S02 9 578-17-012 MECH Calculations.pdf

PDF 3 MB Posted

Attached to
Commissioning Agent Services, Replace Air Handling Unit
Solicitation number
36C25225Q0266
Issued by

About this file

This is a comprehensive mechanical calculations document for the replacement of an Air Handling Unit (AHU) in Building 45 at the Edward Hines Jr. VA Hospital in Hines, Illinois, as part of Project Number 578-17-012. The file contains detailed technical calculations including peak heating and cooling loads for multiple zones, ventilation calculations, humidifier sizing, psychrometric analysis, hydronic piping system loss calculations, duct static pressure loss calculations, steam and condensate pipe calculations, and relief valve calculations. The calculations cover various systems including AHU-1, MAU-1, chilled water supply and return, glycol systems, hydronic systems, steam systems, and condensate systems, providing extensive engineering data to support the AHU replacement project.

The document includes precise technical specifications such as air flow rates, temperature differentials, pressure drops, pipe sizes, friction factors, and system volumes across multiple mechanical systems. Key parameters examined include steam pressures ranging from 15 to 60 psig, steam rates between 300 and 2,100 lb/hr, pipe diameters from 1 to 4 inches, and calculations for different system pressures and temperatures. The calculations are designed to ensure proper sizing, performance, and efficiency of the mechanical systems involved in the AHU replacement, with methodical analysis following engineering standards like ASHRAE guidelines and ASME B31.1 specifications.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veterans Affairs Edward Hines Jr. VA Hospital

Hines, IL

Project Number 578-17-012

(VEG 19.19)

Replace AHU Bldg. 45 TO#2

Calculations

June 15, 2023

MRohall Snapshot

PEAK HEATING LOADSMAIN SYSTEM By Trial AREA ROOM DRY BULBSupply Dry Bulb SPACE AIR FLOw SPACE SENS LOAD COIL supply dry bulbCOIL AIR FLOW COIL Sensible load System Room Zone Peak ft² °F °F cfm Btu/h °F cfm Btu/h

Lobby Peak 400 70.0 90.0 182 -3,958 90.0 182 -6,926

Restrooms Peak 465 70.0 90.0 628 -13,687 90.0 628 -23,952

Storage near restroom Peak 100 70.0 90.0 60 -1,314 90.0 60 -2,299

VCS Store Peak 1,330 70.0 90.0 1,376 -29,985 90.0 1,376 -52,474

VCS store b Peak 1,730 70.0 90.0 1,778 -38,747 90.0 1,778 -67,807

Corridor Peak 587 70.0 90.0 323 -7,035 90.0 323 -12,310

VCS Storage room Peak 953 70.0 90.0 1,614 -35,170 90.0 1,614 -61,547

Vending Area Peak 507 70.0 85.7 423 -7,240 85.7 423 -14,143

Dining Area - Zone 5 Peak 1,420 70.0 85.7 1,183 -20,277 85.7 1,183 -39,613

Dining Area - Zone 6 Peak 1,300 70.0 85.7 1,083 -18,563 85.7 1,083 -36,265

Kitchen Area - South Peak 620 70.0 87.0 439 -8,144 87.0 439 -15,320

Serving Area - South Peak 220 70.0 87.0 156 -2,890 87.0 156 -5,436

General office Peak 365 70.0 90.0 220 -4,795 90.0 220 -8,390

MGR Office Peak 135 70.0 90.0 367 -8,005 90.0 367 -14,008

Dining Area - Zone 9 Peak 1,430 70.0 85.7 1,192 -20,420 85.7 1,192 -39,892

Dining Area - Zone 10 Peak 780 70.0 90.0 688 -14,985 90.0 688 -26,224

Dining Area - Zone 11 Peak 781 70.0 90.0 915 -19,935 90.0 915 -34,887

Serving Area Peak 1,328 70.0 87.0 941 -17,444 87.0 941 -32,815

Kitchen Peak 1,871 70.0 80.0 10,521 -114,607 80.0 10,521 -166,128 -48768

Mechanical Room Peak 211 50.0 80.0 185 -6,054 80.0 185 -2,957 -6460

System - 002 Block 2,082 69.7 80.0 10,706 -120,661 80.0 10,706 -169,086

System - 002 Block 2,082 69.7 80.0 10,706 -120,661 80.0 10,706 -169,086

Project Name: ahu 45 hines.trc Peak Htg Loads Main System Report Page -1 of 1

Zone - 001 Block 965 70.0 90.0 870 -18,958 90.0 870 -33,177 -18,958

Zone - 002A Block 1,330 70.0 90.0 1,376 -29,985 90.0 1,376 -52,474 -29,985

Zone - 002B Block 1,730 70.0 90.0 1,778 -38,747 90.0 1,778 -67,807 -38,747

Zone - 003 Block 1,540 70.0 90.0 1,937 -42,204 90.0 1,937 -73,857 -22,204 20MBH unit heater

Zone - 004 Block 507 70.0 85.7 423 -7,240 85.7 423 -14,143 -7,240

Zone - 005 Block 1,420 70.0 85.7 1,183 -20,277 85.7 1,183 -39,613 -20,277

Zone - 006 Block 1,300 70.0 85.7 1,083 -18,563 85.7 1,083 -36,265 -18,563

Zone - 007 Block 840 70.0 87.0 595 -11,034 87.0 595 -20,756 -11,034

Zone - 008 Block 500 70.0 90.0 587 -12,799 90.0 587 -22,398 -12,799

Zone - 009 Block 1,430 70.0 85.7 1,192 -20,420 85.7 1,192 -39,892 -20,420

Zone - 010 Block 780 70.0 90.0 688 -14,985 90.0 688 -26,224 -14,985

Zone - 011 Block 781 70.0 90.0 915 -19,935 90.0 915 -34,887 -19,935

Zone - 012 Block 1,328 70.0 87.0 941 -17,444 87.0 941 -32,815 -17,444

PEAK COOLING LOADS MAIN SYSTEM By Trial AREA Peaked @ SPACE OA DB SPACE OA WB ROOM DRY BULB Supply Dry Bulb SPACE AIR FLOw SPACE SENS LOADCOIL supply dry bulbPeaked @ COIL OA DB COIL OA WB Supply DB COIL AIRFLOW COIL SENS LOAD COIL LATENT LOAD System Room Zone ft² Mo/Hr °F °F °F °F cfm Btu/h Btu/h Mo/Hr °F °F °F cfm Btu/h Btu/h

Lobby Peak 400 7 17 89 72 75.0 55.0 606 13,199 171 7 15 91 73 55.0 182 6,303 1,624

Restrooms Peak 465 7 17 89 72 75.0 55.0 2,166 47,188 662 7 15 91 73 55.0 667 15,261 821

Storage near restroom Peak 100

VCS Store Peak 1,330 7 17 89 72 75.0 55.0 9,848 214,558 21,078 7 16 90 73 55.0 3,092 85,546 31,995

VCS store b Peak 1,730

Corridor Peak 587 7 17 89 72 75.0 55.0 1,077 23,457 251 7 16 90 73 55.0 323 8,739 2,199

VCS Storage room Peak 953 7 18 87 72 75.0 55.0 5,171 112,656 1,644 7 15 91 73 55.0 1,551 38,846 5,342

Vending Area Peak 507 7 16 90 73 75.0 55.0 1,361 29,655 14,525 7 14 90 73 55.0 1,337 36,364 20,745

Dining Area - Zone 5 Peak 1,420 7 16 90 73 75.0 55.0 2,351 51,232 30,827 7 14 90 73 55.0 1,924 57,280 44,026

Dining Area - Zone 6 Peak 1,300 7 16 90 73 75.0 55.0 2,784 60,659 36,500 7 14 90 73 55.0 2,278 67,821 52,128

Kitchen Area - South Peak 620 7 16 90 73 75.0 55.0 1,246 27,156 3,356 7 14 90 73 55.0 850 26,081 9,820

Serving Area - South Peak 220 7 16 90 73 75.0 55.0 442 9,636 6,265 7 14 90 73 55.0 391 11,195 8,559

General office Peak 365 7 16 90 73 75.0 55.0 734 15,987 867 7 15 91 73 55.0 235 7,019 2,185

