This is a comprehensive mechanical calculations document for the replacement of an Air Handling Unit (AHU) in Building 45 at the Edward Hines Jr. VA Hospital in Hines, Illinois, as part of Project Number 578-17-012. The file contains detailed technical calculations including peak heating and cooling loads for multiple zones, ventilation calculations, humidifier sizing, psychrometric analysis, hydronic piping system loss calculations, duct static pressure loss calculations, steam and condensate pipe calculations, and relief valve calculations. The calculations cover various systems including AHU-1, MAU-1, chilled water supply and return, glycol systems, hydronic systems, steam systems, and condensate systems, providing extensive engineering data to support the AHU replacement project.
The document includes precise technical specifications such as air flow rates, temperature differentials, pressure drops, pipe sizes, friction factors, and system volumes across multiple mechanical systems. Key parameters examined include steam pressures ranging from 15 to 60 psig, steam rates between 300 and 2,100 lb/hr, pipe diameters from 1 to 4 inches, and calculations for different system pressures and temperatures. The calculations are designed to ensure proper sizing, performance, and efficiency of the mechanical systems involved in the AHU replacement, with methodical analysis following engineering standards like ASHRAE guidelines and ASME B31.1 specifications.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs Edward Hines Jr. VA Hospital
Hines, IL
Project Number 578-17-012
(VEG 19.19)
Replace AHU Bldg. 45 TO#2
Calculations
June 15, 2023
MRohall Snapshot
PEAK HEATING LOADSMAIN SYSTEM By Trial AREA ROOM DRY BULBSupply Dry Bulb SPACE AIR FLOw SPACE SENS LOAD COIL supply dry bulbCOIL AIR FLOW COIL Sensible load System Room Zone Peak ft² °F °F cfm Btu/h °F cfm Btu/h
Lobby Peak 400 70.0 90.0 182 -3,958 90.0 182 -6,926
Restrooms Peak 465 70.0 90.0 628 -13,687 90.0 628 -23,952
Storage near restroom Peak 100 70.0 90.0 60 -1,314 90.0 60 -2,299
VCS Store Peak 1,330 70.0 90.0 1,376 -29,985 90.0 1,376 -52,474
VCS store b Peak 1,730 70.0 90.0 1,778 -38,747 90.0 1,778 -67,807
Corridor Peak 587 70.0 90.0 323 -7,035 90.0 323 -12,310
VCS Storage room Peak 953 70.0 90.0 1,614 -35,170 90.0 1,614 -61,547
Vending Area Peak 507 70.0 85.7 423 -7,240 85.7 423 -14,143
Dining Area - Zone 5 Peak 1,420 70.0 85.7 1,183 -20,277 85.7 1,183 -39,613
Dining Area - Zone 6 Peak 1,300 70.0 85.7 1,083 -18,563 85.7 1,083 -36,265
Kitchen Area - South Peak 620 70.0 87.0 439 -8,144 87.0 439 -15,320
Serving Area - South Peak 220 70.0 87.0 156 -2,890 87.0 156 -5,436
General office Peak 365 70.0 90.0 220 -4,795 90.0 220 -8,390
MGR Office Peak 135 70.0 90.0 367 -8,005 90.0 367 -14,008
Dining Area - Zone 9 Peak 1,430 70.0 85.7 1,192 -20,420 85.7 1,192 -39,892
Dining Area - Zone 10 Peak 780 70.0 90.0 688 -14,985 90.0 688 -26,224
Dining Area - Zone 11 Peak 781 70.0 90.0 915 -19,935 90.0 915 -34,887
Serving Area Peak 1,328 70.0 87.0 941 -17,444 87.0 941 -32,815
Kitchen Peak 1,871 70.0 80.0 10,521 -114,607 80.0 10,521 -166,128 -48768
Mechanical Room Peak 211 50.0 80.0 185 -6,054 80.0 185 -2,957 -6460
System - 002 Block 2,082 69.7 80.0 10,706 -120,661 80.0 10,706 -169,086
System - 002 Block 2,082 69.7 80.0 10,706 -120,661 80.0 10,706 -169,086
Project Name: ahu 45 hines.trc Peak Htg Loads Main System Report Page -1 of 1
Zone - 001 Block 965 70.0 90.0 870 -18,958 90.0 870 -33,177 -18,958
Zone - 002A Block 1,330 70.0 90.0 1,376 -29,985 90.0 1,376 -52,474 -29,985
Zone - 002B Block 1,730 70.0 90.0 1,778 -38,747 90.0 1,778 -67,807 -38,747
Zone - 003 Block 1,540 70.0 90.0 1,937 -42,204 90.0 1,937 -73,857 -22,204 20MBH unit heater
Zone - 004 Block 507 70.0 85.7 423 -7,240 85.7 423 -14,143 -7,240
Zone - 005 Block 1,420 70.0 85.7 1,183 -20,277 85.7 1,183 -39,613 -20,277
Zone - 006 Block 1,300 70.0 85.7 1,083 -18,563 85.7 1,083 -36,265 -18,563
Zone - 007 Block 840 70.0 87.0 595 -11,034 87.0 595 -20,756 -11,034
Zone - 008 Block 500 70.0 90.0 587 -12,799 90.0 587 -22,398 -12,799
Zone - 009 Block 1,430 70.0 85.7 1,192 -20,420 85.7 1,192 -39,892 -20,420
Zone - 010 Block 780 70.0 90.0 688 -14,985 90.0 688 -26,224 -14,985
Zone - 011 Block 781 70.0 90.0 915 -19,935 90.0 915 -34,887 -19,935
Zone - 012 Block 1,328 70.0 87.0 941 -17,444 87.0 941 -32,815 -17,444
PEAK COOLING LOADS MAIN SYSTEM By Trial AREA Peaked @ SPACE OA DB SPACE OA WB ROOM DRY BULB Supply Dry Bulb SPACE AIR FLOw SPACE SENS LOADCOIL supply dry bulbPeaked @ COIL OA DB COIL OA WB Supply DB COIL AIRFLOW COIL SENS LOAD COIL LATENT LOAD System Room Zone ft² Mo/Hr °F °F °F °F cfm Btu/h Btu/h Mo/Hr °F °F °F cfm Btu/h Btu/h
Lobby Peak 400 7 17 89 72 75.0 55.0 606 13,199 171 7 15 91 73 55.0 182 6,303 1,624
Restrooms Peak 465 7 17 89 72 75.0 55.0 2,166 47,188 662 7 15 91 73 55.0 667 15,261 821
Storage near restroom Peak 100
VCS Store Peak 1,330 7 17 89 72 75.0 55.0 9,848 214,558 21,078 7 16 90 73 55.0 3,092 85,546 31,995
VCS store b Peak 1,730
Corridor Peak 587 7 17 89 72 75.0 55.0 1,077 23,457 251 7 16 90 73 55.0 323 8,739 2,199
VCS Storage room Peak 953 7 18 87 72 75.0 55.0 5,171 112,656 1,644 7 15 91 73 55.0 1,551 38,846 5,342
Vending Area Peak 507 7 16 90 73 75.0 55.0 1,361 29,655 14,525 7 14 90 73 55.0 1,337 36,364 20,745
Dining Area - Zone 5 Peak 1,420 7 16 90 73 75.0 55.0 2,351 51,232 30,827 7 14 90 73 55.0 1,924 57,280 44,026
Dining Area - Zone 6 Peak 1,300 7 16 90 73 75.0 55.0 2,784 60,659 36,500 7 14 90 73 55.0 2,278 67,821 52,128
Kitchen Area - South Peak 620 7 16 90 73 75.0 55.0 1,246 27,156 3,356 7 14 90 73 55.0 850 26,081 9,820
