S02 - Attachment 17 - Section 07 72 00 - Roofing Accessories.docx

DOCX document 28 KB Posted

Attached to
Z2DA--VAMC Garland Roof Replacement 549-157R (VA-21-00007690)
Solicitation number
36C77621R0023_1
Issued by

About this file

This solicitation seeks a contractor to provide roof replacement and reinsulation services at two buildings located at the Veterans Affairs Medical Center in Garland, Texas. The contractor will be responsible for reroofing and reinsulating the built-up roofing system on the approximately 22,000 square foot Medical Office Building and the approximately 20,000 square foot warehouse using labor, materials, supervision and other resources. The work includes removal of existing roofing materials, insulation, flashing and accessories; installation of new insulation, membrane, flashing and accessories; and any other work required to provide a weathertight roof. The period of performance and response deadline are not specified. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files

File Type Posted
S02 - Attachment 11- Section 01 33 23 - Shop Drawings- Products-and Samples.docx DOCX document
S02 - Attachment 2 - Statement of Work - Garland Roof Replacement - Final (12-3-2020 YMR).docx DOCX document
S02 - Attachment 1 - Spec 001121 - RFP to DB (12-29-2020 YMR).doc DOC document
S02 - Attachment 14 - Section 01 32 16.16 - Network Analysis Schedules (Design-Build Only).docx DOCX document
S02 - Attachment 7- Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
S02 - Attachment 8- Past Performance Questionnaire.docx DOCX document
S02 - Attachment 6 - VHA Master Specifications.docx DOCX document
S02 - Attachment 12 - Section 01 35 26 - Safety Requirements.docx DOCX document
S02 - Attachment 13 - Section 01 57 19 - Temporary Evironmental Controls.doc DOC document
S02 - Attachment 10 - Section 01 42 19 - Reference Standards.docx DOCX document
S02 - 36C77621R0023_1.docx DOCX document
S02 - Attachment 9 - Release of Claims.docx DOCX document
S02 - Attachment 18 - Section 01 32 16 Project Schedules.doc DOC document
S02 - Attachment 15 - Quality Control Requirements Plan SCE 11-19-2018.docx DOCX document
S02 - Attachment 5 - Labor Standards Wage Determination - Dallas County TX.pdf PDF
S02 - Attachment 16- Section 07 51 00 - Built-Bituminous Roofing.docx DOCX document
S02 - Attachment 3 - Drawings.pdf PDF
S02 - Attachment 4 - Construction Wage Determination - Dallas County TX.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10-01-15

SECTION 07 72 00

ROOF ACCESSORIES

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies roof hatches; equipment supports; gravity ventilators; and metal grating roof walkway system.

1.2 RELATED WORK:

//A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.// B. Color and texture of finish: Section 09 06 00, SCHEDULE FOR FINISHES.

C. Sealant material and installation: Section 07 92 00, JOINT SEALANTS.

D. General insulation: Section 07 21 13, THERMAL INSULATION. Rigid insulations for roofing: Section 07 22 00, ROOF AND DECK INSULATION

1.3 QUALITY ASSURANCE:

A.Provide roof accessories that are the products of manufacturers regularly engaged in producing the kinds of products specified.
B.For each accessory type provide the same product made by the same manufacturer.
C.Assemble each accessory to the greatest extent possible before delivery to the site.

1.4 SUBMITTALS:

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

//B. Sustainable Design Submittals, as described below:

//1. Postconsumer and preconsumer recycled content as specified in PART 2 PRODUCTS.// //

C.Samples: Submit representative sample panel of color anodized aluminum not less than 101 x 101 mm (4 x 4 inches). For extrusions, submit width not less than section to be installed. Show coating with integral color and texture and include manufacturer's identifying label.
D.Shop Drawings: Each item specified showing design, details of construction, installation and fastenings.
E.Manufacturer's Literature and Data: Each item specified.
F.Certificates: Stating that aluminum has been given specified thickness of anodizing.

1.5 APPLICABLE PUBLICATIONS:

A.The publications listed below form a part of this specification to the extend referenced. The publications are referenced in the text by the basic designation only.
B.Federal Specifications (Fed. Spec.):
RR-G-1602DGrating, Metal, Other Than Bar Type (Floor, Except for Naval Vessels)
C.ASTM International (ASTM):
A653/A653M-10Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) By the Hot-Dip Process
B209-14Aluminum and Aluminum Alloy-Sheet and Plate
B209M-14Aluminum and Aluminum-Alloy Sheet and Plate (Metric)
B221-14Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes
B221M-13Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)
C726-12Mineral Wool Roof Insulation Board
C1289-14aFaced Rigid Cellular Polyisocyanurate Thermal Insulation Board
D1187/D1187M-97(R2011)Asphalt-Base Emulsions for Use as Protective Coatings for Metal
D.National Association of Architectural Metal Manufacturers (NAAMM):
AMP 500 SeriesMetal Finishes Manual
E.American Architectural Manufacturers Association (AAMA):
2603-13Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels
2605-13High Performance Organic Coatings on Architectural Extrusions and Panels.
611-14Anodized Architectural Aluminum
621-02High Performance Organic Coatings on Coil Coated Architectural Hot Dipped Galvanized (HDG) and Zinc-Aluminum Coated Steel Substrates
F.American Society of Civil Engineers (ASCE):
ASCE 7-10Minimum Design Loads for Buildings and Other Structures
G.U.S. National Archives and Records Administration (NARA):
29 CFR 1910.23Guarding Floor and Wall Openings and Holes

