR QUANTITY (CFM)
THROAT SIZE
ACCESSORIES
ALUMINUM BIRDSCREEN
MANUFACTURER'S ROOF CURB
THROAT AREA (SQ. FT.)
PRESSURE DROP (IN WG)
GV-1
EXHAUST
19,000
28.0
0.10
YES
YES
12'-0" x 2'-4"
NOTES:
NOTES:
NOTES:
VAV TERMINAL NOTES:
NOTES:
(GPM)
COIL FLOW
(MBH)
CAPACITY
MIN.
(CFM)
MAX.
(CFM)
AIRFLOW AIRFLOWMARK
DROP (FT.)
WATER PRES.
RISE (°F)
AIR TEMP.
HOT WATER HEATING COIL PERFORMANCETERMINAL
(NOTE 2)
TYPE
ROWS
NUMBER OF
SIZE
BRANCH PIPE
8.
320 3/4"10.50.8B220
13.8700 3/4"10.5
1.2
C375
23.9630 3/4"135 0.5B630
2.0
INLET
TERMINAL TYPE
TERMINAL
A
C
NECK SIZE (IN)
SUPPLY DUCT
(IN)
MAX AIRFLOW
(CFM)
RADIATED NOISE
(NC)
DISCHARGE
TERMINAL
CONN. SIZE (IN)
DISCHARGE DUCT
(IN)
VAV-A
VAV-B
VAV-C
MIN.
(CFM)
MAX.
(CFM)
AIRFLOW
AIRFLOW
SV-1
MARK
2450 1075
2750 1375
2450 1075
4175 2090
3675 1590
4135 2070
RV-1
SV-2
RV-2
SV-3
RV-3
SV-4
3635 1570
2200 1100
RV-4
SV-5
FUNCTION
SUPPLY
RETURN
SUPPLY
RETURN
SERVICE
OR 1
OR 1
OR 2
OR 2
OR 3
OR 3
OR 4
OR 4
OR 5
VENTURI
VALVE SIZE
14" x 28"
1900 800
2500 1250
2200 950
2400 1200
2100 900
2700 1350
RV-5
SV-6
RV-6
SV-7
RV-7
SV-8
2400 1050
2550 1275
RV-8
SV-9
RETURN
SUPPLY
RETURN
OR 5
OR 6
OR 6
OR 7
OR 7
OR 8
OR 8
OR 9
SUPPLY
RETURN
SUPPLY
RETURN
SUPPLY
2250 975
2650 1325
2350 1025
420 420
2050 1025
RV-9
SV-10
RV-10
SV-11
SV-12
2050 1025
140 140
RV-12
SV-13
RETURN
SUPPLY
RETURN
OR 9
OR 10
OR 10
ANESTHESIA STORAGE
SEMI-RESTRICTED CORR. (N)
SEMI-RESTRICTED CORR. (N)
LAB, FROZEN SECTION
2000 1040
1780 740
270 270
270 270
700 700
700 700
SV-14
RV-14
SV-15
RV-15
SV-16
RV-16
680 680SV-17
SUPPLY
RETURN
SUPPLY
RETURN
SUPPLY
RETURN
SUPPLY
CLEAN CORE
CLEAN CORE
ANESTHESIA WORKROOM
CART HOLDING
CART HOLDING
CARDIO PUMP ROOM
SUPPLY
SUPPLY
RETURN
SUPPLY
SUPPLY
RETURN
SUPPLY
RETURN
SUPPLY
420 420RV-11 ANESTHESIA STORAGE RETURN
ANESTHESIA WORKROOM
550 550RV-17 RETURNCARDIO PUMP ROOM
3000 1500SV-18 SUPPLYSEMI-RESTR CORR (S)
2700 1200RV-18 RETURNSEMI-RESTR CORR (S)
SHUT-OFF
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
SHUT-OFF
VARIABLE
VARIABLE
VARIABLE
VARIABLE
VARIABLE
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
SUPPLY ONLY
ENHANCED TRACKING
ENHANCED TRACKING
SUPPLY ONLY
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
VALVE
OPERATION
VALVE
TYPE
VAV TERMINALS
VARIABLE AIR VOLUME TERMINALS : CONNECTION SCHEDULE
AIR DISTRIBUTION DEVICE (DIFFUSERS, REGISTERS AND GRILLES)
GRAVITY VENTILATOR
AIRFLOW CONTROL VALVES (VENTURI) DUCT MOUNTED HOT WATER REHEAT COILS
DUCT MOUNTED FINAL FILTERS
1. VENTURI VALVES SHALL BE LOW PRESSURE. VALVES PRESSURE DROP RANGE 0.3-3.0 INCHES WC.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
3. VALVE OPERATION IS AS FOLLOWS:
· ENHANCED TRACKING - VARIABLE AIR VOLUME TRACKING PAIR, PROVIDED WITH EXTRA I/O TO MEET THE
NEEDS OF HUMIDITY CONTROL AND PRESSURE MONITORING, PLUS SHUT-OFF CAPABILITY.
· SUPPLY ONLY - SUPPLY VALVE WHERE NO TRACKING EXHAUST VALVE IS INSTALLED.
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1. PROVIDE DUCT SIZES AS INDICATED OR EQUIVALENT FREE AREA AS INDICATED ON PLANS.
