This federal contract opportunity notice solicits bids to upgrade the HVAC system in Building 44 at the Miami VA Medical Center. Key details include the project title, a site visit scheduled for April 24, 2023 at 10:00 AM EST, and the point of contact Apolinar Vargas who can be reached at apolinar.vargas@va.gov. Questions are due by May 1, 2023 at 1:00 PM. The work involves upgrading the HVAC system in the Utility Plant Building 44 and is being conducted by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Level 2 40' - 0"
(E)11-2-CHWP4
(E
C H
R
(E
C H
S
Level 2 40' - 0"
(E)11-2-CHWP4
(E
C H
S
(E) 24" CHS
(E)11-2-CHWP4
(E
C H
R
(E
C H
S
(E) 10" CHS
(E) 10" CHS(E) 10" CHS
UNDERUNDER
(E)11-2-CWP-5A (E)11-2-CWP-5B
M502
Level 2 40' - 0"
(E) 10" CHR (E) 10" CHR
(E) 10" CHS
FRONT FRONT
BACK
(E)11-2-CWP-5B (E)11-2-CWP-5A
Level 2 40' - 0"
(E
C H
R
(E) 10" CHS
(E)11-2-CWP-5A
AMBMICU
TOWER
8 7
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
N.T.S.
KEY PLAN
PLAN
NORTH
TRUE
NORTH
PROJECT AREA
ENLARGED MECHANICAL PIPING
PLANS
UPGRADE HVAC SYSTEM IN
THE UTILITY PLANT BUILDING
VA MIAMI, FL
M401
546-21-110
JMK JSW/RCP03-03-2023
BID DOCUMENTS
0 2' 4'1'0 2' 4'1' 1/2" = 1'-0"M401
3 ELEVATION 1
1/2" = 1'-0"M401
2 ELEVATION 2
1/2" = 1'-0"M401
1 ENLARGED HORIZONTAL SPLIT CASE PUMP
1/2" = 1'-0"M401
6 ELEVATION 1
1/2" = 1'-0"M401
5 ELEVATION 2
1/2" = 1'-0"M401
4 ENLARGED
0 2' 4'1'
0 2' 4'1' 0 2' 4'1' 0 2' 4'1'
M401 DEMOLITION NOTES
NOTE
NUMBER NOTE TEXT
1 REMOVE HSC PUMP, SUCTION DIFFUSER, AND ISOLATION BASE.
CONTRACTOR TO REUSE EXISTING HYDRONIC COMPONENTS SUCH AS
ISOLATION VALVES AND STRAINERS. EXERCISE ISOLATION VALVES AND
CLEAN STRAINERS BEFORE BEGINNING WORK. NOTIFY COR OF ANY
CONCERNS. REMOVE INERTIA BASE AND PREPARE FOR NEW.
2 REMOVE ES PUMP, SUCTION DIFFUSER, HYDRONIC SPECIALTIES SUCH
AS ISOLATION VALVES AND STRAINERS, AND ISOLATION BASE. ALL
HYDRONIC COMPONENTS SHALL BE REPLACED. CONTRACTOR SHALL
UTILIZE PIPE FREEZING TECHNIQUES TO ISOLATE EACH PUMP BEFORE
REMOVING VALVES. SEE PIPE FREEZE NOTES ON SHEET M001. REMOVE
INERTIA BASE AND PREPARE FOR NEW.
2 2 jwilliamson Snapshot
NOTE:
FIGURE NUMBERS ARE TYPICAL TO GRINNELL SUPPORT NUMBERS.
HANGER ROD ATTACHED TO
STRUCTURE ABOVE
PROVIDE RIB-LOCK INSULATION
PROTECTION SHIELD (FIGURE 168) FOR
INSULATED PIPING
(FIGURE CT-65 FOR COPPER TUBING)
PIPE INSULATION
NON-INSULATED
PIPE
INSULATED
PIPE
CLEVIS HANGER
(PROVIDE OVERSIZED HANGER FOR
INSULATED PIPING)
TYPE 1
ADJUSTABLE CLEVIS
HANGER
(FIGURE 260)
TYPE 1
ADJUSTABLE CLEVIS
HANGER
(FIGURE 260)
HANGER ROD ATTACHED TO
STRUCTURE ABOVE
NON-
INSULATED
PIPE
PIPE INSULATION AS
REQUIRED
TYPE 40 & 41 INSULATION PROTECTION
SHIELD (FIGURE 167)
NOTES:
1. SIZE RODS, SPRING CUSHION, AND HORIZONTAL MEMBER APPROVED TO SATISFY LOAD
REQUIREMENT WITH SAFETY FACTOR OF 5.
2. FIGURE NUMBERS ARE TYPICAL TO GRINNELL SUPPORT NUMBERS.
EQUAL LEG ANGLE
ASSEMBLY (FIG. 50 CHANNEL
ASSEMBLY (FIG. 45), OR
UNIVERSAL TRAPEZE
ASSEMBLY (FIG. 46)
INSULATION
PIPE
TYPE 39A, 39B, 40A & 40B PIPE
INSULATION PROTECTION SADDLE.
(FIGURE 160-165)
TYPE 34
SIDE BEAM BRACKET
(FIGURE 202)
TYPE 31 - LIGHT
TYPE 32 - MEDIUM
TYPE 33 - HEAVY
WELD STEEL BRACKET
(FIGURE 193, 194, 195, 99)
NOTE:
FIGURE NUMBERS ARE TYPICAL TO
GRINNELL SUPPORT NUMBERS.
TYPE 41
SINGLE PIPE
ROLLER
(FIGURE 171)
TYPE 43
SINGLE PIPE
ROLLER
(FIGURE 181)
VAPOR BARRIER AND MOISTURE
MIGRATION SEAL
PIPE
INSULATION
APPLY INSULATION AND
VAPOR JACKET SEAL
AROUND ROD ON COLD
SERVICE INSTALLATION
TYPE 3 DOUBLE
BOLT PIPE
CLAMP
ADHESIVE (TYPICAL)
TAPE APPLIED AT
EACH BUTT JOINT
TYPE 17
WELDLESS
EYENUT
ALL WELDED STEEL
FRAMEWORK
STRUCTURAL
STEEL FRAME
TYPICAL STRUCTURAL STEEL
MEMBER FOR EQUIPMENT
SPRING
ISOLATOR
TYPICAL STRUCTURAL STEEL
MEMBER FOR EQUIPMENT
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE "1"
CONCRETE INERTIA BASE
"A"
& DRIVEN EOUIPMENT
SECTION "A-A"
C
"A"
REINFORCING BARS
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE"B"
WELDED STEEL BASE
SLEEVE
ANCHOR BOLT
DRIVEN
EQUIPMENT
MOTOR
SHAFT
L
MOTOR SHAFT
BB
1.
NOTES:
L/10 5" (125 MM) MIN.
16" (400 MM)
PROVIDE #3BARS
SECTION A-A (BASE NOT POURED WITH SLAB)
EQUIPMENT BASE PLATETYPICAL ANCHOR BOLT
NUT & WASHER
SECTION B-BPLAN
FLOOR
2D D
CONCRETE BASE
PIPE SLEEVE (5D, 3"MIN)
TYPICAL ANCHOR BOLT
NUT & WASHER
EQUIPMENT BASE PLATE
WELD HEAD TO PLATE
OR BEND OVER END 5D
SECTION A-A (BASE POURED WITH FLOOR SLAB)
A
A
W
L
PROVIDE DOUBLE SLAB
REINFORCING IN BASE AREA
L AND W DIMENSIONS SHALL BE 6 IN. (150 MM) GREATER THAN THE EQUIPMENT
BASE PLATE.
ANCHOR BOLT (TYPICAL)
1" (25 MM)
5D
5D
L/10 5" (125 MM) MIN.
WAY IN THE BASE AND
12" (300 MM) O.C. EACH
DOWEL BASE TO FLOOR
4"
GAUGE COCK18 GA. S.S. DRIP PAN
4"
4" 4"
RIGID CONDUIT STUB
TO 3" ABOVE BASE
CONCRETE OR INERTIA
BASE AS SPECIFIED
LIQUID TIGHT,
BEVEL
NEOPRENE COATED
FLEXIBLE CONDUIT
1/2" SCH. 40 TO
DRAIN
FOOT ADJUSTABLE
SUCTION DIFFUSER WITH
1/2" DRAIN TAPPING
PIPE TO FLOOR DRAIN
STRAINER
CONCRETE OR INERTIA
BASE AS SPECIFIED
4"
FLEXIBLE COUPLING AND
FLEXIBLE
CONNECTION
COUPLING GUARD
PIPE INSULATION
GAUGE OR GAUGE WITH
DUAL PORT DIFF. PRESS.
