S02 - Attachment 02 - Drawings - EHRM Data Center - Dublin GA.pdf
PDF 20 MB Posted
- Attached to
- 36C77623B0062 - EHRM Infrastructure Data Center Upgrades - Dublin, GA -Solicitation Federal contract opportunity
- Solicitation number
- 36C77623B0062
About this file
This document provides details for a federal solicitation seeking infrastructure upgrades to the EHRM Data Center in Dublin, Georgia. The solicitation number is 36C77623B0062 and was issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation seeks vendor proposals for upgrades to the EHRM Data Center, as outlined in Attachment 02, which contains 20MB of technical drawings. Vendors should respond with proposals by the date listed on SAM.gov to be considered for an award, which is expected in early 2023 contingent upon federal budget appropriations. The opportunity is set aside for small businesses.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INFO MGMT
106B
INFO MGMT TEL SWITCH RM
INFO MGMT OFFICE
INFO MGMT OFFICE
INFO MGMT OFFICE
FACP
EXISTING CLEAN
AGENT HEAD
EXISTING CLEAN
AGENT HEAD
EXISTING CLEAN
AGENT HEAD
SPZ-1
NEW CLEAN
AGENT HEAD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:0
:5
P M
40-FP1
LEVEL 1 FLOOR PLAN - FIRE
PROTECTION
557-20-105
03/07/2023 SLC NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
1/4" = 1'-0" F2
FIRST LEVEL FLOOR PLAN - FIRE PROTECTION
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
C. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
D. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
GENERAL NOTES:
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
C. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
D. REFER TO ARCHITECTS PLANS FOR SMOKE BARRIER LOCATIONS.
E. MECHANICAL EQUIPMENT, ELECTRICAL EQUIPMENT AND COMPUTER ROOMS TO BE ORDINARY HAZARD
GROUP 1.
F. ALL SPRINKLER WORK SHALL COMPLY TO NFPA 13, NFPA 2001, NFPA 75 AND VA FIRE PROTECTION
REQUIREMENTS.
SHEET NOTES:
1. EXISTING CLEAN AGENT TANKS SHALL REMAIN IN PLACE.
2. EXISTING FIRE ALARM PANEL SHALL REMAIN.
3. REPLACE EXISTING QUICK RESPONSE SPRINKLER HEADS WITH STANDARD RESPONSE SPRINKLER HEADS.
4. EXISTING EMERGENCY POWER OFF (EPO) FOR MECHANICAL EQUIPMENT SHUTDOWN. EMERGENCY SHUT
OFF SHALL BE PUSHBUTTON TYPE WITH PROTECTIVE COVER.
5. EXISTING EMERGENCY POWER OFF (EPO) FOR ELECTRICAL SHUTDOWN. EMERGENCY SHUT OFF SHALL BE
PUSHBUTTON TYPE WITH PROTECTIVE COVER.
6. EXISTING ISOLATIONS VALVES FOR FM-200 SYSTEM SHALL REMAIN IN PLACE.
7. RELOCATE EXISTING EMERGENCY POWER OFF (EPO) FOR MECHANICAL EQUIPMENT SHUTDOWN.
EMERGENCY SHUT OFF SHALL BE PUSHBUTTON TYPE WITH PROTECTIVE COVER.
8. RELOCATE EXISTING EMERGENCY POWER OFF (EPO) FOR ELECTRICAL SHUTDOWN. EMERGENCY SHUT OFF
SHALL BE PUSHBUTTON TYPE WITH PROTECTIVE COVER.
9. CONTRACTOR SHALL VERIFY CYLINDER SIZE IS ADEQUATE TO SERVE DATA CENTER. VERIFY CLEAN AGENT HEADS AND PIPING BELOW RAISED FLOOR. PROVIDE CLEAN AGENT COVERAGE BELOW COMPUTER FLOOR IF
NO EXISTING COVERAGE IS PROVIDED.
GENERAL NOTES:
SPZ-1
NOTES:
SPRINKLER PROTECTION AREA LIMITATIONS:
SPRINKLER ZONE 1 - ORDINARY HAZARD GROUP 1 - 1462 SQ. FT.
03/07/2023
Revisions: Date:
CONTRACTOR REQUIREMENTS FOR THE
DEMOLITION OF, OR ADDITION TO, ANY PORTION
OF AIR, OR HYDRONIC SYSTEMS.
COVER SHEET NOTES:
THE FOLLOWING SHALL APPLY TO ALL MECHANICAL SYSTEMS AFFECTED BY CONSTRUCTION ACTIVITIES. SYSTEMS INCLUDED BUT ARE NOT LIMITED TO HVAC, EXHAUST, EQUIPMENT, DUCTWORK, DUCTWORK ACCESSORIES, HYDRONICS, COILS, FILTERS, TEMPERATURE CONTROLS, LIFE SAFETY
CONTROLS AND PRESSURIZATION CONTROLS.
1. AIR QUALITY, QUANTITY AND PRESSURE RELATIONSHIPS SHALL COMPLY WITH THE LATEST, ANSI/ASHRAE/ASHE STANDARD 170
REQUIREMENTS.
2. COMPLY WITH THE FACILITY'S INFECTIOUS CONTROL RISK ASSESSMENT (ICRA) REQUIREMENTS.
3. MAINTAIN EXISTING AIR QUALITY REQUIREMENTS, AIR PRESSURIZATION AND OTHER UTILITY REQUIREMENTS FOR OCCUPIED AREAS
DURING ANY RENOVATION OR CONSTRUCTION.
4. DETERMINE AND VERIFY THE AREAS SERVED BY THE AFFECTED SYSTEMS.
5. TAKE AIR AND OR/ WATER BALANCE READINGS OF THE SYSTEMS BEING AFFECTED.
6. IF THERE ARE SPACES BEING SERVED OUTSIDE OF THE DEMOLITION OR ADDITION AREA, THE FOLLOWING PROCEDURES MUST BE TAKEN:
a. TAKE AIR AND/OR WATER BALANCE READINGS AS NEEDED TO QUANTIFY THE AIR AND/OR WATER FLOWS DELIVERED TO THE
SYSTEMS OUTSIDE THE AFFECTED AREA.
b. DURING DEMOLITION, TAKE ALL NECESSARY MEASURES TO MAINTAIN THE CORRECT AIR AND/OR WATER FLOWS TO THE SYSTEMS
THAT ARE REMAINING.
c. AFTER THE COMPLETION OF DEMOLITION, VERIFY THAT AIR AND/OR WATER FLOWS ARE CORRECT.
d. AFTER COMPLETING ANY ADDITIONS TO THE SYSTEM, VERIFY THAT AIR AND/OR WATER FLOWS ARE CORRECT.