Serving Area - South Peak 220 7 16 90 73 75.0 55.0 442 9,636 6,265 7 14 90 73 55.0 391 11,195 8,559
General office Peak 365 7 16 90 73 75.0 55.0 734 15,987 867 7 15 91 73 55.0 235 7,019 2,185
MGR Office Peak 135 7 16 90 73 75.0 55.0 1,225 26,684 409 7 14 90 73 55.0 367 8,423 1,014
Dining Area - Zone 9 Peak 1,430 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417
Dining Area - Zone 10 Peak 780 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417
Dining Area - Zone 11 Peak 781 7 16 90 73 75.0 55.0 3,579 77,968 31,801 7 14 90 73 55.0 2,116 61,458 45,417
Serving Area Peak 1,328 7 16 90 73 75.0 55.0 2,670 58,167 37,818 7 14 90 73 55.0 2,387 68,176 51,665
System - 001 Peak 14,310 89 72 75.0 55.0 40,891 890,886 249,776 90 73 55.0 21,763 624,195 368,373
System - 001 Block 14,310 7 17 89 72 75.0 55.0 22,221 484,138 248,336 7 14 90 73 55.0 21,627 610,739 373,803
Kitchen Peak 1,871 7 18 87 72 78.0 69.5 10,521 96,863 -35,666 7 18 87 72 69.5 10,521 81,769 -39,865
Mechanical Room Peak 211 7 18 87 72 84.0 65.0 185 3,834 283 7 18 87 72 65.0 185 4,306 671
System - 002 Block 2,082 7 18 87 72 78.1 69.5 10,706 100,697 9,770 7 18 87 72 69.5 10,706 86,033 5,955
Project Name: ahu 45 hines.trc Peak Clg Loads Main System Report Page -1 of 1
Zone - 001 Block 965 7 17 89 72 75.0 55.0 2,166 47,188 833 7 15 91 73 55.0 2,166 49,074 2,444
Zone - 002A Block 1,330 7 17 89 72 75.0 55.0 9,848 214,558 21,078 7 16 90 73 55.0 3,092 85,546 31,995
Zone - 002B Block 1,730
Zone - 003 Block 1,540 7 18 87 72 75.0 55.0 5,171 112,656 1,930 7 15 91 73 55.0 5,171 119,232 7,725
Zone - 004 Block 507 7 16 90 73 75.0 55.0 1,361 29,655 14,525 7 14 90 73 55.0 1,337 36,364 20,745
Zone - 005 Block 1,420 7 16 90 73 75.0 55.0 2,351 51,232 30,827 7 14 90 73 55.0 1,924 57,280 44,026
Zone - 006 Block 1,300 7 16 90 73 75.0 55.0 2,784 60,659 36,500 7 14 90 73 55.0 2,278 67,821 52,128
Zone - 007 Block 840 7 16 90 73 75.0 55.0 1,282 27,923 9,621 7 14 90 73 55.0 1,246 37,390 18,379
Zone - 008 Block 500 7 16 90 73 75.0 55.0 1,225 26,684 1,276 7 15 91 73 55.0 1,225 29,022 3,089
Zone - 009 Block 1,430 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417
Zone - 010 Block 780 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417
Zone - 011 Block 781 7 16 90 73 75.0 55.0 3,579 77,968 31,801 7 14 90 73 55.0 2,116 61,458 45,417
Zone - 012 Block 1,328 7 16 90 73 75.0 55.0 2,670 58,167 37,818 7 14 90 73 55.0 2,387 68,176 51,665 tot people sens people sens lat zone sens zone latent zone
Lobby 261 1,092 2,599 0 0 3952 0 z1 12816 0 1
Restrooms 2785 3,058 3,021 0 0 8864 0 z2a 29,575 7988 2
Storage near restroom 143 658 638 z2b 38,894 10390 3
VCS Store A 5,048 15,886 8,641 17,973 9,985 29,575 7988 z3 22977 0 3
VCS Store B 6,991 20,664 11,239 23,378 12,988 38,894 10,390 z4 29654 13942 4
Corridor 659 1,603 3,814 0 0 6076 0 z5 56798 39050 5
VCS Storage room 7,643 3,253 6,005 0 0 16901 0 z6 51999 35750 6
Vending Area 851 25,566 3,237 27,885 13,943 29654 13942 z7 27920 8800 7
Dining Area ‑ Zone 5 2,382 45,350 9,066 78,100 39,050 56798 39050 z8 9752 700 8
Dining Area - Zone 6 2,181 41,518 8,300 71,500 35,750 51999 35750 z9 57199 39325 9
Kitchen Area ‑ South 884 14,333 3,958 5,500 2,750 19175 2750 z10 32738 21450 10
Serving Area ‑ South 314 7,026 1405 12,100 6,050 8745 6050 z11 31286 21450 11
General office 520 2,400 2330 1,149 638 5250 511 z12 53444 36520 12
MGR Office 2752 888 862 425 236 4502 189
Dining Area - Zone 9 2,399 45,670 9,130 78,650 39,325 57,199 39325
Dining Area - Zone 10 2,847 24,911 4,980 42,900 21,450 32738 21,450
Dining Area - Zone 11 4,822 21,478 4,986 42,900 21,450 31286 21450
Serving Area 1,894 43,012 8,538 73,040 36,520 53,444 36520
45376 318366 92749 475500 240135 0 455052 235365 cfm transfer factor1.06 COOLING SA DB (⁰F): 55 COOLING SETPOINT (⁰F): 75
SF 10.00% HEATING SA DB (⁰F): 90 HEATING SETPOINT (⁰F): 70
AHU VAV ROOM SIZE AHU BLOCK VAV COOLING LOAD
NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC TOTAL OA OA HTG REQ MIN.
SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH ACH ACH % CFM CFM CFM/SQ FT GPM CFM
Zone - 001 965 8.5 VAV 12,816 0 -18,958 665 984 4.86 9.00 2.00 0.4 1230 1230 1.27 2.17 1230
Zone - 002A 1330 9.0 VAV 29,575 7,988 -29,985 1535 1556 7.69 4.00 2.00 0.4 998 1555 1.17 2.75 1000
Zone - 002B 1730 10.0 VAV 38,894 10,390 -38,747 2018 2010 6.97 4.00 2.00 0.4 1442 2020 1.17 3.55 1440
Zone - 003 1540 8.5 VAV 22,977 0 -22,204 1192 1152 5.28 8.00 2.00 0.4 1745 2100 1.36 3.08 1745
Zone - 004 507 10.0 VAV 29,654 13,942 -7,240 1539 462 4.45 4.00 2.00 0.4 423 1540 3.04 0.82 425
Zone - 005 1420 10.0 VAV 56,798 39,050 -20,277 2947 1052 4.45 6.00 5.00 0.4 2958 2960 2.08 5.23 2960
Zone - 006 1300 10.0 VAV 51,999 35,750 -18,563 2698 963 4.45 6.00 5.00 0.4 2708 2710 2.08 4.79 2710
Zone - 007 840 8.5 VAV 27,920 8,800 -11,034 1449 573 4.81 4.00 2.00 0.4 595 1450 1.73 1.05 595
Zone - 008 500 8.5 VAV 9,752 700 -12,799 506 664 7.14 4.00 2.00 0.4 354 665 1.33 1.17 355
Zone - 009 1430 10.0 VAV 57,199 39,325 -20,420 2968 1060 4.45 6.00 5.00 0.4 2979 2980 2.08 5.26 2980
Zone - 010 780 10.0 VAV 32,738 21,450 -14,985 1699 778 5.98 6.00 5.00 0.4 1625 1700 2.18 2.87 1625
Zone - 011 781 10.0 VAV 31,286 21,450 -19,935 1623 1034 7.95 6.00 5.00 0.4 1627 1625 2.08 2.87 1625
Zone - 012 1328 8.5 VAV 53,444 36,520 -17,444 2773 905 4.81 4.00 2.00 0.4 941 2775 2.09 1.66 940 sum 13 14451 455052 235365 -252592 23611 13192 19625 25310 1.75 37.28 19630
GENERAL NOTES: 0.659097328
1. COOLING CFMS CALCULATED AT 510 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 59⁰F AND A COOLING SETPOINT OF 75⁰F.
2. HEATING CFMS CALCULATED AT 510 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 90⁰F AND A HEATING SETPOINT OF 70⁰F.