TWO GAUGE COCKS
(TYP. OF 3)
DRAIN VALVE WITH
HOSE THREAD CONNECTION
(TYPICAL)
18 GA. S.S. DRIP PAN
(CHILLED WATER)
BUTTERFLY VALVE
TRIPLE DUTY
VALVE
NOTE:
TAB CONTRACTOR MARK PUMP
DIFFERENTIAL PRESSURE GAGES
WITH YELLOW LINE FOR NORMAL
COMPONENT INLET PRESSURE AND
RED LINE FOR NORMAL COMPONENT
OUTLET PRESSURE AT FULL FLOW
CONDITIONS.
PLAN VIEW
ELEVATION VIEW
NOTES:
1. PUMP INSTALLATION IS DIAGRAMMATIC AND INTENDED TO SHOW THE MAJOR
COMPONENTS REQUIRED FOR INSTALLATION. THE INSTALLED PIPING
CONFIGURATION SHALL BE BASED ON THE ACTUAL PUMP PROVIDED. THE
CONTRACTOR SHALL SUBMIT FOR APPROVAL A COORDINATION DRAWING SHOWING
PUMP, PIPING, AND ACCESSORIES AS REQUIRED BY THIS INSTALLATION DETAIL.
2. ALL PAD, PUMP, AND PIPING DRAINS SHALL BE HARD PIPED TO NEAREST FLOOR
DRAIN, TYPICAL.
FIRST 3 HANGERS FOR EACH PIPE AND BRANCH SHALL BE SPRING
& NEOPRENE TYPE. TYPE "H" FOR 4" DIA. PIPE AND SMALLER.
TYPE "H-P" FOR 5" DIA. PIPE AND LARGER.
RIGID PIPE
HANGER
(TYPICAL)
INSTALL HANGER AS CLOSE
TO PIPE ELBOW AS POSSIBLE
(TYPICAL)
PRESSURE
GAGE
PUMP
FLOOR
CONCRETE OR INERTIA
BASE AS SPECIFIED
1/2"
FLEXIBLE
CONNECTOR
TYP.
NOTE 3
1" MIN. DIA. PIPE STAND
STRAINER
NON SLAM CHECK
VALVE WITH
COUNTER WEIGHT
BUTTER OR BALL
SHUT OFF VALVE,
TYP.
INLET TO PUMP SHALL BE
MINIMUM OF 3 PIPE
DIAMETERS
ECCENTRIC
REDUCER
AVAV
NOTES:
1. Y TYPE STRAINER BLOWDOWN HEIGHT SHALL ACCOMMODATE 55 GALLON DRUM.
2. PUMP INSTALLATION IS DIAGRAMMATIC AND INTENDED TO SHOW THE MAJOR COMPONENTS
REQUIRED FOR INSTALLATION. THE INSTALLED PIPING CONFIGURATION SHALL BE BASED ON
THE ACTUAL PUMP PROVIDED. THE CONTRACTOR SHALL SUBMIT FOR APPROVAL A
COORDINATION DRAWING SHOWING PUMP, PIPING, AND ACCESSORIES AS REQUIRED BY THIS
INSTALLATION DETAIL.
3. ALL PAD, PUMP, AND PIPING DRAINS SHALL BE HARD PIPED TO NEAREST FLOOR DRAIN, TYPICAL.
DUCT
WALL OR CEILING
1" MINIMUM ALL ROUND
1/4" TO 1/2" CLEARANCE
FUSIBLE LINK SET AT 165 F°
'S' LOCK DUCT CONNECTIONS
DUCT ACCESS PANEL
FOLDING BLADE FIRE
DAMPER IN TYPE 'B'
FRAME, EXCEPT USE TYPE
'CR' WHEN CONNECTING
DIRECTLY TO ROUND DUCT.
NOTES:
A. HORIZONTAL FIRE DAMPER SIMILAR. PROVIDE
SPRING LOADED CURTAIN WITH FUSIBLE LINK SET
AT 165°F.
B. B. DETAIL FOR GENERAL GUIDANCE, INSTALL
EACH FIRE DAMPER IN STRICT ACCORDANCE WITH
INSTALLATION INSTRUCTIONS PACKED WITH FIRE
DAMPER TO ENSURE UL RATING.
2"x2"x1/4" ANGLE IRON
FRAME ALL ROUND, BOTH
SIDES, MITERED AND WELDED
AT CORNERS. OMIT FRAME
ON ROOM SIDE OF WALL
WHEN CONNECTING DIRECTLY
TO SIDEWALL REGISTER.
FACTORY FABRICATED
16 GAUGE SLEEVE.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
HYDRONIC DETAILS UPGRADE HVAC SYSTEM IN
THE UTILITY PLANT BUILDING
VA MIAMI, FL
M501
546-21-110
JMK JSW/RCP
BID DOCUMENTS
03-03-2023
NOT TO SCALEM501
1 SINGLE PIPE CLEVIS HANGER
NOT TO SCALEM501
4 TRAPEZE TYPE PIPE SUPPORT
NOT TO SCALEM501
2 PIPE BRACKETS AND ROLLERS
NOT TO SCALEM501
5 PIPE HANGER, INSULATION AND VAPOR JACKET
NOT TO SCALEM501
3 END SUCTION PUMP
NOT TO SCALEM501
9 HORIZONTALSPLIT CASE PUMP - FLEXIBLE CONNECTORS
NOT TO SCALEM501
6 VIBRATION ISOLATION BASES
NOT TO SCALEM501
7 CONCRETE EQUIPMENT BASES
NOT TO SCALEM501
8 FIRE DAMPER DETAIL
C
C
MIN 18"
FULL SIZE 14 GAUGE SHEET
METAL PLENUM
FULL SIZE MOTORIZED
DAMPERS INTAKE LOUVER. SEE
FLOOR PLAN FOR LOUVER
SIZE.
WALL
WALL
INSULATE PLENUM WHERE
REQUIRED BY DRAWINGS
OR SPECIFICATIONS.
REAR GUARD
WALL SLEEVE
CHANNEL SUPPORTS
GRAVITY DAMPER
(PROVIDE MOTORIZED
DAMPER FOR SUPPLY)
CONTRACTOR
SHALL PROVIDE
SLEEVE, SUPPORTS,
AND BLANK-OFFS
REQUIRED FOR
INSTALLATION.
WALL
BIRD SCREEN
SIZE 1/2" MESH
BIRD SCREEN
SIZE 1/2" MESH
BOLTS
METAL SCREEN
FRAME
EXISTING LOUVER
FLOW
AIR
MOTOR
DUCTWORK
FLEXIBLE
CONNECTION
TYPICAL
ALTERNATE
LOCATION
STEEL SPRING
AND RUBBER IN
SHEAR TYPE
VIBRATION
ISOLATORS
MOUNTING
BRACKETS
THREADED STEEL RODS ATTACH TO
STRUCTURE AS RECOMMENDED BY
MANUFACTURER INSTALLATION &
SMACNA LENGTH OF RODS TO SUIT
SPACE AVAILABLE
5'
3/
A B
1"
DRAW THRU
BLOW THRU
2" PLUS X
1" MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE
SAME SIZE AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR
TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
CONDENSATE PUMP AS
DETAILED THIS SHEET
DRAIN PAN
NOTE:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS INDOORS
AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE TO BE
CONNECTED.
DIELECTRIC FITTING
CWS
CWR
CONNECTIONS
FLOW
AIR
CHILLED WATER
CWS, DOWNSTREAM
COIL
COIL
CWR, UPSTREAM
1/2" DRAIN VALVE WITH HOSE
CONNECTION
STRAINER
FROM CHILLED WATER MAINS.
SEE SCHEDULES FOR SIZES
MANUAL AIR VENT
P/T PLUG
(TYPICAL)
BALL VALVE (TYPICAL)
2-WAY COIL FLOW CONTROL VALVE
AUTOMATIC FLOW
BALANCING VALVE
DUAL CHILLED
WATER COIL
T
T
THERMOMETER (TYP. OF 2)
SYMMETRICAL PIPING BRANCHES SIZED AT
2.0 FT H₂O/100 FT BASED ON INDIVIDUAL
COIL FLOW FOR SUPPLY AND RETURN
Level 3 80' - 0"
12” HIGH STRUCTURAL AIR
HANDLING UNIT SUPPORTS.
SUPPORT AIR HANDLING
UNIT UNDER EACH MODULE.