PART 2 - PRODUCTS

2.1 MATERIALS:

A.Aluminum, Extruded: ASTM B221M (B221).
B.Aluminum Sheet: ASTM B209M (B209).
C.Galvanized Sheet Steel: ASTM A653/A653M; G-90 coating.
D.Metal Grating for Roof Walkway: Fed. Spec. RR-G-1602.

//E. Recycled Content of Metal Products: Postconsumer recycled content plus one-half of preconsumer recycled content not less than // 30 // // // percent. // F. Asphalt Coating: ASTM D1187/D1187M, Type I, quick setting.

2.2 ROOF HATCH (SCUTTLE):

A. Performance Characteristics:

1.Cover to be reinforced to support a minimum live load of 195 kg per sq. m (40 lb. per sq. ft.) with a maximum deflection of 1/150th of the span or 97 kg per sq. m (20 lb. per sq. ft.) wind uplift.
2.Operation of the Cover: Smooth and easy with controlled operation throughout the entire arc of opening and closing.

3. Operation of the Cover: Not affected by temperature.

4. Entire Hatch: Weathertight with fully welded corner joints on cover and curb.

B.Shop fabricate from aluminum with mill finish.
C.Curb and Cover:
1.Exterior facing: Minimum 2.3 mm (0.09 inch) thick sheet aluminum with mill finish.
2.Interior facing: Minimum 1 mm (0.04 inch) thick sheet aluminum.
3.Minimum of 50 mm (2 inch) thick polyisocyanurate insulation (ASTM C1289) with a U-value = 0.47 W/m2 K (R-value = 12) between facings of cover and over exterior face of curb.
4.Form exterior curb facing with an integral 76 mm (3 inch) wide roof flange and cap flashing minimum 2.3 mm (0.09 inch) thick sheet aluminum.
5.Make curb // 305 mm (12 inches) // // // above finish roof surface.
6.Form cover to lap curb and cap flashing.
7.Size opening as shown on construction documents.

8. Finish: // //; color // //.

D.Hardware:
1.Provide spring snap latch with inside and outside operating handles and padlock hasp on inside. Provide two snap latches when hinge side is over 2100 mm (7 feet) long. Bolt hardware into heavy gauge channel reinforcement welded to the underside of the cover and concealed within the insulation space.
2.Provide heavy duty pintle hinges.
3.Provide automatic hold open and operating arm with enclosed torsion or compression spring lifting mechanism.

4. Latch Strike: Stamped component bolted or welded to the curb assembly.

5.Automatically lock in the open position at not less than 70 degrees.
6.Provide weatherstripping at cover closure.
7.Galvanize all hardware items.
E.Assembly:
1.Shop assemble roof scuttle.
2.Weld joints exposed to the weather and built into the roofing.
3.Finish weld smooth where exposed.

F. Safety Accessories:

1. Ladder Assist Post: Provide a telescoping tubular section that locks automatically when fully extended. Control upward and downward movement by a stainless steel spring balancing mechanism. Provide unit completely assembled with fasteners for securing to the ladder rungs in accordance with the manufacturer’s instructions.

2. Safety Railing: Provide a fixed, attached to the roof hatch railing assembly including rails, clamps, fasteners, safety barrier at railing opening, and accessories required for a complete installation; complying with 29 CFR 1910.23 requirements.

2.3 EQUIPMENT SUPPORTS:

A. Supported Load Capacity: // //.

B. Fabricate equipment supports from 1.3 mm (0.0516 inch) thick galvanized ASTM A653/A653M steel fabricate with welded corners and with seams joined by continuous water and air tight welds.

C. Equipment supports to be internally reinforced with angles 1.22 m (48 inches) on center.

D.Form exterior curb with integral base, // and deck closures for curbs installed on steel decking. //
E.Use galvanized steel liners for curbs having inside dimension over 305 mm (12 inches).

F. Internally insulate with 38 mm (1-1/2 inch) glass-fiber board insulation (ASTM C726).

G.Fabricate curb with a minimum height of 203 mm (8 inches) above roof surface.
H.Attach preservative treated wood nailers to top of curb. Provide 50 mm (2 inch) by 50 mm (2 inch) minimum nominal size on curb with openings and 50 mm (2 inch) thick, width of curb up to 305 mm (12 inches) on equipment support curbs.
H.Make size of supports suit size of equipment furnished, with height as shown on construction documents, but not less than 203 mm (8 inches) above roof surface.

I. Top of Equipment Supports: Level with pitch built into curb when deck slopes. Equip supports with water diverter or cricket on side that obstructs water flow.