3. MINIMUM AIRFLOW (IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE) USED FOR AIR CHANGE CALCULATIONS.
HEATING
WATER FLOW
ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE
BLOCK VAV
HEATING LOAD
CALCULATED ROOM AIRFLOW REQUIRED VAV AIRFLOW (PER 2023 VA HVAC DM) SELECTED DESIGN VAV
AIRFLOW
SELECTED DESIGN
MIN AIRFLOW
cfm transfer factor1.057 COOLING SA DB (⁰F): 55 COOLING SETPOINT (⁰F): 75
SF 10.00% HEATING SA DB (⁰F): 90 HEATING SETPOINT (⁰F): 70
AHU ROOM ROOM SIZE AHU PEAK ROOM COOLING LOAD
NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC TOTAL OA OA HTG REQ MIN.
SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH ACH ACH % CFM CFM CFM/SQ FT CFM
Lobby 400 8.5 VAV 3,952 0 -3,958 206 206 3.63 4.00 2.00 0.4 283 600 1.50 283 600
Restrooms 465 8.5 VAV 8,864 0 -13,687 461 712 7.00 4.00 2.00 0.4 329 710 1.53 461 710
Storage near restroom 100 8.5 VAV 0 0 -1,314 0 68 0.00 4.00 2.00 0.4 71 100 1.00 71 100
VCS Store 1330 9.0 VAV 29,575 7,988 -29,985 1539 1560 7.71 4.00 2.00 0.4 998 1560 1.17 1539 1560
VCS store b 1730 9.0 VAV 38,894 10,390 -38,747 2024 2016 7.77 4.00 2.00 0.4 1298 2025 1.17 2016 2025
Corridor 587 8.5 VAV 6,076 0 -7,035 316 366 3.80 4.00 2.00 0.4 416 365 0.62 416 365
VCS Storage room 953 9.0 VAV 16,901 0 -35,170 879 1830 6.15 4.00 2.00 0.4 715 1830 1.92 879 1830
Vending Area 507 8.5 VAV 29,654 13,942 -7,240 1543 463 5.24 4.00 2.00 0.4 359 1545 3.05 463 1545
Dining Area - Zone 5 1420 10.0 VAV 56,798 39,050 -20,277 2955 1055 4.46 4.00 2.00 0.4 1183 2955 2.08 1183 2955
Dining Area - Zone 6 1300 10.0 VAV 51,999 35,750 -18,563 2706 966 4.46 4.00 2.00 0.4 1083 2705 2.08 1083 2705
Kitchen Area - South 620 8.5 VAV 19,175 2,750 -8,144 998 424 4.82 4.00 2.00 0.4 439 1000 1.61 439 1000
Serving Area - South 220 8.5 VAV 8,745 6,050 -2,890 455 150 4.82 4.00 2.00 0.4 156 455 2.07 156 455
General office 365 8.5 VAV 5,250 511 -4,795 273 249 4.82 4.00 2.00 0.4 259 275 0.75 259 275
MGR Office 135 8.5 VAV 4,502 189 -8,005 234 417 12.25 4.00 2.00 0.4 96 415 3.07 234 415
Dining Area - Zone 9 1430 10.0 VAV 57,199 39,325 -20,420 2976 1063 4.46 4.00 2.00 0.4 1192 2975 2.08 1192 2975
Dining Area - Zone 10 780 10.0 VAV 32,738 21,450 -14,985 1703 780 6.00 4.00 2.00 0.4 650 1705 2.19 780 1705
Dining Area - Zone 11 781 10.0 VAV 31,286 21,450 -19,935 1628 1037 7.97 4.00 2.00 0.4 651 1630 2.09 1037 1630
Serving Area 1328 8.5 VAV 53,444 36,520 -17,444 2781 908 4.82 4.00 2.00 0.4 941 2780 2.09 941 2780 sum 14451 455,052 235,365 -272592 23678 14270 11117 25630 1.77 13432 25630
GENERAL NOTES:
1. COOLING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 55⁰F AND A COOLING SETPOINT OF 75⁰F.
2. HEATING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 90⁰F AND A HEATING SETPOINT OF 70⁰F.
3. MINIMUM AIRFLOW (IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE) USED FOR AIR CHANGE CALCULATIONS.
Directions:
Sensible peak room cooling load: From trace room checksums, sum the space peak envelope loads, the space peak internal loads and the space peak ceiling load.
Latent peak room cooling load: From Trace room checksums, subtract the people sensible load from the total people load.
Note:
AHU ROOM ROOM SIZE AHU PEAK ROOM COOLING LOAD
NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC TOTAL OA OA HTG REQ MIN.
SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH ACH ACH % CFM CFM CFM/SQ FT CFM
Kitchen 1871 8.5 VAV 96,863 -39,865 -48,768 6720 5075 19.15 10.00 2.00 100.0 2651 6720 3.59 5075 6720
Mechanical Room 211 12.0 VAV 3,834 671 -6,460 266 672 6.30 4.00 2.00 100.0 169 670 3.18 266 670 sum 2082 100,697 5,955 -55228 6986 2819 7390 3.55 5341 7390
GENERAL NOTES:
1. COOLING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 65 ⁰F AND A COOLING SETPOINT OF 80⁰F.
2. HEATING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 90⁰F AND A HEATING SETPOINT OF 70⁰F.
3. MINIMUM AIRFLOW (IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE) USED FOR AIR CHANGE CALCULATIONS.
AHU ROOM ROOM SIZE AHU PEAK ROOM COOLING LOAD
NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC COOLING HEATING
SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH BTUH BTUH
Kitchen 1871 8.5 VAV 96,863 -39,865 -48,768 6720 5075 19.15 168006 3901440
Mechanical Room 211 12.0 VAV 3,834 671 -6,460 266 672 6.30 6650 516800
174656 4418240
14.55
Kitchen 1871 8.5 VAV 49,763 -39,865 -48,768 3452 5075 13.03 86312 3901440
Mechanical Room 211 12.0 VAV 3,834 671 -6,460 266 672 6.30 6650 516800
92962 4418240
7.75
EQUIPMENT
ON
EQUIPMENT
OFF
PEAK ROOM
HEATING LOAD
CALCULATED ROOM AIRFLOW COIL LOAD
ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE - SYSTEM 2
PEAK ROOM
HEATING LOAD
CALCULATED ROOM AIRFLOW REQUIRED ROOM AIRFLOW (PER 2023 VA HVAC DM) SELECTED DESIGN ROOM
AIRFLOW
SELECTED DESIGN
MIN AIRFLOW ROOM RETURN CFM
REQUIRED ROOM AIRFLOW (PER 2023 VA HVAC DM) SELECTED DESIGN
MIN AIRFLOW
ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE - SYSTEM 1
ROOM RETURN CFM
PEAK ROOM
HEATING LOAD
SELECTED DESIGN ROOM
AIRFLOW
CALCULATED ROOM AIRFLOW
Input
Output