(TYPICAL)
8" THICK CONCRETE BASIN
26"x76" S-O/A
44-3-AHU-1
CONTRACTOR SHALL INSTALL COIL
APPURTENANCES SHOWN ON DUAL
CHILLED WATER COIL PIPING
DETAIL ON THIS SHEET.
20"x20" S/A
MIXING
SECTION
FILTER
SECTION
COOLING COIL
SECTION
FAN SECTION
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
MECHANICAL DETAILS UPGRADE HVAC SYSTEM IN
THE UTILITY PLANT BUILDING
VA MIAMI, FL
M502
546-21-110
JMK JSW/RCP
BID DOCUMENTS
03-03-2023
NOT TO SCALEM502
1 VENTILATION AIR DETAIL
NOT TO SCALEM502
2 WALL MOUNTED EXHAUST FAN DETAIL
NOT TO SCALEM502
3 IN-LINE FAN SUPPORT DETAIL
NOT TO SCALEM502
5 AIR HANDLING UNIT CONDENSATE DRAIN/TRAP DETAIL
NOT TO SCALEM502
4 DUAL CHILLED WATER COIL PIPING
NOT TO SCALEM502
6 AIR HANDLING UNIT ELEVATION VIEW - 44-3-AHU-1
NOT TO SCALEM502
7 AIR HANDLING UNIT PLAN VIEW - 44-3-AHU-1
44-3-AHU-1
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
MECHANICAL SCHEDULES UPGRADE HVAC SYSTEM IN
THE UTILITY PLANT BUILDING
VA MIAMI, FL
M601
546-21-110
JMK JSW/RCP
BID DOCUMENTS
03-03-2023
5. MINIMUM ALLOWED HEATING WATER FLOW IS 0.5 G.P.M.
4. HEATING COIL LVG TEMPERATURE IS AT HEATING C.F.M.
3. PRIMARY AIR VALVE C.F.M. SHALL NOT EXCEED MANUFACTURER'S "NOMINAL C.F.M.".
2. N.C. LEVEL SHALL NOT EXCEED 30db BASED ON 10DB ROOM ABSORPTION, RE RAISED TO THE -12 WATTS.
1. MAXIMUM AIR PRESSURE DROP FOR TERMINAL IS SUM OF DESIGN DROP AND COIL DROP AT MAXIMUM C.F.M
NOTES:
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE (233600)
MARK DESCRIPTION
LAYOUT BASIS INLET
NECK
SIZE
OUTLET
TYPE
PRIMARY AIRFLOW
NC
UNIT
WEIGHT VOLT NOTESMANUFACTURER
MODEL
NO. WIDTH HEIGHT MAX MIN
44-TU-01 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2500 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
44-TU-02 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2500 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
44-TU-03 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2300 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
44-TU-04 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2300 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
44-TU-05 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2300 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
44-TU-06 VAV BOX TITUS DESV 14" 20" 17 1/2" SINGLE DUCT 1760 CFM 0 CFM 30 54 lb 120 V 1:2:3:4:5:
44-TU-07 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2500 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
44-TU-08 VAV BOX TITUS DESV 16" 24" 18" SINGLE DUCT 2500 CFM 0 CFM 30 68 lb 120 V 1:2:3:4:5:
3. FACE AND NECK SIZES ARE SHOWN ON DRAWINGS. UNLESS OTHERWISE NOTED, RUNOUT SIZE IS FULL SIZE OF FACE OR NECK SIZE. (A 10" ROUND NECK WILL BE A 10" ROUND RUNOUT; RECTANGULAR
GEOMETRY SIMILAR)
2. PROVIDE DUCT MOUNTED BALANCING DAMPER ON ALL GRILLES AND DIFFUSERS IN ADDITION TO DAMPER MOUNTED ON GRILLE/DIFFUSER. IN CASES WHERE ONLY ONE OUTLET IS CONNECTED TO VAV
TERMINAL DAMPER IS NOT REQUIRED.
1. PAINT FLAT BLACK INTERIOR DUCT SURFACES VISIBLE FROM OUTSIDE THE GRILLE.
NOTES:
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE (233700)
MARK DESCRIPTION MANUFACTURER MODEL NOTES
A 3-CONE DIFFUSER TITUS TMS-AA 2:3:
B HEAVY DUTY DOUBLE DEFLECTION GRILLE TITUS 300RS-HD 2:3
C EGGCRATE RETURN GRILLE TITUS 50F 1:2:3:
3. PROVIDE WITH VFD CAPABLE MOTOR (REUSE EXISTING VFD).
2. PROVIDE NON-OVERLOADING PUMP SELECTION.
1. PROVIDE SUCTION DIFFUSER.
NOTES:
HYDRONIC PUMP SCHEDULE (232123)
MARK PUMP TYPE
LAYOUT BASIS PUMP MOTOR
NOTESMANUFACTURER MODEL FLOW (GPM) FT HEAD
MIN
EFFICIENCY (%) RPM
IMPELLER
(IN) NPSH-FT MOTOR HP VOLTAGE/PHASE
44-2-CWP-1 DOUBLE SUCTION-SPLIT-CASE BELL & GOSSETT 4600-8x10x10.5 3000 50 78.0% 1780 9 1/2" -- 60 480/3 1:2:3:
44-2-CWP-1 DOUBLE SUCTION-SPLIT-CASE BELL & GOSSETT 4600-8x10x10.5 3000 50 78.0% 1780 9 1/2" -- 60 480/3 1:2:3:
44-2-CWP-2 DOUBLE SUCTION-SPLIT-CASE BELL & GOSSETT 4600-8x10x10.5 3000 50 78.0% 1780 9 1/2" -- 60 480/3 1:2:3:
44-2-CWP-2 DOUBLE SUCTION-SPLIT-CASE BELL & GOSSETT 4600-8x10x10.5 3000 50 78.0% 1780 9 1/2" -- 60 480/3 1:2:3:
44-2-CWP-3 DOUBLE SUCTION-SPLIT-CASE BELL & GOSSETT 4600-8x10x10.5 3000 50 78.0% 1780 9 1/2" -- 60 480/3 1:2:3:
44-2-CWP-4 DOUBLE SUCTION-SPLIT-CASE BELL & GOSSETT 4600-8x10x10.5 3000 50 78.0% 1780 9 1/2" -- 60 480/3 1:2:3:
44-2-CWP-5A END SUCTION BELL & GOSSETT 1510-5EB 1285 78 80.0% 1780 11" -- 40 480/3 1:2:3:
44-2-CWP-5B END SUCTION BELL & GOSSETT 1510-5EB 1285 78 80.0% 1780 11" -- 40 480/3 1:2:3:
44-2-CWP-6A END SUCTION BELL & GOSSETT 1510-6G 1475 45 78.0% 1150 12 1/2" -- 25 480/3 1:2:3:
44-2-CWP-6B END SUCTION BELL & GOSSETT 1510-6G 1475 45 78.0% 1150 12 1/2" -- 25 480/3 1:2:3:
44-2-CWP-7A END SUCTION BELL & GOSSETT 1510-2EB 225 106 73.0% 1780 11" -- 15 480/3 1:2:3:
44-2-CWP-7B END SUCTION BELL & GOSSETT 1510-2EB 225 106 73.0% 1780 11" -- 15 480/3 1:2:3:
44-2-CWP-8A END SUCTION BELL & GOSSETT 1510-5EB 1100 74 81.0% 1780 10 1/2" -- 30 480/3 1:2:3:
44-2-CWP-8B END SUCTION BELL & GOSSETT 1510-5EB 1100 74 81.0% 1780 10 1/2" -- 30 480/3 1:2:3:
44-2-CWP-9A END SUCTION BELL & GOSSETT 1510-6G 1850 143 83.0% 1780 12 1/2" -- 100 480/3 1:2:3:
44-2-CWP-9B END SUCTION BELL & GOSSETT 1510-6G 1850 143 83.0% 1780 12 1/2" -- 100 480/3 1:2:3:
44-2-CWP-10A END SUCTION BELL & GOSSETT 1510-6G 1900 179 80.0% 1780 13 1/2" -- 125 480/3 1:2:3:
44-2-CWP-10B END SUCTION BELL & GOSSETT 1510-6G 1900 179 80.0% 1780 13 1/2" -- 125 480/3 1:2:3:
1. PROVIDE FAN ARRAY WITH 2 SUPPLY AIR FANS. PROVIDE BLANK-OFF PANEL FOR EACH FAN.
NOTES:
AIR HANDLING UNIT SCHEDULE (237300)
MARK MNFR
MODEL
SERIES
OA FLOW
(CFM)
SUPPLY FAN HYDRONIC COOLING COIL FILTRATION PROPERTIES
NOTESTYPE
MAX
(CFM)
MIN
(CFM)
TSP
(IN.WG)
ESP
(IN.WG) CLASS DRIVE
MOTOR
(HP)(EA) CTRL
AIRSIDE PROPERTIES FLUID PROPERTIES PREFILTER 1 PREFILTER 2
COIL
CAPACITY
ENTERING AIR
(F)
LEAVING AIR
(F) MAX
(FPM)
APD
(IN-WG)
MAX
FPI
MAX
ROWS
MIN
AREA
(SQ.FT)
FLOW
(GPM)
FLUID
TYPE
EWT
(F)
LWT
(F)
WPD
(FT) TYPE
APD
(IN-WG) TYPE
APD
(IN-WG)TMBH SMBH DB WB DB WB
44-3-AHU-1 CARRIER 39MN 1300 1X2 PLN
ARRAY
13000 0 4.20 2.00 II DIRECT 10 VFD 433 306 76.7 65.3 55.0 54.2 500 0.50 10 6 26 73.0 WATER 43.0 55.0 12.00 MERV 8 0.50 MERV 13 0.50 1:
1.
