S02 Attachment Twenty Two 22 VHA Program Guide.pdf

PDF 218 KB Posted

Attached to
CBOC Services | West Palm Beach VAMC
Solicitation number
36C24821R0092
Issued by

About this file

This document provides guidance on noise transmission control requirements for federal healthcare facility construction projects. It specifies minimum Sound Transmission Class ratings that must be achieved for partitions, ceilings, doors, and ductwork enclosing spaces like mechanical rooms, auditoriums, examination rooms, and group therapy rooms. These noise control standards are required to suppress noise generation and provide acoustic isolation or speech privacy. Construction methods like double layers of drywall and sound attenuation blankets are recommended. The solicitation seeks consultation services for a Community Based Outpatient Clinic expansion project located at the West Palm Beach Veterans Affairs Medical Center.

View the file

Other files

File Type Posted
36C24821R0092 A0002.pdf PDF
36C24821R0092 A0001.pdf PDF
S02 Attachment Three 3 PAST PERFORMANCE QUESTIONNAIRE.pdf PDF
S02 Attachment Twenty Seven 27 VHA Directive 1660.06 Tricare Network Agreements.pdf PDF
S02 Attachment Six 6 Davis Bacon Act Wage Determination Ft Pierce.pdf PDF
S02 Attachment Thirty 30 VHA HB 1101 11 Coordinated Care For Traveling Veterans.pdf PDF
S02 Attachment Fifteen 15 Medical Care Memorandum Number 548 99 246 Medication Reconcilliation.pdf PDF
S02 Attachment Four 4 IMMIGRAT CERT.pdf PDF
S02 Attachment Eleven 11 VHA Notice 2020-02 -Storage of Vaccines and Medications.pdf PDF
S02 Attachment Twenty Six 26 Environment of Care Assessment and Compliance Rounding Process Guide.pdf PDF
S02 Attachment Seven 7 Quality Assurance Surveillance Plan.pdf PDF
S02 Attachment One 1 ORG CONFLICT CERT.pdf PDF
S02 Attachment Thirty One 31 VHA HB 1101 11 VISN 8 Guidelines on Emergency Generator Power Systems.pdf PDF
S02 Attachment Twenty Four 24 Path and Lab Medicine Service Reference Manual.pdf PDF
S02 Attachment Twenty Three 23 CBOC Laboratory Supplies and Panels.pdf PDF
S02 Attachment Five 5 Service Contract Act Wage Determination Vero Beach.pdf PDF
S02 Attachment Five 5 Service Contract Act Wage Determination Ft Pierce Stuart.pdf PDF
S02 Attachment Eight 8 Patients Rights and Responsibilitiees.pdf PDF
S02 RFP 36C24821R0092.pdf PDF
S02 Attachment Nineteen 19 Updated Pre treatment and Transportation of Soiled Critical and Semi Critical RME.pdf PDF
S02 Attachment Ten 10 Specimen Collection.pdf PDF
S02 Attachment Twenty 20 Pre treatment and Transportation of Soiled Critical and Semi Critical RME_.pdf PDF
S02 Attachment Thirteen 13 VHA Directive 1137.pdf PDF
S02 Attachment Twenty Nine 29 VA Directive 2011 012.pdf PDF
S02 Attachment Five 5 Service Contract Act Wage Determination Okeechobee.pdf PDF
S02 Attachment Twenty Five 25 Service Specific Environment of Care Rounds.pdf PDF
S02 Attachment Twelve 12 Design Framework for Whole Health Implementation.pdf PDF
S02 Attachment Sixteen 16 Medical Care Memorandum Number 548 113 97 Pathology and Laboratory Medicine Service.pdf PDF
S02 Attachment Six 6 Davis Bacon Act Wage Determination Vero Beach.pdf PDF
S02 Attachment Fourteen 14 Medical Care Memorandum Number 548 110 305 Womens Veterans Health Care.pdf PDF
S02 Attachment Nine 9 VHA Directive 1033 Anticoagulation Therapy Management.pdf PDF
S02 Attachment Twenty One 21 VHA Directive 1608 Comperhensive and Compliance Rounding Process Guide.pdf PDF
S02 Attachment Seventeen 17 Medical Care Memorandum Number 548 116 173 Identification and Management of Veterans.pdf PDF
S02 Attachment Thirty Two 32 VHA Directive 1608 Comprehensive Enviroment of Care Program.pdf PDF
S02 Attachment Five 5 Service Contract Act Wage Determination Boca Raton.pdf PDF
S02 Attachment Twenty Eight 28 Medical Care Memorandum Number 548 136 376 Patient Care Data Capture.pdf PDF
S02 Attachment Six 6 Davis Bacon Act Wage Determination Okeechobee.pdf PDF
S02 Attachment Six 6 Davis Bacon Act Wage Determination Boca Raton.pdf PDF
S02 Attachment Eighteen 18 Medical Care Memorandum Number 548 113 074 Point of Care Ancillary Testing Policy.pdf PDF
S02 Attachment Six 6 Davis Bacon Act Wage Determination Stuart.pdf PDF
S02 Attachment Two 2 CONTRACTOR RULES OF BEHAVIOR.pdf PDF
Show all 41

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VHA PROGRAM GUIDE PG-18-3 April 2004

TOPIC 11. NOISE TRANSMISSION CONTROL

1. GENERAL: Where rooms do not contribute to or are not affected by sound transmission from an adjacent space, conventional construction is satisfactory.

2. PARTITION-CEILING-DOOR-DUCT SYSTEM ACOUSTIC DESIGN

a. Acoustical Isolation. Design the sound resistant enclosures of the following spaces to suppress generated noise and provide a satisfactory degree of acoustical isolation for adjacent occupied spaces. Achieve a minimum Sound Transmission Class (STC) rating of 45.

NOTE: When the VA Hospital Building System (VAHBS) is used, achieve the required rating using construction such as a double layer of 16 mm (5/8 in.) gypsum board (GB) on both sides of 100 mm (4 in.) nominal metal studs and 64 mm (2 1/2 in.) sound attenuation blankets between the studs. These should extend above conventional lay-in ceilings to the underside of walk-on deck/platforms.

(1) A/C and other mechanical equipment rooms.

(2) Manual arts therapy shops.

(3) Auditoriums.

(4) Multipurpose rooms.

(5) Mental Health and Behavioral Sciences Service i.e. group therapy rooms.

(6) Emergency generator rooms.

(7) Kitchen & Dishwashing spaces.

NOTE: Alternatively, provide a gypsum board ceiling or gypsum board lay-in panels both with a 65 mm (2 1/2 in.) sound attenuation blanket for non-VAHBS type of construction where ducts, pipes, etc., make it impractical to extend sound partitions to slabs or deck above. Where gypsum board ceilings with attenuation blankets are used, the double GB partitions and sound attenuation blanket should extend 100 mm (4 in.) above the ceiling. Studs should continue to the floor above. Give special attention to details shown on the construction documents to prevent possible flanking paths for noise transmission.

b. Speech Privacy. Design the sound resistant enclosures of the following spaces to assure speech privacy and achieve an STC rating of 40 (45 for space marked with an asterisk).

(1) Conference rooms.

VHA PROGRAM GUIDE PG-18-3 April 2004

(2) Consultation offices.

(3) Examination and Treatment Rooms.

(4) Individual Offices in Mental Health and Behavioral Sciences Service.

(5) Audiology and Speech Pathology Areas.

(6) Medical Media Production Services* (Recording Areas).

NOTE: Partition and ceiling construction should be similar to Paragraph 1.a., except that for spaces requiring an STC value of 40, use only a single layer of gypsum board on both sides.

c. Sound Dampening. Provide sound damping in libraries, chapels, quiet rooms, telephone operator's room, and similar areas by finish materials shown for these areas in Program Guide PG-18-14, "Room Finishes, Door, & Hardware Schedule".

Attachment Twenty-Two (22) 36C24821R0092

NOTE: Where an area generating unusual noise or vibration is located adjacent to occupied spaces, the A/E should obtain the services of a professional acoustical consultant to design the sound suppression measures required to produce a comfortable working environment in the adjacent spaces.

d. Door Types. Use door types 19 and 20 with mechanical seal at entrances to spaces where noise suppression or speech privacy is a requirement. See VA Standard Detail Nos. 08100- 1.DWG and 08100-2.DWG.

NOTE: Duct system sound attenuation and room noise criteria are shown in the heating, ventilating, and air-conditioning (HVAC) design manual.

3. MECHANICAL AND ELECTRICAL ITEMS: Properly locate, detail, and caulk or insulate penetrations of the sound resistant enclosure by electrical boxes, light fixtures, air conditioning or ventilating ducts and grills, and other mechanical and electrical components to suppress generated noise or provide speech privacy for the spaces listed in paragraph 2.a. and 2.b.

Evaluate equipment and mechanical rooms for noise problems and provide recommendations during the design phase as to additional sound attenuation required. In the analysis, list the possible flanking paths for noise transmission and the methods recommended to prevent this leakage through the enclosure.

4. EXTERIOR ENCLOSURES: In the design of exterior building walls and fenestrations at sites near airports, freeways, or heavy city traffic, give consideration for the control of noise transmission from external sources.