S02 Attachment AHU Commissioning Scope 589A5-15-115B ED Phase II.pdf

PDF 1 MB Posted

Attached to
589A5-15-115B, Upgrade ED Topeka Phase II (VA-22-00021800)
Solicitation number
36C25522R0042
Issued by

About this file

This document contains commissioning plans and diagrams for mechanical systems related to a federal construction project to upgrade an emergency department at the Topeka VA Medical Center. The project involves commissioning of existing air handling units that serve the GI lab and emergency department areas to supply air as part of Phase 1 and Phase 2 of the upgrade. Test and balancing of the existing units is required along with commissioning to verify proper system operation per the sequences of operation. Adjustments to air flows and minimum outdoor air levels are specified. The commissioning process is defined in the general commissioning requirements section and will be managed by an appointed commissioning agent, with cooperation from the contractor and VA required for documentation, testing and training of operations and maintenance personnel.

The related federal contract opportunity notice is for solicitation number 36C25522R0042 to upgrade the emergency department at the Topeka VA Medical Center for project number 589A5-15-115B. The opportunity is listed as a pre-solicitation and the Department of Veterans Affairs is identified as the contracting agency.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSTANT VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM

NO SCALE

NO SCALE1

POINT SCALE LIST FOR CONSTANT AIR

HANDLING UNIT WITH MINIMUM OUTSIDE AIR

ALARM

PROCESSING

DU

TY

C

YC

LE

FU

NC

TI

O

N

SC

H

ED

UL

E

ST

AR

T/

ST

O

P

HUMIDITY HIGH LIMIT

SUPPLY FAN VSMC ALARM

STATIC PRESSURE HIGH LIMIT

Supply Air Flow (cfm)

ST

AT

U S

SYSTEM

AL

AR

M

PR

IO

RI

TY

/A D

D-

AL

TE

RN

AT

E

NO

EL

EC

TR

IC

D

EV

IC

E

SP

EE

D C

O M

M

AN

D

PO

IN

T

ID

Discharge Static Pressure

Discharge Air Humidity

Discharge Air Temperature

Pre-Heat Temperature

Mixed Air Temperature

Cooiling Coil Temperature

SYSTEM COMPONENT:

Return Air Flow (cfm)

Return air Temperature

-- O

PE

N/ C

LO

SE

ST

AR

T/

ST

O P

-- VA

LV

E

PO

SI

TI

O N

D

AM

PE

R

PO

SI

TI

O

N

JOB: 0555.09

VAV AIR HANDLER

VA SAMPLE POINO SCALE LIST

SYSTEM:

BUILDING:

LEGEND

POINT

BINARY

TE

M

PE

R

AT

UR

E (T

I)

Lo ca l A la rm P an el

M as te r A la rm

P an el

Ar ea

A la rm P an el

H

IG

H S

TA

TI

C P

R

ES

SU

R

E

HI

G

H H

U M

ID

IT

Y

PR

ES

SU

RE

--LO

W

T

EM

PE

R

AT

UR

E

PE

RC

EN

T

PR

ES

SU

RE

PO

SI

TI

O

N

FL

O W

HI

G

H L

IM

IT

LO

W

L

IM

IT

SYSTEM INPUTS

ANA- BINARY ANALOG

SP

AC

E

TE

M P.

C O

NT

RO

L

--ST

AT

IC

P

R

ES

SU

RE

R

ES

ET

--DE

M

AN

D

LI

M

IT

IN

G

TE

M

PE

RA

TU

RE

R

ES

ET

TE

M

PE

RA

TU

RE

O

VE

RR

ID

E

EN

TH

AL

PY

E

CO

NO

M

IZ

ER

TE

M

PE

RA

TU

RE

E C

O N

O M

IZ

ER

FA

IL

UR

E

M O

DE

PR

ES

SU

R

E/

VO

LU

M

E

CO

NT

RO

L

REMARKS

FU

LL

C O

M M

UN

IC

AT

IO

N

SYSTEM SOFTWARE/CONTROL

APPLICATION/FUNCTION

PAGE:

Return Air Humidity

SUPPLY FAN STATUS

MIXED AIR LOW LIMIT

RETURN AIR DAMPER D-2

STEAM HUMIDIFIER VALVE V-4

COILING VALVE V-1

PRE-HEAT VALVE V-2

SUPPLY FAN VSMC

OUTSIDE AIR DAMPER D-1

ST

AT

IC

P

R

ES

SU

R

E

C

AR

BO

N

M O

NO

XI

DE

H

UM

ID

IT

Y

VA

CU

UM

STEAM ISOLATION VALVE V-3

SUPPLY FAN START/STOP

AI-1

AI-2

AI-3

AI-4

AI-5

AI-6

AI-7

AI-8

AI-9

AI-10

TR

EN

D

IN

G

OUTSIDE AIR TEMPERATURE AI-11

BI-3

BI-4

BI-5

BI-6

BI-7

AO-2

AO-3

AO-4

AO-8

AO-9

AO-10

BO-2

BO-3

FULL COMMUNICATION

AB

BR

EV

IA

TI

O

N

RAT

RAH

RAF

MAT

PHT

CCT

DAT

DASP

DAH

SAF

OAT

SF-STS

TSL-1

SPS-2

HHL

SF-ALA

SF-SPD

OAD

RAD

PHT-V1

CLG-V1

HUM-V4

SF-SST

HUM-ISO-V3

OUTPUTS

LOG

D-3

D-2 P

R E

-F

IL

TE

R

D-1

C O

IL

P

R E

H E

A T

C O

IL

C

O O

LI

N

G

LOCATE SENSOR

OUTSIDE UNDER

SHIELD

MPS

V-2

V-1

NO

CHR

CHS

SUPPLY FAN

A

FM

D

RETURN AIR

A

FM

D

SUPPLY AIR TO

TERMINAL UNIT

TT

TT

TT TT

FT

A

FT

E R

FI

LT

E

R

TT

HS

IT

VSMC

FT

3 6

SD

ONLY WHERE

REQUIRED

PSH

SMOKE

DETECTOR

(EX)VARIABLE SPEED

MOTOR CONTROLLER, TYP.

ZC

ZC

PDS PDS

TT

SST

SD

SPSTSL

TSL-1

V-3

LPS

(EX)STEAM HUMIDIFIER

MS

MC

ECC

MT

PRESSURE SWITCH HIGH TO DISABLE

FAN WHEN HIGH PRESSURE LIMIT

SETPOINT IS REACHED

NOTES:

EXISTING AHU (EX)1-AHU-1 TO REMAIN A CONSTANT VOLUME AHU AND RA TO BE

ADDED AND CONTROL SYSTEM TO BE COMMISSIONED.

CONTROLS EQUIPMENT SHOWN ON NEW RA AND MIXED AIR TEMPERATURE ARE NEW.

1. GENERAL

a. UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1, SHALL BE

FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, SD-1 AND D-2 SHALL BE FULLY OPEN.

2. TEMPERATURE CONTROL

a. SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT VIA DIGITAL CONTROL PANEL BY MODULATING V-1 OR V-2 IN SEQUENCE.

3. AIR FLOW CONTROL

a. THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MAINTAINING THE SUPPLY FAN CONTANT SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" [25mm] OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1. RESET STATIC PRESSURE BASED ON ACTUAL BUILDING LOAD BY POLLING ALL ATU.

b. THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS, SHALL RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN THE SUPPLY AIR AND THE RETURN AIR

EQUAL TO MINIMUM OUTSIDE AIR.

c. USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" [75mm] OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 DOES EXCEED 3" [75mm] THE SUPPLY AIR FAN SHALL STOP. SPS-2 SHALL BE HARDWIRED TO THE SUPPLY FAN VSMC AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. SPS-2 WILL REQUIRE MANUAL RESET AT THE DEVICE.

4. HUMIDITY CONTROL

a. WHEN THE DIGITAL CONTROL PANEL IS NOT CALLING FOR HUMIDITY, SENSED BY RETURN AIR HUMIDITY H-1, 2-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN CLOSED. DISABLE (EX)HUMIDIFIER WHEN THE DIGITAL CONTROL PANEL IS

CALLING FOR HUMIDITY, ENABLE (EX)HUMIDIFIER AND V-3 SHALL REMAIN OPEN.

b. RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT OF 35% RH (ADJ) VIA DIGITAL CONTROL PANEL BY MODULATING HUMIDIFIER TO MAINTAIN THE DESIRED HUMIDITY. THE DCP SHALL OVERRIDE THIS CONTROL TO MAINTAIN

HUMIDITY OF 80% AS SENSED BY H-2. DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. (EX)HUMIDIFIER SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE

TEMPERATURE APPROACHES STEAM TEMPERATURE.

5. FREEZE PROTECTION

a. IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY THE TSL THE SUPPLY AND RETURN FANS

SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL SHALL BE HARDWIRED TO THE SUPPLY FAN UFD AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. TSL WILL

REQUIRE MANUAL RESET AT THE DEVICE.