NOTES:
HYDRONIC FAN COIL SCHEDULE (238200)
MARK MANUFACTURER MODEL CONFIGURATION
FAN COOLING COIL
NOTESCFM OA CFM
ESP
(IN-WG) HP TMBH SMBH
AIRSIDE PROPERTIES FLUID PROPERTIES
EAT DB (F) EAT WB (F) LAT DB (F) LAT WB (F)
FLUID
TYPE
FLOW
(GPM) EWT (F) LWT (F)
WPD
(FT)
44-1-FCU-1 CARRIER 42DE HORIZONTAL 2200 220 0.50 in-wg 1.50 hp 76.4 59.7 80.0 67.0 55.0 54.5 WATER 15.3 45 55 8.2
44-1-FCU-2 CARRIER 42DE HORIZONTAL 270 90 0.50 in-wg 0.10 hp 9.4 7.3 80.0 67.0 55.0 54.5 WATER 2.0 45 55 5.0
44-1-FCU-3 CARRIER 42CG HORIZONTAL 1200 0 0.25 in-wg 0.75 hp 41.7 32.6 80.0 67.0 55.0 54.5 WATER 8.3 45 55 8.2
44-2-FCU-4 CARRIER 42DE HORIZONTAL 555 55 0.50 in-wg 0.50 hp 19.3 15.1 80.0 67.0 55.0 54.5 WATER 3.9 45 55 2.0
44-3-FCU-5 CARRIER 42CG HORIZONTAL 500 0 0.25 in-wg 0.50 hp 17.4 13.6 80.0 67.0 55.0 54.5 WATER 3.5 45 55 5.0
5. SUPPLY FAN.
4. PROVIDE GRAVITY DAMPER.
3. PROVIDE MOTORIZED DAMPER.
2. PWF - PROPELLER WALL FAN
1. ILC - INLINE CENTRIFUGAL.
NOTES:
FAN SCHEDULE (233400)
MARK MANUFACTURER MODEL NO. TYPE ARRANGEMENT
FAN
SOUND PRESS
LEVEL (dBA)
UNIT
WEIGHT VOLT PH NOTES
AIRFLOW VELOCITY PRESS
FAN
RPM
WHEEL
DRIVE
TYPE
MOTOR
DESIGN OUTLET ESP TYPE DIA
TIP
SPEED POWER RPM ECM
44-1-EF-1 GREENHECK SQ-100-VG ILC HORIZONTAL 600 CFM 458 FPM 0.50 in-wg 1232 FC 0" 3609 DIRECT 0.25 hp 1725 No 53 55 lb 208 V 1 1:3:
44-2-EF-1 GREENHECK SQ-120-VG ILC HORIZONTAL 700 CFM 407 FPM 0.75 in-wg 1243 FC 0" 4271 DIRECT 0.50 hp 1725 No 54 63 lb 208 V 1 1:3:
44-2-EF-2 GREENHECK AER-24 PWF SIDEWALL 5575 CFM 1751 FPM 0.50 in-wg 1750 - 24" 11053 DIRECT 1.00 hp 1750 No 76 96 lb 460 V 3 2:4:
44-2-EF-3 GREENHECK AER-24 PWF SIDEWALL 5575 CFM 1751 FPM 0.50 in-wg 1750 - 24" 11053 DIRECT 1.00 hp 1750 No 76 96 lb 460 V 3 2:4:
44-2-EF-4 GREENHECK AER-24 PWF SIDEWALL 5575 CFM 1751 FPM 0.50 in-wg 1750 - 24" 11053 DIRECT 1.00 hp 1750 No 76 96 lb 460 V 3 2:4:
44-2-SF-5 GREENHECK AER-24 PWF SIDEWALL 7000 CFM 2233 FPM 0.50 in-wg 1750 - 24" 11053 DIRECT 1.50 hp 1750 No 80 103 lb 460 V 3 2:4:5:
44-4-EF-6 GREENHECK AER-24 PWF SIDEWALL 4750 CFM 1497 FPM 0.50 in-wg 1750 - 24" 11053 DIRECT 0.75 hp 1750 No 76 96 lb 460 V 3 2:4:
44-4-EF-7 GREENHECK AER-24 PWF SIDEWALL 4750 CFM 1497 FPM 0.50 in-wg 1750 - 24" 11053 DIRECT 0.75 hp 1750 No 76 96 lb 460 V 3 2:4:
4. FOR RECTANGULAR DUCT CONNECTION.
3. FOR ROUND DUCT CONNECTION.
2. CURTIN STYLE DAMPER OUT OF THE AIR STREAM.
1. MINIMAL 2 HOUR RATED WALL.
NOTES:
FIRE DAMPER SCHEDULE (233100)
MARK TYPE DAMPER TYPE NOTES
44-3-FD-1 Round CR 1:2:3:
44-3-FD-2 Round CR 1:2:3:
44-3-FD-3 Rectangular B 1:2:4:
44-3-FD-4 Round CR 1:2:3:
44-3-FD-5 Rectangular B 1:2:4:
44-3-FD-6 Round CR 1:2:3:
44-3-FD-7 Rectangular B 1:2:4:
44-3-FD-8 Round CR 1:2:3:
44-3-FD-9 Round CR 1:2:3:
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
CONTROLS AND SCHEMATICS -
MECHANICAL
UPGRADE HVAC SYSTEM IN
THE UTILITY PLANT BUILDING
VA MIAMI, FL
M801
546-21-110
JMK RCP
BID DOCUMENTS
03-03-2023
DA
C C
T
D
T
X
R
AF
DPT
DPS
FFM
PFS
ASC
VFD
T
CT
SD
OL
SD
HOA
M
T
DA
FT
H
FZ
FS
O
T
H
H C
SH
HH
STEP
SCR
EO
PICV
TEC
O2
FLUID FLOW METER ROUND CONTROL DAMPERAPPLICATION SPECIFIC CONTROLLER
PADDLE TYPE FLOW SWITCH
DUCT MOUNTED TEMP. SENSOR
COOLING COIL
DIFFERENTIAL AIR PRESSURE SWITCH
HEAT EXCHANGER
SENSIBLE WHEEL
REFRIGERANT GAS SENSOR
PARALLEL BLADE DAMPER OPPOSED BLADE DAMPER
AFMS AIR FLOW MEASURING STATION
DIFFERENTIAL PRESSURE SENSOR
DUCT MOUNTED, AVERAGING TEMP. SENSOR
DX COIL
AIR FILTER
CURRENT TRANSDUCER
FAN WITH INLET GUIDE VANES
VARIABLE FREQUENCY DRIVE
TWO WAY ELECTRONIC CONTROL VALVE
THREE WAY ELECTRONIC CONTROL VALVE
PIPE MOUNTED TEMPERATURE SENSOR
FAN
DO
DATA TSTAT
AFMS
NO
NC
AO
DI
BDD
AI
DIGITAL OUTPUT
AIR FLOW MEASUREMENT STATION
NORMALLY OPEN
NORMALLY CLOSED
BINARY DATA LINK THERMOSTAT
HAND-OFF-AUTO SWITCH
SMOKE DETECTOR CONTACTS
SHIELDED BULB AIR TEMPERATURE SENSOR
THERMAL OVERLOADS-NUMBER AS REQUIRED
SMOKE DETECTOR
ANALOG INPUT
DIGITAL INPUT
ANALOG OUTPUT
BACKDRAFT DAMPER
MOTOR START SOLENOID SPACE HUMIDITY SENSOR
SPACE TEMPERATURE SENSOR
DAMPER ACTUATOR (ELECTRONIC)
DUCT MOUNTED HUMIDITY SENSOR
FREEZE PROTECTION THERMOSTAT
STEAM PIT SUMP LEVEL SWITCH
FIRE THERMOSTAT
OCCUPANCY SENSOR
PUMP
HEATING COIL
MOTOR STARTER
FA FIRE ALARM CONTACTS
STROBE/HORN
C COMMONC COMMON
UVC RADIATION SENSOR
ISOLATION ROOM PRESSURE
CONTROLLER KEY SWITCH
PROPORTIONAL HIGH LIMIT HUMIDISTAT
ELECTRIC HEAT STEP CONTROLLER
ELECTRIC HEAT SCR CONTROLLER
EMERGENCY AIR SYSTEM TURN OFF BUTTON
PRESSURE INDEPENDENT CONTROL VALVE
I INPUT / OUTPUT
OXYGEN MONITORING SENSOR
O/ TERMINAL EQUIPMENT CONTROLLER
CONTROL LEGEND
NOT TO SCALE
NOT TO SCALE
DM
CT
PHO
K
CONTROL POINTS SCHEDULE (THIS SHEET ONLY)
AIR DAMPER CONTROLS
WALL MOUNTED EXHAUST
FAN (TYPICAL)
TYPE
MARK
DESCRIPTION NOTES
NOTES:
1. THE NEW WALL EXHAUST FANS AND MOTOR OPERATED LOUVERS PROVIDED SHALL BE OPERATED BY THE THERMOSTAT
SHOWN. THE THERMOSTAT SETPOINT SHALL BE 78° F. ON A CALL FOR COOLING THE THERMOSTAT WILL TURN ON EXHAUST FANS AND SHALL OPEN DAMPER. WHEN THE THERMOSTAT IS SATISFIED THE FANS SHALL TURN OFF AND THE DAMPER SHALL
CLOSE. SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION.