People No. Vent. Airflow (CFM) Cooling Vent. Load (BTU/hr) Heating Vent. Load (BTU/hr) CFM per person (check) Engineer Inputs AHU
AHU-1 879 8314 215915 571072 9.46 air density at site (lb/ft^3) 0.0725
Heating GPM site elevation (ft asl) 617
40% glycol HW 41 CFM Trans Factor 1.06 Enthalpy @ xx% RH hum ratio (lb water/lb dry air)
38 SADB AHU summer (F) 54 22.4 0.0092
SADB AHU winter (F) 65
Summer Design (F) 89.5 <---
Cooling Airflow (CFM) Heating Airflow (CFM) Percent OA Cooling Percent OA Heating Summer Design Wb (F) 73.2 <--- ASHRAE climate data
AHU-1 24424 19630 37% 42% Winter Design (F) 0.2 <---
Summer RA Db (F) 77
Winter RA Db (F) 67 Enthalpy @ xx% RH hum ratio (lb water/lb dry air)
Sens Cooling Load (BTU/hr) Heating Load (BTU/hr) Summer MA Db (F) 81.5875 32.7 0.0126
714229 607057 Winter MA Db (F) 35.82551197
Total Cooling Load (BTU/hr) hw2(lat ht of water @ 0°f) 1060
1078739 chill water delta T 14.0
Cooling GPM Heating GPM heating water delta T 30
40% glycol CW 164 40% glycol HW 40 1.1 HR
154 40 Winter OA 0.000157143 lbs/lb
6.445
Winter RA 0.006445 lbs/lb
People No. Vent. Airflow (CFM) Cooling Vent. Load (BTU/hr) Heating Vent. Load (BTU/hr) CFM per person (check)
MAU-1 31 2205 27580 128084 71.13 Engineer Inputs MAU
Heating GPM air density at site (lb/ft^3) 0.0725
40% glycol HW 9 site elevation (ft asl) 617 psych chart @52
9 CFM Trans Factor 1.06 Enthalpy @ xx% RH hum ratio (lb water/lb dry air)
SADB AHU summer (F) 55 23 0.0102
SADB AHU winter (F) 80
Cooling Airflow (CFM) Heating Airflow (CFM) Percent OA Cooling Percent OA Heating Summer Design (F) 91.8 <---
MAU-1 10706 10706 100% 100% Summer Design Wb (F) 74.6 <--- ASHRAE climate data
Winter Design (F) 0.2 <---
Summer RA Db (F)
Sens Cooling Load (BTU/hr) Heating Load (BTU/hr) Winter RA Db (F) Enthalpy @ xx% RH hum ratio (lb water/lb dry air)
417620 905599 Summer MA Db (F) 91.8 38 0.0144
Total Cooling Load (BTU/hr) Winter MA Db (F) 0.2
688342 hw2(lat ht of water @ 0°f) 1060
Cooling GPM Heating GPM VAV GPM chill water delta T 14
40% glycol CW 105 40% glycol HW 59 37.28 heating water delta T 30
98 60 1.1 HR
Winter OA 0.000157143 lbs/lb
TOTAL: TOTAL: 6.445
BTU 1767081 BTU 1765248 2021.638 Lbm/hr Winter RA 0.006445 lbs/lb
GPM W/ Glycol 269 GPM W/ Glycol 136 8086.55 EDR
GPM 252 GPM 137 4.043275 GPM CONDENSATE
Pipe Size Required 4 in Pipe Size Required 3 in
HEATING GHW LOAD
Ventilation Calculations - System 1
Mixed Air Calculations
Ventilation Calculations - System 2
Mixed Air Calculations
COOLING GCW LOAD
ASHRAE 0.4% CONDITIONS
Humidifier sizing
Sizing criteria:
OA calc. (cfm) = 40% of max. airflow
Indoor conditions: 25% RH
72°F DB
For mechanical ventilation systems having a fixed quantity of outdoor air [(ASHRAE Handbook 2016 - HVAC Systems and Equipment, eq. (2)]:
Total Flow = 19,630 cfm
INPUT:
Qo = 7852 cfm ρ = 0.074 lb/ft
Wi = 25.732 grains of moisture/lbdry air 0.003676 lbwater/lbdry air
Wo = 1.505 grains of moisture/lbdry air 0.000215 lbwater/lbdry air
S = 0 lbwater/h
L = 0 lbwater/h
OUTPUT:
H = 120.7 lbwater/h
Humidifier sizing
Sizing criteria:
OA calc. (cfm) = 100% of max. airflow
Indoor conditions: 25% RH
72°F DB
For mechanical ventilation systems having a fixed quantity of outdoor air [(ASHRAE Handbook 2016 - HVAC Systems and Equipment, eq. (2)]:
Total Flow = 25,545 cfm
INPUT:
Qo = 25545 cfm ρ = 0.074 lb/ft
Wi = 21.721 grains of moisture/lbdry air 0.003103 lbwater/lbdry air
Wo = 14.35 grains of moisture/lbdry air 0.00205 lbwater/lbdry air
S = 0 lbwater/h
L = 0 lbwater/h
OUTPUT:
H = 119.4 lbwater/h
� = 60���( �)-S+L
� = 60���( �)-S+L
Hydronic Primary Circuit Piping Loss Heating Water
Longest Pipe Length (ft) 356
Longest Pipe Length w/ fittings (ft) 712
Pipe drop (ft/100ft of pipe) 4
Pipe Friction Loss (ft head) 28.5
VAV Coil Drop (ft head) 15
Valve Loss (ft head) 12
Heat Exchanger 6.5
Total Head Loss (ft) 62
Hydronic Primary Circuit Piping Loss Glycol Chilled water
Longest Pipe Length (ft) 325
Longest Pipe Length w/ fittings (ft) 650
Pipe drop (ft/100ft of pipe) 4
Pipe Friction Loss (ft head) 26
AHU Coil Drop (ft head) 20
Valve Loss (ft head) 15
Heat Exchanger 10
Total Head Loss (ft) 71
C hapter 7: Psychrom etrics
2019 N
C
EES
7.3 Psychrom
etric Charts
ASHRAE Psychrom etric Chart N
o. 1 - Sea Level
Source: R eprinted w ith perm ission. "A
SH
R
A E Psychrom etric C hart N
o. 1," A
SH
R A
E: 2016.
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Arrow
MHoiles Callout
HR = 0.0122
MHoiles Callout
HR = 0.096
MHoiles Line
MHoiles Text Box
AHU-1
MHoiles Line
MHoiles Callout H=32.7
MHoiles Text Box
ASHRAE 1%
DB (F) 89.5 | WB =73.2
summer MA 81.6 summer RA 77 Summer SA 56
MHoiles Ellipse
MHoiles Line
MHoiles PolyLine
MHoiles Line
MHoiles Line
MHoiles Callout
SHR= .7
MHoiles Callout H=24.6
MHoiles Line
MHoiles Callout 56 dbF
MHoiles Callout 75 dbF
MHoiles Callout
89.5 dbF
MHoiles Line
MHoiles Line
MHoiles Callout 77 dbF
MHoiles Callout
81.6 dbF
MHoiles Callout 74.6wb F
C hapter 7: Psychrom etrics
2019 N
C
EES
7.3 Psychrom
etric Charts
ASHRAE Psychrom etric Chart N
o. 1 - Sea Level
Source: R eprinted w ith perm ission. "A
SH
R
A E Psychrom etric C hart N
o. 1," A
SH
R A
E: 2016.