7. THE CONTRACTOR IS TO PROVIDE TEMPORARY AIR/AND OR WATER SYSTEMS AS NEEDED TO MAINTAIN PROPER TEMPERATURE AND
PRESSURE RELATIONSHIPS OF SPACES REQUIRED TO BE OCCUPIED DURING CONSTRUCTION.
8. ALL TEMPORARY AIR SUPPLY SYSTEMS MUST UTILIZE FINAL FILTERS THAT ARE A MINIMUM OF 90% EFFICIENT (MERV 14). FINAL FILTERS
MUST BE DOWNSTREAM OF ALL AIR SUPPLY COMPONENTS.
ABBREVIATION
GENERAL ABBREVIATIONS
DESCRIPTION ABBREVIATION DESCRIPTION
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
AD ACCESS DOOR/PANEL
AFF ABOVE FINISHED FLOOR
AMB AMBIENT
DIA DIAMETER
DN DOWN
E EXISTING
EC ELECTRICAL CONTRACTOR
EFF EFFICIENCY
GC GENERAL CONTRACTOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
L LENGTH
LF LINEAR FEET
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MFR MANUFACTURER
MIN MINIMUM
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PC PLUMBING CONTRACTOR
PSIG POUNDS PER SQUARE INCH GAUGE
RPM REVOLUTIONS PER MINUTE
SHT SHEET
TOB TOP OF BEAM
GPM GALLONS PER MINUTE
TOS TOP OF STEEL
BOB BOTTOM OF BEAM
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
UNION
Y STRAINER WITH BLOWDOWN
ELBOW UP
ELBOW DOWN
TEE UP
PIPING
- SOLID LINE INDICATES SYSTEM SUPPLY
-- DASHED LINE INDICATES SYSTEM RETURN
NUMBER INDICATES NOMINAL DIAMETER IN INCHES,
LETTER(S) INDICATES SYSTEM.
REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
GENERAL MECHANICAL SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
# SHEET NOTE
DENOTES SPECIFIC REQUIREMENT FOR THE SHEET ON WHICH THE NOTE APPEARS
AND IS USED TO DESCRIBE WORK THAT IS TOO LENGTHY TO PLACE ON PLAN.
DIAMETER
DENOTES CONNECTION OF NEW WORK TO
EXISTING SYSTEM
PROTECT EXISTING SYSTEM FROM ENTRANCE OF FOREIGN DEBRIS DURING WORK.
ARROW INDICATES DOWNWARD PIPE SLOPE
#/# INDICATES SLOPE IN INCHES PER FOOT
WHERE PIPING IS NOT MARKED, REFER TO SPECIFICATIONS FOR REQUIREMENTS
ARROW INDICATES DIRECTION OF FLOW IN PIPING
ISOLATION VALVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CHECK VALVE
ARROW INDICATES DIRECTION OF NORMAL FLOW
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
PIPE IN SLEEVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CIRCUIT SETTER, AUTOFLOW, ETC.
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
PRESSURE GAUGE
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIESTHERMOMETER - HORIZONTAL PIPE
TEE DOWN
TEE HORIZONTAL
PIPE REDUCER
INDICATES POINT WHERE PIPING CHANGES FROM ONE SIZE TO ANOTHER.
SMALL POINT OF ARROW INDICATES SMALLER SIZE SIDE OF TRANSITION.
REQUIRED SERVICE CLEARANCE FOR EQUIPMENT
CONTINUATION
FIRST SYMBOL APPLIES TO ROUND DUCT AND PIPING.
SECOND SYMBOL APPLIES TO RECTANGULAR AND OVAL DUCT.
AIR VENT
AUTOMATIC FLOW CONTROL VALVE
# INDICATES FLOW TO BE BALANCED IN GPM
BACKFLOW PREVENTER
CALIBRATED BALANCING VALVE
VALVE - THROTTLING SERVICE
VALVE - SHUTOFF SERVICE
P/T PORT
PIPE CAP
PIPE CONTINUATION
PRESSURE GAUGE STEAM REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
PRESSURE REDUCING VALVE
PUMP
RELIEF VALVE
S SENSOR
SUCTION DIFFUSER
THERMOMETER - VERTICAL PIPE REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
VACUUM BREAKER
Y STRAINER
STEAM TRAP
CC CONTROLS CONTRACTOR
RECTANGULAR DUCTWORK
W = DIMENSION IN VIEW (INCHES)
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
ROUND DUCTWORK
D = DUCT DIAMETER
TURNING VANES
FLEXIBLE PIPING
WxH
D"Ø
HVAC SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
W/H
FLAT OVAL DUCTWORK
W = DIMENSION IN VIEW (INCHES)
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
DUCT CROSS SECTION - SUPPLY
DUCT CROSS SECTION - RETURN
DUCT CROSS SECTION - EXHAUST
CROSS SECTION INDICATES DUCT EXTENDING PERPENDICULAR TO THE PAGE. IN
PLAN VIEW THIS INDICATES A DUCT RISE OR DROP TO ANOTHER LEVEL. SOLID
INTERIOR LINE INDICATES EXTENSION UP. DASHED INTERIOR LINE INDICATES
EXTENSION DOWN.
MANUAL BALANCE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE MANUAL BALANCE DAMPERS IN AN
ACCESSIBLE LOCATION AND AS CLOSE TO THE MAIN DUCT AS POSSIBLE.
CONTROL DAMPER
FIRE/SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
DIFFUSER
REFER TO SPECIFICATIONS FOR TYPE.
FLEXIBLE DUCT
REFER TO SPECIFICATIONS FOR TYPE. REFER TO DETAILS FOR INSTALLATION
REQUIREMENTS. MAXIMUM LENGTH SHALL BE 48 INCHES UNLESS NOTED OTHERWISE
ON THE PLANS OR IN THE SPECIFICATIONS.
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - NO COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - HOT WATER COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - ELECTRIC COIL
VB-#
### CFM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
### = AIRFLOW IN CFM
REFER TO VARIABLE VOLUME BOX SCHEDULE FOR TYPES AND SIZING. AIRFLOW
LISTED IS NOMINAL DESIGN CFM AND GPM. FINAL VALUES ARE TO BE DETERMINED BY
TESTING AND BALANCING CONTRACTOR AND PROGRAMMED BY CONTROLS
CONTRACTOR.
VB-#
#.# GPM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
#.# = WATER FLOW RATE IN GPM
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - DUAL DUCT
D#
DIFFUSER TAG
D = TYPE # = TYPE NUMBER
### = AIRFLOW IN CFM
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO
AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE
D1 FOR SUPPLY OR G1 FOR RETURN/EXHAUST.