2. CONTRACTOR SHALL PROVIDE ALL TRANSITIONS/OFFSETS AS NECESSARY.
NOTE 1: BASIS OF SPECIFICATION IS PRICE SDV. TERMINALS SHALL BE CAPABLE OF OPERATING WITH A MINIMUM INLET
PRESSURE OF 0.5 IN. W.G. PROVIDE WITH SCREW ACCESS (UN-HINGED) WHERE TERMINALS ARE INSTALLED IN THE
BEAM/JOIST SPACE.
NOTE 2: REFER TO "VARIABLE AIR VOLUME TERMINALS: CONNECTION SCHEDULE" FOR TERMINAL SIZE, DUCT CONNECTIONS
AND DUCT SIZES.
CFM
HOT WATER HEATING COIL PERFORMANCE
MARK
MBH EAT/LAT
MAX. APD
EWT / LWT
WPD
RH-2 2750
RH-1 32"x15" 2750 135.1 55/100 0.60 6.9 180/140 2.4
RH-3 4175
OR 1
OR 2
OR 3
RH-5 2200
RH-4 4135
RH-6 2500
OR 4
OR 5
OR 6
RH-8 2700
RH-7 2400
RH-9 2550
OR 7
OR 8
OR 9
RH-11 420
RH-10 2650
RH-12 2050
OR 10
ANESTHESIA STORAGE
SEMI-RESTRICTED CORR (N)
RH-13 140LAB, FROZEN SECTION
RH-15 270
RH-14
RH-16 700
CLEAN CORE
ANESTH. WORKROOM
CART HOLDING
RH-18 3000
RH-17 680
RH-19 800
CARDIO PUMP ROOM
SEMI-RESTRICTED CORR (S)
IMM. USE STERILIZATION
RH-20 900EQUIPMENT STORAGE
(IN.) (FT.)
FLOW
(GPM)
MARK
OR 1
OR 2
OR 3
OR 4
OR 5
OR 6
OR 7
OR 8
OR 9
OR 10
ANESTHESIA STORAGE
EMI-RESTRICTED CORRIDOR (N)
LAB, FROZEN SECTION
CLEAN CORE
ANESTHESIA WORKROOM
CART HOLDING
CARDIO PUMP ROOM
SEMI RESTRICTED CORRIDOR (S)
IMMEDIATE USE STERILIZATION
EQUIPMENT STORAGE
FF-2
FF-1
FF-3
FF-4
FF-5
FF-6
FF-7
FF-8
FF-9
FF-10
FF-11
FF-12
FF-13
FF-14
FF-15
FF-16
FF-17
FF-18
FF-19
FF-20
1H x 1-1/2W
1H x 1-1/2W
1H x 2W
1H x 2W
1H x 1-1/2W
1H x 1-1/2W
1H x 1-1/2W
1H x 1-1/2W
1H x 1-1/2W
1H x 1-1/2W
1/2H x 1W
1H x 1-1/2W
1/2H x 1W
1/2H x 1W
1H x 1-1/2W
1/2H x 1W
1/2H x 1W
1/2H x 1W
1H x 1-1/2W
1/2H x 1W
28.5H x 40W x 27D
28.5H x 40W x 27D
28.5H x 52W x 27D
28.5H x 52W x 27D
28.5H x 40W x 27D
28.5H x 40W x 27D
28.5H x 40W x 27D
28.5H x 40W x 27D
28.5H x 40W x 27D
28.5H x 40W x 27D
16.5H x 26.4W x 27D
16.5H x 26.4W x 27D
28.5H x 40W x 27D
28.5H x 40W x 27D
16.5H x 26.4W x 27D
16.5H x 26.4W x 27D
16.5H x 26.4W x 27D
28.5H x 40W x 27D
16.5H x 26.4W x 27D
16.5H x 26.4W x 27D
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
32"x15"
44"x15 "
44"x15"
26"x15"
30"x15"
30"x15"
32"x15"
32"x15"
33"x15"
21"x15"
30"x15"
12"x12"
38"x15"
18"x12"
18"x12"
16"x12"
15"x12"
9"x12"
27"x15"
141.3 0.60 7.1 180/140 6.5
211.3 0.62 10.7 180/140 4.5
210.0 0.61 10.6 180/140 4.4
111.0 0.59 5.6 180/140 3.6
ROWS
130.4 0.56 6.6 180/140 5.5
117.1 0.48 6.0 180/140 4.5 2
133.3 0.58 6.8 180/140 2.3 2
128.4 0.53 6.5 180/140 2.2 2
134.7 0.52 6.8 180/140 2.4 2
20.9 0.04 1.1 180/140 0.2
105.9 0.37 5.3 180/140 4.0
6.9 0.03 0.4 180/140 0.1
102.0 0.45 5.2 180/140 3.6
180/140
180/140
180/140
180/140
180/140
180/140
13.0 0.05 0.7 0.2
36.4 0.22 1.9 1.7
34.2 0.25 1.8 1.5
149.5 0.48 7.5 8.2
41.3 0.24 2.1 2.3
44.2 0.32 2.3 2.7
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
BRANCH
PIPE SIZE
(IN)
RESISTANCE
@ MAX. AIR
FLOW (IN.)