2. MECHANICAL CONTRACTOR AND CONTROLS CONTRACTOR COORDINATE VFD COMMUNICATIONS PROTOCOL WITH CONTROL SYSTEM REQUIREMENTS TO ENSURE FULL COMPATIBILITY (ALL DATA POINTS DISPLAYED/ALARMED ON CONTROLS USER
INTERFACE).
3. SEE FLOOR PLANS FOR LOCATIONS.
4. TYPICAL OF ONE ON EACH VAV TERMINAL OF TYPE SHOWN.
5. TYPICAL FOR ONE VFD CONTROLLING TWO SUPPLY FANS.
6. MECHANICAL CONTRACTOR AND CONTROLS CONTRACTOR COORDINATE VFD COMMUNICATIONS PROTOCOL WITH CONTROL SYSTEM REQUIREMENTS TO ENSURE FULL COMPATIBILITY (ALL DATA POINTS DISPLAYED/ALARMED ON CONTROLS USER
INTERFACE).
7. TYPICAL OF 2.
AI FAN MOTOR CURRENT
DO ON/OFF
AO OPERABLE LOUVER DAMPER OPEN/CLOSE
1:
DO PUMP ON/OFF
AI WATER TEMPERATURE
DATA PUMP VFD DATA/STATUS
AO PUMP SPEED CONTROL
SPARE
NOT TO SCALE
PUMP CONTROLS
SPARE
T
6 VFD
CT
PUMP
2:
PUMP SEQUENCE OF CONTROL
A. WATER PUMP OPERATING, AND SAFETY CONTROLS SHALL INCLUDE:
1. WALL MOUNTED DISCONNECT
2. HAND-OFF-AUTO SELECT SWITCH
3. VARIABLE FREQUENCY MOTOR SPEED CONTROL DRIVE (VFD)
B. THE CONTROL SYSTEM SHALL OPERATE PUMPS ON A WEEKLY LEAD LAG SCHEDULE TO MAINTAIN PUMP RUN TIMES EQUAL.
C. UPON FAILURE OF THE LEAD PUMP THE CONTROL SYSTEM SHALL TURN OFF THE LEAD PUMP AND START LAG PUMP.
D. PUMP SPEED AND SYSTEM PRESSURE CONTROLS:
1. PUMP SPEED AND PRESSURE SHALL BE AS CURRENTLY CONTROLLED. CONTRACTOR TO VERIFY CONTROL SEQUENCE
BEFORE BEGINNING WORK.
2. THE MINIMUM PUMPS SPEED SHALL BE HARD SET AT THE VFD TO 20 HZ OR AT PUMP MANUFACTURER'S
RECOMMENDATION WHICHEVER IS HIGHER.
E. THE SYSTEM WATER PRESSURE SETPOINTS SHALL BE DETERMINED BY THE TAB CONTRACTOR DURING TAB WORK.
F. THE CONTROL SYSTEM SHALL ALARM THE USER INTERFACE WHENEVER ANY OF THE FOLLOWING CONDITIONS OCCURS:
1. PUMP FAILURE.
T
AI SPACE TEMPERATURE
NC
ROOM VENTILATION EXHAUST FAN AND DAMPERS SEQUENCE OF CONTROL
A. THE DDC CONTROL SYSTEM SHALL TURN ON THE MECHANICAL ROOM EXHAUST FAN AND OPEN THE AIR DAMPER WHEN THE
TEMPERATURE IS 80 F OR HIGHER.
B. THE DDC CONTROL SYSTEM SHALL TURN OFF THE EXHAUST FAN AND CLOSE THE AIR DAMPER WHEN THE MECHANICAL
ROOM TEMPERATURE FALLS BELOW 78 F.
C. THE ON AND OFF SETPOINT SHALL BE SOFTWARE ADJUSTABLE ONLY.
D. THE DDC CONTROL SYSTEM SHALL MONITOR THE EXHAUST FAN MOTOR CURRENT AND ALARM THE USER INTERFACE AND
DIAL OUT IF THE MOTOR CURRENT INDICATES MOTOR FAILURE OR BROKEN BELT.
C W
R
C W
S
NC
C
C SF
CT
12 13
T
SPACE SENSORS
H2O
AUXILIARY PAN
DUCTED
AO FAN COIL UNITS CHILLED WATER COIL VALVE MODULATION
AI FAN COIL UNITS FAN MOTOR CURRENT
DO FAN COIL UNITS ON/OFF
AI FAN COIL UNITS SPACE TEMP. SENSOR 3:
DO FAN COIL UNITS MOISTURE SENSOR
SPARE
FAN COIL UNIT SEQUENCE OF CONTROL
A. THE FAN COIL UNITS OPERATING AND SAFETY CONTROLS SHALL INCLUDE:
1. FAN MOTOR CURRENT TRANSDUCER.
2. AUXILIARY DRAIN PAN MOISTURE SWITCH (SHUTS OF UNIT).
B. THE CONTROL SYSTEM SHALL CYCLE THE FAN COIL UNIT FAN ON AND OFF AND SHALL MODULATE THE COOLING COIL CHILLED WATER VALVE TO MAINTAIN THE SPACE AT 77 F (SOFTWARE ADJUSTABLE ONLY) SETPOINT.
C. THE CONTROL SYSTEM SHALL ALARM THE USER INTERFACE FOR THE FOLLOWING:
1. SPACE TEMPERATURE MORE THAT 2 F (ADJUSTABLE) ABOVE SETPOINT FOR 5 MINUTES (ADJUSTABLE) OR LONGER.
2. FAN COIL UNIT FAN MOTOR BROKEN AS DETERMINED BY SYSTEM CALLING FOR COOLING AND ZERO AMPS ON THE FAN
MOTOR.
3. MOISTURE IN THE AUXILIARY CONDENSATE PAN.
NOT TO SCALE
4 6
NOT TO SCALE
NOT TO SCALE
DAAF
T
SPACE SENSORS
T
23 25
CT
VAV TERMINALSINLINE EXHAUST FAN
AI VAV TERMINAL SPACE TEMP. SENSOR 3:4:
AI VAV TERMINAL AIR FLOW SENSOR 4:
AI VAV TERMINAL TEMPERATURE SENSOR 4:
AO VAV TERMINAL DAMPER MODULATION 4:
DI VAV TERMINAL OCCUPANCY OVERRIDE 3:4:
AI INLINE EXHAUST FAN FAN MOTOR CURRENT
DO INLINE EXHAUST FAN ON/OFF
SPARE
VAV TERMINALS SEQUENCE OF CONTROL
A. ALL VAV TERMINALS SHALL OPERATE THE PRIMARY AIR DAMPER TO MAINTAIN SPACE TEMPERATURE AT SETPOINT (75 F;
ADJUSTABLE).