FLOW ARROW ARROW INDICATES DIRECTION OF AIRFLOW FROM DIFFUSERS WITH ADJUSTABLE
THROWS.
DIFFUSER BLANK OFF SHADED AREA INDICATES QUADRANT OF DIFFUSER TO BE PROVIDED WITH BLANK OFF
PANEL.
RETURN GRILLE
EXHAUST GRILLE
WALL REGISTER / GRILLE
DUCT MOUNTED REGISTER / GRILLE
LINEAR SLOT
REFER TO VARIABLE VOLUME BOX SCHEDULE FOR TYPES AND SIZING. AIRFLOW
LISTED IS NOMINAL DESIGN CFM AND GPM. FINAL VALUES ARE TO BE DETERMINED BY
TESTING AND BALANCING CONTRACTOR AND PROGRAMMED BY CONTROLS
CONTRACTOR.
SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
ABBREVIATION
HVAC ABBREVIATIONS
DESCRIPTION
AIR BLENDERAB
AIR CONDITIONING UNIT (SPLIT SYSTEM INDOOR UNIT)AC
AIR HANDLING UNITAHU
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
BOILER FEED UNITBFU
BOILERBLR
CONSTANT AIR VOLUME BOXCAV
COOLING COILCC
CONDENSATE DRAINCD
CUBIC FEET PER MINUTECFM
CHILLERCH
CONDENSATE PUMPCP
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
COOLING TOWERCT
CONDENSING UNITCU
CABINET UNIT HEATERCUH
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
DIFFUSERD
DUAL DUCTDD
DIRECT EXPANSIONDX
EXHAUST AIREA
ENTERING AIR TEMPERATUREEAT
EXHAUST FANEF
EFFICIENCYEFF
ENERGY RECOVERY COILERC
ENERGY RECOVERY WHEELERW
EXPANSION TANKET
ENTERING WATER TEMPERATUREEWT
FILTER BANK (CONSISTING OF ONE OR MORE FILTERS)FB
FAN COIL UNITFCU
FLOW MEASURING STATIONFMS
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
FUEL OIL VENTFOV
FIRE DAMPERFRD
FIRE SMOKE DAMPERFSD
FINNED TUBE RADIATORFTR
GRILLEG
GLYCOL CHILLED WATER RETURNGCWR
GLYCOL CHILLED WATER SUPPLYGCWS
GRAVITY EXHAUSTGE
GLYCOL HEATING HOT WATER RETURNGHWR
GLYCOL HEATING HOT WATER SUPPLYGHWS
GRAVITY INTAKEGI
HEATING COILHC
PRESSURE/TEMPERATURE TEST PORT
TEMPERATURE CONTROL SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
WALL MOUNTED CONTROL DEVICE
# INDICATES TYPE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON MONOXIDE, ETC.)
OCCUPANCY SENSOR
REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. WHEN SENSOR IS
NOT SHOWN ON ELECTRICAL DRAWINGS IT SHALL BE PROVIDED AND INSTALLED BY
THE TEMPERATURE CONTROLS CONTRACTOR.
DUCT, PIPE, OR CEILING MOUNTED CONTROL
SENSOR
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON DIOXIDE, ETC.)
CONTROL VALVE (3-WAY)
CONTROL VALVE (2-WAY)
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
F/S FLOW MEASURING STATION REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
FIRE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
CD
FD
SD
FS
DAMPER SHALL BE SAME SIZE AS DUCT UNLESS NOTED OTHERWISE. REFER TO
SEQUENCES, SCHEMATICS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
FLOW SWITCHF
ABBREVIATION DESCRIPTION
HORSEPOWERHP
HIGH PRESSURE STEAM CONDENSATEHPC
HIGH PRESSURE STEAM SUPPLY (86 PSIG AND ABOVE)HPS
HEAT RECOVERY CHILLERHRC
HUMIDIFIERHUM
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
LOW PRESSURE STEAM CONDENSATELPC
LOW PRESSURE STEAM SUPPLY (0-12 PSIG)LPS
LOUVERLV
LEAVING WATER TEMPERATURELWT
BTU (1000'S)MBH
MANUAL DAMPERMD
MOTOR OPERATED DAMPERMOD
MEDIUM PRESSURE STEAM CONDENSATEMPC
MEDIUM PRESSURE STEAM SUPPLY (13-85 PSIG)MPS
NORMALLY CLOSED, NOISE CRITERIANC
NORMALLY OPEN, NUMBERNO
OUTDOOR AIROA
PUMPP
PUMPED CONDENSATEPC
PRESSURE REDUCING VALVEPRV
PUMPED STEAM CONDENSATEPSC
REGISTERR
RETURN AIRRA
RELIEF AIRREA
REFRIGERANT DX LIQUIDREFL
REFRIGERANT DX SUCTION GASREFS
RETURN FANRF
RELATIVE HUMIDITYRH
ROOF TOP UNITRTU
SUPPLY AIRSA
SMOKE DAMPERSD
SUPPLY FANSF
STATIC PRESSURESP
STEAMSTM
TEMPERATURETEMP
TRANSFERTR
UNIT HEATERUH
VARIABLE AIR VOLUME BOXVAV
VENT THROUGH ROOFVTR
WET BULB TEMPERATUREWB
WATER COLUMNWC
WATER PRESSURE DROPWPD
WATER SOURCE HEAT PUMP RETURNWSHPR
WATER SOURCE HEAT PUMP SUPPLYWSHPS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTSNOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
MECHANICAL GENERAL NOTES:
A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING, AND TEMPERATURE CONTROLS WORK. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. WHERE A DISCREPANCY EXISTS BETWEEN THESE PLANS AND THE PROJECT SPECIFICATIONS, THE
SPECIFICATION REQUIREMENTS SHALL TAKE PRECEDENCE OVER THE DRAWINGS.
B. VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL. BE ADVISED THAT LOCATIONS SHOWN ARE APPROXIMATE. AN ATTEMPT HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. CONTRACTOR SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL COMPONENTS NEED TO BE REMOVED IN THE DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS. IF DEVIATION BETWEEN EXISTING CONDITIONS AND NEW WORK IS FOUND, CONTRACTOR SHALL NOTIFY
ENGINEER.
C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. PLAN TO COMPLETE SHUTDOWNS DURING OFF HOURS TO MINIMIZE IMPACT TO THE OWNER. COORDINATE SHUTDOWNS WITH THE COR A MINIMUM OF 14 DAYS PRIOR TO WORK.
PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING EQUIPMENT. TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS ARE OPERATIONAL AND HAVE PASSED ALL REQUIRED TESTING.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND
REFINISHING SHALL MATCH THE EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE.
E. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS AS "TO BE RETAINED, RELOCATED", ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW CONSTRUCTION AND/OR
WITH PROPOSED USAGE OF SPACE BY OWNER AS FOLLOWS:
a. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE
MAIN WITH MATERIAL TO MATCH EXISTING.
b. REMOVE ALL FIXTURES, CARRIERS, SUPPLY AND WASTE AND VENT PIPING, STEAM, HEATING HOT WATER, HVAC SUPPLY, RETURN AND EXHAUST AS NOTED. CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE MAIN. SUPPLY AND RETURN MAINS ON PIPING SYSTEMS
CONVEYING WATER OR GASES SHALL BE VALVED AND CAPPED
c. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE ACCOMPLISHED IN THE
REMODELED AREA.
d. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH EXISTING.
e. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED PIPING OR DUCTWORK SHALL BE PATCHED
TO MATCH EXISTING CONSTRUCTION.
f. RE-SUPPORT ANY PIPING AND DUCTWORK THAT WAS SUPPORTED FROM BUILDING ELEMENTS REMOVED AS PART OF THE WORK.
g. MAINTAIN CONTROL WIRING OR PNEUMATIC TUBING REQUIRED FOR THE CONTINUED PROPER OPERATION OF THE BUILDING
AUTOMATION SYSTEM.
F. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO THE COR FOR FIRST RIGHT OF SALVAGE. IF COR REFUSES SALVAGE
ITEMS, REMOVING CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL.
G. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH EXTENT OF WORK INCLUDING BUT NOT
LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING
REMOVED AND/OR REPLACED, ETC.
H. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS, VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS, DRAINS, AND DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING
SYSTEM.
I. PERFORM AIR AND FLUID BALANCE PRE-TEST ON ALL DISTRIBUTION EQUIPMENT AND ALL AIR OUTLETS IN THE AREA PRIOR TO COMMENCING
WORK. SUBMIT PRE-TEST INFORMATION TO ENGINEER/COR.
J. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS REQUIRED AND ACTIVITY.
INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE REMOVAL OF ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC. INSTALL IN A LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT REQUIRED.
WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A FIRE AND/OR SMOKE RATING, ACCESS DOOR SHALL
MAINTAIN THE REQUIRED RATING.
K. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) WITH NON-COMBUSTIBLE MATERIAL. SEAL PENETRATIONS INTO ROOMS THAT REQUIRE PRESSURE CONTROL OR SOUND ISOLATION. WITH NON-COMBUSTIBLE MATERIAL AND CAULK.
L. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER, DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR DRAIN PIPING AS REQUIRED BY THE
SPECIFICATIONS.
M. LOCATE PIPING AND DUCTWORK IN EXTERIOR BUILDING WALLS ON THE WARM SIDE OF THE BUILDING AND VAPOR BARRIER. COORDINATE INSTALLATION OF BUILDING INSULATION TO RUN CONTINUOUS BETWEEN PIPING AND BUILDING WALL.
N. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. ROUTE DUCT MAINS TIGHT TO STRUCTURE UNLESS NOTED OTHERWISE. HOLD PIPING TIGHT TO BOTTOM OF STRUCTURAL MEMBERS OR RUN THROUGH JOIST WEBS IF POSSIBLE. DO NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER PIPING, DUCTWORK, AND/OR ELECTRICAL CONDUITS. DO NOT SUPPORT FROM WOOD TONGUE AND GROOVE ROOF DECK. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS. ALL COMPONENTS REQUIRING MAINTENANCE SHALL BE SUPPORTED IN SUCH A MANNER AS TO BE READILY ACCESSIBLE WITHOUT REMOVAL OF THE CEILING SYSTEM AND TO ALLOW FOR REMOVAL FROM THE SYSTEM WHEN SUCH REMOVAL IS REQUIRED FOR
MAINTENANCE.
O. PROVIDE CONSTRUCTION FILTERS ON AIR MOVING EQUIPMENT SERVING THE CONSTRUCTION AREA AS WELL AS ALL RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION
FILTERS AND PROVIDE NEW FILTERS FOR ALL AIR MOVING EQUIPMENT.
P. PROTECT ALL DUCTWORK AND PIPING DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. AT A MINIMUM, DUCTWORK AND PIPING ENDS SHALL BE COVERED AND SEALED TO PREVENT THE COLLECTION OF DUST AND DEBRIS. CLEAN ALL INTERIOR
SURFACES PRIOR TO INSTALLATION AND PROTECT ONCE INSTALLED.
Q. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS PROVIDED AS A PART OF THE WORK AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED. ON EXISTING EQUIPMENT, COORDINATE WORK WITH COR.
R. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK
INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
S. REFER TO SCHEDULES FOR SIZES OF FINAL RUNOUTS TO EQUIPMENT, FIXTURES, DIFFUSERS, GRILLES, AND TERMINAL DEVICES. FINAL RUNOUT SIZES LISTED SHALL BE USED TO WITHIN 10 EQUIVALENT DIAMETERS OF FINAL CONNECTION POINT. FINAL PIPING CONNECTION TO EQUIPMENT SHALL MATCH EQUIPMENT CONNECTION SIZE, PROVIDE TRANSITIONS AS REQUIRED. REFER TO DETAILS, DIAGRAMS AND SCHEMATICS FOR
ADDITIONAL FINAL CONNECTION REQUIREMENTS.
T. FOR DUCTWORK PENETRATING A ONE HOUR FIRE RATED WALL WHERE A FIRE DAMPER IS NOT SHOWN, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. THE SYSTEM SHALL BE FIRE TESTED PER ASTM E119 AND COMPLY WITH EXCEPTION 1 OF 2018 IBC PART 717.5.2. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO A ONE HOUR FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS.
REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS. ALL DUCTWORK PENETRATIONS SHALL BE INSPECTED BY AN APPROVED THIRD PARTY INSPECTION AGENCY IN ACCORDANCE WITH ASTM E2174. THE INSPECTION AGENCY SHALL BE PROCURED BY THE CONTRACTOR. DOCUMENTATION OF APPROVED INSPECTION SHALL BE INCLUDED WITH PROJECT CLOSEOUT
DOCUMENTATION.
U. FIRE ALARM CONTRACTOR SHALL PROVIDE A DUCT SMOKE DETECTOR FOR EACH SMOKE OR FIRE/SMOKE DAMPER AS REQUIRED BY CODE.
MECHANICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF EACH DUCT SMOKE DETECTOR AND SHALL INSTALL THEM IN THE DUCT.
V. FOR ALL PIPING, CONDUIT, AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS. REFER TO ARCHITECTURAL FOR
FIRE RATED WALL LOCATIONS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:1
:0
P M
40-M1
MECHANICAL SYMBOLS AND
ABBREVIATIONS
557-20-105
03/07/2023 JMM NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
(E) LIEBERT 2 CU
(E) LIEBERT 2
(E) LIEBERT 3
(E) LIEBERT 1 CU (E)LIEBERT 1
(E) SSCU
(E) SSCU
(E) SSCU
(E)DCW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:1
:0
P M
40-M2
LEVEL 1 FLOOR PLAN -
MECHANICAL - DEMOLITION
557-20-105
03/07/2023 JMM NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
C. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
D. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
GENERAL NOTES:
1/4" = 1'-0" F1
FIRST LEVEL FLOOR PLAN - MECHANICAL - DEMOLITION
SHEET NOTES:SHEET NOTES:
1. ALL ABANDONED DUCTWORK, PIPING AND CONTROLS WIRING ABOVE THE CEILING IN INDICATED AREA SHALL
BE REMOVED.
2. DEMOLISH WATER HEATER AND ALL ASSOCIATED WATER PIPING AND MIXING VALVE.
(E) RTU-1
(E) RTU-2
LIEBERT 3 CU
(E)EF
(E)EF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:1
:0
P M
40-M3
LEVEL 2 FLOOR PLAN -
MECHANICAL - DEMOLITION
557-20-105
03/07/2023 JMM NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
1/4" = 1'-0" F1
ROOF PLAN - MECHANICAL - DEMOLITION
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
C. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
D. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
GENERAL NOTES:
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
C. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
D. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
GENERAL NOTES:
SHEET NOTES:SHEET NOTES:
1. REMOVE CONDENSING UNIT AND PIPING. PATCH ROOF AS REQUIRED.
INFO MGMT
106B
INFO MGMT TEL SWITCH RM
INFO MGMT OFFICE
INFO MGMT OFFICE
INFO MGMT OFFICE
CRAH-2CRAH-1
CRCU-3
(E) SSCU
(E) SSCU
(E) SSCU
CRAH-3 CRAH-4
INFO MGMT COMP RM
40x30 RA x2
R
A x2
R
A x2
R
A
36x20 RA
40x30 RA
12x12 RA
1 1/4" PC
1 1/4" PC
1 1/4" PC
CRCU-2
CRCU-4CRCU-1
1 1/4" PC 36x20 RA
CDCD CDCD
CDCD CDCD
5 5
(E)DCW
1/2" DCW
1/2" DCW
1/2" DCW
7 7
1 1/4" PC
1 1/2" PC
1 1/4" PC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:1
:0
P M
40-M4
LEVEL 1 FLOOR PLAN -
MECHANICAL
557-20-105
03/07/2023 JMM NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
1/4" = 1'-0" F1
FIRST LEVEL FLOOR PLAN - MECHANICAL
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
C. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
D. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
SHEET NOTES:
GENERAL NOTES:
A. COVER SHEET GENERAL NOTES APPLY TO ALL SHEETS.
B. ON DEMOLITION PLANS; EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HATCHED AND/OR DASHED, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER
PLANS, NEW MECHANICAL SYSTEMS ARE INDICATED WITH HEAVY LINE WEIGHTS.
C. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL
PIPING, EQUIPMENT AND DUCTWORK INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
D. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR FOR THE MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO
PERFORM THIS WORK.
E. FLEXIBLE DUCTWORK SHALL NOT BE USED TO CONNECT TO DIFFUSERS.
SHEET NOTES:
1. PROVIDE 1/2" DOMESTIC COLD WATER FROM NEAREST DOMESTIC WATER MAIN.
2. ROUTE RETURN DUCTWORK OVER RACK EXHAUST CHIMNEYS.
3. REFRIGERANT PIPING SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS. REFRIGERANT PIPING SHOWN TO INDICATED PIPE ROUTING.
4. PIPE CONDENSATE TO STORM DRAIN. PROVIDE AIR GAP.
5. MOTORIZED ISOLATION DAMPER. INTERLOCK OPERATION WITH OPERATION OF CRAH.
6. SET CONSENDING UNIT ON EXISTING CONCRETE PAD.
7. CONDENSING UNITS SHALL BE SET ON NEW CONCRETE PAD.
8. 4 FOOT LONG, 18 INCH HIGH EQUIPEMNT RAIL. REFRIFERANT PIPING SHALL BE ANCHORED TO EQUIPMENT
RAIL. TYPICAL FOR EACH PIPING SUPPORT.
GENERAL NOTES:
REMARKS:
1. PERFORMANCE BASED ON CONDITIONS INDICATED IN THIS SCHEDULE.
2. PROVIDE CURB RAILS AND ROOF SUPPORTS FOR OUTDOOR UNIT.
3. PROVIDE THE FOLLOWING ACCESSORIES: DISCONNECT, HAIL GUARDS, WIND BAFFLES.
4. EQUIPMENT SHORT CIRCUIT CURRENT RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SHORT CIRCUIT CURRENT. REVIEW SHORT CIRCUIT CURRENT RATING
WITH ELECTRICAL CONTRACTOR PRIOR TO ORDERING EQUIPMENT.
COMPUTER ROOM AIR:
• CONSISTS OF FLOOR MOUNTED BLOWER EVAPORATOR UNITS WITH LOCAL MONITORING PANEL, GRADE MOUNTED
CONDENSING UNITS, AND MANUFACTURER CONDITIONING SYSTEMS, AND SUPPLIED TEMPERATURE CONTROLLER.
• ALL FOUR CRAC UNITS SHALL BE INTERLOCKED WITH EMERGENCY POWER OFF SWITCHES. ALL FOUR CRAC UNITS SHALL
BE INTERLOCKED WITH CLEAN AGENT SYSTEM TO SHUT DOWN CRAC UNIT SYSTEM UPON ACTIVATION OF CLEAN AGENT
SYSTEM.
• INDOOR EVAPORATOR LOCAL MONITORING PANEL SHALL ACCESS THE FOLLOWING:
1. AUTOMATIC RESTART WITH PROGRAMMABLE DELAY
2. SENSOR CALIBRATION
3. SEQUENTIAL LOAD ACTIVATION
4. CURRENT TEMPERATURE SET POINT AND LOCATION OF SET POINT
5. CURRENT SUPPLY AND RETURN TEMPERATURE AND HUMIDITY
6. UNIT DIAGNOSTICS
7. ALARM HISTORY
8. RUNTIME LOG
9. AUDIBLE/VISUAL ALARM
• CYCLE CONDENSING UNITS AND INDOOR UNITS IN UNISON TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 75° F (ADJUSTABLE) AND RELATIVE HUMIDITY SETPOINT OF 30-60% (ADJUSTABLE). MONITOR ROOM TEMPERATURE, EQUIPMENT STATUS AND CONDENSATE ALARM OUTPUTS FROM EQUIPMENT SUPPLIED CONTROLS THROUGH DDC. SEND ALARM TO THE OPERATOR INTERFACE IF THE SPACE TEMPERATURE EXCEEDS 80° F (ADJUSTABLE) OR SPACE RELATIVE HUMIDITY IS BELOW 20% (ADJUSTABLE) OR ABOVE 70%. (ADJUSTABLE). INTEGRATE ALL MONITORED PARAMETERS INTO EXISTING BMS.
1. NORMAL OPERATION MODE:
A. ALL FOUR UNITS OPERATING AT PART LOAD TO PROVIDE 18,000 CFM OR 4,500 CFM EACH.
2. MAINTENANCE/REPAIR OPERATIONS MODE:
A. THREE UNITS OPERATING AT 6,000 CFM EACH TO PROVIDE 18,000 CFM.
• ALL UNITS SHALL BE CAPABLE OF BEING ISOLATED FOR MAINTENANCE PURPOSES WHILE NOT IMPACTING DATA CENTER
COOLING CAPACITY.
1. UNIT OPERATION SHALL BE INTERLOCKED WITH AN ISOLATION DAMPER LOCATED IN THE RETURN DUCT SERVING EACH
UNIT TO PREVENT RETURN AIR FROM CIRCULATING THROUGH A CRAC UNIT WHILE DOWN FOR MAINTENANCE.
• PROVIDE TEMPERATURE AND HUMIDITY SENSORS IN THE FOLLOWING LOCATIONS FOR IT EQUIPMENT CABINETS.
1. MINIMUM 2 SENSORS PER MONITORED CABINET.
2. SENSORS SHALL BE LOCATED IN CABINETS AT THE ENDS OF CONTIGUOUS ROWS, AND IN EVERY THIRD CABINET IN THE
MIDDLE OF A CONTIGUOUS ROW.
3. TEMPERATURE SENSORS SHALL BE PROVIDED IN THE FRONT MIDDLE AND REAR TOP OF MONITORED CABINETS.
A. FRONT MIDDLE (FM): CENTERED HORIZONTALLY, INSIDE THE FRONT DOOR, 4 FT +/-6 IN. FROM THE FINISHED FLOOR
SURFACE.
B. REAR TOP (RT): CENTERED HORIZONTALLY, INSIDE THE REAR DOOR, NO MORE THAN 1 FT FROM THE TOP OF THE
CABINET.
4. HUMIDITY SENSORS SHALL BE PROVIDED IN THE FRONT MIDDLE OF MONITORED CABINETS.
A. FRONT MIDDLE (FM): CENTERED HORIZONTALLY, INSIDE THE FRONT DOOR, 4 FT +/-6 IN. FROM THE FINISHED FLOOR
SURFACE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:1
:0
P M
40-M5
MECHANICAL SCHEDULES,
DETAILS AND CONTROLS
557-20-105
03/07/2023 JMM NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:1
:0
P M
40-M5
MECHANICAL SCHEDULES,
DETAILS AND CONTROLS
557-20-105
03/07/2023 JMM NLC
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
COMPUTER ROOM AIR CONDITIONER SCHEDULE
MARK SERVES
NOMINAL
CAPACITY
[TONS]
TOTAL
COOLING
CAPACITY
[MBH]
SENSIBLE
COOLING
CAPACITY
[MBH]
CONDENSATE
DRAIN SIZE
INDOOR UNIT OUTDOOR UNIT ELECTRICAL DATA
MANUFACTURER REMARKS
DIMENSIONS [IN] EAT
(DB / WB)
[°F]
AIRFLOW
[CFM]
E.S.P.
[IN W.C.] MODEL
DIMENSIONS [IN] SUMMER
AMBIENT AIR
[°F]
WINTER AMBIENT
AIR
[°F]
OPERATING
WEIGHT
[LBS] MODEL FLA VOLTAGE PHASE MCA MOCP DISCONNECT BYLENGTH WIDTH HEIGHT LENGTH WIDTH HEIGHT CRAH-1 INFO MGMT COMP RM 12 139 136 1 1/4" 72" 35" 76" 85/65 6200 0.5 DS042ADC1E1 1470 - 78.2 208 V 3 95.7 110 ELECTRICAL CONTRACTOR LIEBERT 1, 4
CRAH-2 INFO MGMT COMP RM 12 139 136 1 1/4" 72" 35" 76" 85/65 6200 0.5 DS042ADC1E1 1470 - 78.2 208 V 3 95.7 110 ELECTRICAL CONTRACTOR LIEBERT 1, 4
CRAH-3 INFO MGMT COMP RM 12 139 136 1 1/4" 72" 35" 76" 85/65 6200 0.5 DS042ADC1E1 1470 - 78.2 208 V 3 95.7 110 ELECTRICAL CONTRACTOR LIEBERT 1, 4
CRAH-4 INFO MGMT COMP RM 12 139 136 1 1/4" 72" 35" 76" 85/65 6200 0.5 DS042ADC1E1 1470 - 78.2 208 V 3 95.7 110 ELECTRICAL CONTRACTOR LIEBERT 1, 4
CRCU-1 CRAH-4 - - - 0" - - - - 124" 54" 36" 105 15 602 MCL110E8 11.4 208 V 3 12.8 15 ELECTRICAL CONTRACTOR LIEBERT 1, 2, 3, 4
CRCU-2 CRAH-1 - - - 0" - - - - 124" 54" 36" 105 15 602 MCL110E8 11.4 208 V 3 12.8 15 ELECTRICAL CONTRACTOR LIEBERT 1, 2, 3, 4
CRCU-3 CRAH-2 - - - 0" - - - - 124" 54" 36" 105 15 602 MCL110E8 11.4 208 V 3 12.8 15 ELECTRICAL CONTRACTOR LIEBERT 1, 2, 3, 4
CRCU-4 CRAH-3 - - - 0" - - - - 124" 54" 36" 105 15 602 MCL110E8 11.4 208 V 3 12.8 15 ELECTRICAL CONTRACTOR LIEBERT 1, 2, 3, 4
NO SCALE
COMPUTER ROOM AIR CONDITIONER CONTROLS
03/07/202303/07/2023
Revisions: Date:Revisions: Date:
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
D. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
E. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
F. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
G. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
H. FEEDER CONDUCTORS SHALL HAVE A MAXIMUM VOLTAGE DROP IS 2%. FEEDER CONDUCTORS THAT ARE
DEDICATED TO EMERGENCY SERVICES ARE EXEMPT FROM THIS REQUIREMENT.
I. BRANCH CIRCUIT CONDUCTORS SHALL HAVE A MAXIMUM VOLTAGE DROP OF 3%. BRANCH CIRCUIT CONDUCTORS THAT ARE DEDICATED TO EMERGENCY SERVICES ARE EXEMPT FROM THIS REQUIREMENT.
J. DO NOT INSTALL ELECTRICAL BOXES IN ACOUSTIC RATED WALLS CLOSER THAN 2'-0" TO EACH OTHER.
PROVIDE PUTTY PADS ON EACH BOX INSTALLED.
K. PLANS DO NOT GENERALLY INDICATE WIRE COUNTS. FOR EACH 20 AMP, 120 VOLT OR 277 VOLT CIRCUIT, PROVIDE (1) #12 PHASE CONDUCTOR, (1) #12 NEUTRAL CONDUCTOR AND (1) #12 GROUNDING CONDUCTOR.
WHERE DRAWINGS INDICATE WIRE SIZES/COUNTS, PROVIDE SUCH CIRCUIT, NEUTRAL AND GROUNDING
CONDUCTORS FOR THE PORTION OF THE CIRCUIT WHERE SUCH CONDUCTORS SHARE A COMMON
CONDUIT. GROUND WIRE INSULATION: GREEN. ALL WORK COMPLY WITH NEC 300.17.
L. ALL CONDUCTORS AND EQUIPMENT TO BE INSTALLED OR PERMANENTLY CONNECTED (HARDWIRED) MUST BE LISTED, LABELED OR CERTIFIED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) AS RECOGNIZED BY THE U.S. DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION. [NEC 110.2]
M. IN ALL CASES AND FOR ALL SYSTEMS AND COMPONENTS, USE ONLY EQUIPMENT IN ACCORDANCE WITH ITS
LISTING OR LABELING. [NEC 110.3(B)]
N. USE ONLY EQUIPMENT MARKED (LISTED/LABELED) AS SUITABLE FOR INSTALLATION AND WITH HIGHER TEMPERATURE RATED CONDUCTORS AT THE AMPACITY OF THE HIGHER RATED CONDUCTORS. REFER TO THE UL ELECTRICAL CONSTRUCTION MATERIAL DIRECTORY FOR CIRCUIT BREAKERS, SWITCHES, PANELBOARDS, SWITCHBOARDS, ETC. [NEC 110.14(C)]
O. PROVIDE SUFFICIENT ACCESS AND WORKING CLEARANCE ABOUT THE ELECTRICAL EQUIPMENT IN
ACCORDANCE WITH NEC 110.26(A).
P. PROVIDE ACCESS AND ENTRANCES TO AND EGRESS FROM WORKING SPACE ABOUT ELECTRICAL
EQUIPMENT IN ACCORDANCE WITH NEC 110.26(C).
Q. ALL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, AND MOTOR CONTROL CENTERS SHALL BE LOCATED IN DEDICATED SPACES AND PROTECTED FROM DAMAGE. SEE EXCEPTIONS. [NEC 110.26(E)]
R. PROVIDE TASK ILLUMINATION FOR THE WORK SPACE ABOUT THE ELECTRICAL EQUIPMENT IN ACCORDANCE
WITH NEC 110.26(D).
S. RECEPTACLES INSTALLED ON 20 AMP BRANCH CIRCUITS SHALL BE OF THE GROUNDING TYPE. GROUNDING- TYPE RECEPTACLES SHALL BE INSTALLED ONLY ON CIRCUITS OF THE VOLTAGE CLASS AND CURRENT FOR
WHICH THEY ARE RATED. [NEC 406.4(A)]
T. INSTALL ONLY RECEPTACLE OUTLETS WITH GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION IN LOCATIONS SUCH AS BATHROOMS, KITCHENS, ROOFTOPS, OUTDOOR, WITHIN 6' FROM THE OUTSIDE EDGE
OF SINKS, AND LOCKER ROOMS WITH SHOWERING FACILITIES. [NEC 210.8(B)]
U. PROVIDE OUTLET DEVICE(S) INSTALLED ON A BRANCH CIRCUIT WITH A RATING IN ACCORDANCE WITH NEC
210.21(B) (SEE EXCEPTIONS AND REFER TO 210.21(B) TABLE(S)).
V. DO NOT INSTALL CONDUCTORS OTHER THAN SERVICE CONDUCTORS IN THE SAME SERVICE RACEWAY OR SERVICE CABLE WITH OTHER CONDUCTORS. SEE EXCEPTIONS. [NEC 230.7] [DELETE NOTE IF NO NEW
WORK]
W. PROVIDE GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH NEC 250.24, 250.30 AND 250.50 (SEE
EXCEPTIONS).
X. PROVIDE A BOX OR TERMINAL FITTING HAVING A SEPARATELY BUSHED HOLE FOR EACH CONDUCTOR WHEREVER A CHANGE IS MADE FROM SURFACE RACEWAY WIRING TO OPEN WIRING OR KNOB-AND-TUBE
WIRING. [NEC 300.16]
Y. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE-RESISTANT-RATED WALLS, PARTITIONS, FLOORS, OR CEILINGS SHALL BE FIRESTOPPED USING APPROVED METHODS TO MAINTAIN THE FIRE RESISTANCE RATING. FIRE STOP MATERIAL SHALL BE TESTED AND ASSEMBLY-APPROVED BY THE OSHPD
FIRE MARSHAL. [NEC 300.21]
Z. FLAT CONDUCTOR CABLE (FCC) SHALL NOT BE USED IN HOSPITAL BUILDINGS. [NEC 324.12]
AA. FOR PERMANENTLY CONNECTED APPLIANCES RATED OVER 300 VOLTAMPERES OR 1/8 HORSEPOWER, THE BRANCH-CIRCUIT SWITCH OR CIRCUIT BREAKER SHALL BE PERMITTED TO SERVE AS THE DISCONNECTING MEANS WHERE THE SWITCH OR CIRCUIT BREAKER IS WITHIN SIGHT FROM THE APPLIANCE OR IS LOCKABLE
IN ACCORDANCE WITH NEC 110.25. [NEC 422.31(B)]
BB. THE DISCONNECTING MEANS SHALL BE LOCATED IN SIGHT FROM THE CONTROLLER LOCATION. [NEC 430.102(A)]
CC. PROVIDE INSULATED COPPER GROUNDING CONDUCTOR FOR RECEPTACLES AND FIXED ELECTRIC EQUIPMENT IN PATIENT CARE AREAS IN ACCORDANCE WITH NEC 517.13(B) (SEE EXCEPTIONS, AND REFER
TO 250.122 TABLE(S)).
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
EE. PROVIDE GROUND FAULT PROTECTION FOR THE OPERATION OF SERVICE OR FEEDER DISCONNECTING
MEANS AND AN ADDITIONAL STEP OF GROUND FAULT PROTECTION IN ALL NEXT LEVEL FEEDER
DISCONNECTING MEANS TOWARD THE LOAD IN ACCORDANCE WITH NEC 215.10, NEC 230.95 AND NEC 517.17
(SEE EXCEPTIONS).
FF. CONNECT ONLY THOSE LOADS LISTED IN NEC 517.32 TO THE LIFE SAFETY BRANCH.
GG. PERMANENTLY MARK ALL BOXES AND ENCLOSURES FOR EMERGENCY CIRCUITS SO THEY WILL BE READILY IDENTIFIED AS A COMPONENT OF AN EMERGENCY CIRCUIT OR SYSTEM. LABEL ELECTRICAL DEVICES AS SPECIFIED ELSEWHERE. LABEL PULLBOX COVERS WITH CIRCUIT NUMBERS. ALL WIRING DEVICES, DEVICE
PLATES, JUNCTION BOXES AND OUTLET BOXES ON EMERGENCY POWER SHALL BE IDENTIFIED
PERMANENTLY WITH RED COLORED PLATES AND/OR COLORED DEVICES. ALL DUPLEX RECEPTACLES SHALL
BE HOSPITAL GRADE. [NEC 700.10]
HH. THE FIRE ALARM EQUIPMENT AND SYSTEMS REQUIRED TO BE INSTALLED SHALL CONFORM TO THE APPLICABLE PERFORMANCE AND CONSTRUCTION STANDARDS SPECIFIED IN NFPA 72-2019. [NEC 760]
II. SEE OTHER NOTES AND REQUIREMENTS ON ALL DRAWINGS.
JJ. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
KK. DRAWINGS AND SPECIFICATIONS COMPLIMENT EACH OTHER. REQUIREMENT BY EITHER INFERS
REQUIREMENT BY BOTH.
LL. CONNECT EQUIPMENT AND DEVICES FURNISHED UNDER OTHER DIVISIONS OF THIS CONTRACT, BY OWNER
OR BY OTHER CONTRACTS.
MM. UNLESS OTHERWISE NOTED, PROVIDE CONCEALED AND FLUSH MOUNTED INSTALLATION OF DEVICES AND
EQUIPMENT IN AREAS.
NN. PROVIDE SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN 120 VOLT, MULTI-WIRE CIRCUITS.
OO. FOR 120 VOLT, 20 AMP CIRCUITS, WHERE CIRCUIT DISTANCE FROM PANELBOARD TO FARTHEST
DEVICE/LUMINAIRE EXCEEDS 75 FEET, PROVIDE #10 SIZE CONDUCTOR.
PP. RUN ELECTRICAL CONDUIT CONCEALED AND PARALLEL TO BUILDING LINES. VERIFY WITH ARCHITECT.
QQ. RECEPTACLE OUTLETS SHALL BE INSTALLED IN COMPLIANCE WITH NEC SECTIONS 210.7 AND 210.50.
RR. LIGHTS, SWITCHES AND CONTROL MECHANISMS SHALL COMPLY WITH NEC SECTION 404.
SS. BRACE ELECTRICAL EQUIPMENT TO RESIST A HORIZONTAL FORCE THAT ACT IN ANY DIRECTION. COMPLY
WITH TITLE 24 REQUIREMENTS.
TT. INSTALL COMPLETE SYSTEM OF CONDUCTORS IN METAL RACEWAY SYSTEM THROUGHOUT BUILDING FOR
FEEDERS, BRANCH CIRCUITS, ETC.
UU. OCCUPANCY SENSOR NOTES:
1. WALL SENSORS
a. SENSOR MUST HAVE CLEAR "VIEW" OF OCCUPANTS. WHERE SENSOR WILL BE BLOCKED, SUBSTITUTE WITH SMALL-ROOM CEILING SENSOR.
2. SEE MANUFACTURER'S SPECIFICATION REGARDING PLACING SENSORS AWAY FROM STRONG AIR-
FLOW. INDICATE PRECISE LOCATION OF EACH CEILING SENSOR WHERE DRAWINGS INDICATE AIR
SUPPLIES.
3. IN INDIVIDUAL ROOMS WITH CEILING SENSORS AND DUAL-LEVEL LIGHTING, ASSUME TWO TOGGLE
SWITCH OVERRIDES PER ROOM.
4. PRIOR TO INSTALLATION, RECEIVE FACTORY-TRAINING AND LAYOUT-ASSISTANCE. IF LOCAL AGENT
CHANGES LIGHTING DRAWINGS, CONTACT FACTORY REPRESENTATIVE.
VV. PROVIDE DESIGN BUILD FOR FIRE ALARM SYSTEM. FIRE ALARM DEVICES SHOWN ON PLANS ARE FOR COORDINATION PURPOSES ONLY. SUBMIT COMPLETE DRAWINGS TO THE FIRE MARSHAL FOR APPROVAL AND ASSUME FULL RESPONSIBILITY OF THE SYSTEM, DEVICE QUANTITY AND LOCATION, WIRING, PROGRAMMING AND CONTROL PANELS. COORDINATE FINAL DEVICE LOCATIONS WITH THE ARCHITECT
PRIOR TO ROUGH-IN. USE THIS NOTE ONLY FOR NEW CONSTRUCTION.
WW. ALL AIC RATINGS SHOWN ARE MINIMUM REQUIREMENTS. COORDINATE AND UPGRADE RATINGS FOR ALL DISTRIBUTION EQUIPMENT AS PER SHORT CIRCUIT ANALYSIS RECOMMENTATIONS. USE THIS NOTE ONLY
FOR PROJECTS WITH NEW PANELBOARDS AND SWITCHBOARDS ADDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
NC Engineering License No.: P-0214 NC Architectural License No.: 51254
03/07/2023
B
IM
/2
.0
V A
D u b lin
E H
R M
I n fr a s tr u c tu re U p g ra d e s /5
-1
.M
E P
R
.r v t
/2
/2
:4
:1
P M
40-E1
ELECTRICAL SYMBOLS AND
ABBREVIATIONS
557-20-105
03/07/2023 SBH SBH
100% BID DOCUMENTS
Carl Vinson VAMC
557-20-105 - EHRM Infrastructure
Data Center Upgrades
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DUPLEX - CONV
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
EMERGENCY POWER OFF
SWITCH
GENERAL:
PROVIDE STI (SAFETY TECHNOLOGY INTERNATIONAL, INC) MODEL [SS2-231PO-EN FLUSH MOUNT] [SS2-271PO-EN SURFACE MOUNT] EPO SWITCH AND PROTECTIVE COVER, OR PRIOR APPROVED EQUIVALENT, AT APPROXIMATE LOCATIONS INDICATED ON PLANS.