HOUSING
DIMENSIONS
(INCHES)
HEPA HOUSING
(SEE NOTE)
SERVICE MAXIMUM AIR
FLOW (CFM)
MINIMUM AIR
FLOW (CFM)
SERVICE FIN
LENGTH
x HEIGHT
8"Ø
12"Ø
6"Ø
10"Ø
10x10
22x12
12x8
14x12.528
MARK TYPE
S1
(INCHES)
FACE SIZE
24x24
COLORSTYLE
ALUMINUMWHITE
MATERIAL
- 1
NOTESFACTORY
DAMPER
(INCHES)
NECK SIZE
SEE TAGSUPPLY
DIFFUSER
R1 RETURN
WHITE -
GRILLE
24x12 PERFORATED FACE
LAY-IN
SEE TAG 1ALUMINUM
R2 24x24 WHITE - 1SEE TAG ALUMINUM
PERFORATED FACE
LAY-IN
RETURN
GRILLE
S3 12x24 YES 1,36"ØSUPPLY
DIFFUSER
S4 24x24 YES 1,38"ØSUPPLY
DIFFUSER
LAMINAR FLOW
SURFACE MOUNTED
STAINLESS STEEL
S2 24x24 ALUMINUM - 1SEE TAGSUPPLY
DIFFUSER
WHITE
E1 EXHAUST
WHITE -
GRILLE
24x12 PERFORATED FACESEE TAG 1ALUMINUM
S7 24x60 10"ØSUPPLY
DIFFUSER
STAINLESS STEEL
R3 YES 1,2,4RETURN
GRILLE
SINGLE DEFLECTION
SIDEWALL MOUNTED
LAY-IN
PLAQUE FACE
LAY-IN
PLAQUE FACE
LAY-IN
E3 EXHAUST
WHITE -
GRILLE
50x22 SINGLE DEFLECTION48x20 1ALUMINUM
DUCT MOUNTED
E2 EXHAUST
WHITE -
GRILLE
24x24 PERFORATED FACESEE TAG 1ALUMINUM
LAY-IN
YES
1. HEPA HOUSING IS MAGNA PACK HEPA (WITHOUT PREFILTER).
2. HEPA FILTER BASIS SIZES:
A. 24"x24"
B. 12"x24"
3. ALL WELDED, 14-GAUGE 304 STAINLESS STEEL CONSTRUCTION.
4. CAPABLE OF WITHSTANDING 8.0" WG POSITIVE OR NEGATIVE PRESSURE.
5. PROVIDE WITH STANDING FLANGES FOR MATING TO HVAC DUCTWORK.
6. DUAL ACCESS DOORS, HINGED.
7. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. COILS SHALL HAVE COPPER TUBES, COPPER FINS, AND STAINLESS STEEL CASINGS.
1.
2.
3.
4.
WHERE DIFFUSER/GRILLE IS INSTALLED IN ROOM WITH SOLID GYP. BOARD CEILING, PROVIDE CABLE
CONTROLLED VOLUME DAMPER WITH ZINC-PLATED STEEL CEILING CAP FOR ADJUSTER ACCESS.
MOUNT ADJUSTMENT CONTROLLER IN CEILING AT LOCATION DESIGNATED ON DRAWINGS. REFER TO
ARCHITECTURAL CEILING PLAN FOR CEILING TYPES.
MOUNT BOTTOM OF GRILLE AT 7 INCHES ABOVE FINISHED FLOOR.
FACTORY STAINLESS STEEL PLENUM, INSULATED.
X
GV
X
FF
X
RH
X
SV
X
VAV
X X-X
XXX
LAMINAR FLOW
SURFACE MOUNTED
STAINLESS STEEL STAINLESS STEEL
STAINLESS STEEL STAINLESS STEEL
STAINLESS STEEL STAINLESS STEEL
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
14" x 28"
14" x 28"
14" x 28"
14" x 42"
14" x 42"
14" x 42"
14" x 42"
14" x 28"
12" x 24"
14" x 28"
14" x 28"
14" x 28"
12" x 24"
14" x 28"
14" x 28"
14" x 28"
14" x 28"
14" x 28"
14" x 28"
10" ROUND
10" ROUND
12" x 24"
12" x 24"
10" ROUND
12" x 24"
12" x 24"
10" ROUND
10" ROUND
12" ROUND
12" ROUND
12" ROUND
12" ROUND
14" x 42"
14" x 42"
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
ENHANCED TRACKING
800 800SV-19 SUPPLYIMM. USE STERILIZATION
900 900SV-20 STORAGEEQUIPMENT STORAGE
VARIABLE
SUPPLY ENHANCED TRACKING
14" ROUND
14" ROUND
900 900RV-20 STORAGEEQUIPMENT STORAGE RETURN ENHANCED TRACKING14" ROUND
X
RV
NOTES:
MARK
STYLE
TYPE
AIR FLOW (CFM)
PERFORMANCE
STATIC PRESSURE (IN W.G.)