B. UPON A CALL FOR COOLING THE PRIMARY AIR CFM SETPOINT SHALL INCREASE AND THE DAMPER SHALL MODULATE TO
MAINTAIN AIR FLOW AT SETPOINT.
C. UPON A CALL FOR HEATING THE PRIMARY AIR CFM SETPOINT SHALL DECREASE AND THE DAMPER SHALL MODULATE TO
MAINTAIN AIR FLOW AT SETPOINT.
D. THE CONTROL SYSTEM SHALL MONITOR AND DISPLAY THE VAV TERMINAL LEAVING AIR TEMPERATURE AND FLOW.
GENERAL INLINE EXHAUST FANS SEQUENCE OF CONTROL
A. THE DDC CONTROL SYSTEM SHALL MONITOR THE EXHAUST FANS MOTOR CURRENT AND ALARM THE USER INTERFACE WHEN EXHAUST FANS IS NOT OPERATING CORRECTLY DUE TO FAULTY MOTOR OR BROKEN FAN BELT AS DETERMINED BY THE
MOTOR CURRENT CT.
B. FAN RUNS CONTINUOUSLY.
44-3-AHU-1 SEQUENCE OF CONTROL
A. SUPPLY FAN OPERATING AND SAFETY CONTROLS SHALL INCLUDE:
1. WALL MOUNTED DISCONNECT.
2. VARIABLE FREQUENCY MOTOR SPEED CONTROL DRIVE (VFD). (ONE DRIVE CONTROLLING TWO FANS)
3. SUPPLY AIR SMOKE DETECTOR.
4. FREEZE PROTECTION THERMOSTAT.
5. GENERAL FIRE ALARM SYSTEM CONTACTOR.
6. HIGH PRESSURE DUCT CUT OUT SWITCH.
7. LOW PRESSURE DUCT CUT OUT SWITCH.
8. AUXILIARY DRAIN PAN MOISTURE SWITCH.
B. THE SMOKE DETECTORS, FREEZE PROTECTION THERMOSTAT, FIRE ALARM CONTACTOR, AND HIGH AND LOW PRESSURE SWITCHES SHALL BE HARD WIRED INTO BOTH FAN'S MOTOR CONTROL CIRCUITS AND SHALL SEND A SIGNAL FROM AN AUXILIARY CONTACT TO THE DDC CONTROL SYSTEM. IN ADDITION, THE SMOKE DETECTORS SHALL SEND A SIGNAL TO THE
BUILDING FIRE ALARM SYSTEM.
C. SUPPLY FAN INTERLOCK: IF ANY FAN FAILS AS INDICATED BY VFD STATUS AND / OR BY AIR FLOW MEASURING STATION STATUS THE CONTROL SYSTEM SHALL TURN OFF THE OTHER FAN AND SHALL GENERATE AN ALARM TO THE CONTROL
SYSTEM'S USER INTERFACE.
D. WITH THE SAFETY CONTROLS IN THE NORMAL POSITION AND THE VFD IN THE AUTO POSITION THE FAN MOTORS SHALL RUN
CONTINUOUSLY:
E. FANS AND CONTROLS INTERLOCK: WHENEVER THE FANS ARE OFF AS INDICATED BY NO FLOW AT AIR FLOW MEASUREMENT
STATIONS, ALL CONTROL ACTUATORS SHALL BE PLACED IN THEIR NORMAL POSITION.
F. SUPPLY FAN SPEED CONTROL:
1. THE DDC SYSTEM SHALL MODULATE THE VFD OUTPUT TO MAINTAIN SUPPLY DUCT STATIC PRESSURE AT SETPOINT.
2. THE CONTROL SYSTEM SHALL RESET THE SUPPLY DUCT STATIC PRESSURE SETPOINT BASED ON THE POSITION OF THE VAV TERMINAL DAMPERS. EVERY 15 MINUTES THE CONTROL SYSTEM SHALL LOWER THE SETPOINT BY 0.05" WG IF AT LEAST ONE TERMINAL IS AT MINIMUM POSITION AND NO TERMINALS ARE FULLY OPEN. IF AT LEAST ONE TERMINAL IS
FULLY OPEN THE CONTROL SYSTEM SHALL INCREASE THE SETPOINT BY 0.05" WG.
G. MIXED AIR SECTION CONTROL:
1. THE MIXED AIR SECTION SHALL OPERATE TO MAINTAIN MINIMUM OUTSIDE AIR.
H. SUPPLY AIR TEMPERATURE: THE CONTROL SYSTEM SHALL MODULATE THE COOLING COIL TO MAINTAIN SUPPLY AIR
TEMPERATURE AT SETPOINT 55° F (ADJUSTABLE).
I. FILTER MONITORING: THE CONTROL SYSTEM SHALL MONITOR AIR PRESSURE DROP ACROSS EACH FILTER BANK AND
RESPOND AS FOLLOWS:
1. ALARM WHEN FILTER PRESSURE DROP EXCEEDS MANUFACTURER'S LIMIT. LIMIT TO BE DETERMINED FROM FILTER AND AIR HANDLING UNIT SUBMITTALS AND UPDATED IN CONTROL CONTRACTOR'S SEQUENCE OF CONTROL.
2. ALARM WHEN FILTER PRESSURE DROP INDICATES THAT A FILTER IS MISSING FROM THE RACK. SETPOINT PRESSURE TO
BE DETERMINED DURING TEST AND BALANCE BY REMOVAL OF A FILTER FROM THE RACK.
J. ALARMS: THE CONTROL SYSTEM SHALL ALARM THE USER INTERFACE AND TAKE THE INDICATED ACTIONS WHENEVER ANY OF
THE FOLLOWING CONDITIONS OCCURS:
1. FAN FAILURE AS DETERMINED BY VFD STATUS AND AIR FLOW MEASUREMENTS.
2. COOLING COIL LEAVING AIR TEMPERATURE NOT AT SETPOINT FOR FIVE MINUTES OR LONGER.
3. SUPPLY DUCT STATIC PRESSURE NOT AT SETPOINT FOR 5 MINUTES OR LONGER.
4. WHEN ANY FAN IS OPERATING IN MANUAL OVERRIDE AS DETERMINED BY FAN OPERATION OUTSIDE THE CONTROL OF THE
CONTROL SYSTEM.
5. ANY FAN SAFETY CONTROL TRIP SHALL GENERATE AN ALARM.
6. MOISTURE IN THE AUXILIARY CONDENSATE PAN.
ATM.
SD-1
SP=40°F
FZ
FA
C W
R
C W
S
DPS-1 DPS-2
NC
NOT TO SCALE
DA
NO
T
T
NC
DA DPT
DPT
FZ SD-1 T
27 28 29 31
32 33
SF
VFD
T
DPT
C
C
DPS-1
ATM
DPS-2
ATM
AFMS
AFMS
AIR HANDLING UNIT 44-3-AHU-1
DATA 44-3-AHU-1 SUPPLY FAN VFD DATA/STATUS 5:6:
AI 44-3-AHU-1 PRE-FILTER STATUS
AO 44-3-AHU-1 CHILLED WATER COIL VALVE MODULATION
AI 44-3-AHU-1 INTERMEDIATE FILTER STATUS
AO 44-3-AHU-1 RETURN DAMPER MODULATION
AO 44-3-AHU-1 OUTDOOR AIR DAMPER MODULATION
AI 44-3-AHU-1 MIXED AIR STATIC PRESSURE
AI 44-3-AHU-1 OUTDOOR AIR TEMPERATURE
AI 44-3-AHU-1 SUPPLY AIR - AIR STATIC PRESSURE
AO 44-3-AHU-1 SUPPLY FAN SPEED CONTROL
DO 44-3-AHU-1 SUPPLY FANS ON/OFF
DI 44-3-AHU-1 SUPPLY AIR SMOKE DETECTOR STATUS
AI 44-3-AHU-1 SUPPLY AIR TEMPERATURE
DI 44-3-AHU-1 FREEZE STAT STATUS
AI 44-3-AHU-1 MIXED AIR TEMPERATURE
5:
5:
DI 44-3-AHU-1 HIGH LIMIT PRESSURE SWITCH
AI
AI
44-3-AHU-1 SUPPLY AIR FLOW
44-3-AHU-1 RETURN AIR FLOW
AI 44-3-AHU-1 RETURN AIR TEMPERATURE
DI 44-3-AHU-1 LOW LIMIT PRESSURE SWITCH
7:
7:
SPARE
EMERGENCY REFIGERANT EXHAUST
A. THE DDC CONTROL SYSTEM SHALL MONITOR THE EXHAUST FANS MOTOR CURRENT AND ALARM THE USER INTERFACE WHEN EXHAUST FANS IS NOT OPERATING CORRECTLY DUE TO FAULTY MOTOR OR BROKEN FAN BELT AS DETERMINED BY THE
MOTOR CURRENT CT.