MGR Office Peak 135 7 16 90 73 75.0 55.0 1,225 26,684 409 7 14 90 73 55.0 367 8,423 1,014

Dining Area - Zone 9 Peak 1,430 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417

Dining Area - Zone 10 Peak 780 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417

Dining Area - Zone 11 Peak 781 7 16 90 73 75.0 55.0 3,579 77,968 31,801 7 14 90 73 55.0 2,116 61,458 45,417

Serving Area Peak 1,328 7 16 90 73 75.0 55.0 2,670 58,167 37,818 7 14 90 73 55.0 2,387 68,176 51,665

System - 001 Peak 14,310 89 72 75.0 55.0 40,891 890,886 249,776 90 73 55.0 21,763 624,195 368,373

System - 001 Block 14,310 7 17 89 72 75.0 55.0 22,221 484,138 248,336 7 14 90 73 55.0 21,627 610,739 373,803

Kitchen Peak 1,871 7 18 87 72 78.0 69.5 10,521 96,863 -35,666 7 18 87 72 69.5 10,521 81,769 -39,865

Mechanical Room Peak 211 7 18 87 72 84.0 65.0 185 3,834 283 7 18 87 72 65.0 185 4,306 671

System - 002 Block 2,082 7 18 87 72 78.1 69.5 10,706 100,697 9,770 7 18 87 72 69.5 10,706 86,033 5,955

Project Name: ahu 45 hines.trc Peak Clg Loads Main System Report Page -1 of 1

Zone - 001 Block 965 7 17 89 72 75.0 55.0 2,166 47,188 833 7 15 91 73 55.0 2,166 49,074 2,444

Zone - 002A Block 1,330 7 17 89 72 75.0 55.0 9,848 214,558 21,078 7 16 90 73 55.0 3,092 85,546 31,995

Zone - 002B Block 1,730

Zone - 003 Block 1,540 7 18 87 72 75.0 55.0 5,171 112,656 1,930 7 15 91 73 55.0 5,171 119,232 7,725

Zone - 004 Block 507 7 16 90 73 75.0 55.0 1,361 29,655 14,525 7 14 90 73 55.0 1,337 36,364 20,745

Zone - 005 Block 1,420 7 16 90 73 75.0 55.0 2,351 51,232 30,827 7 14 90 73 55.0 1,924 57,280 44,026

Zone - 006 Block 1,300 7 16 90 73 75.0 55.0 2,784 60,659 36,500 7 14 90 73 55.0 2,278 67,821 52,128

Zone - 007 Block 840 7 16 90 73 75.0 55.0 1,282 27,923 9,621 7 14 90 73 55.0 1,246 37,390 18,379

Zone - 008 Block 500 7 16 90 73 75.0 55.0 1,225 26,684 1,276 7 15 91 73 55.0 1,225 29,022 3,089

Zone - 009 Block 1,430 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417

Zone - 010 Block 780 7 16 90 73 75.0 55.0 2,816 61,342 31,801 7 14 90 73 55.0 2,031 60,109 45,417

Zone - 011 Block 781 7 16 90 73 75.0 55.0 3,579 77,968 31,801 7 14 90 73 55.0 2,116 61,458 45,417

Zone - 012 Block 1,328 7 16 90 73 75.0 55.0 2,670 58,167 37,818 7 14 90 73 55.0 2,387 68,176 51,665 tot people sens people sens lat zone sens zone latent zone

Lobby 261 1,092 2,599 0 0 3952 0 z1 12816 0 1

Restrooms 2785 3,058 3,021 0 0 8864 0 z2a 29,575 7988 2

Storage near restroom 143 658 638 z2b 38,894 10390 3

VCS Store A 5,048 15,886 8,641 17,973 9,985 29,575 7988 z3 22977 0 3

VCS Store B 6,991 20,664 11,239 23,378 12,988 38,894 10,390 z4 29654 13942 4

Corridor 659 1,603 3,814 0 0 6076 0 z5 56798 39050 5

VCS Storage room 7,643 3,253 6,005 0 0 16901 0 z6 51999 35750 6

Vending Area 851 25,566 3,237 27,885 13,943 29654 13942 z7 27920 8800 7

Dining Area ‑ Zone 5 2,382 45,350 9,066 78,100 39,050 56798 39050 z8 9752 700 8

Dining Area - Zone 6 2,181 41,518 8,300 71,500 35,750 51999 35750 z9 57199 39325 9

Kitchen Area ‑ South 884 14,333 3,958 5,500 2,750 19175 2750 z10 32738 21450 10

Serving Area ‑ South 314 7,026 1405 12,100 6,050 8745 6050 z11 31286 21450 11

General office 520 2,400 2330 1,149 638 5250 511 z12 53444 36520 12

MGR Office 2752 888 862 425 236 4502 189

Dining Area - Zone 9 2,399 45,670 9,130 78,650 39,325 57,199 39325

Dining Area - Zone 10 2,847 24,911 4,980 42,900 21,450 32738 21,450

Dining Area - Zone 11 4,822 21,478 4,986 42,900 21,450 31286 21450

Serving Area 1,894 43,012 8,538 73,040 36,520 53,444 36520

45376 318366 92749 475500 240135 0 455052 235365 cfm transfer factor1.06 COOLING SA DB (⁰F): 55 COOLING SETPOINT (⁰F): 75

SF 10.00% HEATING SA DB (⁰F): 90 HEATING SETPOINT (⁰F): 70

AHU VAV ROOM SIZE AHU BLOCK VAV COOLING LOAD

NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC TOTAL OA OA HTG REQ MIN.

SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH ACH ACH % CFM CFM CFM/SQ FT GPM CFM

Zone - 001 965 8.5 VAV 12,816 0 -18,958 665 984 4.86 9.00 2.00 0.4 1230 1230 1.27 2.17 1230

Zone - 002A 1330 9.0 VAV 29,575 7,988 -29,985 1535 1556 7.69 4.00 2.00 0.4 998 1555 1.17 2.75 1000

Zone - 002B 1730 10.0 VAV 38,894 10,390 -38,747 2018 2010 6.97 4.00 2.00 0.4 1442 2020 1.17 3.55 1440

Zone - 003 1540 8.5 VAV 22,977 0 -22,204 1192 1152 5.28 8.00 2.00 0.4 1745 2100 1.36 3.08 1745

Zone - 004 507 10.0 VAV 29,654 13,942 -7,240 1539 462 4.45 4.00 2.00 0.4 423 1540 3.04 0.82 425

Zone - 005 1420 10.0 VAV 56,798 39,050 -20,277 2947 1052 4.45 6.00 5.00 0.4 2958 2960 2.08 5.23 2960

Zone - 006 1300 10.0 VAV 51,999 35,750 -18,563 2698 963 4.45 6.00 5.00 0.4 2708 2710 2.08 4.79 2710

Zone - 007 840 8.5 VAV 27,920 8,800 -11,034 1449 573 4.81 4.00 2.00 0.4 595 1450 1.73 1.05 595

Zone - 008 500 8.5 VAV 9,752 700 -12,799 506 664 7.14 4.00 2.00 0.4 354 665 1.33 1.17 355

Zone - 009 1430 10.0 VAV 57,199 39,325 -20,420 2968 1060 4.45 6.00 5.00 0.4 2979 2980 2.08 5.26 2980

Zone - 010 780 10.0 VAV 32,738 21,450 -14,985 1699 778 5.98 6.00 5.00 0.4 1625 1700 2.18 2.87 1625

Zone - 011 781 10.0 VAV 31,286 21,450 -19,935 1623 1034 7.95 6.00 5.00 0.4 1627 1625 2.08 2.87 1625

Zone - 012 1328 8.5 VAV 53,444 36,520 -17,444 2773 905 4.81 4.00 2.00 0.4 941 2775 2.09 1.66 940 sum 13 14451 455052 235365 -252592 23611 13192 19625 25310 1.75 37.28 19630

GENERAL NOTES: 0.659097328

1. COOLING CFMS CALCULATED AT 510 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 59⁰F AND A COOLING SETPOINT OF 75⁰F.

2. HEATING CFMS CALCULATED AT 510 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 90⁰F AND A HEATING SETPOINT OF 70⁰F.

3. MINIMUM AIRFLOW (IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE) USED FOR AIR CHANGE CALCULATIONS.

HEATING

WATER FLOW

ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE

BLOCK VAV

HEATING LOAD

CALCULATED ROOM AIRFLOW REQUIRED VAV AIRFLOW (PER 2023 VA HVAC DM) SELECTED DESIGN VAV

AIRFLOW

SELECTED DESIGN

MIN AIRFLOW

cfm transfer factor1.057 COOLING SA DB (⁰F): 55 COOLING SETPOINT (⁰F): 75

SF 10.00% HEATING SA DB (⁰F): 90 HEATING SETPOINT (⁰F): 70

AHU ROOM ROOM SIZE AHU PEAK ROOM COOLING LOAD

NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC TOTAL OA OA HTG REQ MIN.

SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH ACH ACH % CFM CFM CFM/SQ FT CFM

Lobby 400 8.5 VAV 3,952 0 -3,958 206 206 3.63 4.00 2.00 0.4 283 600 1.50 283 600

Restrooms 465 8.5 VAV 8,864 0 -13,687 461 712 7.00 4.00 2.00 0.4 329 710 1.53 461 710

Storage near restroom 100 8.5 VAV 0 0 -1,314 0 68 0.00 4.00 2.00 0.4 71 100 1.00 71 100

VCS Store 1330 9.0 VAV 29,575 7,988 -29,985 1539 1560 7.71 4.00 2.00 0.4 998 1560 1.17 1539 1560

VCS store b 1730 9.0 VAV 38,894 10,390 -38,747 2024 2016 7.77 4.00 2.00 0.4 1298 2025 1.17 2016 2025

Corridor 587 8.5 VAV 6,076 0 -7,035 316 366 3.80 4.00 2.00 0.4 416 365 0.62 416 365

VCS Storage room 953 9.0 VAV 16,901 0 -35,170 879 1830 6.15 4.00 2.00 0.4 715 1830 1.92 879 1830

Vending Area 507 8.5 VAV 29,654 13,942 -7,240 1543 463 5.24 4.00 2.00 0.4 359 1545 3.05 463 1545

Dining Area - Zone 5 1420 10.0 VAV 56,798 39,050 -20,277 2955 1055 4.46 4.00 2.00 0.4 1183 2955 2.08 1183 2955

Dining Area - Zone 6 1300 10.0 VAV 51,999 35,750 -18,563 2706 966 4.46 4.00 2.00 0.4 1083 2705 2.08 1083 2705

Kitchen Area - South 620 8.5 VAV 19,175 2,750 -8,144 998 424 4.82 4.00 2.00 0.4 439 1000 1.61 439 1000

Serving Area - South 220 8.5 VAV 8,745 6,050 -2,890 455 150 4.82 4.00 2.00 0.4 156 455 2.07 156 455

General office 365 8.5 VAV 5,250 511 -4,795 273 249 4.82 4.00 2.00 0.4 259 275 0.75 259 275

MGR Office 135 8.5 VAV 4,502 189 -8,005 234 417 12.25 4.00 2.00 0.4 96 415 3.07 234 415

Dining Area - Zone 9 1430 10.0 VAV 57,199 39,325 -20,420 2976 1063 4.46 4.00 2.00 0.4 1192 2975 2.08 1192 2975

Dining Area - Zone 10 780 10.0 VAV 32,738 21,450 -14,985 1703 780 6.00 4.00 2.00 0.4 650 1705 2.19 780 1705

Dining Area - Zone 11 781 10.0 VAV 31,286 21,450 -19,935 1628 1037 7.97 4.00 2.00 0.4 651 1630 2.09 1037 1630

Serving Area 1328 8.5 VAV 53,444 36,520 -17,444 2781 908 4.82 4.00 2.00 0.4 941 2780 2.09 941 2780 sum 14451 455,052 235,365 -272592 23678 14270 11117 25630 1.77 13432 25630

GENERAL NOTES:

1. COOLING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 55⁰F AND A COOLING SETPOINT OF 75⁰F.

2. HEATING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 90⁰F AND A HEATING SETPOINT OF 70⁰F.

3. MINIMUM AIRFLOW (IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE) USED FOR AIR CHANGE CALCULATIONS.

Directions:

Sensible peak room cooling load: From trace room checksums, sum the space peak envelope loads, the space peak internal loads and the space peak ceiling load.

Latent peak room cooling load: From Trace room checksums, subtract the people sensible load from the total people load.

Note:

AHU ROOM ROOM SIZE AHU PEAK ROOM COOLING LOAD

NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC TOTAL OA OA HTG REQ MIN.

SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH ACH ACH % CFM CFM CFM/SQ FT CFM

Kitchen 1871 8.5 VAV 96,863 -39,865 -48,768 6720 5075 19.15 10.00 2.00 100.0 2651 6720 3.59 5075 6720

Mechanical Room 211 12.0 VAV 3,834 671 -6,460 266 672 6.30 4.00 2.00 100.0 169 670 3.18 266 670 sum 2082 100,697 5,955 -55228 6986 2819 7390 3.55 5341 7390

GENERAL NOTES:

1. COOLING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 65 ⁰F AND A COOLING SETPOINT OF 80⁰F.

2. HEATING CFMS CALCULATED AT 617 FT ELEVATION WITH A SUPPLY AIR TEMPERATURE OF 90⁰F AND A HEATING SETPOINT OF 70⁰F.

3. MINIMUM AIRFLOW (IN MOST CASES, THIS IS THE HEATING AIR FLOW RATE) USED FOR AIR CHANGE CALCULATIONS.

AHU ROOM ROOM SIZE AHU PEAK ROOM COOLING LOAD

NAME AREA HEIGHT SYSTEM TYPE SENSIBLE LATENT COOLING HEATING CALC COOLING HEATING

SF FT VAV OR CV BTUH BTUH BTUH CFM CFM ACH BTUH BTUH

Kitchen 1871 8.5 VAV 96,863 -39,865 -48,768 6720 5075 19.15 168006 3901440

Mechanical Room 211 12.0 VAV 3,834 671 -6,460 266 672 6.30 6650 516800

174656 4418240

14.55

Kitchen 1871 8.5 VAV 49,763 -39,865 -48,768 3452 5075 13.03 86312 3901440

Mechanical Room 211 12.0 VAV 3,834 671 -6,460 266 672 6.30 6650 516800

92962 4418240

7.75

EQUIPMENT

ON

EQUIPMENT

OFF

PEAK ROOM

HEATING LOAD

CALCULATED ROOM AIRFLOW COIL LOAD

ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE - SYSTEM 2

PEAK ROOM

HEATING LOAD

CALCULATED ROOM AIRFLOW REQUIRED ROOM AIRFLOW (PER 2023 VA HVAC DM) SELECTED DESIGN ROOM

AIRFLOW

SELECTED DESIGN

MIN AIRFLOW ROOM RETURN CFM

REQUIRED ROOM AIRFLOW (PER 2023 VA HVAC DM) SELECTED DESIGN

MIN AIRFLOW

ROOM COOLING AND HEATING LOADS OUTPUT DATA SUMMARY SCHEDULE - SYSTEM 1

ROOM RETURN CFM

PEAK ROOM

HEATING LOAD

SELECTED DESIGN ROOM

AIRFLOW

CALCULATED ROOM AIRFLOW

Input

Output

People No. Vent. Airflow (CFM) Cooling Vent. Load (BTU/hr) Heating Vent. Load (BTU/hr) CFM per person (check) Engineer Inputs AHU

AHU-1 879 8314 215915 571072 9.46 air density at site (lb/ft^3) 0.0725

Heating GPM site elevation (ft asl) 617

40% glycol HW 41 CFM Trans Factor 1.06 Enthalpy @ xx% RH hum ratio (lb water/lb dry air)

38 SADB AHU summer (F) 54 22.4 0.0092

SADB AHU winter (F) 65

Summer Design (F) 89.5 <---

Cooling Airflow (CFM) Heating Airflow (CFM) Percent OA Cooling Percent OA Heating Summer Design Wb (F) 73.2 <--- ASHRAE climate data

AHU-1 24424 19630 37% 42% Winter Design (F) 0.2 <---

Summer RA Db (F) 77

Winter RA Db (F) 67 Enthalpy @ xx% RH hum ratio (lb water/lb dry air)

Sens Cooling Load (BTU/hr) Heating Load (BTU/hr) Summer MA Db (F) 81.5875 32.7 0.0126

714229 607057 Winter MA Db (F) 35.82551197

Total Cooling Load (BTU/hr) hw2(lat ht of water @ 0°f) 1060

1078739 chill water delta T 14.0

Cooling GPM Heating GPM heating water delta T 30

40% glycol CW 164 40% glycol HW 40 1.1 HR

154 40 Winter OA 0.000157143 lbs/lb

6.445

Winter RA 0.006445 lbs/lb

People No. Vent. Airflow (CFM) Cooling Vent. Load (BTU/hr) Heating Vent. Load (BTU/hr) CFM per person (check)

MAU-1 31 2205 27580 128084 71.13 Engineer Inputs MAU

Heating GPM air density at site (lb/ft^3) 0.0725

40% glycol HW 9 site elevation (ft asl) 617 psych chart @52

9 CFM Trans Factor 1.06 Enthalpy @ xx% RH hum ratio (lb water/lb dry air)

SADB AHU summer (F) 55 23 0.0102

SADB AHU winter (F) 80

Cooling Airflow (CFM) Heating Airflow (CFM) Percent OA Cooling Percent OA Heating Summer Design (F) 91.8 <---

MAU-1 10706 10706 100% 100% Summer Design Wb (F) 74.6 <--- ASHRAE climate data

Winter Design (F) 0.2 <---

Summer RA Db (F)

Sens Cooling Load (BTU/hr) Heating Load (BTU/hr) Winter RA Db (F) Enthalpy @ xx% RH hum ratio (lb water/lb dry air)

417620 905599 Summer MA Db (F) 91.8 38 0.0144

Total Cooling Load (BTU/hr) Winter MA Db (F) 0.2

688342 hw2(lat ht of water @ 0°f) 1060

Cooling GPM Heating GPM VAV GPM chill water delta T 14

40% glycol CW 105 40% glycol HW 59 37.28 heating water delta T 30

98 60 1.1 HR

Winter OA 0.000157143 lbs/lb

TOTAL: TOTAL: 6.445

BTU 1767081 BTU 1765248 2021.638 Lbm/hr Winter RA 0.006445 lbs/lb

GPM W/ Glycol 269 GPM W/ Glycol 136 8086.55 EDR

GPM 252 GPM 137 4.043275 GPM CONDENSATE

Pipe Size Required 4 in Pipe Size Required 3 in

HEATING GHW LOAD

Ventilation Calculations - System 1

Mixed Air Calculations

Ventilation Calculations - System 2

Mixed Air Calculations

COOLING GCW LOAD

ASHRAE 0.4% CONDITIONS

Humidifier sizing

Sizing criteria:

OA calc. (cfm) = 40% of max. airflow

Indoor conditions: 25% RH

72°F DB

For mechanical ventilation systems having a fixed quantity of outdoor air [(ASHRAE Handbook 2016 - HVAC Systems and Equipment, eq. (2)]:

Total Flow = 19,630 cfm

INPUT:

Qo = 7852 cfm ρ = 0.074 lb/ft

Wi = 25.732 grains of moisture/lbdry air 0.003676 lbwater/lbdry air

Wo = 1.505 grains of moisture/lbdry air 0.000215 lbwater/lbdry air

S = 0 lbwater/h

L = 0 lbwater/h

OUTPUT:

H = 120.7 lbwater/h

Humidifier sizing

Sizing criteria:

OA calc. (cfm) = 100% of max. airflow

Indoor conditions: 25% RH

72°F DB

For mechanical ventilation systems having a fixed quantity of outdoor air [(ASHRAE Handbook 2016 - HVAC Systems and Equipment, eq. (2)]:

Total Flow = 25,545 cfm

INPUT:

Qo = 25545 cfm ρ = 0.074 lb/ft

Wi = 21.721 grains of moisture/lbdry air 0.003103 lbwater/lbdry air

Wo = 14.35 grains of moisture/lbdry air 0.00205 lbwater/lbdry air

S = 0 lbwater/h

L = 0 lbwater/h

OUTPUT:

H = 119.4 lbwater/h

� = 60���( �)-S+L

� = 60���( �)-S+L

Hydronic Primary Circuit Piping Loss Heating Water

Longest Pipe Length (ft) 356

Longest Pipe Length w/ fittings (ft) 712

Pipe drop (ft/100ft of pipe) 4

Pipe Friction Loss (ft head) 28.5

VAV Coil Drop (ft head) 15

Valve Loss (ft head) 12

Heat Exchanger 6.5

Total Head Loss (ft) 62

Hydronic Primary Circuit Piping Loss Glycol Chilled water

Longest Pipe Length (ft) 325

Longest Pipe Length w/ fittings (ft) 650

Pipe drop (ft/100ft of pipe) 4

Pipe Friction Loss (ft head) 26

AHU Coil Drop (ft head) 20

Valve Loss (ft head) 15

Heat Exchanger 10

Total Head Loss (ft) 71

C hapter 7: Psychrom etrics

2019 N

C

EES

7.3 Psychrom

etric Charts

ASHRAE Psychrom etric Chart N

o. 1 - Sea Level

Source: R eprinted w ith perm ission. "A

SH

R

A E Psychrom etric C hart N

o. 1," A

SH

R A

E: 2016.

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Arrow

MHoiles Callout

HR = 0.0122

MHoiles Callout

HR = 0.096

MHoiles Line

MHoiles Text Box

AHU-1

MHoiles Line

MHoiles Callout H=32.7

MHoiles Text Box

ASHRAE 1%

DB (F) 89.5 | WB =73.2

summer MA 81.6 summer RA 77 Summer SA 56

MHoiles Ellipse

MHoiles Line

MHoiles PolyLine

MHoiles Line

MHoiles Line

MHoiles Callout

SHR= .7

MHoiles Callout H=24.6

MHoiles Line

MHoiles Callout 56 dbF

MHoiles Callout 75 dbF

MHoiles Callout

89.5 dbF

MHoiles Line

MHoiles Line

MHoiles Callout 77 dbF

MHoiles Callout

81.6 dbF

MHoiles Callout 74.6wb F

C hapter 7: Psychrom etrics

2019 N

C

EES

7.3 Psychrom

etric Charts

ASHRAE Psychrom etric Chart N

o. 1 - Sea Level

Source: R eprinted w ith perm ission. "A

SH

R

A E Psychrom etric C hart N

o. 1," A

SH

R A

E: 2016.

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Arrow

MHoiles Callout

HR = 0.0144

MHoiles Callout

HR = 0.0102

MHoiles Text Box

MAU-1

MHoiles Text Box

ASHRAE 0.4%

DB (F) 91.8 | WB =74.6

summer SA 57

MHoiles PolyLine

MHoiles Line

MHoiles Callout H=38

MHoiles Line

MHoiles Callout H=24.6

MHoiles Line

MHoiles Line

MHoiles Line

MHoiles Callout 57 dbF

MHoiles Callout 74.6wb F

MHoiles Callout 75 dbF

MHoiles Callout

91.8 dbF

MHoiles Callout

SHR= .7609

ASHRAE PIPE THERMAL EXPANSION CALCULATIONS - L , Z, AND U BENDS/EXPANSION LOOPS

use pipe dropdown FROM HVAC SYSTEMS AND EQUIPMENT - CHAPTER 46. PIPES, TUBES, AND FITTINGS

---------------------> 3" STANDARD Δ (IN/100FT) L BEND FT Z BEND FT

COPPER 3.105 L, COPPER 18 L 11.5

60 PSI steam STEEL 2.53 U BEND FT

W 3.75 change pipe length ---------> ANCH-ANCH EXP/L1 for L loops 85.00 H 7.5

ACTUAL Δ COPPER 2.63925 2H 15

ACTUAL Δ STEEL 2.15 L BEND FT Z BEND FT

L, STEEL 17.25 L 11.00

OD 3.125 U BEND FT

OD 3.500 W 3.50

H 7.00

2H 14.00

*Rounded lengths up to nearest 0.25 ft

L1

U-bend

ASHRAE PIPE THERMAL EXPANSION CALCULATIONS - L , Z, AND U BENDS/EXPANSION LOOPS

use pipe dropdown FROM HVAC SYSTEMS AND EQUIPMENT - CHAPTER 46. PIPES, TUBES, AND FITTINGS

---------------------> 3" STANDARD Δ (IN/100FT) L BEND FT Z BEND FT

COPPER 2.05 L, COPPER 11.25 L 7.25

hydronic @ 180°F STEEL 1.37 U BEND FT

W 2.25 change pipe length ---------> ANCH-ANCH EXP/L1 for L loops 50.00 H 4.50

ACTUAL Δ COPPER 1.03 2H 9.00

ACTUAL Δ STEEL 0.69 L BEND FT Z BEND FT

L, STEEL 9.75 L 6.25

OD 3.125 U BEND FT

OD 3.500 W 2.00

H 4.00

2H 8.00

*Rounded lengths up to nearest 0.25 ft

L1

U-bend

DUCT STATIC PRESSURE LOSS CALCULATIONS

CLIENT: VA FILE NAME: 19.19 Replace AHU Bldg 45_MECH_R19 PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: Supply DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Diffuser 850 24 24 24.0 1.00 213 0.00 0.050 0.050

2 Flex Duct 850 16.0 1.00 609 0.02 0.000 0.050

3 Round Take Off 850 16.0 5.6 1.00 609 0.02 0.129 0.179

4 Duct 850 14 12 13.2 10.583 1.00 729 0.03 0.064 0.007 0.186

5 Transition 45 850 14 12 13.2 0.29 1.00 729 0.03 0.010 0.196

6 Duct 1700 24 12 17.7 12.916 1.00 850 0.05 0.060 0.008 0.204

7 Elbow 90 1700 24 12 17.7 0.01 1.00 850 0.05 0.000 0.204

6 Duct 1700 24 12 17.7 8.625 1.00 850 0.05 0.060 0.005 0.209

7 Elbow 90 1700 24 12 17.7 0.01 1.00 850 0.05 0.000 0.210

8 Duct 1700 24 12 17.7 36.583 1.00 850 0.05 0.060 0.003 0.212

9 Transition 45 1700 17 16 16.6 0.29 1.00 900 0.05 0.015 0.227

10 Duct 1700 17 16 16.6 0.833 1.00 900 0.05 0.073 0.003 0.230

11 VAV 1700 0.0 1.00 0 0.00 0.700 0.930

12 Duct 1700 14.0 3.416 1.00 1590 0.16 0.264 0.009 0.939

13 Round Take Off 1700 14.0 4 5.6 1.00 1590 0.16 0.264 0.011 0.949

14 Duct 6305 28 20 24.5 18.25 1.00 1621 0.16 0.139 0.025 0.974

15 Elbow 90 6305 28 20 24.5 0.01 1.00 1621 0.16 0.002 0.976

16 Duct 6305 28 20 24.5 5.333 1.00 1621 0.16 0.139 0.007 0.984

17 Elbow 90 6305 28 20 24.5 0.01 1.00 1621 0.16 0.002 0.985

18 Transition 30 6305 28 20 24.5 0.25 1.00 1621 0.16 0.041 1.026

19 Duct 6305 30 20 25.4 5.75 1.00 1513 0.14 0.116 0.007 1.033

20 Transition 30 6305 30 20 25.4 0.25 1.00 1513 0.14 0.036 1.069

21 Duct 9073 30 24 27.5 31.833 1.00 1815 0.21 0.149 0.047 1.116

22 Elbow 90 9073 30 24 27.5 0.01 1.00 1815 0.21 0.002 1.118

23 Rect. Duct 23861 113 32 62.7 5.166 1.00 950 0.06 0.016 0.001 1.119

24 AHU 23861 113 32 62.7 0.86 1.00 950 0.06 0.048 1.167

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: Return DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Diffuser 3000 24 24 26.2 1.00 750 0.04 0.050 0.050

2 Duct 3000 20 20 21.9 1.416 1.00 1080 0.07 0.074 0.001 0.051

3 Take off 3000 20 20 21.9 1.17 1.00 1080 0.07 0.085 0.136

4 Duct 6000 50 18 31.8 9.75 1.00 960 0.06 0.037 0.004 0.140

5 Elbow 30 6000 50 18 31.8 0.0045 1.00 960 0.06 0.000 0.140

6 Duct 6000 50 18 31.8 9.333 1.00 960 0.06 0.037 0.003 0.143

7 Elbow 30 6000 50 18 31.8 0.0045 1.00 960 0.06 0.000 0.144

8 Duct 6000 50 18 31.8 26.666 1.00 960 0.06 0.037 0.010 0.154

9 Elbow 90 6000 50 18 31.8 0.01 1.00 960 0.06 0.001 0.154

10 Duct 6000 50 18 31.8 37.416 1.00 960 0.06 0.037 0.014 0.168

11 Transition 45 6000 50 18 31.8 0.29 1.00 960 0.06 0.017 0.185

12 Duct 14500 50 30 42.0 34.833 1.00 1392 0.12 0.054 0.019 0.204

13 Elbow 90 14500 50 30 42.0 1.2 1.00 1392 0.12 0.145 0.349

14 Transition 45 6000 50 30 42.0 0.29 1.00 576 0.02 0.006 0.355

15 Duct 14500 60 32 47.3 5.916 1.00 1088 0.07 0.029 0.002 0.350

16 Elbow 30 14500 60 32 47.3 0.0045 1.00 1088 0.07 0.000 0.351 17 Duct 14500 60 32 47.3 3.583 1.00 1088 0.07 0.029 0.001 0.352

18 Elbow 30 14500 60 32 47.3 0.0045 1.00 1088 0.07 0.000 0.352

19 Duct 19550 60 32 47.3 5.916 1.00 1466 0.13 0.051 0.003 0.355

20 Elbow 90 19550 60 32 47.3 1.3 1.00 1466 0.13 0.174 0.529

21 Duct 19550 60 32 47.3 4.124 1.00 1466 0.13 0.051 0.002 0.531

22 AHU 19550 60 32 47.3 0.86 1.00 1466 0.13 0.115 0.647

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-1 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Hood 1520 96 55 78.7 1.00 41 0.00 0.050 0.050

2 Duct 1520 18 18 19.7 3.653 1.00 676 0.03 0.034 0.001 0.051

3 45-EF-1 1520 22 22 24.0 0.86 1.00 0 0.00 0.000 0.051

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-3 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Exhaust hood 1200 60 42 54.7 1.00 69 0.00 0.050 0.050

2 Duct 1200 18 18 19.7 3.25 1.00 533 0.02 0.022 0.001 0.051

3 Elbow 1.18 1200 18 18 19.7 0 1.00 533 0.02 0.000 0.051

4 Duct 1200 18 18 19.7 0.75 1.00 533 0.02 0.022 0.000 0.051

5 45-EF-3 1200 26 26 28.4 0.86 1.00 256 0.00 0.004 0.054

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-4 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Exhaust Hood 750 48 36 45.3 1.00 63 0.00 0.050 0.050

2 Duct 750 12 12 13.1 2 1.00 750 0.04 0.069 0.001 0.051

3 Elbow 90 750 12 12 13.1 0.01 1.00 750 0.04 0.000 0.052

4 Duct 750 12 12 13.1 0.646 1.00 750 0.04 0.069 0.000 0.052

5 Elbow 40 750 12 12 13.1 0.006 1.00 750 0.04 0.000 0.052

6 Duct 750 12 12 13.1 9.494 1.00 750 0.04 0.069 0.007 0.059

7 Elbow 40 750 12 12 13.1 0.006 1.00 750 0.04 0.000 0.059

8 Duct 750 12 12 13.1 1 1.00 750 0.04 0.069 0.001 0.060

9 Elbow 90 750 12 12 13.1 0.01 1.00 750 0.04 0.000 0.060

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-5 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Exhaust Hood 5400 97 110 112.9 1.00 73 0.00 0.050 0.050

2 Duct 5400 26 26 28.4 3.666 1.00 1150 0.08 0.060 0.002 0.052

3 Elbow 1.18 5400 26 26 28.4 0 1.00 1150 0.08 0.000 0.052

4 Duct 5400 26 26 28.4 0.75 1.00 1150 0.08 0.060 0.000 0.053

5 45-EF-5 5400 46 46 50.3 0.86 1.00 367 0.01 0.007 0.060

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-6 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Diffuser 300 24 24 26.2 1.00 75 0.00 0.050 0.050

2 Duct 300 12 10 12.0 4 1.00 360 0.01 0.019 0.001 0.051

3 Elbow 90 300 12 10 12.0 0.01 1.00 360 0.01 0.000 0.051

4 Duct 300 12 10 12.0 9.083 1.00 360 0.01 0.019 0.002 0.053

5 Elbow 90 300 12 10 12.0 0.01 1.00 360 0.01 0.000 0.053

6 Duct 900 14 14 15.3 30.416 1.00 661 0.03 0.045 0.014 0.066

7 Transition 45 900 14 14 15.3 0.29 1.00 661 0.03 0.008 0.074

8 Duct 1200 14 14 15.3 3.083 1.00 882 0.05 0.077 0.002 0.077

9 Transition 45 1200 14 14 15.3 0.29 1.00 882 0.05 0.014 0.091

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-7 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Exhaust Hood 665 48 36 45.3 1.00 55 0.00 0.050 0.050

2 Duct 665 18 18 19.7 0.25 1.00 296 0.01 0.007 0.000 0.050

3 Elbow 90 665 18 18 19.7 0.01 1.00 296 0.01 0.000 0.050

4 Duct 665 18 18 19.7 0.833 1.00 296 0.01 0.007 0.000 0.050

5 Elbow 90 665 18 18 19.7 0.01 1.00 296 0.01 0.000 0.050

6 Duct 665 18 18 19.7 0.5 1.00 296 0.01 0.007 0.000 0.050

7 Elbow 45 665 18 18 19.7 0.006 1.00 296 0.01 0.000 0.050

8 Elbow 45 665 18 18 19.7 0.006 1.00 296 0.01 0.000 0.050

9 Duct 665 18 18 19.7 0.5 1.00 296 0.01 0.007 0.000 0.050

10 45-EF-7 665 26 26 28.4 0.86 1.00 142 0.00 0.001 0.051

PROJECT NUMBER: 19.19 DESIGNER: Claire Kincaid

DESCRIPTION: 45-EF-8 DATE: 04/13/23

Flow Rectangular Size Equivalent Duct LOSS CORR Velocity Friction Loss Cumulative

No Item (CFM) Width Height Diameter Length COEFF Factor FPM Vp per 100' per Item Loss

1 Diffuser 700 24 24 26.2 1.00 175 0.00 0.050 0.050

2 Duct 700 12 12 13.1 1.583 1.00 700 0.03 0.060 0.001 0.051

3 Take Off 700 12 12 13.1 5.13 1.00 700 0.03 0.157 0.208

4 Duct 700 12 12 13.1 3.833 1.00 700 0.03 0.060 0.002 0.210

5 Elbow 90 700 12 12 13.1 0.01 1.00 700 0.03 0.000 0.210

6 Duct 1500 16 14 16.4 12.416 1.00 964 0.06 0.085 0.010 0.221

7 Elbow 90 1500 16 14 16.4 0.01 1.00 964 0.06 0.001 0.221

8 Duct 1500 16 14 16.4 3.5 1.00 964 0.06 0.085 0.003 0.224

9 Transition 45 1500 16 14 16.4 0.006 1.00 964 0.06 0.000 0.225

10 Duct 1800 18 14 17.3 15.333 1.00 1029 0.07 0.089 0.014 0.238

11 Elbow 90 1800 18 14 17.3 0.01 1.00 1029 0.07 0.001 0.239

12 Duct 1800 18 14 17.3 2 1.00 1029 0.07 0.089 0.002 0.241

13 Take off 1800 18 14 17.3 5.13 1.00 1029 0.07 0.338 0.579

14 Duct 1800 18 18 19.7 2.583 1.00 800 0.04 0.047 0.001 0.580

15 Elbow 1.18 1800 18 18 19.7 0 1.00 800 0.04 0.000 0.580

16 Duct 1800 18 18 19.7 0.75 1.00 800 0.04 0.047 0.000 0.581

17 45-EF-8 1800 26 26 28.4 0.86 1.00 383 0.01 0.008 0.589

Piping System Loss Calculation Sheet

Project Name:

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100') *

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 184.8 264 4 3.905 10 Other 1 184.84 Copper 150 3.93 7.3 15.4 115.0

Elbow 7 264 4 3.905 10 90° Elbow 1 7 Copper 150 3.93 0.3 0.6 4.4

Tee 1 264 4 3.905 10 Tee - Line Flow 6 6 Copper 150 3.93 0.2 0.5 3.7

High 3.93

Low 3.93

Average 3.93

7.8 16.5 123.1

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Chilled Water Return

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 176.7 291 4 3.905 10 Other 1 176.66 Copper 150 4.71 8.3 14.7 109.9

Elbow 6 291 4 3.905 10 90° Elbow 10 60 Copper 150 4.71 2.8 5.0 37.3

Tee 1 291 4 3.905 10 Tee - Line Flow 6 6 Copper 150 4.71 0.3 0.5 3.7

High 4.71

Low 4.71

Average 4.71

11.4 20.2 151.0

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Chilled Water Supply

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 98.3 290 4 4.026 10 Other 1 98.3 Steel 130 5.25 5.2 8.7 65.0

Elbow 90 11 290 4 4.026 10 90° Elbow 10 110 Steel 130 5.25 5.8 9.7 72.7

Tee 1 290 4 4.026 10 Tee - Line Flow 6 6 Steel 130 5.25 0.3 0.5 4.0

Inline Pump 1 290 4 4.026 10 Steel 130

High 5.25

Low 5.25

Average 5.25

11.3 18.9 141.7

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Glycol Chilled Water Return

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 94.42 290 4 4.026 10 Other 1 94.42 Steel 130 5.25 5.0 8.3 62.4

Elbow 90 8 290 4 4.026 10 90° Elbow 10 80 Steel 130 5.25 4.2 7.1 52.9

Tee 1 290 4 4.026 10 Tee - Line Flow 6 6 Steel 130 5.25 0.3 0.5 4.0

HX 1 10.0

ahu 1 20.0 valve 1 15.0

High 5.25

Low 5.25

Average 5.25

54.5 15.9 119.3

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Glycol Chilled Water Supply

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 80.32 2.2 1 1/4 1.265 5 Other 1 80.32 Copper 150 0.13 0.1 0.7 5.2

Elbow 90 8 2.2 1 1/4 1.265 5 90° Elbow 3.1 24.8 Copper 150 0.13 0.0 0.2 1.6

High 0.13

Low 0.13

Average 0.13

0.1 0.9 6.9

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

30 PSI Medium Pressure Return

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Ref

Inside

Diameter

Steel

Inside

Diameter

Copper

Inside

Diameter

Pipe Size

Reference

Fitting Type Fitting

Type

Reference

Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 21.87 0.6 1 1/2 5 1.61 1.505 1.505 6 Other 1 1 21.87 Copper 150 0.01 0.0 0.3 2.0

Pipe 2.63 0.6 2 1/2 7 2.469 2.465 2.465 8 Other 1 1 2.63 Copper 150 0.00 0.0 0.1 0.7 pipe 11.88 0.6 3 8 3.068 2.945 2.945 9 Other 1 1 11.88 Copper 150 0.00 0.0 0.6 4.2 pipe 84.66 0.6 4 9 4.026 3.905 3.905 10 Other 1 1 84.66 Copper 150 0.00 0.0 7.0 52.7 pipe 0.65 0.6 5 10 5.047 4.875 4.875 11 Other 1 1 0.65 Copper 150 0.00 0.0 0.1 0.6

Elbow 90 2 0.6 4 3 1.049 1.025 1.025 10 90° Elbow 2 10 20 Copper 150 0.03 0.0 0.1 0.9

Elbow 90 3 0.6 3 8 3.068 2.945 2.945 9 90° Elbow 2 7 21 Copper 150 0.00 0.0 1.0 7.4

Elbow 90 4 0.6 2 1/2 7 2.469 2.465 2.465 8 90° Elbow 2 5 20 Copper 150 0.00 0.0 0.7 5.0

Elbow 90 2 0.6 1 1/2 5 1.61 1.505 1.505 6 90° Elbow 2 3.6 7.2 Copper 150 0.01 0.0 0.1 0.7

Tee 3 0.6 2 1/2 7 2.469 2.465 2.465 8 Tee - Line Flow 4 3 9 Copper 150 0.00 0.0 0.3 2.2

Tee 1 0.6 3 8 3.068 2.945 2.945 9 Tee - Line Flow 4 5 5 Copper 150 0.00 0.0 0.2 1.8

Tee 1 0.6 1 1/2 5 1.61 1.505 1.505 6 Tee - Branch Flow 5 7.1 7.1 Copper 150 0.01 0.0 0.1 0.7

210.99 High 0.03

Low 0.00

Average 0.00

0.0 10.5 78.1

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

30 PSI Medium Pressure Steam

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 253.4 10.8 1 1/2 1.505 6 Other 1 253.4 Copper 150 1.10 2.8 3.1 23.4

Elbow 90 7 10.8 1 1/2 1.505 6 90° Elbow 3.6 25.2 Copper 150 1.10 0.3 0.3 2.3

High 1.10

Low 1.10

Average 1.10

3.1 3.4 25.7

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Pumped Condensate

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

Pipe 5.18 1180 2 1/2 2.469 8 Other 1 5.18 Steel 130 760.44 39.4 0.2 1.3

Pipe 248.4 1180 3 3.068 9 other 1 248.35 steel 130 264.29 656.4 12.7 95.4

Elbow 90 4 1180 2 1/2 2.469 8 90° Elbow 5 20 Steel 130 760.44 152.1 0.7 5.0

Tee 1 1180 3 3.068 9 Tee - Line Flow 5 5 Steel 130 264.29 13.2 0.3 1.9

High 760.44

Low 264.29

Average 512.36

861.1 13.8 103.6

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Medium Pressure Steam

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Ref

Inside

Diameter

Steel

Inside

Diameter

Copper

Inside

Diameter

Pipe Size

Reference

Fitting Type Fitting

Type

Reference

Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculated

Volume

(Gal)

MAU RISER 13.3 60 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 53.2 Copper 150 6.82 3.6 1.1 8.6

AHU RISER 13.3 40 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 53.2 Copper 150 3.22 1.7 1.1 8.6

Tee 1 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 4 Copper 150 17.55 0.7 0.1 0.6

AHU/MAU PIPE 8 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 32 Copper 150 17.55 5.6 0.7 5.1

Elbow 90 1 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 4 Copper 150 17.55 0.7 0.1 0.6

Pipe 14.25 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 57 Copper 150 17.55 10.0 1.2 9.2 elbow 90 1 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 4 Copper 150 17.55 0.7 0.1 0.6 pipe 3.15 100 2 6 2.067 1.985 1.985 7 90° Elbow 2 4 12.6 Copper 150 17.55 2.2 0.3 2.0

Elbow 90 2 55 2 1/2 7 2.469 2.465 2.465 8 90° Elbow 2 5 10 Copper 150 2.02 0.2 0.3 2.5

Elbow 90 1 65 3 8 3.068 2.945 2.945 9 90° Elbow 2 7 7 Copper 150 1.16 0.1 0.3 2.5

Tee 1 6 1 3 1.049 1.025 1.025 4 90° Elbow 2 2.3 2.3 Copper 150 2.40 0.1 0.0 0.1

Tee 1 10 1 1/4 4 1.38 1.265 1.265 5 Tee - Line Flow 4 2 2 Copper 150 2.22 0.0 0.0 0.1

Tee 2 25 1 1/2 5 1.61 1.505 1.505 6 Tee - Line Flow 4 2.4 4.8 Copper 150 5.19 0.2 0.1 0.4

Tee 2 45 2 6 2.067 1.985 1.985 7 Tee - Line Flow 4 2.8 5.6 Copper 150 4.01 0.2 0.1 0.9

Tee 1 55 2 1/2 7 2.469 2.465 2.465 8 Tee - Line Flow 4 3 3 Copper 150 2.02 0.1 0.1 0.7

Tee 1 65 3 8 3.068 2.945 2.945 9 Tee - Line Flow 4 5 5 Copper 150 1.16 0.1 0.2 1.8

Tee 1 3 3/4 2 0.824 0.785 0.785 3 Tee - Branch Flow 5 3.6 3.6 Copper 150 2.44 0.1 0.0 0.1

Vav 1 Copper 150 15.0 valve 1 12.0

HX 1 6.5

High 17.55

Low 1.16 2.6 19.7

Average 6.27

47.5

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Glycol HR Total System Volume

Project Number:

Date:

Modification Date:

System:

User should enter data in yellow colored cells and not copper colored cells.

To add rows, right click on the last row number (left side of sheet), choose "Copy, right click on the last row number again and choose "Insert Copied Cells".

Steel= 130 Copper= 150 1.3

Description Qua/

Length

Flow

(GPM)

Pipe Size Inside

Diameter

Pipe Size

Reference

Fitting Type Equivalent

Length Ea.

(ft wg)

Equivalent

Length Tot

(ft wg)

Tubing

(Copper or Steel)

Friction

Factor

Friction

(ft wg/100')

Calculated

Friction

(ft wg)

Given

Friction

(ft wg)

Calculated

Volume

(ft^3)

Calculate d Volume

(Gal)

Pipe 20.09 3 3/4 0.785 3 Other 1 20.09 Copper 150 2.44 0.5 0.1 0.5

Pipe 59.1 6 1 1.025 4 Other 1 59.1 Copper 150 2.40 1.4 0.3 2.5

Pipe 99.86 10 1 1/4 1.265 5 Other 1 99.86 Copper 150 2.22 2.2 0.9 6.5

Pipe 58.69 25 1 1/2 1.505 6 Other 1 58.69 Copper 150 5.19 3.0 0.7 5.4

Pipe 37.6 45 2 1.985 7 Other 1 37.6 Copper 150 4.01 1.5 0.8 6.0

Pipe 79.23 55 2 1/2 2.465 8 Other 1 79.23 Copper 150 2.02 1.6 2.6 19.6

Pipe 0.35 65 3 2.945 9 Other 1 0.35 Copper 150 1.16 0.0 0.0 0.1

Elbow 90 1 6 1 1.025 4 90° Elbow 2.3 2.3 Copper 150 2.40 0.1 0.0 0.1

Elbow 90 1 10 1 1/4 1.265 5 90° Elbow 3.1 3.1 Copper 150 2.22 0.1 0.0 0.2

Elbow 90 2 25 1 1/2 1.505 6 90° Elbow 3.6 7.2 Copper 150 5.19 0.4 0.1 0.7

Elbow 90 2 45 2 1.985 7 90° Elbow 4 8 Copper 150 4.01 0.3 0.2 1.3

Elbow 90 2 55 2 1/2 2.465 8 90° Elbow 5 10 Copper 150 2.02 0.2 0.3 2.5

Elbow 90 1 65 3 2.945 9 90° Elbow 7 7 Copper 150 1.16 0.1 0.3 2.5

Tee 1 6 1 1.025 4 Tee - Line Flow 1.6 1.6 Copper 150 2.40 0.0 0.0 0.1

Tee 1 10 1 1/4 1.265 5 Tee - Line Flow 2 2 Copper 150 2.22 0.0 0.0 0.1

Tee 2 25 1 1/2 1.505 6 Tee - Line Flow 2.4 4.8 Copper 150 5.19 0.2 0.1 0.4

Tee 2 45 2 1.985 7 Tee - Line Flow 2.8 5.6 Copper 150 4.01 0.2 0.1 0.9

Tee 1 55 2 1/2 2.465 8 Tee - Line Flow 3 3 Copper 150 2.02 0.1 0.1 0.7

Tee 1 65 3 2.945 9 Tee - Line Flow 5 5 Copper 150 1.16 0.1 0.2 1.8

Tee 1 3 3/4 0.785 3 Tee - Branch Flow 3.6 3.6 Copper 150 2.44 0.1 0.0 0.1

High 5.19

Low 1.16

Average 2.79

12.1 7.0 52.1

* Based on Hazen-Williams pipe friction equation as listed in Cameron Hydraulic Data , copyright 1998 - Ingersoll-Dresser Pump Co.

Hazen-Williams Friction Factors: Fitting Multiplier:

Total System Losses

Replace AHU Bldg 45

19.19

9/17/2020

6/15/2023

Hydronic Supply

Parameters Symbol Value Unit Reference

Actual Mass Flow Rate through Relief Valve W 0.583333333 lb/s Process Data

Discharge Elbow Size inch P&ID

Thickness of Discharge Pipe SCH P&ID

Discharge Pipe Outer Diameter 3.5 inch Pipe Data

Discharge Pipe Thickness 0.216 inch Pipe Data

Discharge Elbow Area A1 7.39 inch 2 Pipe Data

Stagnation Enthalpy at Safety Valve Inlet h0 1160 btu/lb Steam Table steam enthalpy plus kinetic

Gravitational Constant gc 32.2 ft/s

Steam Condition Process Data

Joule's Constant J 778.16 ft-lb/btu

Calculation Constant a 823 btu/lb ASME B 31.1

Calculation Constant b 4.33 ASME B 31.1

Atmospheric Pressure Pa 14.7 psi Process Data

Pressure at Discharge Elbow Outlet P1 2.80 psia ASME B 31.1

Velocity at Discharge Elbow Outlet V1 1484.83 ft/s ASME B 31.1

Reaction Force at Discharge Elbow Outlet F1 -61.09 lbf ASME B 31.1

Equivalent length from valve outlet to discharge elbow outlet Lmax 19 inch Layout

Darcy Weisback friction factor f 0.013 Moody's Graph f(Lmax/D) 0.081 ASME B 31.1

Specific Heat Ratio k 1.1 ASME B 31.1

Pressure Ratio P/P* 1.231

ASME B 31.1 also fanno lines pdf ensure your calculated value is in the charts on the right or manually input values.

Pressure at Discharge Elbow Inlet P1a 3.44 psia ASME B 31.1

Vent Pipe Size P&ID

Thickness of Vent Pipe P&ID

Vent Pipe Outer Diameter 4.5 inch Pipe Data

Vent Pipe Thickness 0.237 inch Pipe Data

Vent Pipe Area A3 12.73 inch 2 Pipe Data

Pressure at Discharge of Vent Pipe P3 1.63 psia ASME B 31.1

Velocity at Discharge of Vent Pipe V3 1484.83 ft/s ASME B 31.1

Reaction Force at Discharge of Vent Pipe F3 -139.55 lbf ASME B 31.1

Equivalent length of Vent Pipe Lmax 164 inch Layout f(Lmax/D) 0.530 ASME B 31.1

Pressure Ratio P/P* 1.608

ASME B 31.1 also fanno lines pdf ensure your calculated value is in the charts on the right or manually input values.

Velocity Ratio V/V* 0.654

ASME B 31.1 also fanno lines pdf ensure your calculated value is in the charts on the right or manually input values.

Pressure at Inlet of Vent Pipe P2 2.61 psia ASME B 31.1

Velocity at Inlet of Vent Pipe V2 971.21 ft/s ASME B 31.1

Reaction Force at Inlet of Vent Pipe F2 -136.28 lbf ASME B 31.1

Bevel Angle at Vent Exit with Vertical Axis θ 0 deg

Height of Anchor from Vent Pipe Exit H 0 ft Layout

Vertical Force on Vent Pipe Anchor FV 3.27 lbf ASME B 31.1

Moment on Vent Pipe Anchor M 0.61 lbf ASME B 31.1

Blow-back Check if error shows, values for V/V or P/P must be manually entered from the flow charts or website

Weight of Safety Valve W 800 lb Process Data

Distance of Run Pipe Wall to Valve Outlet Centre Line h 19 inch Layout

Young's Modulus of Inlet Pipe E 2.30E+07 psi Pipe Data

Inlet Pipe Size P&ID

Inlet Pipe Thickness P&ID

Outer Diameter of Inlet Pipe Do 3.5 inch Pipe Data

Thickness of Inlet Pipe t 0.216 inch Pipe Data

Inner Diameter of Inlet Pipe Di 3.068 inch Pipe Data

Area Moment of Inertia of Inlet Pipe I 3.02 inch 4 Pipe Data

Safety Valve Installation Period T 5.19E-02 s ASME B 31.1

Valve Rise Time t0 0.04 s Process Data

Ratio of Valve Rise Time to Installation Period t0/T 0.77 ASME B 31.1

Dynamic Load Factor DLF 1.57 ASME B 31.1

Force to Piping System for Relief Valve Operation F -95.76 lbf ASME B 31.1

VENT PIPE SIZE IS OK

RELIEF VALVE CALCULATION AS PER ASME B31.1

Saturated Steam;>90% quality; 15 psia<pressure<1000 psia

STD

Steam and Condensate Pipe Calculator hidden background calcs above. FRICTION FACTOR CALC BROKEN

Color Legend:

Altitude 730 ft User Data Entry for the Pipe Scenario

Steam Pressure 60 psig MPS Informative Calculations

Steam Rate 2100 lb/hr Pressure Drop/Velocity Calculations within Acceptable Ranges

Steam Pipe Diameter 3 inches Pressure Drop/Velocity Calculations Near Edge of Acceptable Range. Okay but Consider Upsizing.

Steam Temperature 307 °F Pressure Drop/Velocity Calculations Outside of Acceptable Ranges. DO NOT SELECT HERE!

Steam BTU Rate 1,902 MBH

Steam velocity 4,200 fpm VA max 7,200 fpm

Pressure Drop 0.26 psig/100ft VA max 1 psi/100ft for LPS 2 psi/100ft for MPS & HPS

Condensate GPM 4.2 GPM

Condensate Pipe Diameter 2 inches

Max lb/hr @ 1/16 psi/100ft 989 lb/hr VA max for LPS 0.0625 psi/100ft for LPS

Max lb/hr @ 1/4 psi/100ft 2102 lb/hr VA max for MPS 0.25 psi/100ft for MPS

Max lb/hr @ 1 psi/100ft 0 lb/hr VA max for HPS 1 psi/100ft for HPS

Pressure Drop 1.28 psig/100ft

Dry Condensate Velocity 4,074 fpm VA max 7,000 fpm

Color Legend:

Altitude 730 ft User Data Entry for the Pipe Scenario

Steam Pressure 30 psig MPS Informative Calculations

Steam Rate 2100 lb/hr Pressure Drop/Velocity Calculations within Acceptable Ranges

Steam Pipe Diameter 3 inches Pressure Drop/Velocity Calculations Near Edge of Acceptable Range. Okay but Consider Upsizing.

Steam Temperature 273 °F Pressure Drop/Velocity Calculations Outside of Acceptable Ranges. DO NOT SELECT HERE!

Steam BTU Rate 1,954 MBH

Steam velocity 6,847 fpm VA max 7,200 fpm

Pressure Drop 0.26 psig/100ft VA max 1 psi/100ft for LPS 2 psi/100ft for MPS & HPS

Condensate GPM 4.2 GPM

Condensate Pipe Diameter 2 inches

Max lb/hr @ 1/16 psi/100ft 1585 lb/hr VA max for LPS 0.0625 psi/100ft for LPS

Max lb/hr @ 1/4 psi/100ft 3369 lb/hr VA max for MPS 0.25 psi/100ft for MPS

Max lb/hr @ 1 psi/100ft 0 lb/hr VA max for HPS 1 psi/100ft for HPS

Pressure Drop 1.28 psig/100ft

Dry Condensate Velocity 2,951 fpm VA max 7,000 fpm

Color Legend:

Altitude 730 ft User Data Entry for the Pipe Scenario

Steam Pressure 15 psig LPS Informative Calculations

Steam Rate 300 lb/hr Pressure Drop/Velocity Calculations within Acceptable Ranges

Steam Pipe Diameter 1.5 inches Pressure Drop/Velocity Calculations Near Edge of Acceptable Range. Okay but Consider Upsizing.

Steam Temperature 248 °F Pressure Drop/Velocity Calculations Outside of Acceptable Ranges. DO NOT SELECT HERE!

Steam BTU Rate 284 MBH

Steam…

This is the start of the file's text. The full file is on GovTribe.