FRPM
NOISE LEVEL (SONES)
TYPE OF DRIVE
MOTOR
MOTOR SIZE (HP)
VOLTS-PHASE-HERTZ
VARIABLE SPEED MOTOR CONTROLLER
ACCESSORIES
FACTORY DISCONNECT
GRAVITY BACKDRAFT DAMPER
ALUMINUM BIRDSCREEN
EF-2
CENTRIFUGAL
HIGH PLUME
LAB EXHAUST
EF-3
0.75 0.75
65 dBA
BELT
3/4
460-3-60
1/4
115-1-60
YES
NO
NO
YES
11.2
MANUFACTURER'S ROOF CURB YES
CENTRIFUGAL
DOWNBLAST
NO
YES
YES
YES
YES
EF-4
0.75
1/2
115-1-60
CENTRIFUGAL
DOWNBLAST
NO
YES
YES
YES
YES
NOTES 1
SPARK PROOF CONSTRUCTION YES NO NO
SINGLE POINT POWER CONNECTION YES YES YES
11, 4, 5, 6, 7
EFFECTIVE PLUME HEIGHT (FT) 14.4 -
64 dBA
EF-5
0.5
1.5
460-3-60
CENTRIFUGAL
DOWNBLAST
YES
NO
NO
YES
YES
1, 4, 6
YES
YES
12.1
MOTORIZED BACKDRAFT DAMPER YES NO NO YES
SF-5
0.75
2.0
460-3-60
PROPELLER
SIDEWALL
NO
NO
NO
YES
NO
1,2,3,4
NO
YES
YES
FANS
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. FULL WALL HOUSING WITH FAN GUARD.
3. PROVIDE FILTER RACK FOR 2" THROWAWAY FILTER.
4. DISCONNECT BY EC. REFER TO ELECTRICAL PLANS.
EF
X
DIRECT DIRECT DIRECT DIRECT
55/100
55/100
1-1/4"
1-1/4"
1"
3/4"
1-1/4"
1-1/4"
3/4"
3/4"
1-1/4"
1"
3/4"
3/4"
3/4"
3/4"
5. CORROSION RESISTANT CONSTRUCTION.
6. VFD RATED MOTOR.
7. PROVIDE WITH SIDE EXHAUST CONNECTION AND ELECTRIC ACTUATED BYPASS DAMPER/HOOD WITH INLET SCREEN.
1,3
S6 SUPPLY
DIFFUSER
YESSTAINLESS STEEL STAINLESS STEEL 1,3
S5 24x36 8" ØSUPPLY
DIFFUSER
YESSTAINLESS STEEL STAINLESS STEEL 1,3
LAMINAR FLOW
SURFACE MOUNTED
24x48 10" Ø
LAMINAR FLOW
SURFACE MOUNTED
LAMINAR FLOW
SURFACE MOUNTED
18x18 16x16
DEDUCT ALTERNATE 2
DEDUCT ALTERNATE 1
DEDUCT ALTERNATE 1
DEDUCT ALTERNATE 1
DEDUCT ALTERNATE 2
PHASE 2 2 3 3 3
PHASE
PHASE 3
PHASE
PHASE
PHASE
B 70010"Ø8"Ø 16x1212x1027
OUTSIDE AIR (CFM)
VOLTS - PHASE - HZ
ELECTRICAL - OUTDOOR UNIT
MAX CURRENT AMPS
OVER-CURRENT PROTECTION DEVICE (AMPS)
FAN MOTOR (HORSEPOWER)
MAX CURRENT AMPS
CONDENSATE PUMP
OPERATING WEIGHT
VOLTS - PHASE - HZ
ELECTRICAL - INDOOR UNIT
FULL LOAD AMPS
7 YEAR COMPRESSOR WARRANTY
INDOOR UNIT (LBS)
OUTDOOR UNIT (LBS)
ACCESSORIES
SENSIBLE CAPACITY (MBH)
TOTAL CAPACITY (MBH)
FAN MOTOR OUTPUT (WATTS)
AIRFLOW (CFM)
CONDENSER FAN
CONDENSING UNIT RATING CONDITIONS (°F)
NO. OF FANS
ENTERING AIR WET BULB (°F)
REFRIGERANT
NO. COMPRESSORS / CAPACITY STEPS
LOW AMBIENT CAPABILITY TO (°F)
ENTERING AIR DRY BULB (°F)
DX COOLING
PHASE
WALL MOUNTED
SINGLE ZONE
CONFIGURATION
ELECTRICAL
ROOM 2C214
AC-1 / CU-1
AREA SERVED
MARK (INDOOR/OUTDOOR)
DUCTLESS SPLIT SYSTEMS
12.2
9.0
80.0
67.0
95.0
410A
-30.0
0.074
208-1-60
0.76
1.0
208-1-60
9.0
YES
YES
REMOTE THERMOSTAT YES
LINESET AND CONTROL WIRING YES
NOTES:
1.
2.
3.
4.
5.
6.
PIPE PER MANUFACTURER'S RECOMMENDATIONS.
PROVIDE CLOGGED FILTER SWITCH.
LOW AMBIENT KIT.
RELAY ALARMS TO TRIDIUM BAS.
HOT GAS BYPASS.
INTEGRAL CONDENSATE PUMP.
X
AC
X
CU
WALL MOUNTED
SINGLE ZONE
SWITCHGEAR
ROOM S105
AC-2 / CU-2
30.7
30.7
80.0
67.0
95.0
410A
-30.0
0.103
208-1-60
0.76
1.0
208-1-60
21.0
25.0
YES
YES
YES
YES
FAN
2 3
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
55/100
3RD FLOOR PENTHOUSE
AHU S-2-2
P1A, P1B, P1C
EXISTING CHILLERS 7TH FLOOR
CH-1 AND CH-2
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN THE
SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED
WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE. COPYRIGHT C 2019.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
18067
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:4
:3
P
M
0-H0-5
10701 East Blvd. Cleveland, OH 44106
06/26/2020 LDH DML
541-19-101Renovate Operating RoomsBID ISSUEMECHANICAL SCHEDULES
UNIT AIR FLOW
OUTDOOR AIR SETTING (CFM)
MAXIMUM AIR FLOW (CFM)
EXTERNAL STATIC PRESSURE (IN W.G.)