6. AUTOMATIC SHUTDOWN/RESTART

a. WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY FANS SHALL SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. ALL SMOKE DAMPERS IN THE SUPPLY SHALL CLOSE.

b. EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. SUPPLY AND RETURN FANS SHALL RESTART AND SMOKE DAMPER SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.

7. EMERGENCY CONSTANT SPEED OPERATION

a. UPON FAILURE OF THE VSMC, THE SUPPLY FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL CONTROL PANEL OR THE BAS THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.

SEQUENCE OF OPERATION FOR EXISTING CONSTANT VOLUME AHU WITH MINIMUM OUTSIDE AIR

SA = 4105 CFM

RANEGATIVE = 1670 CFM OANEGATIVE = 2435 CFM

RAPOSITIVE = 2080 CFM OAPOSITIVE = 2025 CFM

5TH FLOOR PENTHOUSE - GI LAB AHU

NO SCALE3

N

A

A

B

C o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

F

E

D

C

B

A

97 8654321

ARCHITECTS/ENGINEERS: VA EASTERN KANSAS

HEALTH CARE SYSTEM

Dwight D. Eisenhower VA Medical Center Leavenworth

Colmery-O'Neil VA Medical Center Topeka

Drawing Title:

Scale:

Approved:

Building Number:

Location:

Project Title:

Checked By: Drawing No.

Project No.

Drawn By:

Date:

D e p a rt m e n t o f

V e te ra n s A ff a ir s

Dwg. Of

Building Key Plan: A/E Seal:

BLDG. 1

BIM 360://15G69-000 - VA Topeka - ED Renovation & Addn MEPT/15G69-000-MASTER MECH-R19.rvt

12" = 1'-0"

MC800

MECHANICAL

COMMISSIONING PLANS -

GI LAB AHU #589A5-15-115B

UPGRADE

EMERGENCY

DEPARTMENT

TOPEKA, KS

TJS KWP

05/07/2021

SA = 4105 CFM

RANEGATIVE = 1670 CFM OANEGATIVE = 2435 CFM

RAPOSITIVE = 2080 CFM OAPOSITIVE = 2035 CFM

TEST AND BALANCING AND COMMISSIONING OF EXISTING GI LAB. AHU-1:

1. THE CONTRACTOR SHALL PROVIDE TEST AND BALANCING SERVICES FOR THE EXISTING GI LAB AHU-1.

2. COMMISSION SERVICES SHALL ALSO INCLUDE COMMISSIONING OF EXISTING GI LAB AHU-1. THE COMMISSIONING PROCESS, WHICH THE CONTRACTOR IS

RESPONSIBLE TO EXECUTE, IS DEFINED IN SECTION 01 91 00 GENERAL COMMISSIONING REQUIREMENTS. A COMMISSIONING AGENT (CXA) APPOINTED BY THE VA

WILL MANAGE THE COMMISSIONING PROCESS.

3. COMMISSIONING OF A SYSTEM OR SYSTEMS SPECIFIED IN DIVISION 23 IS PART OF THE CONSTRUCTION PROCESS. DOCUMENTATION AND TESTING OF THESE SYSTEMS, AS WELL AS TRAINING OF THE VA’S OPERATION AND MAINTENANCE PERSONNEL IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 01 91 00 AND OF DIVISION 23, IS REQUIRED IN COOPERATION WITH THE VA AND THE COMMISSIONING AGENT.

NOTE:

EXISTING SCHEDULE IS FROM ORIGINAL AHU INSTALLATION AND IS BASED ON THE BEST

INFORMATION AVAILABLE.

(PART OF PHASE 2)

NEW SHEET

No. Description Date

ADDENDUM 1 7/6/20211

07/07/2021

(E)1-AHU19

(E )3

2x

(E)32x18

(E)1-AHU1

(E )4

4x

(E)32x18

(E )4

4x

(E)44x24

(E )4

4x 18 (E

)4 4x

(E)30x18

(E)1-AFMD1

(E)1-AFMD2(E)1-AFMD3

(E) RETURN FAN

(E) FILTER BANK

(E)26"ø UP IN CHASE

(E )3

0x

(E )2

2x

(E)30x18

SA = 5130 CFM

RA = 3870 CFM

OA = 1350 CFM

EXISTING CONTROL DIAGRAMS

MOUNTED ON WALL.