B. THE DDC CONTROL SYSTEM SHALL TURN ON THE EXHAUST FAN UPON SIGNAL FROM THE REFRIGERANT MONITOR(S).
C. THE DDC CONTROL SYSTEM SHALL TURN OFF THE EXHAUST FAN UPON SIGNAL FROM THE REFRIGERANT MONITOR(S).
NOT TO SCALE
CT
WALL MOUNTED EXHAUST
FAN (REFRIGERANT PURGE)
49 50
RF
AI FAN MOTOR CURRENT
DO ON/OFF
1:AI EMERGENCY REFRIGERANT MONITOR
H2OCONCRETE BASIN
44-3-AHU-1 MOISTURE SENSORDO
AI 44-3-AHU-1 OUTDOOR AIR FLOW
OA
RA
AFMS
DPS
ATM
FAN COIL UNITS CONTROL SCHEMATIC
SHEET NAMING CONVENTION
E-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
ELECTRICAL GENERAL NOTES:
1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
A. NFPA 70-2020 (NATIONAL ELECTRICAL CODE)
B. ANSI C2-2020 (NATIONAL ELECTRICAL SAFETY CODE)
C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE
LAWS.
2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY
SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS
THAN 40% FULL.
3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH
OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND
SHALL BE RESPONSIBLE FOR SECURING SPACE
REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE
FOR RECESSED LUMINAIRES AND CORRECT ROUGH-IN
LOCATIONS OF ELECTRICAL CONNECTIONS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
CATALOG NUMBERS ON THESE DRAWINGS TO MATCH WITH
MATERIAL DESCRIPTIONS INDICATED.
5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND
BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE
WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING
HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET
BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS
USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE
COUNTERTOP.
6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS
BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE
SAME LOCATION SHALL BE GANGED TOGETHER IN ONE
COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE
PLATE.
7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN
INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL
ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH
DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE
PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL
CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH
CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND
CONDUCTOR.
8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR
LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS
FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO
INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND
EQUIPMENT BEFORE ROUGHING-IN.
9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN,
UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING
ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT,
FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR
DELETED IN THE PROCESS OF CONSTRUCTION OR
REMODELING WHICH IS DONE AS A RESULT OF CONTRACT
PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY
DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID
CIRCUIT OR FEEDER SHALL BE RESTORED TO WORKING
CONDITION. THE RESTORATION SHALL INCLUDE RE-ROUTING,
RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE
REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED
SHALL BE INCLUDED IN THE CONTRACT AND NO EXTRA
COMPENSATION WILL BE GRANTED.
10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A
UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE
CHECKED AGAINST EXISTING WORK FOR TYPE MOUNTING,
MOUNTING HEIGHTS, ETC. ITEMS SHOWN IN NEW WORK AT
VARIANCE FROM THE EXISTING SHALL BE REFERRED TO THE
ARCHITECT FOR DECISION BEFORE ROUGH-IN.
11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER
DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN
ON PLANS.
12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS
OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED
TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT,
CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS
ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL
SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS
AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE
ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS
HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT
EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE
OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH
FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST
OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S
RESPONSIBILITY.
14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED
AS ALUMINUM.
15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,
DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF
ANY MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS
OR SUBMITTALS.
16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED
LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION
BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT
SHALL BE BLACK, 1/8” IN HEIGHT PRINTED ON A CLEAR
LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT
FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING
WHICH CAN BE HANDWRITTEN WITH AN INDELIBLE MARKER.
17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT
SHALL EXTEND 2” BEYOND THE FOOTPRINT OF THE
EQUIPMENT.
18. EMT SHALL COMPLY WITH ANSI C80.3 AND UL 797. ALL EMT
SHALL BE FACTORY PAINTED. PROVIDE THE FOLLOWING
COLORS FOR EACH SYSTEM:
• FIRE ALARM - RED
• TELECOMMUNICATIONS - ORANGE
• 480/277V POWER - YELLOW
• 208/120V POWER - BLUE
• GENERATOR POWER - GREEN
• SECURITY - PURPLE
ELECTRICAL ABBREVIATIONS
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS
THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE
DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT
SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A
PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY
SYSTEM
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-
SECONDARY SYSTEM
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR
SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS MAIN GROUNDING
BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
P R
O F
E
S S
I ONA L ENG
I N E
E R
J
ER
EM
Y M. KNOW
LESL
I C ENS E
F L O R I D A
No. 90210
STATE OF
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
ELECTRICAL GENERAL NOTES
AND ABBREVIATIONS
UPGRADE HVAC SYSTEM IN
THE UTILITY PLANT BUILDING
VA MIAMI, FL
E001
546-21-110
FK EO
BID DOCUMENTS
03-03-2023
NOTE:
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS
PROJECT.
WIRE SIZE FOR ALL 277V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 170 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 280 FT
AND GREATER THAN OR EQUAL TO 170 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 440 FT
AND GREATER THAN OR EQUAL TO 280 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 700 FT
AND GREATER THAN OR EQUAL TO 440 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
WIRE SIZE FOR ALL 120V, 20A CIRCUITS,
UIO:
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,
PROVIDE 2#12 & 1#12G, 3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT
AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT
AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT
AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,
3/4"C.
NOTES:
1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.
ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,
DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT
IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF
EACH:
EXISTING EQUIPMENT
NEW OR RELOCATED EQUIPMENT
HATCH INDICATES EQUIPMENT TO BE DEMOLISHED
MECHANICAL EQUIPMENT SCHEDULE
AHU VOLTAGE POLES KVA FLA
MOCP
(AMPS) HP DISCONNECT FEEDER SIZE NOTES
44-1-EF-1 120 V 1 700 VA 1.1 20 0.25 30 3#12 + 1#12G, 3/4"C 1
44-1-FCU-1 277 V 1 1884 VA 6.8 20 30 3#12 + 1#12G, 3/4"C 1
44-1-FCU-2 120 V 1 588 VA 4.9 20 30 3#12 + 1#12G, 3/4"C 1
44-1-FCU-3 120 V 1 590 VA 4.9 20 0.75 30 3#12 + 1#12G, 3/4"C 1
44-2-CWP-1 480 V 3 64000 VA 77.0 175 60 VFD 3#1 + 1#6G, 1-1/4"C 1
44-2-CWP-2 480 V 3 64000 VA 77.0 175 60 VFD 3#1 + 1#6G, 1-1/4"C 1
44-2-CWP-3 480 V 3 64000 VA 77.0 175 60 VFD 3#1 + 1#6G, 1-1/4"C 1
44-2-CWP-4 480 V 3 64000 VA 77.0 175 60 VFD 3#1 + 1#6G, 1-1/4"C 1
44-2-CWP-5A 480 V 3 43212 VA 52.0 125 40 VFD 3#4 + 1#6G, 1"C 1
44-2-CWP-5B 480 V 3 43212 VA 52.0 125 40 VFD 3#4 + 1#6G, 1"C 1
44-2-CWP-6A 480 V 3 28254 VA 34.0 80 25 VFD 3#6 + 1#8G, 3/4"C 1
44-2-CWP-6B 480 V 3 28254 VA 34.0 80 25 VFD 3#6 + 1#8G, 3/4"C 1
44-2-CWP-7A 480 V 3 17451 VA 21.0 50 15 VFD 3#10 + 1#10G, 3/4"C 1
44-2-CWP-7B 480 V 3 17451 VA 21.0 50 15 VFD 3#10 + 1#10G, 3/4"C 1
44-2-CWP-8A 480 V 3 33240 VA 40.0 100 30 VFD 3#6 + 1#8G, 3/4"C 1
44-2-CWP-8B 480 V 3 33240 VA 40.0 100 30 VFD 3#6 + 1#8G, 3/4"C 1
44-2-CWP-9A 480 V 3 103044 VA 124.0 300 100 VFD 3#2/0 + 1#4G, 2"C 1
44-2-CWP-9B 480 V 3 103044 VA 124.0 300 100 VFD 3#2/0 + 1#4G, 2"C 1
44-2-CWP-10A 480 V 3 129636 VA 156.0 350 125 VFD 3#3/0 + /#3G, 2"C 1
44-2-CWP-10B 480 V 3 129636 VA 156.0 350 125 VFD 3#3/0 + /#3G, 2"C 1
44-2-EF-1 120 V 1 768 VA 1.1 20 0.50 30 3#12 + 1#12G, 3/4"C 1
44-2-EF-2 480 V 3 1745 VA 2.1 20 1 30 3#12 + 1#12G, 3/4"C 1
44-2-EF-3 480 V 3 1745 VA 2.1 20 1 30 3#12 + 1#12G, 3/4"C 1
44-2-EF-4 480 V 3 1745 VA 2.1 20 1 30 3#12 + 1#12G, 3/4"C 1
44-2-FCU-4 120 V 1 588 VA 4.9 20 0.5 30 3#12 + 1#12G, 3/4"C 1
44-2-SF-5 480 V 3 2493 VA 3.0 20 1.50 30 3#12 + 1#12G, 3/4"C 1
44-3-AHU-1 480 V 3 6316 VA 7.6 20 5 30 3#12 + 1#12G, 3/4"C 1
44-3-FCU-5 120 V 1 300 VA 1.9 20 0.5 30 3#12 + 1#12G, 3/4"C 1
44-4-EF-6 480 V 3 914 VA 1.1 20 0.50 30 3#12 + 1#12G, 3/4"C 1
44-4-EF-7 480 V 3 1330 VA 1.6 20 0.75 30 3#12 + 1#12G, 3/4"C 1
44-TU-01 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-02 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-03 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-04 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-05 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-06 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-07 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
44-TU-08 120 V 1 120 VA 1.0 20 MRS 3#12 + 1#12G, 3/4"C 2
NOTES:
1. MECHANICAL EQUIPMENT SHALL BE CIRCUITED TO THE SAME PANEL AS THE EXISTING MECHANICAL EQUIPMENT IT IS REPLACING.
2. MECHANICAL EQUIPMENT SHALL BE CIRCUITED TO THE CLOSET 208Y/120V 3-PHASE 4-WIRE PANEL. PROVIDE CIRCUIT BREAKER AS SHOWN ON MECHANICAL
EQUIPMENT SCHEDULE. SEE FLOOR PLANS FOR MORE INFORMATION.
3. ALL CONDUCTORS FOR MECHANICAL AND PLUMBING EQUIPMENT SHALL BE COPPER. THE USE OF ALUMINUM CONDUCTORS TO FEED THIS EQUIPMENT IS NOT
PERMITTED.
1/2
B
W
SB
M
M
2/60/40/1
60/40/3/3R
40/3/3R
CB
T
M
EM
J J
J
G
G4
A
AE
M
X X
C
D a b
LUMINAIRES
LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER
INDICATES SWITCHLEG DESTINATION.
LUMINAIRE AND OUTLET BOX, WITH PROVISIONS
FOR EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND
OUTLET BOX. PROVIDE NUMBER OF ARROWS
AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNT AT 96" ABOVE FINISHED FLOOR.
RECESSED OR PENDANT MOUNTED LUMINAIRE
AND OUTLET BOX. LETTER INDICATES LUMINAIRE
TYPE. SEE LUMINAIRE SCHEDULE.
WALL MOUNTED LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE
LUMINAIRE SCHEDULE.
CEILING OR WALL MOUNTED LUMINAIRE AND
OUTLET BOX WITH PROVISIONS FOR
EMERGENCY LIGHTING. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
EMERGENCY LIGHT UNIT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
REMOTE HEAD OR FLOOD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
WALL WASH DOWNLIGHT. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POLE MOUNTED LUMINAIRE. LETTER INDICATES
LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.
POST-TOP OR BOLLARD LUMINAIRE. LETTER
INDICATES LUMINAIRE TYPE. SEE LUMINAIRE
SCHEDULE.
EQUIPMENT
MOTOR, HORSEPOWER AS INDICATED
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR
STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/
NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE
SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-
FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER,
(CIRCUIT BREAKER SIZE/ POLES/ NEMA
ENCLOSURE)
DRY TYPE TRANSFORMER, KVA AS INDICATED
METER
ELECTRONIC METER
PANELBOARD, SEE SCHEDULES
DISTRIBUTION PANELBOARD, SEE SCHEDULES
EQUIPMENT AS INDICATED
CEILING OR WALL MOUNTED JUNCTION BOX
PULL OR JUNCTION BOX
CEILING MOUNTED BLUE LIGHT SYSTEM
ROTATING BEACON
WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE
DROP CEILING
BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT
48" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
WHITE NOISE ROTARY VOLUME CONTROL;
MOUNT 48" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE.
CR
ST
TR
M
R
LA-1,3,5
WIRING DEVICES
LOW VOLTAGE ON/OFF WALL SWITCH, WALL
MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE
DIMMER CONTROL WITH DIMMABLE FIXTURES
INTEGRAL WITH SWITCH.
CEILING MOUNTED DUAL TECHNOLOGY
OCCUPANCY SENSOR
CEILING MOUNTED DUAL TECHNOLOGY
VACANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
WIRING
CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5
ADJACENT TO ARROW INDICATES HOMERUN OF
CIRCUITS, 1,3,5 TO PANEL LA. MARKS ACROSS
RACEWAY INDICATE THE NUMBER OF PHASE
CONDUCTORS AND NEUTRAL IN RACEWAY.
GROUND CONDUCTORS ARE INDICATED BY
LONGER HASHMARKS. NO MARKS ACROSS
RACEWAY INDICATES 2#12 CONDUCTORS AND 1
#12 GROUND CONDUCTOR. CONDUCTOR SIZE #
12 UNLESS INDICATED OTHERWISE. MINIMUM
RACEWAY SIZE SHALL BE 3/4"
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR
ABOVE FINISHED CEILING
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
PLUG-IN BUSWAY, UNLESS INDICATED
OTHERWISE
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
LADDER TYPE CABLE TRAY (SIZE AS INDICATED
ON PLAN)
DUCTBANK, TEXT INDICATES QUANTITY AND
SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)
LIGHTNING PROTECTION
3/4" x 10'-0" COPPERCLAD GROUND ROD, 18" BFG
GROUND ROD TEST WELL
BARE COPPER GROUND CONDUCTOR, 1/0
UNLESS INDICATED OTHERWISE.
4/0 BARE COPPER GROUND CONDUCTOR
LIGHTNING PROTECTION SYSTEM AIR TERMINAL
LIGHTNING PROTECTION ROOF CONDUCTOR
ELECTRICAL CONNECTION
SITE
ELECTRICAL MANHOLE
ELECTRICAL HANDHOLE
PAD MOUNTED TRANSFORMER
POWER POLE
DOWN GUY AND ANCHOR (QUANTITY AS
INDICATED)
2W4"
WIRING DEVICES
SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE.
DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"
ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"
ABOVE FINISHED FLOOR OR ABOVE COUNTER
TOP/BACKSPLASH
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
18" ABOVE FINISHED FLOOR, UNLESS INDICATED
OTHERWISE
DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT
48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 18" ABOVE FINISHED FLOOR, UNLESS
INDICATED OTHERWISE
SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,
MOUNT 48" ABOVE FINISHED FLOOR OR ABOVE
COUNTER TOP/BACKSPLASH
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
SWITCHED DUPLEX GFI RECEPTACLE NEMA
5-20R, MOUNT 48" ABOVE FINISHED FLOOR OR
ABOVE COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX GFI RECEPTACLE, NEMA
5-20R, MOUNTED CONCEALED BEHIND ELECTRIC
WATER COOLER
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA
5-20R. PROVIDE FIRE RATED POKE THRU
DEVICES ON ALL FLOORS ABOVE GROUND
LEVEL.
SPECIAL RECEPTACLE, NEMA TYPE AS
INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,
UNLESS INDICATED OTHERWISE
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA
5-20R
RECEPTACLE WP = IN-USE WEATHER PROOF
SUBSCRIPTS TR = TAMPER RESISTANT
TV = TELEVISION, MOUNT AT 60" ABOVE
FINISHED FLOOR
AFCI = ARC FAULT CIRCUIT INTERRUPTER
FLOOR BOX SUITABLE FOR CONCRETE FLOOR
POUR; TWO COMPARTMENTS - POWER AND
TELECOMMUNICATIONS; FLUSH COVER/FLANGE
WITH HINGED ACCESS TO RECEPTACLES AND
JACKS RECESSED BELOW COVER IN FLOOR
BOX. PROVIDE 8" FIRE RATED POKE THRU
ABOVE GROUND FLOOR.
WALL SWITCH, AC TYPE, SPST, MOUNT 48"
ABOVE FINISHED FLOOR
WALL SWITCH, AC TYPE, DPDT, MOUNT 48"
ABOVE FINISHED FLOOR
3-WAY WALL SWITCH, MOUNT 48" ABOVE
FINISHED FLOOR
4-WAY WALL SWITCH,…