TOTAL STATIC PRESSURE (IN W.G.)
FAN TYPE
MOTOR SIZE (HORSEPOWER)
VOLTS-PHASE-HERTZ
CAPACITY (MBH)
STEAM PREHEAT COIL (VIFB)
ENTERING AIR TEMPERATURE (°F)
LEAVING AIR TEMPERATURE (°F)
AIR PRESSURE DROP (IN W.G.)
CONDENSATE LOAD (LB/HR)
STEAM PRESSURE (PSIG)
MINIMUM COIL SIZE (SQ. FT.)
NUMBER OF COILS IN BANK
PRIMARY CHILLED WATER COIL
TOTAL CAPACITY (MBH)
SENSIBLE CAPACITY (MBH)
ENTERING AIR DB/WB (°F)
LEAVING AIR DB/WB (°F)
AIR PRESSURE DROP (IN W.G.)
WATER FLOW (GPM)
ENTERING WATER TEMPERATURE (°F)
LEAVING WATER TEMPERATURE (°F)
WATER PRESSURE DROP (FEET)
TOTAL MAXIMUM AIR FLOW (CFM)
FAN PERFORMANCE
FAN SPEED AT 60 HERTZ SPEED (RPM)
CAPACITY (LB/HR)
STEAM HUMIDIFIER
STEAM PRESSURE (PSIG)
ABSORPTION DISTANCE (INCHES)
MANUFACTURER
MANUFACTURER
MAXIMUM FACE VELOCITY (FPM)
NUMBER OF ROWS/FPI
SAF-2
31,500
5.0
460-3-60
11.2
42,000
12,600
SAF-1
31,500
5.0
DWDI
460-3-60
1,088
46.0
70.0
0.20
1,143
56.0
DRI-STEEM
11.2
1,617
1,050
77.0/63.5
50.4/49.9
0.7
13.8
6/10
RAF-1
30,000
2.5
DWDI
460-3-60
3.8
RAF-2
30,000
2.5
DWDI
460-3-60
3.8
DWDI
NUMBER OF COILS IN BANK
SECONDARY CHILLED WATER COIL
TOTAL CAPACITY (MBH)
SENSIBLE CAPACITY (MBH)
ENTERING AIR DB/WB (°F)
LEAVING AIR DB/WB (°F)
AIR PRESSURE DROP (IN W.G.)
WATER FLOW FOR BANK (GPM)
ENTERING WATER TEMPERATURE (°F)
LEAVING WATER TEMPERATURE (°F)
WATER PRESSURE DROP (FEET)
MAXIMUM FACE VELOCITY (FPM)
NUMBER OF ROWS/FINS PER INCH
1,617
1,050
77/63.5
50.4/49.9
1.1
42.0
54.0
26.2
10/10
SERVICE AREA SURGERY SUITE
DRIVE BELT BELT BELTBELT
AIR ENTERPRISES
FACE VELOCITY (FPM)
NUMBER OF ROWS/FPI
1/6
NO. OF COMPRESSORS
ELECTRICAL
CAPACITY (TONS)
LEAVING FLUID TEMP. (DEG. F.)
VOLTS-PHASE-HERTZ
COOLING PERFORMANCE
OUTDOOR AIR TEMP. (DEG. F.)
BASIS OF SPECIFICATION
MANUFACTURER
PROPYLENE GLYCOL CONCENTRATION (%)
REFRIGERANT
MCA/MOP
MARK
EER
TYPE
WATER FLOW (GPM)
MAX. WATER PRESSURE DROP (FEET)
RLA (COMPRESSOR #1)
RLA (COMPRESSOR #2)
BUILDING CONTROLS NETWORK INTERFACE (ANDOVER)
RLA (COMPRESSOR #3)
RLA (COMPRESSOR #4)
IPLV
ENTERING FLUID TEMP. (DEG. F.)
EXISTING AIR COOLED CHILLERS
EXISTING PUMPS
EXISTING AIR HANDLER AHU-S-2-2
85.0
42.0
R-410a
35.0
CH-1 AND CH-2
460-3-60
230/250
TRANE
9.6
SCROLL
35.0
43.0
43.0
YES
54.5
54.5
14.2
54.0
MARK
SERVICE
TYPE
TEMPERATURE (°F)
FLUID - PROPYLENE GLYCOL (%)
PERFORMANCE
FLOW (GPM)
TOTAL HEAD (FEET)
SPEED (RPM)
MOTOR
SIZE (HP)
VOLT-PHASE-HERTZ
MANUFACTURER
P-1A, P-1B, P-1C
CHILLED WATER
20.0
460-3-60
TACO
EFFICIENCY (%) 63.0
VARIABLE FREQUENCY DRIVE YES
BASE MTD,
END SUCTION
EXISTING SURGERY SUITE MECHANICAL EQUIPMENT
THE FOLLOWING SHALL BE COMPLETED FOR THE EXISTING AIR HANDLING UNIT S-2-2:
THOROUGHLY CLEAN INTERIOR OF AHU-S-2-2.