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Arrow
MHoiles Callout
HR = 0.0144
MHoiles Callout
HR = 0.0102
MHoiles Text Box
MAU-1
MHoiles Text Box
ASHRAE 0.4%
DB (F) 91.8 | WB =74.6
summer SA 57
MHoiles PolyLine
MHoiles Line
MHoiles Callout H=38
MHoiles Line
MHoiles Callout H=24.6
MHoiles Line
MHoiles Line
MHoiles Line
MHoiles Callout 57 dbF
MHoiles Callout 74.6wb F
MHoiles Callout 75 dbF
MHoiles Callout
91.8 dbF
MHoiles Callout
SHR= .7609
ASHRAE PIPE THERMAL EXPANSION CALCULATIONS - L , Z, AND U BENDS/EXPANSION LOOPS
use pipe dropdown FROM HVAC SYSTEMS AND EQUIPMENT - CHAPTER 46. PIPES, TUBES, AND FITTINGS
---------------------> 3" STANDARD Δ (IN/100FT) L BEND FT Z BEND FT
COPPER 3.105 L, COPPER 18 L 11.5
60 PSI steam STEEL 2.53 U BEND FT
W 3.75 change pipe length ---------> ANCH-ANCH EXP/L1 for L loops 85.00 H 7.5
ACTUAL Δ COPPER 2.63925 2H 15
ACTUAL Δ STEEL 2.15 L BEND FT Z BEND FT
L, STEEL 17.25 L 11.00
OD 3.125 U BEND FT
OD 3.500 W 3.50
H 7.00
2H 14.00
*Rounded lengths up to nearest 0.25 ft
L1
U-bend
ASHRAE PIPE THERMAL EXPANSION CALCULATIONS - L , Z, AND U BENDS/EXPANSION LOOPS
use pipe dropdown FROM HVAC SYSTEMS AND EQUIPMENT - CHAPTER 46. PIPES, TUBES, AND FITTINGS
---------------------> 3" STANDARD Δ (IN/100FT) L BEND FT Z BEND FT
COPPER 2.05 L, COPPER 11.25 L 7.25
hydronic @ 180°F STEEL 1.37 U BEND FT
W 2.25 change pipe length ---------> ANCH-ANCH EXP/L1 for L loops 50.00 H 4.50
ACTUAL Δ COPPER 1.03 2H 9.00
ACTUAL Δ STEEL 0.69 L BEND FT Z BEND FT
L, STEEL 9.75 L 6.25
OD 3.125 U BEND FT
OD 3.500 W 2.00
H 4.00
2H 8.00
*Rounded lengths up to nearest 0.25 ft
L1
U-bend
DUCT STATIC PRESSURE LOSS CALCULATIONS
CLIENT: VA FILE NAME: 19.19 Replace AHU Bldg 45_MECH_R19 PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: Supply DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Diffuser 850 24 24 24.0 1.00 213 0.00 0.050 0.050
2 Flex Duct 850 16.0 1.00 609 0.02 0.000 0.050
3 Round Take Off 850 16.0 5.6 1.00 609 0.02 0.129 0.179
4 Duct 850 14 12 13.2 10.583 1.00 729 0.03 0.064 0.007 0.186
5 Transition 45 850 14 12 13.2 0.29 1.00 729 0.03 0.010 0.196
6 Duct 1700 24 12 17.7 12.916 1.00 850 0.05 0.060 0.008 0.204
7 Elbow 90 1700 24 12 17.7 0.01 1.00 850 0.05 0.000 0.204
6 Duct 1700 24 12 17.7 8.625 1.00 850 0.05 0.060 0.005 0.209
7 Elbow 90 1700 24 12 17.7 0.01 1.00 850 0.05 0.000 0.210
8 Duct 1700 24 12 17.7 36.583 1.00 850 0.05 0.060 0.003 0.212
9 Transition 45 1700 17 16 16.6 0.29 1.00 900 0.05 0.015 0.227
10 Duct 1700 17 16 16.6 0.833 1.00 900 0.05 0.073 0.003 0.230
11 VAV 1700 0.0 1.00 0 0.00 0.700 0.930
12 Duct 1700 14.0 3.416 1.00 1590 0.16 0.264 0.009 0.939
13 Round Take Off 1700 14.0 4 5.6 1.00 1590 0.16 0.264 0.011 0.949
14 Duct 6305 28 20 24.5 18.25 1.00 1621 0.16 0.139 0.025 0.974
15 Elbow 90 6305 28 20 24.5 0.01 1.00 1621 0.16 0.002 0.976
16 Duct 6305 28 20 24.5 5.333 1.00 1621 0.16 0.139 0.007 0.984
17 Elbow 90 6305 28 20 24.5 0.01 1.00 1621 0.16 0.002 0.985
18 Transition 30 6305 28 20 24.5 0.25 1.00 1621 0.16 0.041 1.026
19 Duct 6305 30 20 25.4 5.75 1.00 1513 0.14 0.116 0.007 1.033
20 Transition 30 6305 30 20 25.4 0.25 1.00 1513 0.14 0.036 1.069
21 Duct 9073 30 24 27.5 31.833 1.00 1815 0.21 0.149 0.047 1.116
22 Elbow 90 9073 30 24 27.5 0.01 1.00 1815 0.21 0.002 1.118
23 Rect. Duct 23861 113 32 62.7 5.166 1.00 950 0.06 0.016 0.001 1.119
24 AHU 23861 113 32 62.7 0.86 1.00 950 0.06 0.048 1.167
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: Return DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Diffuser 3000 24 24 26.2 1.00 750 0.04 0.050 0.050
2 Duct 3000 20 20 21.9 1.416 1.00 1080 0.07 0.074 0.001 0.051
3 Take off 3000 20 20 21.9 1.17 1.00 1080 0.07 0.085 0.136
4 Duct 6000 50 18 31.8 9.75 1.00 960 0.06 0.037 0.004 0.140
5 Elbow 30 6000 50 18 31.8 0.0045 1.00 960 0.06 0.000 0.140
6 Duct 6000 50 18 31.8 9.333 1.00 960 0.06 0.037 0.003 0.143
7 Elbow 30 6000 50 18 31.8 0.0045 1.00 960 0.06 0.000 0.144
8 Duct 6000 50 18 31.8 26.666 1.00 960 0.06 0.037 0.010 0.154
9 Elbow 90 6000 50 18 31.8 0.01 1.00 960 0.06 0.001 0.154
10 Duct 6000 50 18 31.8 37.416 1.00 960 0.06 0.037 0.014 0.168
11 Transition 45 6000 50 18 31.8 0.29 1.00 960 0.06 0.017 0.185
12 Duct 14500 50 30 42.0 34.833 1.00 1392 0.12 0.054 0.019 0.204
13 Elbow 90 14500 50 30 42.0 1.2 1.00 1392 0.12 0.145 0.349
14 Transition 45 6000 50 30 42.0 0.29 1.00 576 0.02 0.006 0.355
15 Duct 14500 60 32 47.3 5.916 1.00 1088 0.07 0.029 0.002 0.350
16 Elbow 30 14500 60 32 47.3 0.0045 1.00 1088 0.07 0.000 0.351 17 Duct 14500 60 32 47.3 3.583 1.00 1088 0.07 0.029 0.001 0.352
18 Elbow 30 14500 60 32 47.3 0.0045 1.00 1088 0.07 0.000 0.352
19 Duct 19550 60 32 47.3 5.916 1.00 1466 0.13 0.051 0.003 0.355
20 Elbow 90 19550 60 32 47.3 1.3 1.00 1466 0.13 0.174 0.529
21 Duct 19550 60 32 47.3 4.124 1.00 1466 0.13 0.051 0.002 0.531
22 AHU 19550 60 32 47.3 0.86 1.00 1466 0.13 0.115 0.647
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-1 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Hood 1520 96 55 78.7 1.00 41 0.00 0.050 0.050
2 Duct 1520 18 18 19.7 3.653 1.00 676 0.03 0.034 0.001 0.051
3 45-EF-1 1520 22 22 24.0 0.86 1.00 0 0.00 0.000 0.051
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-3 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Exhaust hood 1200 60 42 54.7 1.00 69 0.00 0.050 0.050
2 Duct 1200 18 18 19.7 3.25 1.00 533 0.02 0.022 0.001 0.051
3 Elbow 1.18 1200 18 18 19.7 0 1.00 533 0.02 0.000 0.051
4 Duct 1200 18 18 19.7 0.75 1.00 533 0.02 0.022 0.000 0.051
5 45-EF-3 1200 26 26 28.4 0.86 1.00 256 0.00 0.004 0.054
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-4 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Exhaust Hood 750 48 36 45.3 1.00 63 0.00 0.050 0.050
2 Duct 750 12 12 13.1 2 1.00 750 0.04 0.069 0.001 0.051
3 Elbow 90 750 12 12 13.1 0.01 1.00 750 0.04 0.000 0.052