J. Finish: // //; color // //.

2.4 LOW SILHOUETTE GRAVITY VENTILATORS

A. Fabricate base of 1 mm (0.04 inch) thick aluminum, and vent of 0.8 mm (0.032 inch) thick aluminum.

1. Height not to exceed 305 mm (12 inches) above top of roof curb.

2. Design ventilators to withstand 137 Km (85 miles) per hour wind velocity.

3. Provide ventilators with a removable 18 by 18 mesh by 0.28 mm (0.11 inch) diameter aluminum wire cloth insect screen.

//4. Provide security grille where indicated on construction documents. // B. Construct damper of the same material as the ventilator and design to completely close opening or remain wide open. Hold damper in closed position by a brass chain and catch. Extend chains 305 mm (12 inches) below and engage catch when damper is closed.

C. Finish: // //; color // //.

2.5 METAL GRATING ROOF WALKWAY SYSTEM:

A.Provide metal grating roof walkway system consisting of prefabricated pans, of 14 gauge, galvanized (G-90 Coating) steel grating with slip resistant surface.
B.Grating units to be in 610 mm (2 foot) widths and in 3048 to 3658 mm (10 to 12 foot long) sections as required.
C.Provide complete with support framing, brackets, connectors, nosings and other accessories as required for complete roof walkway system.

1. Include support stands at minimum 1524 mm (5 feet) on center to hold planks a minimum of 228 mm (9 inches) above roof surface.

2. Provide wind restraint attachment to roof structure of size and spacing required to meet wind uplift requirements.

D. Include step units, nosings framing and connectors to provide changes in elevation as required. Comply with ASCE 7 and 29 CFR 1910.23.

E. Equip walkways with safety railings where required by 29 CFR 1910.23.

F. Provide neoprene rubber pads having a shore A hardness of 80 to 90-Durometer under each support, or bearing surface.

G. Finish: // //; color // //.

2.6 FINISH:

A. In accordance with NAAMM AMP 500 Series.

//B. Aluminum, Mill Finish: AA-MIX, as fabricated.// //C. Aluminum, Clear Finish AAMA 611: AA-M12C22A41 medium matte, clear anodic coating, // Class I, Architectural, 0.018 mm (0.7 mils) thick (min.) //. // AA-M12C22A31 Class II, Architectural, 0.010 mm (0.4 mils) thick (min.). // // //D. Aluminum Colored Finish AAMA 611: AA-C22A42 (anodized or AA-M12C22A44 (electrolytically deposited metallic compound) medium matte, integrally colored coating, // Class 1, Architectural, 0.018 mm (0.7 mils) thick (min.)//. // AA-M12C22A32/A33 Class II, Architectural, 0.010 mm (0.4 mils) thick (min.). // Dyes will not be accepted.// //E. Baked-Enamel or Powder-Coat Finish: AAMA 2603 except with a minimum dry film thickness of 0.04 mm (1.5 mils). Comply with coating manufacturer’s written instructions for cleaning, conversion coating, and applying and baking finish. // //F. Fluoropolymer Finish: High performance organic coating. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturer’s written instructions.

//1. Two-Coat Fluoropolymer Finish: AAMA 2605. System consisting of primer and fluoropolymer color topcoat containing not less than 70 percent PVDF resin by weight. // //2. Two-Coat Fluoropolymer Finish: AAMA 621. System consisting of primer and fluoropolymer color topcoat containing not less than 70 percent PVDF resin by weight.// //

PART 3 - EXECUTION

3.1 INSTALLATION:

A.Install roof specialties where indicated on construction documents.
B.Secure with fasteners in accordance with manufacture's printed installation instructions and approved shop drawings unless shown otherwise.
C.Coordinate to install insulation where shown; see Section 07 21 13, THERMAL INSULATION and Section 07 22 00, ROOF AND DECK INSULATION.
D.Comply with section 07 92 00, JOINT SEALANTS to install sealants where required by manufactures installation instructions require sealant.
E.Coordinate with roofing work for installation of items in sequence to prevent water infiltration.
1.After completion of base flashing bend down cap flashing flange and secure to blocking with screws.
2.Install expansion joint cover with 6 mm (1/4 inch) wide space at end joints and tension bars at 610 mm (24 inches) on center.
3.Install cover plates with formed aluminum flashing concealed and centered on joint. Flashing to lap cover not less than 101 mm (4 inches).
F.Equipment Supports: Do not anchor to insulating concrete or metal deck. Anchor only to building structure as per manufacturers recommendations.

3.2 PROTECTION OF ALUMINUM:

A.Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with two (2) coats of asphalt coating (complete coverage), or by separating the contact surfaces with a preformed neoprene tape having pressure sensitive adhesive coating on side.
B.Paint aluminum in contact with wood, concrete and masonry, or other absorptive materials, that may become repeatedly wet, with two coats of asphalt coating.

3.3 ADJUSTING:

A. Adjust roof hatch hardware to operate freely and so that cover will operate without binding, close tightly at perimeter, and latch securely.

3.4 PROTECTION:

A. Protect roof accessories from damage during installation and after completion of the work from subsequent construction.

- - - E N D - - - 07 72 00 - 1