REPLACE EXISTING 40-HP RETURN AIR FAN MOTORS (QUANTITY = 2). NEW MOTORS SHALL BE SAME
SIZE, PREMIUM EFFICIENCY, INVERTER READY, INSULATION CLASS.
REPLACE EXISTING 100-HP SUPPLY AIR FAN MOTORS (QUANTITY = 2). NEW MOTORS SHALL BE SAME
SIZE, PREMIUM EFFICIENCY, INVERTER READY, INSULATION CLASS.
REPLACE AHU-S-2-2 FAN BEARINGS ON ALL SUPPLY FANS AND RETURN FANS.
REPLACE AHU-S-2-2 VARIABLE FREQUENCY DRIVES (2 SUPPLY / 2 RETURN). VARIABLE FREQUENCY
DRIVES SHALL BE MANUFACTURED BY ABB (WITH SWINGING DC CHOKE).
REPLACE ALL LIGHT BULBS IN EXISTING AHU-S-2-2.
REPLACE ALL FILTERS UPON START-UP.
REFER TO TEMPERATURE CONTROLS PLANS FOR ADDITIONAL WORK.
REPLACE STEAM COIL, OS&Y VALVE WITH NEW VALVE, SAME SIZE.
REPLACE ALL FAN BELTS.
LUBRICATE ALL POINTS.
LEAK/PRESSURE TEST OF UNIT. COMPLETE SEALING/CAULKING AS REQUIRED IN ORDER TO MEET
MANUFACTURER'S STANDARDS. SEAL AROUND ALL PENETRATIONS, SECTION JOINTS, ETC.
PROVIDE FULL START-UP SERVICES.
COMPLETE TEST AND BALANCE.
THE FOLLOWING SHALL BE COMPLETED FOR THE EXISTING SURGERY CHILLED WATER SYSTEM:
FLUSH AND FILL SECONDARY CHILLED WATER SYSTEM. SYSTEM SHALL BE FILLED WITH 35%
PROPYLENE GLYCOL SOLUTION. FILL TANK SHALL BE RE-FILLED.
REPLACE EXISTING 20-HP SECONDARY CHILLED WATER PUMP MOTORS (QUANTITY = 3). NEW MOTORS
SHALL BE SAME SIZE, PREMIUM EFFICIENCY, INVERTER READY, INSULATION CLASS.
REPLACE EXISTING SECONDARY CHILLED WATER PUMP VARIABLE FREQUENCY DRIVES (QUANTITY =
3). NEW VARIABLE FREQUENCY DRIVES SHALL BE ABB (WITH SWINGING DC CHOKE).
REPLACE CHILLER USER INTERFACE CONTROL PANELS (TRANE, QUANTITY = 2) WITH NEW.
LUBRICATE ALL POINTS.
REPAIR LEAK ON CHILLER CH-2, CIRCUIT #2. RE-CHARGE CIRCUIT.
PROVIDE CHANGEABLE CORE LIQUID LINE FILTER DRIER ON EACH CHILLER.
UPON COMPLETION OF THE ABOVE TASKS, PERFORM FULL TEST AND BALANCE OF EQUIPMENT.
SAMPLE REFRIGERANT. REFERENCE SCHEDULES ON DRAWING 0-H0-5 FOR PERFORMANCE. SUBMIT
TAB REPORT TO VA AND A/E FOR REVIEW.
FULL START-UP SERVICES.
COMPLETE TEST AND BALANCES.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
NOT TO SCALE
MECHANICAL KEY PLAN 1N
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS FOR PURPOSES OTHER THAN THE
SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED
WRITTEN CONSENT OF PERSPECTUS
ARCHITECTURE. COPYRIGHT C 2019.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
18067
Z M y D o c u m e n ts
\1
F
F H
C F
R
J C a rt e r5
.r v t
/2
/2
:4
:4
P
M
0-H0-6
10701 East Blvd. Cleveland, OH 44106
06/26/2020 LDH DML
541-19-101Renovate Operating RoomsBID ISSUETEMPERATURE CONTROLS
EA
I - EA FAN STATUS
EA
M
CT
I - FAN STATUS
O - FAN START/STOP
EA
NC
I - EXHAUST AIR DAMPER STATUS
O - EXHAUST AIR DAMPER
M
CT
I - FAN STATUS
OA
NC
I - INTAKE AIR DAMPER STATUS
O - INTAKE AIR DAMPER
M
CT
I - FAN STATUS
O - FAN START/STOP
LH
I - FILTER STATUS
T
THERMOSTAT
FAN OPERATION:
A. SUPPLY FAN SF-5 AND EXHAUST FAN EF-5 SHALL BE INTERLOCKED.
B. UPON A RISE IN SPACE TEMPERATURE ABOVE 80°F (ADJ), THE FANS SHALL
ENERGIZE AND ASSOCIATED MOTORIZED DAMPERS SHALL OPEN.
C. THE FANS SHALL STOP AND THE DAMPERS SHALL CLOSE UPON REACHING A SPACE
TEMPERATURE OF 65°F (ADJ).
D. BELOW A ROOM TEMPERATURE OF 58°F, EXISTING ROOM UNIT HEATER SHALL
OPERATE TO MAINTAIN TEMPERATURE SETPOINT.
