This document contains specifications for an uninterruptible power supply (UPS) panel for a Department of Veterans Affairs data center upgrade project. Key details include a 120% minimum interrupting rating for the panel, specifications for circuit breaker options including shunt trip and ground fault types, enclosure and mounting requirements, voltage and phase configuration, and load information for two power distribution units totaling 625 amps to be supported by the 400 amp panel. The related solicitation is for infrastructure upgrades at the VA data center in Dublin, Georgia, under opportunity number 36C77623B0062, with no further information provided on response or award dates.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
400 A
SPARE CAPACITY:
100 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 400 A
CONSIDER 125% DEMAND: 0 A
DEMAND CURRENT: 0 A
DEMAND LOAD: 0 VA
CONNECTED CURRENT: 0 A
CONNECTED LOAD: 0 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 0 A 0 A 0 A
TOTAL LOAD: 0 VA 0 VA 0 VA
11 0 VA 0 VA 12
9 0 VA 0 VA 10
PDU #1B -- 225 A 3
0 VA 0 VA
3 400 A -- PDU #2B
5 0 VA 0 VA 6
3 0 VA 0 VA 4
PDU #1A -- 225 A 3
0 VA 0 VA
3 400 A -- PDU #2A
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): PANEL POLES: 12
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: CRITICAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: PHASES: 3 MCB/MLO RATING: 400 A
LOCATION: VOLTS: 208/120 WYE MAINS TYPE: MCB
EXISTING PANEL: UPS PANEL