4 Duct 750 12 12 13.1 0.646 1.00 750 0.04 0.069 0.000 0.052
5 Elbow 40 750 12 12 13.1 0.006 1.00 750 0.04 0.000 0.052
6 Duct 750 12 12 13.1 9.494 1.00 750 0.04 0.069 0.007 0.059
7 Elbow 40 750 12 12 13.1 0.006 1.00 750 0.04 0.000 0.059
8 Duct 750 12 12 13.1 1 1.00 750 0.04 0.069 0.001 0.060
9 Elbow 90 750 12 12 13.1 0.01 1.00 750 0.04 0.000 0.060
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-5 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Exhaust Hood 5400 97 110 112.9 1.00 73 0.00 0.050 0.050
2 Duct 5400 26 26 28.4 3.666 1.00 1150 0.08 0.060 0.002 0.052
3 Elbow 1.18 5400 26 26 28.4 0 1.00 1150 0.08 0.000 0.052
4 Duct 5400 26 26 28.4 0.75 1.00 1150 0.08 0.060 0.000 0.053
5 45-EF-5 5400 46 46 50.3 0.86 1.00 367 0.01 0.007 0.060
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-6 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Diffuser 300 24 24 26.2 1.00 75 0.00 0.050 0.050
2 Duct 300 12 10 12.0 4 1.00 360 0.01 0.019 0.001 0.051
3 Elbow 90 300 12 10 12.0 0.01 1.00 360 0.01 0.000 0.051
4 Duct 300 12 10 12.0 9.083 1.00 360 0.01 0.019 0.002 0.053
5 Elbow 90 300 12 10 12.0 0.01 1.00 360 0.01 0.000 0.053
6 Duct 900 14 14 15.3 30.416 1.00 661 0.03 0.045 0.014 0.066
7 Transition 45 900 14 14 15.3 0.29 1.00 661 0.03 0.008 0.074
8 Duct 1200 14 14 15.3 3.083 1.00 882 0.05 0.077 0.002 0.077
9 Transition 45 1200 14 14 15.3 0.29 1.00 882 0.05 0.014 0.091
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-7 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Exhaust Hood 665 48 36 45.3 1.00 55 0.00 0.050 0.050
2 Duct 665 18 18 19.7 0.25 1.00 296 0.01 0.007 0.000 0.050
3 Elbow 90 665 18 18 19.7 0.01 1.00 296 0.01 0.000 0.050
4 Duct 665 18 18 19.7 0.833 1.00 296 0.01 0.007 0.000 0.050
5 Elbow 90 665 18 18 19.7 0.01 1.00 296 0.01 0.000 0.050
6 Duct 665 18 18 19.7 0.5 1.00 296 0.01 0.007 0.000 0.050
7 Elbow 45 665 18 18 19.7 0.006 1.00 296 0.01 0.000 0.050
8 Elbow 45 665 18 18 19.7 0.006 1.00 296 0.01 0.000 0.050
9 Duct 665 18 18 19.7 0.5 1.00 296 0.01 0.007 0.000 0.050
10 45-EF-7 665 26 26 28.4 0.86 1.00 142 0.00 0.001 0.051
PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid
DESCRIPTION: 45-EF-8 DATE: 04/13/23
Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative
No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss
1 Diffuser 700 24 24 26.2 1.00 175 0.00 0.050 0.050
2 Duct 700 12 12 13.1 1.583 1.00 700 0.03 0.060 0.001 0.051
3 Take Off 700 12 12 13.1 5.13 1.00 700 0.03 0.157 0.208
4 Duct 700 12 12 13.1 3.833 1.00 700 0.03 0.060 0.002 0.210
5 Elbow 90 700 12 12 13.1 0.01 1.00 700 0.03 0.000 0.210
6 Duct 1500 16 14 16.4 12.416 1.00 964 0.06 0.085 0.010 0.221
7 Elbow 90 1500 16 14 16.4 0.01 1.00 964 0.06 0.001 0.221
8 Duct 1500 16 14 16.4 3.5 1.00 964 0.06 0.085 0.003 0.224
9 Transition 45 1500 16 14 16.4 0.006 1.00 964 0.06 0.000 0.225
10 Duct 1800 18 14 17.3 15.333 1.00 1029 0.07 0.089 0.014 0.238
11 Elbow 90 1800 18 14 17.3 0.01 1.00 1029 0.07 0.001 0.239
12 Duct 1800 18 14 17.3 2 1.00 1029 0.07 0.089 0.002 0.241
13 Take off 1800 18 14 17.3 5.13 1.00 1029 0.07 0.338 0.579
14 Duct 1800 18 18 19.7 2.583 1.00 800 0.04 0.047 0.001 0.580
15 Elbow 1.18 1800 18 18 19.7 0 1.00 800 0.04 0.000 0.580
16 Duct 1800 18 18 19.7 0.75 1.00 800 0.04 0.047 0.000 0.581
17 45-EF-8 1800 26 26 28.4 0.86 1.00 383 0.01 0.008 0.589
Piping System Loss Calculation Sheet
Project Name:
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100') *
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 184.8 264 4 3.905 10 Other 1 184.84 Copper 150 3.93 7.3 15.4 115.0
Elbow 7 264 4 3.905 10 90° Elbow 1 7 Copper 150 3.93 0.3 0.6 4.4
Tee 1 264 4 3.905 10 Tee - Line Flow 6 6 Copper 150 3.93 0.2 0.5 3.7
High 3.93
Low 3.93
Average 3.93
7.8 16.5 123.1
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Chilled Water Return
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 176.7 291 4 3.905 10 Other 1 176.66 Copper 150 4.71 8.3 14.7 109.9
Elbow 6 291 4 3.905 10 90° Elbow 10 60 Copper 150 4.71 2.8 5.0 37.3
Tee 1 291 4 3.905 10 Tee - Line Flow 6 6 Copper 150 4.71 0.3 0.5 3.7
High 4.71
Low 4.71
Average 4.71
11.4 20.2 151.0
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Chilled Water Supply
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 98.3 290 4 4.026 10 Other 1 98.3 Steel 130 5.25 5.2 8.7 65.0
Elbow 90 11 290 4 4.026 10 90° Elbow 10 110 Steel 130 5.25 5.8 9.7 72.7
Tee 1 290 4 4.026 10 Tee - Line Flow 6 6 Steel 130 5.25 0.3 0.5 4.0
Inline Pump 1 290 4 4.026 10 Steel 130
High 5.25
Low 5.25
Average 5.25
11.3 18.9 141.7
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Glycol Chilled Water Return
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 94.42 290 4 4.026 10 Other 1 94.42 Steel 130 5.25 5.0 8.3 62.4
Elbow 90 8 290 4 4.026 10 90° Elbow 10 80 Steel 130 5.25 4.2 7.1 52.9
Tee 1 290 4 4.026 10 Tee - Line Flow 6 6 Steel 130 5.25 0.3 0.5 4.0
HX 1 10.0
ahu 1 20.0 valve 1 15.0
High 5.25
Low 5.25
Average 5.25
54.5 15.9 119.3
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Glycol Chilled Water Supply
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 80.32 2.2 1 1/4 1.265 5 Other 1 80.32 Copper 150 0.13 0.1 0.7 5.2
Elbow 90 8 2.2 1 1/4 1.265 5 90° Elbow 3.1 24.8 Copper 150 0.13 0.0 0.2 1.6
High 0.13
Low 0.13
Average 0.13
0.1 0.9 6.9
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
30 PSI Medium Pressure Return
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Ref
Inside
Diameter
Steel
Inside
Diameter
Copper
Inside
Diameter
Pipe Size
Reference
Fitting Type Fitting
Type
Reference
Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 21.87 0.6 1 1/2 5 1.61 1.505 1.505 6 Other 1 1 21.87 Copper 150 0.01 0.0 0.3 2.0
Pipe 2.63 0.6 2 1/2 7 2.469 2.465 2.465 8 Other 1 1 2.63 Copper 150 0.00 0.0 0.1 0.7 pipe 11.88 0.6 3 8 3.068 2.945 2.945 9 Other 1 1 11.88 Copper 150 0.00 0.0 0.6 4.2 pipe 84.66 0.6 4 9 4.026 3.905 3.905 10 Other 1 1 84.66 Copper 150 0.00 0.0 7.0 52.7 pipe 0.65 0.6 5 10 5.047 4.875 4.875 11 Other 1 1 0.65 Copper 150 0.00 0.0 0.1 0.6
Elbow 90 2 0.6 4 3 1.049 1.025 1.025 10 90° Elbow 2 10 20 Copper 150 0.03 0.0 0.1 0.9
Elbow 90 3 0.6 3 8 3.068 2.945 2.945 9 90° Elbow 2 7 21 Copper 150 0.00 0.0 1.0 7.4
Elbow 90 4 0.6 2 1/2 7 2.469 2.465 2.465 8 90° Elbow 2 5 20 Copper 150 0.00 0.0 0.7 5.0
Elbow 90 2 0.6 1 1/2 5 1.61 1.505 1.505 6 90° Elbow 2 3.6 7.2 Copper 150 0.01 0.0 0.1 0.7
Tee 3 0.6 2 1/2 7 2.469 2.465 2.465 8 Tee - Line Flow 4 3 9 Copper 150 0.00 0.0 0.3 2.2
Tee 1 0.6 3 8 3.068 2.945 2.945 9 Tee - Line Flow 4 5 5 Copper 150 0.00 0.0 0.2 1.8
Tee 1 0.6 1 1/2 5 1.61 1.505 1.505 6 Tee - Branch Flow 5 7.1 7.1 Copper 150 0.01 0.0 0.1 0.7
210.99 High 0.03
Low 0.00
Average 0.00
0.0 10.5 78.1
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
30 PSI Medium Pressure Steam
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 253.4 10.8 1 1/2 1.505 6 Other 1 253.4 Copper 150 1.10 2.8 3.1 23.4
Elbow 90 7 10.8 1 1/2 1.505 6 90° Elbow 3.6 25.2 Copper 150 1.10 0.3 0.3 2.3
High 1.10
Low 1.10
Average 1.10
3.1 3.4 25.7
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Pumped Condensate
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
Pipe 5.18 1180 2 1/2 2.469 8 Other 1 5.18 Steel 130 760.44 39.4 0.2 1.3
Pipe 248.4 1180 3 3.068 9 other 1 248.35 steel 130 264.29 656.4 12.7 95.4
Elbow 90 4 1180 2 1/2 2.469 8 90° Elbow 5 20 Steel 130 760.44 152.1 0.7 5.0
Tee 1 1180 3 3.068 9 Tee - Line Flow 5 5 Steel 130 264.29 13.2 0.3 1.9
High 760.44
Low 264.29
Average 512.36
861.1 13.8 103.6
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Medium Pressure Steam
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Ref
Inside
Diameter
Steel
Inside
Diameter
Copper
Inside
Diameter
Pipe Size
Reference
Fitting Type Fitting
Type
Reference
Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculated
Volume
(Gal)
MAU RISER 13.3 60 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 53.2 Copper 150 6.82 3.6 1.1 8.6
AHU RISER 13.3 40 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 53.2 Copper 150 3.22 1.7 1.1 8.6
Tee 1 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 4 Copper 150 17.55 0.7 0.1 0.6
AHU/MAU PIPE 8 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 32 Copper 150 17.55 5.6 0.7 5.1
Elbow 90 1 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 4 Copper 150 17.55 0.7 0.1 0.6
Pipe 14.25 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 57 Copper 150 17.55 10.0 1.2 9.2 elbow 90 1 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 4 Copper 150 17.55 0.7 0.1 0.6 pipe 3.15 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 12.6 Copper 150 17.55 2.2 0.3 2.0
Elbow 90 2 55 2 1/2 7 2.469 2.465 2.465 8 90° Elbow 2 5 10 Copper 150 2.02 0.2 0.3 2.5
Elbow 90 1 65 3 8 3.068 2.945 2.945 9 90° Elbow 2 7 7 Copper 150 1.16 0.1 0.3 2.5
Tee 1 6 1 3 1.049 1.025 1.025 4 90° Elbow 2 2.3 2.3 Copper 150 2.40 0.1 0.0 0.1
Tee 1 10 1 1/4 4 1.38 1.265 1.265 5 Tee - Line Flow 4 2 2 Copper 150 2.22 0.0 0.0 0.1
Tee 2 25 1 1/2 5 1.61 1.505 1.505 6 Tee - Line Flow 4 2.4 4.8 Copper 150 5.19 0.2 0.1 0.4
Tee 2 45 2 6 2.067 1.985 1.985 7 Tee - Line Flow 4 2.8 5.6 Copper 150 4.01 0.2 0.1 0.9
Tee 1 55 2 1/2 7 2.469 2.465 2.465 8 Tee - Line Flow 4 3 3 Copper 150 2.02 0.1 0.1 0.7
Tee 1 65 3 8 3.068 2.945 2.945 9 Tee - Line Flow 4 5 5 Copper 150 1.16 0.1 0.2 1.8
Tee 1 3 3/4 2 0.824 0.785 0.785 3 Tee - Branch Flow 5 3.6 3.6 Copper 150 2.44 0.1 0.0 0.1
Vav 1 Copper 150 15.0 valve 1 12.0
HX 1 6.5
High 17.55
Low 1.16 2.6 19.7
Average 6.27
47.5
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Glycol HR Total System Volume
Project Number:
Date:
Modification Date:
System:
User should enter data in yellow colored cells and not copper colored cells.
To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".
Steel= 130 Copper= 150 1.3
Description Qua/
Length
Flow
(GPM)
Pipe Size Inside
Diameter
Pipe Size
Reference
Fitting Type Equivalent
Length Ea.
(ft wg)
Equivalent
Length Tot
(ft wg)
Tubing
(Copper or Steel)
Friction
Factor
Friction
(ft wg/100')
Calculated
Friction
(ft wg)
Given
Friction
(ft wg)
Calculated
Volume
(ft^3)
Calculate d Volume
(Gal)
Pipe 20.09 3 3/4 0.785 3 Other 1 20.09 Copper 150 2.44 0.5 0.1 0.5
Pipe 59.1 6 1 1.025 4 Other 1 59.1 Copper 150 2.40 1.4 0.3 2.5
Pipe 99.86 10 1 1/4 1.265 5 Other 1 99.86 Copper 150 2.22 2.2 0.9 6.5
Pipe 58.69 25 1 1/2 1.505 6 Other 1 58.69 Copper 150 5.19 3.0 0.7 5.4
Pipe 37.6 45 2 1.985 7 Other 1 37.6 Copper 150 4.01 1.5 0.8 6.0
Pipe 79.23 55 2 1/2 2.465 8 Other 1 79.23 Copper 150 2.02 1.6 2.6 19.6
Pipe 0.35 65 3 2.945 9 Other 1 0.35 Copper 150 1.16 0.0 0.0 0.1
Elbow 90 1 6 1 1.025 4 90° Elbow 2.3 2.3 Copper 150 2.40 0.1 0.0 0.1
Elbow 90 1 10 1 1/4 1.265 5 90° Elbow 3.1 3.1 Copper 150 2.22 0.1 0.0 0.2
Elbow 90 2 25 1 1/2 1.505 6 90° Elbow 3.6 7.2 Copper 150 5.19 0.4 0.1 0.7
Elbow 90 2 45 2 1.985 7 90° Elbow 4 8 Copper 150 4.01 0.3 0.2 1.3
Elbow 90 2 55 2 1/2 2.465 8 90° Elbow 5 10 Copper 150 2.02 0.2 0.3 2.5
Elbow 90 1 65 3 2.945 9 90° Elbow 7 7 Copper 150 1.16 0.1 0.3 2.5
Tee 1 6 1 1.025 4 Tee - Line Flow 1.6 1.6 Copper 150 2.40 0.0 0.0 0.1
Tee 1 10 1 1/4 1.265 5 Tee - Line Flow 2 2 Copper 150 2.22 0.0 0.0 0.1
Tee 2 25 1 1/2 1.505 6 Tee - Line Flow 2.4 4.8 Copper 150 5.19 0.2 0.1 0.4
Tee 2 45 2 1.985 7 Tee - Line Flow 2.8 5.6 Copper 150 4.01 0.2 0.1 0.9
Tee 1 55 2 1/2 2.465 8 Tee - Line Flow 3 3 Copper 150 2.02 0.1 0.1 0.7
Tee 1 65 3 2.945 9 Tee - Line Flow 5 5 Copper 150 1.16 0.1 0.2 1.8
Tee 1 3 3/4 0.785 3 Tee - Branch Flow 3.6 3.6 Copper 150 2.44 0.1 0.0 0.1
High 5.19
Low 1.16
Average 2.79
12.1 7.0 52.1
* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.
Hazen-Williams Friction Factors: Fitting Multiplier:
Total System Losses
Replace AHU Bldg 45
19.19
9/17/2020
6/15/2023
Hydronic Supply
Parameters Symbol Value Unit Reference
Actual Mass Flow Rate through Relief Valve W 0.583333333 lb/s Process Data
Discharge Elbow Size inch P&ID
Thickness of Discharge Pipe SCH P&ID
Discharge Pipe Outer Diameter 3.5 inch Pipe Data
Discharge Pipe Thickness 0.216 inch Pipe Data
Discharge Elbow Area A1 7.39 inch 2 Pipe Data
Stagnation Enthalpy at Safety Valve Inlet h0 1160 btu/lb Steam Table steam enthalpy plus kinetic
Gravitational Constant gc 32.2 ft/s
Steam Condition Process Data
Joule's Constant J 778.16 ft-lb/btu
Calculation Constant a 823 btu/lb ASME B 31.1
Calculation Constant b 4.33 ASME B 31.1
Atmospheric Pressure Pa 14.7 psi Process Data
Pressure at Discharge Elbow Outlet P1 2.80 psia ASME B 31.1
Velocity at Discharge Elbow Outlet V1 1484.83 ft/s ASME B 31.1
Reaction Force at Discharge Elbow Outlet F1 -61.09 lbf ASME B 31.1
Equivalent length from valve outlet to discharge elbow outlet Lmax 19 inch Layout
Darcy Weisback friction factor f 0.013 Moody's Graph f(Lmax/D) 0.081 ASME B 31.1
Specific Heat Ratio k 1.1 ASME B 31.1
Pressure Ratio P/P* 1.231
ASME B 31.1 also fanno lines pdf ensure your calculated value is in the charts on the right or manually input values.
Pressure at Discharge Elbow Inlet P1a 3.44 psia ASME B 31.1
Vent Pipe Size P&ID
Thickness of Vent Pipe P&ID
Vent Pipe Outer Diameter 4.5 inch Pipe Data
Vent Pipe Thickness 0.237 inch Pipe Data
Vent Pipe Area A3 12.73 inch 2 Pipe Data
Pressure at Discharge of Vent Pipe P3 1.63 psia ASME B 31.1
Velocity at Discharge of Vent Pipe V3 1484.83 ft/s ASME B 31.1
Reaction Force at Discharge of Vent Pipe F3 -139.55 lbf ASME B 31.1
Equivalent length of Vent Pipe Lmax 164 inch Layout f(Lmax/D) 0.530 ASME B 31.1
Pressure Ratio P/P* 1.608
ASME B 31.1 also fanno lines pdf ensure your calculated value is in the charts on the right or manually input values.
Velocity Ratio V/V* 0.654
ASME B 31.1 also fanno lines pdf ensure your calculated value is in the charts on the right or manually input values.
Pressure at Inlet of Vent Pipe P2 2.61 psia ASME B 31.1
Velocity at Inlet of Vent Pipe V2 971.21 ft/s ASME B 31.1
Reaction Force at Inlet of Vent Pipe F2 -136.28 lbf ASME B 31.1
Bevel Angle at Vent Exit with Vertical Axis θ 0 deg
Height of Anchor from Vent Pipe Exit H 0 ft Layout
Vertical Force on Vent Pipe Anchor FV 3.27 lbf ASME B 31.1
Moment on Vent Pipe Anchor M 0.61 lbf ASME B 31.1
Blow-back Check if error shows, values for V/V or P/P must be manually entered from the flow charts or website
Weight of Safety Valve W 800 lb Process Data
Distance of Run Pipe Wall to Valve Outlet Centre Line h 19 inch Layout
Young's Modulus of Inlet Pipe E 2.30E+07 psi Pipe Data
Inlet Pipe Size P&ID
Inlet Pipe Thickness P&ID
Outer Diameter of Inlet Pipe Do 3.5 inch Pipe Data
Thickness of Inlet Pipe t 0.216 inch Pipe Data
Inner Diameter of Inlet Pipe Di 3.068 inch Pipe Data
Area Moment of Inertia of Inlet Pipe I 3.02 inch 4 Pipe Data
Safety Valve Installation Period T 5.19E-02 s ASME B 31.1
Valve Rise Time t0 0.04 s Process Data
Ratio of Valve Rise Time to Installation Period t0/T 0.77 ASME B 31.1
Dynamic Load Factor DLF 1.57 ASME B 31.1
Force to Piping System for Relief Valve Operation F -95.76 lbf ASME B 31.1
VENT PIPE SIZE IS OK
RELIEF VALVE CALCULATION AS PER ASME B31.1
Saturated Steam;>90% quality; 15 psia<pressure<1000 psia
STD
Steam and Condensate Pipe Calculator hidden background calcs above. FRICTION FACTOR CALC BROKEN
Color Legend:
Altitude 730 ft User Data Entry for the Pipe Scenario
Steam Pressure 60 psig MPS Informative Calculations
Steam Rate 2100 lb/hr Pressure Drop/Velocity Calculations within Acceptable Ranges
Steam Pipe Diameter 3 inches Pressure Drop/Velocity Calculations Near Edge of Acceptable Range. Okay but Consider Upsizing.
Steam Temperature 307 °F Pressure Drop/Velocity Calculations Outside of Acceptable Ranges. DO NOT SELECT HERE!
Steam BTU Rate 1,902 MBH
Steam velocity 4,200 fpm VA max 7,200 fpm
Pressure Drop 0.26 psig/100ft VA max 1 psi/100ft for LPS 2 psi/100ft for MPS & HPS
Condensate GPM 4.2 GPM
Condensate Pipe Diameter 2 inches
Max lb/hr @ 1/16 psi/100ft 989 lb/hr VA max for LPS 0.0625 psi/100ft for LPS
Max lb/hr @ 1/4 psi/100ft 2102 lb/hr VA max for MPS 0.25 psi/100ft for MPS
Max lb/hr @ 1 psi/100ft 0 lb/hr VA max for HPS 1 psi/100ft for HPS
Pressure Drop 1.28 psig/100ft
Dry Condensate Velocity 4,074 fpm VA max 7,000 fpm
Color Legend:
Altitude 730 ft User Data Entry for the Pipe Scenario
Steam Pressure 30 psig MPS Informative Calculations
Steam Rate 2100 lb/hr Pressure Drop/Velocity Calculations within Acceptable Ranges
Steam Pipe Diameter 3 inches Pressure Drop/Velocity Calculations Near Edge of Acceptable Range. Okay but Consider Upsizing.
Steam Temperature 273 °F Pressure Drop/Velocity Calculations Outside of Acceptable Ranges. DO NOT SELECT HERE!
Steam BTU Rate 1,954 MBH
Steam velocity 6,847 fpm VA max 7,200 fpm
Pressure Drop 0.26 psig/100ft VA max 1 psi/100ft for LPS 2 psi/100ft for MPS & HPS
Condensate GPM 4.2 GPM
Condensate Pipe Diameter 2 inches
Max lb/hr @ 1/16 psi/100ft 1585 lb/hr VA max for LPS 0.0625 psi/100ft for LPS
Max lb/hr @ 1/4 psi/100ft 3369 lb/hr VA max for MPS 0.25 psi/100ft for MPS
Max lb/hr @ 1 psi/100ft 0 lb/hr VA max for HPS 1 psi/100ft for HPS
Pressure Drop 1.28 psig/100ft
Dry Condensate Velocity 2,951 fpm VA max 7,000 fpm
Color Legend:
Altitude 730 ft User Data Entry for the Pipe Scenario
Steam Pressure 15 psig LPS Informative Calculations
Steam Rate 300 lb/hr Pressure Drop/Velocity Calculations within Acceptable Ranges
Steam Pipe Diameter 1.5 inches Pressure Drop/Velocity Calculations Near Edge of Acceptable Range. Okay but Consider Upsizing.
Steam Temperature 248 °F Pressure Drop/Velocity Calculations Outside of Acceptable Ranges. DO NOT SELECT HERE!
Steam BTU Rate 284 MBH
Steam…