ALARMS:
A. FAN FAILURE
B. FAN IN HAND
C. ROOM TEMPERATURE
STATUS:
A. FAN STATUS
B. INTAKE FILTER STATUS
FAN OPERATION:
A. THE FAN SHALL OPERATE CONTINUOUSLY.
B. THE FAN SHALL OPERATE TO MAINTAIN SCHEDULED AIR FLOW.
ALARMS:
A. VFD FAULT
B. FAN FAILURE
C. FAN IN HAND
STATUS:
A. FAN STATUS
FAN OPERATION:
A. THE FAN SHALL OPERATE CONTINUOUSLY.
B. VFD SHALL BE LOCKED-IN TO A CONSTANT, BALANCED AIR
FLOW.
C. THE MOTORIZED DAMPER SHALL OPEN ANYTIME THE FAN RUNS
AND SHALL CLOSE, ANYTIME THE FAN STOPS.
ALARMS:
A. VFD FAULT
B. FAN FAILURE
C. FAN IN HAND
STATUS:
A. FAN STATUS
IN DIAGRAMS, 'I' INDICATES AN INPUT, 'O' INDICATES AN OUTPUT.
DAMPER OPERATORS TO BE PROVIDED BY TEMPERATURE CONTROLS CONTRACTOR.
TEMPERATURE CONTROL TEST SHALL INCLUDE, BUT NOT BE LIMITED TO:
· DAMPER OPERATION
· VALVE ACTUATION RESPONSE AND VALIDATION OF CORRECT OPERATION
· VERIFIED ENTIRE CONTROL SEQUENCE OPERATES PER DESIGN
· ACCOUNT FOR ALL CONTROL POINTS LISTED
ALL SYSTEMS SHALL BE COMMISSIONED. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
REFERENCE SPECIFICATION SECTIONS 230923 AND 230940 FOR ADDITIONAL INFORMATION.
CONTRACTOR SHALL CONDUCT TEMPERATURE CONTROLS CHARETTE MEETINGS AT BEGINNING
OF CONSTRUCTION. MEETINGS SHALL INCLUDE TC. A/E, AND VA AND SHALL BE SCHEDULED FOR
TWO 4-HOUR SEQUENCES AND DISCUSS ANY NECESSARY ADJUSTMENTS AND CHANGES PRIOR
TO ANY TC WORK.
TEMPERATURE CONTROLS GENERAL NOTES
A.
B.
C.
D.
E.
F.
SEQUENCE OF OPERATION FOR EXHAUST FAN EF-2
SEQUENCE OF OPERATION FOR EXHAUST FANS EF-3 AND EF-4
SEQUENCE OF OPERATION FOR EXHAUST FAN EF-5 AND SUPPLY FAN SF-5
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
T
E
H O
T W
A T
E R
R E
H E
A T
XFORMER
AIR FLOW
SENSOR
UNITARY
CONTROLLER
NEW DDC
THERMOSTAT
SUPPLY AIR DUCT
120 VAC
BY E.C.
TYPICAL VAV TERMINAL
WITH REHEAT
120V/24 AC
TRANSFORMER
BY T.C.C.
LOW VOLTAGE WIRING
BY T.C.C.
COMMUNICATION
BUS TO OTHER
CONTROLLERS
OPERATION:
A. SPACE THERMOSTAT SHALL MODULATE DAMPER
TO MAINTAIN SET POINT.
B. ON CALL FOR HEAT, RETURN DAMPER TO MINIMUM
POSITION AND MODULATE HOT WATER VALVE TO
MAINTAIN SETPOINT.
NOT TO SCALE
SEQUENCE OF OPERATION FOR VAV BOXES
VFD
O - FAN VFD SPEED
I- FAN VFD FAULT
NC
I - MOTORIZED DAMPER STATUS
O - MOTORIZED DAMPER
CONTRACTOR SHALL REMOVE EXISTING ANDOVER CONTROLLERS AND REPLACE WITH JCI FX (OR
EQUAL).
REPLACE ALL EXISTING SENSORS IN SECONDARY CHILLED WATER SYSTEM WITH NEW SENSORS IN
COMPLIANCE WITH SPECIFICATION 230923.
REPLACE ALL EXISTING CONTROL VALVES WITH NEW DEVICES IN COMPLIANCE WITH SPECIFICATION 230923.
EXISTING MOTORS AND VARIABLE FREQUENCY DRIVES ON CHILLED WATER PUMPS SHALL BE REPLACED
UNDER THIS PROJECT. PROVIDE ALL NEW POINTS TO BAS.
PROVIDE ALL NECESSARY CONTROLLERS, DEVICES, WIRING, AND PROGRAMMING/LOGIC. PLACE
SECONDARY CHILLED WATER SYSTEM ON TRIDIUM CONTROL SYSTEM.
SECONDARY CHILLED WATER SYSTEM TEMPERATURE CONTROLS NOTES:
A.
B.
C.
D.
E.