MRI ZONE II

C146

OUTPATIENT ENTRY

C100

ED ENTRY

AC100

CORRIDOR

C144

ED WAITING

AC101

VA POLICE

AC101A

TLT

C130

ADMIT

AC101B

ADMIT

AC101C

WORK

AC132

NURSE MGR

AC133

WAITING

AC137

TLT

AC134A

(E)175

(E)260

(E)260

(E)200

(E)200(E)445

T

T

(E)85

(E)125

(E)150

(E)100

(E)130

(E)80 (E)80 (E)80

(E)210

(E)190

(E)210 (E)210

(E)90 (E)90 (E)90

(E)90 (E)80 (E)190

(E)190

(E)130

(E)100

(E)110

(E)120

(E)120

(E)150

ADJUST OUTPUT OF EXISTING

1-AHU19 TO 5130 SA WITH A

MIN OA OF 1380 CFM

(E)200

(E)120

(E)130

(E)80 (E)80

3870CFM DN. ADJUST OUTPUT

OF RETURN FAN 2 TO 3745 CFM

(E)90 (E)80

(E)100(E)380

(E)120

(E)130

(E)150

(E)120

(E)200 (E)200

(E)90 (E)90

(E)150

(E)85

(E)200

(E)250

(E)90

(E)90

(E)90

(E)90

(E)100

(E)100

(E)100

(E)90

(E)100

(E)110

(E)125260CFM FROM

MRI BATHROOM

(E)85

(E)90

(E)250

(E)250

(E)190

(E)80

(E)100

(E)90

(E)110 (E)125 (E)80

G

F

D

CBA

E

N o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

F

E

D

C

B

A

97 8654321

Drawing Title:

Scale:

Approved:

Building Number:

Location:

Project Title:

Checked By: Drawing No.

Project No.

Drawn By:

Date:

D e p a rt m e n t o f

V e te ra n s A ff a ir s

Dwg. Of

BLDG. 1

ARCHITECTS/ENGINEERS:

VA EASTERN KANSAS

HEALTH CARE SYSTEM

Dwight D. Eisenhower VA Medical Center Leavenworth

Colmery-O'Neil VA Medical Center Topeka

Building Key Plan: A/E Seal

BIM 360://15G69-000 - VA Topeka - ED Renovation & Addn MEPT/15G69-000-MASTER MECH-R19.rvt

1/8" = 1'-0"

7/6/2021 1:11:26 PM

MC801

MECHANICAL

COMMISSIONING PLANS -

ED PHASE 1 & 2 AHUs #589A5-15-115B

TOPEKA, KS

05/07/2021

TJS KWP

UPGRADE

EMERGENCY

DEPARTMENT

1/8" = 1'-0" MC801

1 COMMISSIONING PLAN - BASEMENT

1/8" = 1'-0" MC801

2 COMMISSIONING PLAN - FIRST FLOOR

NEW SHEET

TEST AND BALANCING AND COMMISSIONING OF EXISTING 1-AHU19:

1. THE CONTRACTOR SHALL PROVIDE TEST AND BALANCING SERVICES FOR THE EXISTING 1-AHU19.

2. COMMISSION SERVICES SHALL ALSO INCLUDE COMMISSIONING OF EXISTING 1-AHU19. THE COMMISSIONING PROCESS, WHICH THE CONTRACTOR IS

RESPONSIBLE TO EXECUTE, IS DEFINED IN SECTION 01 91 00 GENERAL COMMISSIONING REQUIREMENTS. A COMMISSIONING AGENT (CXA) APPOINTED BY THE VA

WILL MANAGE THE COMMISSIONING PROCESS.

3. COMMISSIONING OF A SYSTEM OR SYSTEMS SPECIFIED IN DIVISION 23 IS PART OF THE CONSTRUCTION PROCESS. DOCUMENTATION AND TESTING OF THESE SYSTEMS, AS WELL AS TRAINING OF THE VA’S OPERATION AND MAINTENANCE PERSONNEL IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 01 91 00 AND OF DIVISION 23, IS REQUIRED IN COOPERATION WITH THE VA AND THE COMMISSIONING AGENT.

4. COMMISSIONING AGENT TO REFER TO EXISTING CONTROL DIAGRAMS MOUNTED ON WALL AND VERIFY UNIT OPERATION PER SEQUENCE.

5. TEST AND BALANCE CONTRACTOR TO PROVIDE FINAL BALANCING OF EXISTING 1-AHU-1 FURNISHED IN PHASE 1.

No. Description Date

ADDENDUM 1 7/6/20211

07/07/2021

Sheets
MC800 - MECHANICAL COMMISSIONING PLANS - GI LAB AHU
MC801 - MECHANICAL COMMISSIONING PLANS - ED PHASE 1 & 2 AHUs

File details come from the government source that posted it. Updated .