SEQUENCE OF OPERATION FOR SECONDARY
CHILLED WATER SYSTEM
T
H
L
T
I - SCHWR TEMP
I - DIFFERENTIAL PRESSURE
I - CHILLED WATER FLOW
VFD
I - P-1A VFD FAULT
O - P-1A VFD SPEED
M
CT
I - P-1A STATUS
O - P-1A START/STOP
I - SCHWS TEMP
O - CHILLER ENABLE
I - CHILLER STATUS
CH-1
O - CHILLER ENABLE
I - CHILLER STATUS
CH-2
S
C H
W R
S C
H W
S
S C
H W
R
S C
H W
S
VFD
I - P-1B VFD FAULT
O - P-1B VFD SPEED
M
CT
I - P-1B STATUS
O - P-1B START/STOP
P-1A
P-1B
VFD
I - P-1C VFD FAULT
O - P-1C VFD SPEED
M
CT
I - P-1C STATUS
O - P-1C START/STOP
P-1C
O - CH-1 ISOLATION VALVE O - CH-2 ISOLATION VALVE
I - CHILLED WATER FLOW
SCHWR
(FROM AHU-S-2-2)
SCHWS
(TO AHU-S-2-2)
1. SECONDARY CHILLED WATER SYSTEM CONSISTS OF (2) AIR COOLED CHILLERS OPERATING
IN LEAD-LAG AND (3) VARIABLE FLOW PRIMARY PUMPS OPERATING IN LEAD-LAG.
2. THE CHILLER SYSTEM SHALL BE ACTIVATED BY THE DDC CONTROL SYSTEM WHEN THE
SYSTEM CALLS FOR COOLING. THE CHILLER CONTROLLERS SHALL SEQUENCE ON TO
MAINTAIN A SUPPLY WATER TEMPERATURE OF 42 DEG F (ADJ). WHEN THE SYSTEM
CALLS FOR COOLING, THE LEAD CHILLER CONTROL ISOLATION VALVE SHALL OPEN AND
THE CHILLER SHALL MODULATE TO MAINTAIN THE SYSTEM SUPPLY TEMPERATURE. AT THIS
TIME, THE LAG CHILLER ISOLATION VALVE SHALL BE CLOSED. IF THE LEAD CHILLER IS
NOT MAINTAINING SETPOINT, THE LAG CHILLER ISOLATION VALVE SHALL OPEN AND THE
LAG CHILLER SHALL OPERATE. TO AVOID CHILLER SHOCK, THE LEAD CHILLER SHALL
REDUCE CAPACITY TO 60% (ADJ) TWO (2) MINUTES PRIOR TO THE LAG CHILLER
ISOLATION VALVE OPENING. THE CHILLER CONTROLLER SHALL ALTERNATE THE LEAD
CHILLER MONTHLY (OR AS SELECTED BY USER).
3. THE CHILLED WATER LEAD PUMP SHALL BE SELECTED AT THE CONTROL CENTER. THE
LEAD PUMP SHALL OPERATE FIRST. ON FAILURE OF THE LEAD PUMP, A LAG PUMP
SHALL RUN AND THE LEAD PUMP SHALL TURN OFF. ON DECREASING CHILLED WATER
DIFFERENTIAL PRESSURE, THE LAG PUMP SHALL STAGE ON AND RUN IN UNISON WITH
THE LEAD PUMP TO MAINTAIN WATER DIFFERENTIAL PRESSURE SETPOINT (12 PSI ADJ).
THE DESIGNATED LEAD PUMP SHALL ROTATE MONTHLY (OR AS SELECTED BY USER).
4. THE CONTROLLER SHALL MEASURE CHILLED WATER DIFFERENTIAL PRESSURE AND
MODULATE THE PUMP VFDs IN SEQUENCE TO MAINTAIN SETPOINT.
5. ALARMS SHALL BE PROVIDED AS FOLLOWS:
5.1. P-1A
5.1.1. FAILURE: COMMANDED ON, BUT STATUS IS OFF.
5.1.2. RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
5.1.3. RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS USER DEFINED LIMIT.
5.1.4. VFD FAULT.
5.2. P-1B
5.2.1. FAILURE: COMMANDED ON, BUT STATUS IS OFF.
5.2.2. RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
5.2.3. RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS USER DEFINED LIMIT.
5.2.4. VFD FAULT.
5.3. P-1C
5.3.1. FAILURE: COMMANDED ON, BUT STATUS IS OFF.
5.3.2. RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
5.3.3. RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS USER DEFINED LIMIT.
5.3.4. VFD FAULT.
5.2. DIFFERENTIAL PRESSURE
5.2.1. HIGH HW DIFFERENTIAL PRESSURE: IF 25% (ADJ) GREATER THAN SETPOINT.
5.2.2. LOW HW DIFFERENTIAL PRESSURE: IF 25% (ADJ) BELOW SETPOINT.
5.3. CHILLED WATER TEMPERATURE
5.3.1. HIGH CHILLED WATER SUPPLY TEMPERATURE: IF GREATER THAN 40 DEG F (ADJ)
5.3.2. LOW CHILLED WATER SUPPLY TEMPERATURE: IF LESS THAN 36 DEG F (ADJ)
SECONDARY CHILLED WATER SYSTEM CONTROL DIAGRAM
DEDUCT ALTERNATE 2 NOTE:
AS PART OF DEDUCT ALTERNATE 2, THIS WORK SHALL BE DELETED.
O - EXHAUST FAN ENABLE/DISABLE
O - EXHAUST FAN VFD SPEED
I - EXHAUST AIR VFD FAULT
VFD
O - FAN START/STOP
M
CT
NOT TO SCALE
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
1DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF